Technical training seminars are available through Rice Lake Weighing Systems.
Course descriptions and dates can be viewed at www.ricelake.com/training
or obtained by calling 715-234-9171 and asking for the training department.
2.3.1 The following information is provided to help the installer with the correct installation of the 320IS system.
See Figure 2-1 below for a diagram of a typical intrinsically safe system. 9
This manual is intended for use by service technicians responsible for installing and servicing 320IS digital weight
indicators. This manual applies to indicators using Version 2.1 of the 320IS software.
Configuration and calibration of the indicator can be accomplished using the indicator front panel keys, the EDP
command set, or the
320IS configuration utility. See Section 3.1 on page 20 for information about configuration
methods.
The 320IS is a Factory Mutual-Entity approved component. This approval is valid only if the installation
conforms to the guidelines described in this manual and FM-approved control drawing (PN 72717). If
modifications are made to the installation procedure, or the instrumentation is changed in any way,
including field repair or modification, Factory Mutual approval is void, and all warranties, expressed or implied are void.
The customer becomes fully responsible and liable for such modifications.
Manuals can be viewed or downloaded on the Rice Lake Weighing Systems distributor site at
www.ricelake.com.
Safety
Safety Symbol Definitions
Indicates a potentially hazardous situation that, if not avoided, could result in serious injury or death, and
includes hazards that are exposed when guards are removed.
Indicates a potentially hazardous situation that, if not avoided may result in minor or moderate injury.
Indicates information about procedures that, if not observed, could result in damage to equipment or
corruption to and loss of data.
Safety Precautions
Do not operate or work on this equipment unless you have read and understand the instructions and
warnings in this manual. Failure to follow the instructions or heed the warnings could result in injury or
death. Contact any Rice Lake Weighing Systems dealer for replacement manuals. Proper care is your
responsibility.
General Safety
Failure to heed may result in serious injury or death.
Some procedures described in this manual require work inside the indicator enclosure. These procedures are to be
performed by qualified service personnel only. Improper specification, installation, or service of this equipment could
result in personal injury or property damage.
DO NOT allow minors (children) or inexperienced persons to operate this unit.
DO NOT use for purposes other than weight taking.
DO NOT operate indicator without enclosure fully assembled.
DO NOT use this product if any of the components are cracked.
DO NOT exceed the rated load limit of the unit.
DO NOT make alterations or modifications to the unit.
DO NOT remove or obscure warning labels.
DO NOT submerge.
Before opening the unit, ensure power is disconnected.
The non-metallic parts are considered to constitute an electrostatic discharge hazard. Clean only with a damp cloth.
Substitution of components may impair intrinsic safety.
To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
320IS Installation Manual - Introduction1
1. 1O ve r vi e w
WARNING
The 320IS is a single-channel digital weight indicator designed and approved to operate as an intrinsically safe
system in a wide variety of scale and weighing applications. The indicator is housed in a NEMA 4X/IP66-rated
stainless steel sealed case. The standard unit is equipped with a tilt stand base for tabletop or wall mounting
applications. The indicator front panel consists of a large (0.8 in, 20 mm, 16-segment), six-digit LED display,
6-button keypad and eight LED annunciators. Features include:
•Drives up to four 350or eight 700 load cells
•Supports four-wire and six-wire load cell connections (six-wire remote sense recommended)
•Full-duplex fiber optic interface to attach an external I/O board located in the safe area
The 320IS is NTEP-certified and pending Measurement Canada approval for Classes I, II and III at 10,000
divisions.
See Section 8.9 on page 65 for detailed specifications.
Available with optional I/O Module (PN 72721):
•Four configurable digital inputs
•Four digitally-controlled single pole single throw-normally open non-latching relay contact outputs
•Electronic data processing (EDP) port communications at up to 38400 bps for full duplex RS-232/RS-422/
RS-485 and Current loop
•Printer port communications at up to 38400 bps for full duplex RS-232/RS-422/RS-485 and Current loop
•Two 16-bit analog output channels provide ±10V or ±5V, 0-5V or 0-10V, and 4-20 mA tracking of gross
or net weight values
1.2Factory Mutual Approval
The 320IS is Factory Mutual (FM) Entity approved for:
•Classes I, II, and III
•Divisions 1 and 2
•Groups A, B, C, D, E, F and G
•T-rating T4
Only devices that have FM Entity Approval with proper entity parameters may be used unless specifically listed in
this manual or control drawing PN 72717 as part of the Rice Lake Factory Mutual systems approval. Failure to
comply with this voids the FM approval.
The classification of hazardous materials are different in the US and European standards. Because of this, the
safety class of the
•US standards: Class I, II, III, DIV1, Groups A-G.
320IS is declared in the following regulations:
1.3Operating Modes
The 320IS has three modes of operation.
Normal (Primary) Mode
Normal mode is the “default” mode of the indicator. The indicator displays gross or net weights as indicated by
LED annunciators (see
Setup Mode
Most of the procedures described in this manual require the indicator to be in setup mode including configuration
and calibration.
To enter setup mode, remove the large fillister head screw from the enclosure backplate. Insert a non-metal
screwdriver or a similar tool into the access hole and press the setup switch once. The indicator display changes to
show the word
Test Mo de
Test mode provides a number of diagnostic functions for the 320IS indicator. Like setup mode, test mode is entered
using the setup switch (
2 320IS Installation Manual
Substitution of components may impair intrinsic safety.
To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
Figure 1-1) to indicate scale status and the type of weight value displayed.
CONFIG.
Section 7.8 on page 55).
1.4Front Panel Keypad
kg
Gross
Net
lb
Count
Figure 1-1 shows the 320IS LED annunciators, keypad, and normal mode key functions. Tab l e 1-1 on page 4
details the function of each key in different display modes.
The symbols shown above the keys (representing up, down, enter, left, right) describe the key functions assigned in
setup mode. In setup mode, the keys are used to navigate through menus, select digits within numeric values, and
increment/decrement values. See
mode.
Section 3.2.3 on page 21 for information about using the front panel keys in setup
Figure 1-1. 320IS Front Panel
320IS Installation Manual - Introduction3
Key Functions
Note
Move Up and
Down (vertically)
Enter
Move Left and
Right (horizontally)
Display Mode
NormalSetupTe stCount
Turn the indicator on or off
Return gross weight
display to zero
Toggle between gross,
net and piece count
mode
Press to enter an auto
tare or keyed tare
Toggle between primary
and secondary units
Print using GFMT Move right (horizontally)Print Print using CFMT
• Move up (vertically)
• Increment value
• Exit (top level only)
• Move down (vertically)
• Decrement value
EnterEnterPerform a piece count
• Move left (horizontally)
• Previous
ExitN/A
N/AToggle between gross,
net and piece count
mode
Move left (horizontally)Select a sample size
Table 1-1. Indicator Display Key Functions
SERIAL, PFORMT, DIG IN and ALGOUT menu functions require fiber optics communications with
I/O module to operate.
Figure 1-2. Front Panel Key Functions in Setup Mode
Four front panel keys are used as directional keys to navigate through the menus in setup mode (see Figure 1-2).
The UNITS ( ) and PRINT ( ) keys scroll left and right (horizontally) on the same menu level; ZERO ( ) and
GROSS/NET ( ) move up and down (vertically) to different menu levels. The TARE key ( ) serves as an enter key
for selecting parameter values within the menus. A label above each of these keys identifies the direction provided
by the key when navigating through the setup menus.
Figure 1-3. Setup Mode Menu Navigation
To select a parameter, press or to scroll left or right until the desired menu group appears on the display, then
press to move down to the submenu or parameter you want. When moving through the menu parameters, the
default or previously selected value appears first on the display.
4 320IS Installation Manual
To change a parameter value, scroll left or right to view the values for that parameter. When the desired value
1
st
Level
Parameter
Default value
2
nd
Level
Parameter
Value Value
1
st
Level
Parameter
2
nd
Level
Parameter
When moving thr ough values below the first menu level, press to r etur n to the level
above. Pr ess or to move to the next parameter on the level above.
Value
When editing numeric values, press or to change th e
digit selected. Press or to incr ement or decrement the
value of t he selected digit, or use t he numeric keypad.
Pr ess to save the value entered and return to the level above.
0 0 0 0 0 0
0
appears on the display, press
to select the value and move back up one level. To edit numerical values, use the
navigation keys to select the digit and to increment or decrement the value or use the numeric keypad (see
Figure 1-4).
Figure 1-4. Editing Procedure for Numeric Values
1.5LED Annunciators
The 320IS display uses a set of eight LED annunciators to provide additional information about the value being
displayed (see
Figure 1-1 on page 3):
Gross
Net
Center of ZeroGross weight is ±0.25 graduations of zero. This
LED Annunciators
The Gross and Net annunciators are lit to show
whether the displayed weight is a gross or net
weight.
annunciator lights when the scale is zeroed
.
StandstillScale is at standstill or within the specified motion
CountThe Count annunciator is lit to show that the indicator
band. Some operations, including tare functions and
printing, can only be done when the standstill symbol
is shown.
The Tare Acquired light shows that a tare value has
been entered.
is in piece count mode.
Table 1-2. LED Annunciators
320IS Installation Manual - Introduction5
LED Annunciators
0 lblb and kg annunciators indicate the units associated
0kg
with the displayed value: lb=pounds, kg=kilograms.
Two units of measurement can be chosen to toggle
between.
The displayed units can also be set to ounces (oz),
short tons (tn), metric tons (t), grams (g), or they can
be disabled. A user-defined unit can also be set as
secondary unit by declaring a conversion factor in the
setup menu. The
and secondary units annunciators for some
combinations of primary and secondary units. If
neither primary nor secondary units are lb, kg, oz, or
lb annunciator is lit for primary units, kg for
g, the
secondary units.
lb and kg LED’s function as primary
Table 1-2. LED Annunciators
Table 1-3 shows which annunciators are used for all combinations of configured primary and secondary units. For
example:
•If the primary unit is pounds (lb) and the secondary unit is kilograms (kg), the lb LED is lit for primary
units, kg for secondary units.
•If the primary unit is pounds (lb) and the secondary unit is short tons (tn), the lb LED is lit for primary
kg for secondary units. There is no LED for short tons, so the kg LED is used as the secondary units
units,
annunciator.
•If the primary unit is short tons (tn) and the secondary unit is pounds (lb), the lb LED is lit for primary units
(tn), and kg is lit for secondary units (lb). Because there is no LED for short tons, the lb and kg LEDs are
used as primary and secondary units annunciators.
See Section 3.3.2 on page 24 for more information about configuring primary and secondary display units.
Table 1-3. Unit Annunciators, Primary/Secondary LEDs Used For All Configurations
1. 6Indicator Operations
Basic 320IS operations are summarized below.
1.6.1Toggle Gross/Net Mode
Press the GROSS/NET key to switch the display mode from gross to net, or from net to gross. If a tare value has been
entered or acquired, the net value is the gross weight minus the tare. The
value is currently stored in memory.
1.6.2Toggle Units
Press the UNITS key to switch between primary and secondary units. The appropriate units LED to the right of the
display is lit.
Tare () annunciator is lit when a tare
6 320IS Installation Manual
1.6.3Zero Scale
Note
Note
1. In gross mode, remove all weight from the scale and wait for .
2. Press the ZERO key. annunciator lights to indicate the scale is zeroed.
1.6.4Acquire Tare
0
1. Place container on scale.
2.
When is lit
, press the
TARE
key. The indicator switches to net mode.
3. To display the current tare value,press the DISPLAY TARE key.
1.6.5Remove Stored Tare Value
1. Remove all weight from the scale and wait for the standstill annunciator ().
2. When is lit
, press the
TARE
key. The indicator switches to
gross mode, indicating the tare value has
been removed.
1.6.6Acquire Parts Sample
1. Place empty parts container on scale.
2. Press TAR E to acquire the tare weight of the container.
3. Press GROSS/NET key to enter piece count mode.
Press the CLEAR key to exit.
4. Press the UNITS key to enter sample acquisition mode.
Addnnn displays, nnn is the sample quantity to be placed on the scale.
•Add the number of parts shown.
•Choose a different sample size. Press the SAMPLE key to scroll through the selectable sample quantities (5,
10, 20, 50, 100) or use the numeric keypad to specify a custom sample size.
•Specify a known piece weight. Press the SAMPLE key to scroll through the selectable sample quantities
until the
PC WGT prompt is shown. Use the numeric keypad to enter the piece weight.
5. Once the sample quantity is on the scale, press ENTER to calibrate the indicator for counting the new parts.
6. If a sample size was specified, the indicator display shows the message –CNT– as it acquires the sample
weight, then switches to count display mode and shows the part quantity.
7. If a known piece weight was specified, the display switches to count display mode immediately.
1.6.7Display Part Weight
To view gross and net weight parts, press MODE to switch from count display mode to normal weighing mode.
To view the current piece weight while in count mode, press DISPLAY TARE key.
1.6.8Print Ticket
Requires optional I/O Module (PN 72721).
Wait for the standstill annunciator (). Press the PRINT key to send data to the serial port. Standstill must be lit
to print.
320IS Installation Manual - Introduction7
2.0Installation
CAUTION
Important
WARNING
This section describes installation of load cells, power supply, fiber optics, and ferrite bead for the 320IS indicator.
Use a wrist strap to ground yourself and protect components from electrostatic discharge (ESD) when
working inside the indicator enclosure.
It is mandatory to return the 320IS to Rice Lake Weighing Systems for circuit board level service.
Component level repair, excluding board-swapping, is not permitted on Factory Mutual Approved
equipment by anyone other than the manufacturer.
2.1Unpacking and Assembly
Immediately after unpacking, visually inspect the 320IS to ensure all components are included and undamaged.
The shipping carton should contain the indicator with attached tilt stand, this manual, and a parts kit. If any parts
are missing or were damaged in shipment, notify Rice Lake Weighing Systems and the shipper immediately. See
Table 2-5 on page 19 for parts kit.
2.2Enclosure Disassembly
The indicator enclosure must be opened to connect cables for load cells, communications, and power.
Before opening the unit, ensure the power is disconnected from the power outlet.
1. Ensure power to the indicator is disconnected.
2. Place the indicator face-down on an antistatic work mat.
3. Remove the screws that hold the backplate to the enclosure body.
4. Lift the backplate away from the enclosure and set it aside.
8 320IS Installation Manual
2.3Hazardous Area Installation of the 320IS
Junction
Box
(Optional)
AC Power
Supply
(Intrinsically
Safe Output)
FM-Approved
Load Cells
(up to 4–350Ω)
Battery
(Optional)
I/O Module
(Optional)
Battery
Charger
(Optional)
Load Cell
Input
Fiber Optic
VDC115/230VAC
WARNING
2.3.1The following information is provided to help the installer with the correct installation of the 320IS system.
Figure 2-1 below for a diagram of a typical intrinsically safe system.
See
2.3.2Power Supply to Indicator
The indicator should be powered by an FM-approved Rice Lake power supply or alternatively from an external
battery pack. The power requirements of the
The DC power cable should be attached to connector CN1 (see Table 2-1). Care must be taken to wire CN1 with
the correct DC polarity. See Section 2.4 on page 10 for information on cabling through metal cord grips.
Figure 2-1. Intrinsically Safe System Diagram
Do not, under any circumstances, connect or disconnect the DC wire from the indicator while the AC
power is applied to the power supply. This will cause the power supply fuse to blow.
320IS are as follows:
•Minimum input voltage: 5.8 V
•Maximum input voltage: 7.9 V
•Peak current consumption: 190 mA
•Average input current (with four load cells): 140 mA
CN1 PinFunctionWire Color
1+ Voltage (5.8 – 7.9 V)Green
2Ground (V–, Common)Brown
Table 2-1. DC Power Supply Connections
320IS Installation Manual - Installation9
A separate conduit system is recommended for installation. The type suggested for this application is 3/4" rigid
Note
Note
Note
steel conduit with pull boxes located at required intervals. The conduit provides additional noise protection for the
low-level signals, while automatically complying with the requirements for two-inch separation between
intrinsically safe circuits and other electrical cables. Conduit seals are necessary where a gas tight seal is required
between hazardous area and safe area.
2.3.3AC Power Wiring
Standard units are powered by an F.M. approved power supply. We recommend the 100–240 VAC into RLWS
IS-EPS-100-240 Intrinsically safe DC output power supply (PN 72713).
See the IS-EPS-100-240 Power Supply Instruction Sheet (PN 79820) for information on wiring and power
specifications.
2.3.4Battery Option
The optional battery pack provides an intrinsically safe battery that can replace the power supply. The battery is
approved for use in hazardous environments and limited use operations such as bench scales and platform scales. A
low battery error message will display to indicate that the battery needs to be recharged. Always charge the battery
overnight. The yellow indicator light will remain on until the battery is charged at about 70%, at which point the
indicator light will turn green and the charger will switch to float charge mode. Once the light turns green, the
battery requires another 3 hours on float charge before the battery is fully charged.
To keep battery at full capacity, it is recommended to leave the battery connected to the charger, in float
charge mode, until ready to use. The battery can remain on the charger in float charge mode indefinitely
without damaging the battery. See Battery Charging Instruction Sheet (PN 96567) for instructions on charging
the battery.
Load Cell SizeQuantity of cellsOperating Time
350 load cell140 - 50 hours
435 - 40 hours
700 load cell145 - 55 hours
440 - 50 hours
Table 2-2. Estimated Battery Operating Times
While connected to the DC battery pack with the indicator off, the 320IS still draws a small amount of current
that will shorten battery run time. To preserve battery life, disconnect the battery when not in use.
2.4Cable Connections and Installation
The following sections contain information on cable connections and installation for the 320IS.
Intrinsically safe cables are specified by control drawing. All cables must have appropriate internal inductance
and capacitance. Cable lengths are based on group classifications.
Figure 2-2. Metal Cord Grip
10 320IS Installation Manual
Before connecting the AC power to the power supply:
WARNING
Note
1. Determine the length of AC power cord necessary to reach from the AC power panel to the power supply
where it is mounted.
2. Cut the AC power cord to that length. If you are mounting the I.S. power supply in a hazardous area, all
AC power must be routed through approved conduit, where necessary make allowances in length of the
conduit.
3. Install the AC power cord but do not hook up to the AC power.
Do not, under any circumstances, connect or disconnect the DC wire from the indicator while the AC
power is applied to the power supply. This will cause the power supply fuse to blow.
4. Determine the length of the DC power cord necessary to reach from the AC power supply to the 320IS
Plus indicator and add 7" to that length.
5. Cut the DC power cord to that length.
2.4.1Braided Power Cable Connection with Ferrite Core
Use the following procedure for connecting braided power cable with the ferrite core:
1. If using the ferrite core, carefully remove 7" of the outer blue insulation and 6.5" of braid from the cable. If
not using the ferrite core, go to Section 2.4.2.
2. Remove the reducing gland and metal sleeve from the center cord grip of the indicator. Place them on a
work surface.
3. Remove the cap and reducing gland from the 320IS Plus parts kit.
The cap and reducing gland from the parts kit have larger holes. DO NOT confuse these parts with the
parts removed from the cord grip of the indicator.
4. Take the metal sleeve (from step 2) and insert it into the reducing gland taken from the parts kit.
5. Place the domed cap and reducing gland that were removed from the 320IS cord grip, into the parts kit (to
be used as spares).
6. Thread the DC cable through the domed cap, then through the reducing gland/metal sleeve combination.
7. Lower the reducing gland assembly so that the end of the metal sleeve is at the edge of the insulation and
fold the braid over the metal sleeve (
Figure 2-2). Trim the braid if necessary.
8. Trim the white wire back to match the end of the braid.
9. Tin the green and brown wire ends.
10. Thread the cable through the cord grip stem.
Chassis ground is made through the braid compressed between the metal sleeve and the cord grip stem.
11. Lower the domed cap onto the cord grip stem and tighten until a small swelling of the rubber of the
reducing gland appears between the domed cap and cable (see
Figure 2-3. Proper Cord Grip Compression
Figure 2-3).
12. Thread the green and brown wires two times through the ferrite core from the parts kit. See Figure 2-4 as
an example picture.
320IS Installation Manual - Installation11
13. Connect the green and brown wires to the connector for CN1, observing polarities. See Table 2-3 below.
Note
Note
Note
CN Pin 1FunctionColor
1+ Voltage (5.8 - 7.9)Green
2Ground (V-, Common)Brown
Table 2-3. DC Power Supply Connections — CN1
14. Plug the connector onto CN1.
15. Connect the AC power.
2.4.2Braided Power Cable Connection Without Ferrite Core
Use the following procedure for connecting a braided power cable without a ferrite core.
1. If not using a ferrite core, carefully remove 3" of outer blue insulation and 2.5" of braid from the cable.
2. Remove the domed cap, reducing gland and the metal sleeve from the center cord grip of the indicator.
Place them on a work surface.
3. Remove the domed cap and reducing gland from the 320IS Plus parts kit.
The domed cap and reducing gland from the parts kit have larger holes. DO NOT confuse these parts with the
parts removed from the cord grip.
4. Take the metal sleeve (from step 2) and insert it into the reducing gland taken from the parts kit.
5. Place the domed cap and reducing gland that were removed from the 320IS cord grip, into the parts kit (to
be used as spares).
6. Thread the DC cable through the domed cap, then through the reducing gland/metal sleeve combination.
7. Lower the reducing gland assembly so that the end of the metal sleeve is at the edge of the insulation and
fold the braid over the metal sleeve (
Figure 2-2). Trim the braid if necessary.
8. Trim the white wire back to match the end of the braid.
9. Tin the end of the green and brown wires.
10. Thread the cable through the cord grip stem.
Chassis ground is made through the braid compressed between the metal sleeve and the cord grip stem.
11. Lower the domed cap onto the cord grip stem and tighten until a small swelling of the rubber of the
reducing gland appears between the domed cap and cable (see
Figure 2-3).
12. Connect the green and brown wires to the connector for CN1. Observe polarity. See Table 2-3.
13. Plug the cable into CN1.
14. Connect the AC power.
2.4.3 Braided Load Cell Cable Connection
Use the following procedure for connecting braided load cell cable:
If Using 6 Wire Load Cell Cable
1. Carefully remove 8" of outside insulation and 7 1/2" of braid from the load cell cable.
2. Remove the metal domed cap, reducing gland and metal sleeve from the left metal cord grip. Place them on
a work surface.
3. Remove the reducing gland and metal domed cap from the 320IS plus parts kit.
These have a larger hole than those removed from the cord grip — DO NOT confuse them.
4. Take the metal sleeve from step 2, and insert it into the reducing gland taken from the parts kit.
5. Retain the cord grips.
6. Thread the load cell cable through the domed cap, then through the reducing gland/metal sleeve assembly.
7. Lower the reducing gland assembly so that the end of the metal sleeve is at the edge of the insulation and
fold the braid back over the sleeve (see
Figure 2-2). Trim if necessary.
8. Thread the cable through the cord grip stem.
12 320IS Installation Manual
Chassis ground is made through the braid compressed between the metal sleeve and the cord grip stem.
Note
Note
Note
9. Lower the domed cap onto the cord grip stem and tighten until a small swelling of the rubber of the
reducing gland appears between the dome cap and the cable (see
Figure 2-3).
10. Thread the load cell cable through the ferrite core, from the parts kit, twice. Keep the ferrite core as close to
the backplate as possible (see Figure 2-4).
If Using 4 Wire Load Cell Cable
1. Carefully remove 8" of outside insulation and 7 1/2" of braid from the load cell cable.
2. Remove the metal domed cap and reducing gland from cord grip, place them on a work surface.
3. Thread the load cell cable through the domed cap, then through the reducing gland/metal sleeve assembly.
4. Lower the reducing gland assembly so that the end of the metal sleeve is at the edge of the insulation and
fold the braid back over the sleeve (see
Figure 2-2). Trim if necessary.
5. Thread the cable through the cord grip stem.
Chassis ground is made through the braid compressed between the metal sleeve and the cord grip stem.
6. Lower the domed cap onto the cord grip stem and tighten until a small swelling of the rubber of the
reducing gland appears between the domed cap and the cable (see
Figure 2-3).
7. Thread the load cell cable through the ferrite core, from the parts kit, twice. Keep the ferrite core as close to
the backplate as possible (see
Figure 2-4).
Figure 2-4. Ferrite Core Wire Wrap
2.4.4Foil Load Cell Cable Connection
Use the following procedure for connecting foil load cell cable:
1. Carefully remove 8" of insulation and 7 1/2" of foil from cable.
2. Remove domed cap, reducing gland and metal sleeve from cord grip and place them on the cable (see
Figure 2-2).
3. Thread the load cell cable through the domed cap, then through the reducing gland metal sleeve assembly.
4. Lower reducing gland metal sleeve assembly to edge of insulation and wrap foil over metal sleeve of
reducing gland leaving the silver side out.
5. Thread the cable through the cord grip stem.
Chassis ground is made through the foil compressed between the metal sleeve and the cord grip stem.
6. Lower the domed cap onto cord grip stem.
7. Tighten until a small swelling of the rubber between the domed cap and the cable builds (see Figure 2-3).
8. Thread wires through ferrite core two times. Keep the ferrite as close to the backplate as possible (see
Figure 2-4).
320IS Installation Manual - Installation13
9. Wire cable to connector CN3.
Load cell
connector
Power cable connector
Green = +Voltage
Brown = Return
125mA fully –
encapsulated
fuses
F1 & F2
Blue pptical
output
Black optical
input
Ferrite cores
Chassis
ground
Sense jumpers
J1 & J2
1 2 3 4 5 6
CN3
-Excitation
-Sense
-Signal
+Signal
+Sense
+Excitation
Figure 2-5. Cable Connections
2.4.5Load Cells
To attach cable from a load cell or junction box, use six-position connector in parts kit. See Section 2.4 on page 10
for information on cabling through metal cord grips.
Wire the load cell cable from the load cell or junction box to connector CN3 as shown in Figure 2-6. If using 6-wire
load cell cable (with sense wires), remove jumpers J1 and J2 before installing connector CN3. For four-wire
installation, leave jumpers J1 and J2 on.
When connections are complete, reinstall connector CN3 on the board and use two cable ties to secure the load cell
cable to the inside of the enclosure.
• For six-wire connections, remove jumpers J1 and
J2.
• For four-wire connections, leave jumpers J1 and
J2 on.
Table 2-4. CN3 Pin Assignments
2.5Fiber Optics Installation
The 320IS is equipped with a duplex fiber optic port for communicating with an I/O Module located outside the
hazardous area. This is the only communications channel of the indicator. The indicator communicates with
external devices through the optional I/O Module’s physical interfaces (RS–232, RS–422, RS–485, Current Loop)
and provides analog and digital I/O functions such as setpoint relays and analog outputs.
The fiber optics port is located on the indicator CPU board (see Figure 2-5).
2.5.1Assembling Fiber Optics Connectors
Use the following steps for assembling the fiber optic connectors of the 320IS:
1. Cut off the ends of the fiber optic cable (PN 74000) with a single-edge razor blade or hot knife (PN 85548).
Try to obtain a precise 90º angle.
2. Insert the fiber through the locking nut and into the connector until the core tip seats against the internal
micro-lens.
3. Screw the connector locking nut down to a snug fit, locking the fiber in place.
4. Secure fiber with 3-inch nylon cable ties in parts kit and 3/4-inch square nylon mounts.
Figure 2-7. Fiber Optics Connector
2.6Enclosure Reassembly
1. Position the backplate over the enclosure.
2. Reinstall the backplate screws. Use the torque pattern shown in Figure 2-8 to prevent distorting the
backplate gasket. Torque screws to 15 in-lb (1.7 N-m).
Torqued screws may become less tight as the gasket is compressed during torque pattern, therefore a
second torque is required using the same pattern and torque value.
320IS Installation Manual - Installation15
Figure 2-8. 320IS Enclosure Backplate
Setup switch access screw
Fillister head screws
10
9
8
7
4
3
1
2
5
6
Torque pattern
Load cell connection cord grip
DC power cord grip
Fiber optics
cord grip
Ground lug
LH
*4
5
.
0
5
&
;
&
3
4&561
P[
H
MC
%4
%4
*4
%4
/
0
3
&
5
"
%4
%4
%4
'
51
$
3
-
9
$
$
3
$
2
$
3
3
3
2
$
$
$
3
$
2
3
$
$
$
3/
$
$
2
3
3
6
3
$
3
$
3
$
3
3
$
;
;
574&(
+
$
3
51
+
$
$
$
-
3
3
3/
3
$
3
3
3
$
-
2
3
3
3
3
3
.&$$"
48
.
%
%
3
$
$
$
$
(/%
%(/%
6
$
$
$
$
$
$
$
3
$
2
2
2
3
6
$
$
$
6
$
6
$
2
3
2
6
$
(/%
$/
$
$
,&:1"%
$
3
2
3
6
9
.&$$"
6
$
2
2
3
3
3
2
2
3
6
2
3
3
$
$
3
6
.
.
6
3
$
3/
$
3
2
2
%
6
6
;
'
2
$
;
.
6
574"(
;
;
;
;
%
%
6
9
3'*&(
3'*"(
3
2
6
+
;
;
6
(&
$
2
2
*'%
1%
2
$
6
3
4*&9&9 4&4*
4&
$/
6
6
'
2
$
-%
6
$/
$/
0QUJDBM0VUQVU
0QUJDBM*OQVU
1PXFS
$POOFDUPS
-PBE$FMM$POOFDUPS
16 320IS Installation Manual
Part NumberDescription (Quantity)Part Number Description (Quantity)
450434 in. W/No. 8 Ground Wire 146268–32NC Hex Kep Nut
16892Earth Ground Label195381.25 x 1 Slotted Black Post
15627PG–9 Metal Lock Nut91852 PG–9 Metal Cord Grip
15626PG–9 Black Cord Grip82432125 mA Encapsulated Time–Lag Fuse
50962PCN–9 Black Nut72916Backplate
45042SS Bonded Sealing Washer, #8148628–32NC x 3/8 Screw
Figure 2-9. 320IS CPU Board
Table 2-5. Hardware Replacement List
Part NumberDescription (Quantity)Part Number Description (Quantity)
39037Backplate Gasket68216Rice Lake Nameplate
426401/4 – 28NF x 1/4 Screw44676Bonded Sealing Washer, 1/4"
29635SS Tilt Stand684031/4 – 20 Two-Prong Black Knob
151441/4 x 1 x 1/16 Nylon Washer
100345Reconditioned/Exchange 320IS
Table 2-5. Hardware Replacement List
320IS Installation Manual - Installation17
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.