Hybrid Tank-Tankless Water Heater
RH180 (REU-VA1320WF-US)
Technical Data Sheet
Temperature
Display
Indicates
temperature
setting or flashes
error code.
Temperature
Selector
In Use Indicator
Indicates the
water heater is in
a recovery mode.
ON / OFF
Button
Gas Pressure Setting
NOTE: For additional installation and commissioning information
refer to the Operation and Installation Manual.
This appliance must be installed, serviced and removed by a
trained and qualified person. During pressure testing of the
consumer piping, ensure gas valve is turned off before unit is shut
off. Failure to do so may result in serious injury to yourself or
damage to the unit.
APPLIANCE OPERATING PRESSURES
Water Inlet Max is 150 PSI
Gas Inlet Min/Max
Nat. G. LPG Nat. G. LPG Nat. G. LPG
4" W.C. /
10.5" W.C.
Ensure gas pressure check under Commissioning has been
completed first! The regulator is electronically controlled and
factory pre-set. Under normal circumstances it does not require
adjustment during installation. Make adjustments only if the unit is
not operating correctly and all other possible causes for incorrect
operation have been eliminated.
1. Turn OFF the gas supply.
2. Turn OFF the 120 V power supply.
3. Remove the front panel from the appliance.
4. Check the gas type using the data plate on the side of the unit.
If using a spare PC board, check that the gas type switches are
in the correct position (dip switch 1: ON for natural gas, NG, and
OFF for propane, LPG). See dip switch settings section below. (ON
is towards the right and OFF is towards the left.)
5. Attach the pressure gauge to the burner test point, located on
the gas control (Fig. 2).
6. Turn ON the gas supply.
7. Turn ON the 120 V power supply.
8. Turn the unit ON with the controller. Select the maximum delivery
temperature and open an available hot water fixture. Leave the
fixture on until all gas pressure setting is complete
9. When the red “In Use” light turns on, set the unit to “Forced Low”
combustion by setting No. 7 dip switch to ON (Fig. 3).
10. Check the burner test point pressure.
11. Remove the rubber access plug and adjust the regulator screw
on the modulating valve (Fig. 4) as required in Table 1. Replace the
rubber access plug.
12. Set the unit to “Forced High” combustion by setting both No. 7
and No. 8 dip switches to ON (Fig. 5). Ensure maximum water flow.
13. Check the burner test point pressure.
14. Adjust the high pressure potentiometer (POT) on the PC board
as required to the pressure shown in Table 1.
15. Return the unit to normal operation by setting dip switches 7
and 8 back to OFF (Fig. 6). Close all water taps.
16. Turn OFF the gas supply and 120 V power supply.
17. Remove the pressure gauge and install sealing screw.
18. Turn ON the gas supply and 120 V power supply.
19. Operate the unit and check for gas leaks at the test point.
20. Install the front panel.
NOTE: For additional installation and commissioning information
refer to the Operation and Installation Manual.
8" W.C. /
13.5" W.C.
Forced Low
1.10" W.C. 1.23" W.C. 2.8" W.C. 3.0"
Forced High
Table 1
W .C
Commissioning
With all gas appliances in operation at maximum gas rate, the
flowing inlet pressure at the incoming test point on the Rinnai
water heater should read 4" W.C. - 10.5" W.C. on natural gas
and 8" W.C. - 13.5" W.C. on propane gas. If the pressure is
lower, the gas supply is inadequate and the unit will not operate
to specification. Check the gas meter regulator and pipework for
correct operation/sizing and correct as required.
TROUBLESHOOTING
Important Safety Notes
There are a number of (live) tests that are required when fault
finding this product. Extreme care should be used at all times
to avoid contact with energized components inside the water
heater. Only trained and qualified service technicians should
attempt to repair this product. Before checking for resistance
readings, disconnect the power source to the unit and isolate
the item from the circuit (unplug it).
(SV1, SV2 and POV) Gas valve and Modulating solenoids
(Set meter above 2K)
Wire Color Voltage Resistance
Connec
Pin #’s
Thermistors:
Check all thermistors by inserting meter leads into each end
of the thermistor plug. Set your meter to the 20 K scale and
read resistance. Applying heat to the thermistor bulb should
decrease the resistance. Applying ice to the thermistor bulb
should increase the resistance. See below for examples of
typical temperatures and resistance readings.
(Main) Pink -
(SV1) Blue -
(SV2) Yellow -
(POV) Orange -
(M) Water Flow Control Servo or Geared Motor
Red - Orange N/A (G) 5 - O
Blue - Orange N/A (G) 3 - O
Grey - Yellow N/A GY - (G)1
(QS) Water Flow Sensor:
Red - Black
Yellow - Black 4 ~ 7 VDC N/A (A) 1 - 5
Note: Red turns to Orange and Black turns Grey on the PCB.
(IG) Ignition System
Grey - Grey
(FM) Combustion Fan Motor:
Red - Black 7 ~ 45 VDC N/A (B) 1 - 2
Yellow - Black
White - Black 7 ~ 45 VDC N/A (B) 4 - 2
(FV) Flammable Vapor Sensor:
Red - Black
White - Yellow
11 ~ 13
11 ~ 13
11 ~ 13
2 ~ 15 VDC
5 ~ 7 VDC
4 ~ 6 VDC
11 ~ 13
90 ~ 110
11 ~ 13
1.9 ~ 2.1
25.5 ~ 39.5
39 ~ 44
35 ~ 41
39 ~ 44
65 ~ 85
ohms
ohms
ohms
ohms
N/A (A) 9 - 5
N/A H1 (H) 1 - 2
N/A (B) 3 - 2
N/A (D) 1 - 6
N/A (D) 4 - 3
F6 (F) 6 - 7
F7 (F) 5 - 6
F8 (F) 4 - 6
F2 & F3 (F) 9 - 10
G1
A1
B1
D1
6 - 5 )G(A/NkniP - deR
4 - 3 )G(A/NetihW - eulB
Wire Color Voltage Resistance
Tank Temperature Thermistor (White & Yellow at the PCB)
White - W hite
Heat Exchanger Temperature Thermistor
(Brown & Yellow at the PCB)
White - W hite
Burner Sensor Temperature Thermistor
(Pink & Grey at the PCB)
Black - Black
2)G( - YGA/NnworB - yerG
Surge Protector:
Blue - Brown
Black White
With the power off you can check the continuity through the
surge protector. Place a meter lead on the top pin #1 of the
surge protector and pin #3 on the bottom of the surge protector. Check across the top pin #3 and bottom pin #1. If you read
continuity across these two points then the surge protector is
good. If you do not get continuity then replace the surge
protector.
Amp Fuses:
This unit has one inline (5) amp glass fuse. Remove the fuse
and check continuity through it. If you have continuity through
the fuseB then it is good. Otherwise the fuse is blown and
N/A
N/A
N/A
108 ~ 132
VAC
108 ~ 132
VAC
See Chart
See Chart
See Chart
N/A
N/A
Connec
A2
A3
A4
I1
I2
Pin #’s
(A) 3 - (A)
(A) 7 - (A)
(A)10 -
(I)1 - (I)3
N/A
(COS) Carbon Monoxide Sensor:
Red - Black
Blue - Yellow
Thermal Fuse / Overheat Switch
White - White
Note: White turns to red on the PCB
Set dip switches 2 and 3 to the values shown in table below for your altitude.
The default setting for the appliance is 0 - 2000 ft (0 - 610 m) with switches
No. 2 and No. 3 in the OFF position.
1.9 ~ 2.1
29 ~ 31
11 ~ 13
N/A (C) 1 - 5
C1
N/A (C) 4 - 3
Below 1 ohm A6 F1
(F) 12 -
Switch No. 2
Switch No. 3
0-2000 ft
(0-610 m)
OFF
OFF
SWITCH
2001-5400 ft
(610-1646 m)
OFF
ON
SWITCH
WATER FLOW
SENSOR
Y
QS
BK
TANK THERMISTOR
OUTGOING THERMISTOR
BURNER THERMISTOR
BK
BK
BK
FM
COMBUSTION FAN
D
1
FV
FLAM ABLE SENSOR
THERMAL FUSES
OVERHEAT
SWITCH
MODUL ATING
SOLENOID VALVE
FLAME ROD
MAIN SOLENOID VALVE
SOLENOID VALVE 1
(SMALL)
SOLENOID VALVE 2
(LARGE)
A
1
OR
Y
GY
A
W
Y
BR
Y
P
GY
F
3
POV
F
2
A
3
A
4
B
1
R
BK
Y
W
A
6
R
W
W
R
F
1
O
O
Y
5
F
6
SV0
Bk
F
7
BL
SV1
Bk
F
8
SV2
Bk
W
W
W
W
R
Y
W
BK
R
Y
W
GAS CONTROL UNIT
SV2
SV1
WIRE DIAGRAM
COLOR CODING
W :White
BK:Black
BR
PU
PU
Y
P
P
W
J
1
BL
R
BL
GY
Y
GY
BK
WW
BK
G/Y
GY
BR
O
Y
W
P
BL
R
BR:Brown
R :Red
BL:Blue
Y :Yellow
P :Pink
O :Orange
GY:Gray
PU:Purple
OPERATION
UNIT
G
1
PUMP
P
AC120VAC120V
HOT
HOT
NEUTRAL
GROUND
GNDGND
COS
CO SENSOR
R Y BK
C
1
BK
Y
GY
GY
IG
14
GY
GY
R
BL
7
ED
BK
W
H
2
1
I
1 3
G/Y
BL
BR
1
MAX
MIN
Dip SW1
O
F
F
1
RBRBLPUGYPYPUGY
YBLP
1
G
W
BR
BL
Y
1
MODUL ATING VALVE
CURRENT ADJUSTING
1
Gas t ype
2
3
4
5
6
7
Gas p ressu re Setting
8
BL
R
BL
GY
Y
GY
BK
6
P
R
2
E
1
Y
P
BR
PU
P
PU
W
WATER FLOW
CONTROL D EVICE
GY
BR
O
Y
W
P
BL
R
J
BK
W
BK
G/Y
GND
G/Y
SURGE
PROTECTOR
1
BL
3
BR
I
1
3
1
G/Y
I
BK
W
2
FUSE
(5A)
BK
W
GY
BR
A
11
O Y
P
GY
1 4
YWY
R
1
BL
Y
R
BK
B
WYBKR
1 5
C
1 6
WY BKR
F
1
Y
Y
BK
BL
F
2
O
O
O
O
Y
Y
F
4
P
Y
12
R
O
P
O
GY
GY
H
1
IGNITER
SPARK
ELECTRODE
GND
GND
SOLENOID VALVE
CONNECTING
WIRING COLOR
BK
BK
Y
SV0
BK
P
BL