WARNING:
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION
VARIABLE SPEED R-410A AIR CONDITIONING
WARNING
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT, AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLO W THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE, OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH.
OUTDOOR UNITS
Enabled
(-)A20 (20 SEER) EQUIPPED WITH ECONET™ COMMUNICATIONS
Do not destroy this manual. Please read carefully and keep in a safe place for future reference by a serviceman.
[ ] indicates metric conversions.
92-104921-12-00 (12/15)
Printed in USA
Page 2
CONTENTS
Important Safety Information ��������������������������������������������� 3 General Information ����������������������������������������4-7
Checking Product Received ����������������������������������������4
Contents
Application �������������������������������������������������������������������4 Electrical and Physical Data ������������������������������������� 5-6 Specifications ����������������������������������������������������������� 6-7 Proper Installation ��������������������������������������������������������7
Installation ���������������������������������������������������� 8-22
Choosing a Location �������������������������������������� 8-10
Operational Issues��������������������������������������������������������8 Corrosive Environment �������������������������������������������������8 For Units With Space Limitations ���������������������������������������������������������9 Customer Satisfaction Issues ��������������������������������������9 Unit Mounting ���������������������������������������������������������������9 Factory-Preferred Tie-Down Method���������������������������������������������������������9 Snow Depth Table ������������������������������������������������������ 10
Tools and Refrigerant ���������������������������������������11
Tools Required for Installing and Servicing R-410A Models ������������������������������������������11 Specifications of R-410A �������������������������������������������11 Quick-Reference Guide for R-410A �������������������������������������������������������11
Replacement Units �������������������������������������������12 Indoor Coil ��������������������������������������������������������12
Location ����������������������������������������������������������������������12
Interconnecting Tubing �������������������������������� 12-22
Refrigerant Level Adjustment �������������������������������������12 Interconnecting Tubing and Fitting Losses �������������������������������������������������������������13 Liquid Line Selection ��������������������������������������������������13 Long Line Set Applications ����������������������������������������14 Oil Level Adjustments for Long Line ��������������������������14 Suction Line Selection �����������������������������������������������15 Refrigerant Migration During Off Cycle ����������������������15 Tubing Installation ������������������������������������������������������ 20 Tubing Connections ��������������������������������������������������� 21 Leak Testing ���������������������������������������������������������������22
Wiring ���������������������������������������������������������23-26
EcoNet™ Control Communications ���������������������������23 Control Wiring ������������������������������������������������������������23 EcoNet™ Control Board Communication Wiring ���������������������������������������������� 23 Conventional 24VAC Thermostat Control Wiring ������ 24 Conventional 24VAC Mode of Operation �������������������24 Typical Noncommunicating Thermostat Wiring Diagrams ���������������������������������������������������������24 Power Wiring ��������������������������������������������������������������25 Grounding �������������������������������������������������������������������26
Start-Up ������������������������������������������������������27-32
Start-Up ����������������������������������������������������������������������27 Checking Airflow ��������������������������������������������������������27 Evacuation Procedure ����������������������������������������������� 28 Final Leak Testing �������������������������������������������������������28
Checking Refrigerant Charge ���������������������� 29-32
Charging Units With R-410A Refrigerant ��������������������������������������������29 Confirm ID Airflow and Coils Are Clean ���������������������29 Measurement Device Setup ���������������������������������������29 Charging by Weight ����������������������������������������������������29 Setting Compressor Speed ����������������������������������������30 Gross Charging by Pressures ������������������������������������30 Final Charge by Subcooling ���������������������������������������31 Finishing Up Installation ��������������������������������������������� 31
Components and Controls ��������������������������33-51
Compressor Stator Heat (CSH) �������������������������33
Stator Heat Operation ������������������������������������������������ 33
High- and Low-Pressure
Controls (HPC and SPT) ������������������������������������33
Accumulator ���������������������������������������������������� 34 Outdoor Fan Motors����������������������������������������� 34 Outdoor Fan Blades ����������������������������������������� 34 Alternate Suction LINE THERMISTOR ������������� 35 Coil Thermistor ������������������������������������������������ 35 Compressor Sump Thermistor ������������������������� 35 Suction Pressure Transducer (SPT) ����������������� 36 Discharge Line Thermistor ������������������������������ 36 Power Inverter Compressor Controls �������������� 36 Choke/Inductor ������������������������������������������������ 37 Filter & Ferrite Rings ��������������������������������������� 37 EcoNet™ Variable Speed Unitary Control ������������������������������������������������ 38
Test and SW2 Buttons �����������������������������������������������38 Memory Card �������������������������������������������������������������39 Factory Programmed Superheat ��������������������������������39 Compressor Operation �����������������������������������������������40 Active Compressor Protection Mode �������������������������42 Default Operations Upon Component Failure ������������49 Test and Fault Recall Modes �������������������������������������� 49 Agency Test Mode Instructions ��������������������������������� 50
Accessories �����������������������������������������������������52
Air Conditioner Thermostat Warning Light Kit ���������� 52 Communicating 2 Wire Kit ���������������������������������������� 52
Diagnostics ������������������������������������������������ 53-73
Replacement of EcoNet™ Variable Speed Unitary Control Board ����������������������������������������������� 53 ICC Diagnostic Codes ������������������������������������������54-57 Electrical, Mechanical Checks Flowcharts ����������58-61 General Troubleshooting Chart ��������������������������������� 62 Service Analyzer Charts ��������������������������������������� 63-70 ICC Diagnostic Codes ������������������������������������������71-72 Cooling and Heating Mode Troubleshooting Tips ���� 73
Wiring Diagram ���������������������������������������������������������� 74
2
Page 3
IMPORTANT SAFETY INFORMATION
WARNINGS:
These instructions are intended as an aid to
qualified, licensed service personnel for proper installation, adjustment, and operation of this unit� Read these instructions thoroughly before
attempting installation or operation� Failure to
follow these instructions may result in improper installation, adjustment, service, or maintenance possibly resulting in fire, electrical shock, property damage, personal injury, or death.
• The unit must be permanently grounded. Failure
to do so can cause electrical shock resulting in severe personal injury or death.
• Turn off electric power at the fuse box or service
panel before making any electrical connections.
• Complete the ground connection before making
line voltage connections. Failure to do so can result in electrical shock, severe personal injury, or death.
• Disconnect all power to unit before starting
maintenance. Failure to do so can cause electrical shock resulting in severe personal injury or death.
• Never assume the unit is properly wired and/or grounded. Always test the unit cabinet with a noncontact voltage detector available at most electrical supply houses or home centers before removing access panels or coming into contact with the unit cabinet.
• Do not use oxygen to purge lines or pressurize system for leak test. Oxygen reacts violently with oil, which can cause an explosion resulting in
severe personal injury or death.
The top of the scroll compressor shell is hot� Touching the compressor top may result in serious personal injury�
The manufacturer’s warranty does not cover any damage or defect to the unit caused by the attachment or use of any components, accessories, or devices (other than those authorized by the manufacturer) into, onto, or in conjunction with
the air conditioner� You should be aware that the
use of unauthorized components, accessories,
or devices may adversely affect the operation of the air conditioner and may also endanger life and property. The manufacturer disclaims
any responsibility for such loss or injury resulting from the use of such unauthorized components, accessories, or devices�
CAUTIONS:
R-410A systems operate at approximately 60%
higher pressures (1�6 times) than R-22 systems� Do not use R-22 service equipment or components on R-410A equipment� Use appropriate care when using this refrigerant� Failure to exercise care may result in equipment damage or personal injury�
Only match this outdoor unit with a matched indoor
coil or air handler approved for use with this outdoor unit per the unit manufacturer’s specification sheet� The use of unmatched coils or air handler will likely result in a charge imbalance between the cooling and heating modes which can cause unsatisfactory operation including a high-pressure switch lockout condition�
Only use indoor coils approved for use on R-410A
systems� An R-22 coil will have a TXV or fixed restrictor device that is not designed to operate properly in an R-410A system and will result in serious operational issues� The R-22 coil could also contain mineral oil which is incompatible with the POE oil used in R-410A systems and could result in reliability issues with the compressor and TXVs�
When coil is installed over a finished ceiling and/or
living area, it is required that a secondary sheet metal condensate pan be constructed and installed under the entire unit� Failure to do so can result in property damage�
The compressor has an internal overload protector�
Under some conditions, it can take up to 2 hours for this overload to reset� Make sure overload has had time to reset before condemning the compressor�
UNIT MAY START SUDDENLY AND WITHOUT
WARNING� A flashing red light on the air conditioner/ defrost control indicates a call for unit operation is present at the air conditioner/defrost control� The air conditioner/defrost control will attempt to start unit after the anti-short cycle time expires, when a high or low pressure control automatically resets, or when the air conditioner/defrost control exits the lockout mode as the temperature rises above 5°F�
Safety
3
Page 4
GENERAL INFORMATION
WARNING:
Improper installation, or installation not made in accordance with these instructions, can result
in unsatisfactory operation and/or dangerous
conditions and can cause the related warranty not to apply.
The RP series of air conditioners are designed to operate with standard 24 VAC thermostats and air handlers or gas furnaces�
This installation instruction manual contains complete instructions for installation and setup using conventional 24 VAC controls� Please refer to the manufacturer’s specification sheets for complete performance data, thermostat, and accessory listings�
The information contained in this manual has been prepared to assist in the proper installation, operation, and maintenance of the air conditioning system�
General Information
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation� Homeowner should retain this manual for future reference�
To achieve optimum efficiency and capacity, the matching indoor cooling coils listed in the manufacturer’s specification sheet must be used for this model air conditioner�
Checking Product Received
Upon receiving unit, inspect it for any shipping damage� Claims for damage, either apparent or concealed, should be filed immediately with the shipping company� Check model number, electrical characteristics, and accessories to determine if they are correct� Check system components (indoor coil, outdoor unit, air handler/furnace, etc�) to make sure they are properly matched�
Application
Before specifying any air conditioner equipment, a survey of the structure and a heat loss and heat gain calculation must be made� A heat loss calculation involves identifying all surfaces and openings that lose heat to the surrounding air and quantifying that heat loss� A cooling heat gain calculation makes similar measurements and determines the amount of heat needed to be removed� A heat gain calculation also calculates the extra heat load caused by sunlight and by humidity removal� These factors must be considered before selecting an air conditioner system to provide year-round comfort� The Air Conditioning Contractors of America (ACCA) J Manual method of load calculation is one recognized procedure for determining the heating and cooling load�
After the proper equipment combination has been selected, satisfying both sensible and latent requirements, the system must be properly installed� Only then can the unit provide the comfort it was designed to provide�
There are several factors that installers must consider�
Outdoor unit location
Indoor unit blower speed and airflow
Proper equipment evacuation
Supply and return air duct design and sizing
Refrigerant charge
System air balancing
Diffuser and return air grille location and sizing
4
Page 5
GENERAL INFORMATION
VARIABLESPEEDR410AAIR CONDITIONINGOUTDOORUNITS
Startwith921050740502markupsandusethefollowinginformationasneeded.
FrontPage
Changethetitletoalignwiththetitleabove. Change()P17(17SEER)to()A20(20SEER)
Contentspg2
Updateasneeded.
ElectricalandPhysicalData
Electrical and Physical Data
Rev.11/15 Electrical
Compressor
Model
Number
()A20
24 160208/230 15.0/15.0 35 1.4 25 35 36 160208/230 20.1/20.1 35 3.5 35 45 48 160208/230 32.0/32.0 50 5.3 60 70 60 160208/230 34.1/34.1 50 5.3 60 80
Rev.11/15 Physical
Model
Number
()A20
24 22.23 1 3328/1796/1264 148(4195) 198 206 36 22.34 1 4313/2065/1050 193.6
48 32.45 1 6242/3212/1853 196(5556) 255 263 60 32.45 2 6173/2932/1466 376(10659) 300 307
Phase Frequency(Hz) Voltage(Volts)
FaceArea
Sq.Ft.[m²]
RatedLoad
Amperes
(RLA)
OutdoorCoil Refrig.Per
No.Rows CFM[L/s] NetLbs.
Locked
Rotor
Amperes
(LRA)
FanMotor
FullLoad Amperes
(FLA)
CircuitOz.
[g]
(5488)
FuseorHACRCircuit
Breaker
Minimum
Amperes
[kg]
236 244
Maximum
Amperes
Weight
Shipping
Lbs.[kg]
General Information
5
Page 6
“ L”
“W”
“H”
A
I
R
D
I
S
C
H
A
R
G
E
ALLOW 60” [1524mm]
OF CLEARANCE
AIR INLET LOUVERS ALLOW
6” [152mm] Min. OF CLEARANCE ALL SIDES
12” [305mm] RECCOMMENDED
SERVICE PANELS/
INLET CONNECTIONS / HIGH & LOW
VOLTAGE ACCESS
ALLOW 24” [ 610 mm] OF CLEARANCE
ST-A1226-02-00
R A 20 36 A J V C A
MINOR SERIES
Z
TYPE V - INVERTER
VOLTAGE J = 1 PH, 208-230/60
MAJOR SERIES
CAPACITY 24 = 24000 BTU/HR [7.03 kW] 36 = 36000 BTU/HR [10.55 kW] 48 = 48000 BTU/HR [14.07 kW] 60 = 60000 BTU/HR [17.58 kW]
20 SEER
AIR CONDITIONER
BRAND
CONTROLS C - COMMUNICATING
GENERAL INFORMATION
General Information
AIR INLET LOUVERS ALLOW 6" [152 mm] OF CLEARANCE ALL SIDES 12" [305 mm] RECOMMENDED
ALLOW 60" [1524mm] OF
CLEARANCE
SERVICE PANELS/ INLET CONNECTIONS / HIGH & LOW VOLTAGE ACCESS ALLOW 24" [610 mm] OF CLEARANCE
6
Page 7
Specifications
DIMENSIONAL DATA
DimensionalData
()A20 24 36 48 60 Height“H”inches(mm) 39(991) 39(991) 51(1295) 51(1295) Length“L”inches(mm) 33.75(857) 33.75(857) 35.75(908) 35.75(908) Width“W”inches(mm) 33.75(857) 33.75(857) 35.75(908) 35.75(908)
Proper Installation
Proper sizing and installation of this equipment is critical to achieve optimal performance� Use the information in this Installation Instruction Manual and reference the applicable manufacturer’s specification sheet when installing this product�
IMPORTANT: This product has been
designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropriate indoor components� However, proper refrigerant charge and proper airflow are critical to achieve rated capacity and efficiency� Installation of this product should follow the manufacturer’s refrigerant charging and airflow instructions� Failure to confirm proper charge
and airflow may reduce energy efficiency and shorten equipment life�
GENERAL INFORMATION
General Information
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
• INDOOR THERMOSTAT
7
Page 8
INSTALLATION
Choosing a Location
Location
IMPORTANT:
national building codes and ordinances for special installation requirements� Following location information will provide longer life and simplified servicing of the outdoor air conditioner�
Consult local and
NOTICE: These units must be installed
outdoors� No ductwork can be attached, or other modifications made, to the discharge grille� Modifications will affect performance or operation�
Operational Issues
IMPORTANT: Locate the unit
in a manner that will not prevent, impair, or compromise the performance of other equipment installed in proximity to the unit� Maintain all required minimum distances to gas and electric meters, dryer vents, and exhaust and inlet openings� In the absence of national codes or manufacturers’ recommendations, local code recommendations and requirements will take precedence�
• Refrigerant piping and wiring should be properly
sized and kept as short as possible to avoid capacity losses and increased operating costs�
• Locate the unit where water runoff will not create
a problem with the equipment� Position the unit away from the drip edge of the roof whenever possible� Units are weatherized, but can be affected by the following:
• Water pouring into the unit from the junction
of rooflines, without protective guttering� Large volumes of water entering the air conditioner while in operation can impact fan blade or motor life, and coil damage may occur to an air conditioner if moisture cannot drain from the unit under freezing conditions�
• Freezing moisture or sleeting conditions can
cause the cabinet to ice-over prematurely and prevent air conditioner operation, requiring backup heat, which generally results in less economical operation�
• Closely follow the clearance recommendations
on page 8�
• 24" [61.0 cm] to the service panel access
• 60" [152.4 cm] above air conditioner fan
discharge (unit top) to prevent recirculation
• 6" [15.2 cm] to air conditioner coil grille air
inlets
with 12" [30.5 cm] minimum recommended
Corrosive Environment
The metal parts of this unit may be subject to rust or deterioration if exposed to a corrosive environment� This oxidation could shorten the equipment’s useful life�
Corrosive elements include, but are not limited to, salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petroleum refineries�
If the unit is to be installed in an area where contaminants are likely to be a problem, special attention should be given to the equipment location and exposure�
• Avoid having lawn sprinkler heads spray directly
on the unit cabinet�
• In coastal areas, locate the unit on the side of
the building away from the waterfront�
• Shielding provided by a fence or shrubs may
give some protection, but cannot violate minimum airflow and service access clearances�
• Elevating the unit off its slab or base enough to
allow air circulation will help avoid holding water against the base pan�
WARNING: Disconnect all power
to unit before starting maintenance� Failure to do so can cause electrical shock resulting in severe personal injury or death�
Regular maintenance will reduce the buildup of contaminants and help to protect the unit’s finish�
• Frequent washing of the cabinet, fan blade, and
coil with fresh water will remove most of the salt or other contaminants that build up on the unit�
• Regular cleaning and waxing of the cabinet with
a good automobile polish will provide some protection�
• A good liquid cleaner may be used several times
a year to remove matter that will not wash off with water�
8
Page 9
INSTALLATION
SERVICE PANELS/
INLET CONNECTIONS
/ HIGH & LOW
VOLTAGE ACCESS
ALLOW 24” [610 mm] OF
CLEARANCE
ALLOW 60” [1524 mm]
OF CLEARANCE
AIR INLET LOUVERS ALLOW
6” [152 mm] Min. OF
CLEARANCE ALL SIDES
12” [305 mm] RECOMMENDED
ST-A1226-04-00
6" MIN. (152 mm) FOR 1.5 & 2 TON 9" MIN. (229 mm) FOR 2.5-5 TON 24" MIN. (610 mm)
ST-A1226-03-00
ELEVATE ABOVE
ANTICIPATE HIGH
SNOW FALL
DO NOT BLOCK
OPENINGS IN BASE PAN
BASE PAD
(CONCRETE OR OTHER SUITABLE
MATERIAL)
Choosing a Location (cont�)
For Units With Space Limitations
In the event that a space limitation exists, we will permit the following clearances:
Single-Unit Applications: Clearances below 6" [15.2 cm] will reduce unit capacity and efficiency. Do not reduce the 60" [152.4 cm] discharge or the 24" [61.0 cm] service clearances.
Multiple-Unit Applications: When multiple
condenser grille sides are aligned, a 6" [15.2 cm] clearance is recommended for 1.5 and 2 ton models and 9" [22.9 cm] for 2.5 ton to 5 ton
models� Two combined clearances below the minimum will reduce capacity and efficiency� Do
not reduce the 60" [152.4 cm] discharge or 24" [61.0 cm] service clearances.
Location
• If elevating a unit on a flat roof, use 4" x 4" [10.2 cm x 10.2 cm] or equivalent stringers
positioned to distribute unit weight evenly and prevent noise and vibration�
• Where snowfall is anticipated, raise the unit
above the base pad to prevent ice buildup and coil damage� Mount the unit high enough to be above the average accumulated area snowfall� See “Ground Snow Depth” chart on page 10 for representative snow depths�
NOTICE: Do not block drain openings on
bottom of unit�
• If unit must be elevated because of anticipated
snowfall, secure unit and elevating stand such that unit and/or stand will not tip over or fall off� Keep in mind that someone may try to climb on unit�
Customer Satisfaction Issues
• The air conditioner should be located away from
the living, sleeping, and recreational spaces of the owner and those spaces on adjoining property�
• To prevent noise transmission, the mounting pad
for the outdoor unit should not be connected to the structure and should be located a sufficient distance above grade to prevent ground water from entering the unit�
Unit Mounting
WARNING: Secure an elevated unit
and its elevating stand in order to prevent tipping� Failure to do so may result in severe personal injury or death�
Elevation of Unit
If elevating the air conditioner, either on a flat roof or on a slab, observe the following guidelines�
Factory-Preferred Tie-Down Method for High Wind or Seismic Loads
IMPORTANT: The manufacturer-
approved/recommended method is a guide to securing equipment for wind and seismic loads� Other methods might provide the same result, but the manufacturer method is the only one endorsed by the manufacturer for securing equipment where wind or earthquake damage can occur� Additional information is available in the PTS (Product Technical Support) section of the manufacturer’s Web sites MyRheem�com, or MyRuud�com and can be found as a listing under each outdoor model� If you do not have access to this site, your distributor can offer assistance�
9
Page 10
INSTALLATION
Choosing a Location (cont�)
Location
ALABAMA INDIANA MINNESOTA NEW MEXICO PENNSYLVANIA VIRGINIA
Huntsville 7 Evansville 12 Duluth 64 Albuquerque 4 Allentown 23 Dulles Airport 19
ARIZONA
Flagstaff 48 Indianapolis 21
Prescott 3 South Bend 44 Rochester 50
Winslow 7
ARKANSAS
Ft. Smith 5 Des Moines 22 Jackson 3 Buffalo 42 Williamsport 20
Little Rock 6 Dubuque 38 MISSOURI
CALIFORNIA
Blue Canyon 25 Waterloo 36 Kansas City 18 Rochester 38
Mt. Shasta 69
COLORADO
Alamosa 15 Dodge City 12
Colorado Springs 14 Goodland 14 Billings 17 Cape Hattaras 5 Aberdeen 42
Denver 15 Topeka 19 Glasgow 17 Charlotte 10 Huron 43 Beckley 51
Grand Junction 16 Wichita 11 Great Falls 16 Greensboro 11 Rapid City 14 Charleston 20
Pueblo 7
CONNECTICUT
Bridgeport 23 Lexington 12 Kalispell 53 Winston-Salem 17 Bristol 8
Hartford 29 Louisville 11 Missoula 23
New Haven 15
DELAWARE
Wilmington 13 Portland 62 Lincoln 20 Williston 25 Nashville 8 Milwaukee 32
GEORGIA MARYLAND
Athens 5 Baltimore 17 North Platte 15 Akron-Canton 15 Abilene 6 Casper 10
Macon 8
IDAHO
Boise 6 Nantucket 18 Valentine 22 Dayton 11 El Paso 5 Sheridan 25
Lewiston 9 Worcester 35
0 Pocatello 7
ILLINOIS
Chicago O’Hare 18 Detroit City 9 Reno 11
Chicago 22 Detroit Airport 17 Winnemucca 6 Oklahoma City 5 Wichita Falls 5
Moline 17
Peoria 16 Flint 28 Concord 66
Rockford 25 Grand Rapids 37
Springfield 23 Houghton Lake 56 Atlantic City 11 Eugene 17 Wendover 3
NOTICE:
Local records and experience must be considered when establishing the unit installation height� There is a 2% probability that
Fort Wayne 17 International Falls 43 Clayton 10 Erie 19 Lynchburg 16
IOWA
Burlington 17
Sioux City 33 Columbia 21
KANSAS
Concordia 23 Springfield 14
KENTUCKY
Covington 12 Helena 18 Wilmington 9
MAINE NEBRASKA
Caribou 100 Grand Island 30 Fargo 34 Memphis 5 Madison 32
MASSACHUSETTS
Boston 30 Scottsbluff 11 Columbus 10 Dallas 3 Lander 20
MICHIGAN
Alpena 53 Ely 9 Youngstown 12 Midland 2
Detroit – Willow Run
Lansing 42 Newark 15 Medford 8
Marquette 53 Pendleton 11 Burlington 37
Muskegon 43 Portland 10
Sault Ste. Marie 80 Salem 7
the ground snow depth shown in this table will be exceeded annually� Drifts have not been considered� This data represents 184
10
National Weather Service locations at which measurements are made and assumes a nationwide snow density of 12 lb�/ft�
GROUND SNOW DEPTH – INCHES
Minneapolis/St. Paul
St. Cloud 53 Albany 25 Pittsburgh 22 Richmond 12
MISSISSIPPI
St. Louis 16 Syracuse 35 Columbia 12 Spokane 41
MONTANA
Havre 24 Raleigh-Durham 10 Sioux Falls 38 Elkins 21
Norfolk 29
Omaha 20 Cleveland 16 Amarillo 10 Cheyenne 15
NEVADA
Elko 20 Toledo Express 8 Lubbock 10
NEW HAMPSHIRE
21
NEW JERSEY
50 Roswell 8 Harrisburg 23 National Airport 18
NEW YORK
Binghamton 35 Scranton 16 Roanoke 17
NYC – Kennedy Airport 18
NYC – LaGuardia Airport 18
NORTH CAROLINA
Asheville 12
NORTH DAKOTA
Bismarck 25 Knoxville 8 La Crosse 32
OHIO TEXAS WYOMING
Mansfield 17 Fort Worth 6
OKLAHOMA
Tulsa 8
OREGON
Burns City 24 Salt Lake City 8
Philadelphia 16 Norfolk 9
WASHINGTON
RHODE ISLAND
Providence 21 Quillayute 24
SOUTH CAROLINA
Greenville 4 Stampede Pass 51
SOUTH DAKOTA
TENNESSEE
Chattanooga 6 Green Bay 36
San Antonio 3
UTAH
Milford 16
VERMONT
Olympia 24
Seattle-Tacoma 14
Yakima 25
WEST VIRGINIA
Huntington 15
WISCONSIN
3
Page 11
Tools and Refrigerant
Ambient and Tube
Thermometers
Manifold
Gauge
Set
Brazing
Rods
Torch Nitrogen
Reclaimer
Recovery Cylinders
Allen Wrench
Crescent Wrench
INSTALLATION
Tools Required for Installing and Servicing R-410A Models
Manifold Sets: – Up to 800 PSIG High-Side – Up to 250 PSIG Low-Side – 550 PSIG Low-Side Retard Manifold Hoses: – Service Pressure Rating of 800 PSIG Recovery Cylinders: – 400 PSIG Pressure Rating – Dept� of Transportation 4BA400 or BW400
CAUTION: R-410A systems operate
at higher pressures than R-22 systems� Do not use R-22 service equipment or components on R-410A equipment�
Specifications of R-410A
Application: R-410A is not a drop-in replacement for R-22� Equipment designs must
accommodate its higher pressures� It cannot be retrofitted into R-22 air conditioners�
Physical Properties: R-410A has an atmospheric
boiling point of -62.9°F [-52.7°C] and its saturation pressure at 77°F [25°C] is 224.5 psig.
Composition: R-410A is a near-azeotropic mixture of 50% by weight difluoromethane (HFC-
32) and 50% by weight pentafluoroethane (HFC-
125)�
Pressure: The pressure of R-410A is approximately 60% (1�6 times) greater than R-22� Recovery and recycle equipment, pumps,
hoses, and the like must have design pressure ratings appropriate for R-410A� Manifold sets
need to range up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service pressure rating, DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, a mixture of R-410A and air can become combustible� R-410A and air should
never be mixed in tanks or supply lines or be allowed to accumulate in storage tanks� Leak checking should never be done with a mixture of R-410A and air� Leak-checking can
be performed safely with nitrogen or a mixture of R-410A and nitrogen�
Quick-Reference Guide For R-410A
• R-410A refrigerant operates at approximately
60% higher pressure (1�6 times) than R-22� Ensure that servicing equipment is designed to operate with R-410A�
• R-410A refrigerant cylinders are light rose in
color�
• R-410A, as with other HFCs, is only compatible
with POE oils�
• Vacuum pumps will not remove moisture from
POE oil used in R-410A systems�
• R-410A systems are to be charged with liquid
refrigerants� Prior to March 1999, R-410A refrigerant cylinders had a dip tube� These cylinders should be kept upright for equipment charging� Post-March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid charging of the equipment�
• Do not install a suction line filter drier in the
liquid line�
• A factory-approved biflow liquid line filter drier
is shipped with every unit and must be installed in the liquid line at the time of installation� Only manufacturer-approved liquid line filter driers can be used� These are Sporlan (CW083S) and Alco (80K083S) driers� These filter driers are rated for minimum working pressure of 600 psig� The filter drier will only have adequate moisture-holding capacity if the system is properly evacuated�
• Desiccant (drying agent) must be compatible for
POE oils and R-410A refrigerant�
Tools
11
Page 12
INSTALLATION
Replacement Units
Tubing
To prevent failure of a new unit, the existing line set must be correctly sized and cleaned or replaced� Care must be exercised that the expansion device is not plugged� For new and replacement units, a liquid line filter drier must be installed and refrigerant tubing must be properly sized� Test the oil for acid� If positive, a suction line filter drier is mandatory�
Indoor Coil
CAUTION: Only use evaporators
approved for use on R-410A systems that are specifically matched with the outdoor unit per the manufacturer’s specification sheets� Use of existing R-22 evaporators can introduce mineral oil to the R-410A refrigerant, forming two different liquids and decreasing oil return to the compressor� This can result in compressor failure�
REFER TO INDOOR COIL MANUFACTURER’S INSTALLATION INSTRUCTIONS.
IMPORTANT: The manufacturer is not
responsible for the performance and operation of a mismatched system or for a match listed with another manufacturer’s coil�
NOTICE: All outdoor units must be
installed with a matched TXV indoor coil� Refer to manufacturer’s outdoor unit specification sheet for approved indoor coils�
IMPORTANT: When replacing an
R-22 unit with an R-410A unit, either replace the line set or ensure that residual mineral oil is drained from existing lines including oil trapped in low spots�
The thermostatic expansion valve in the matching coil is specifically designed to operate with R-410A� DO NOT use an R-22 TXV or
evaporator� The existing evaporator must be replaced with the factory-specified TXV evaporator specifically designed for R-410A�
Location
Do not install the indoor coil in the return duct system of a gas or oil furnace� Provide a service inlet to the coil for inspection and cleaning� Keep the coil pitched toward the drain connection�
CAUTION: When coil is installed
over a finished ceiling and/or living area, it is required that a secondary condensate pan be installed under entire unit� Failure to do so can result in property damage�
12
Interconnecting Tubing
The purpose of this section is to specify the best construction/sizing practices for installing interconnection tubing between the indoor and outdoor unit�
Refrigerant Level Adjustment
All units are factory-charged with R-410A refrigerant to cover 15 feet of standard size interconnecting liquid and vapor lines not including the required liquid line drier� Refrigerant must be added for the filter/drier� Adjustment of charge may be necessary even if the application has exactly 15 feet of line set due to other installation variables such as pressure drop, vertical lift, and indoor coil size� For different lengths, adjust the charge as indicated below�
• 1/4" ± .3 oz./foot [6.4 mm ± 8.5 g/.30 m]
• 5/16" ± .4 oz./foot [7.9 mm ± 11.3 g/.30 m]
• 3/8" ± .6 oz./foot [9.5 mm ± 17.0 g/.30 m]
• 1/2" ± 1.2 oz./foot [12.7 mm ± 34.0 g/.30 m]
• 6 oz. required factory supplied field-installed
filter drier�
Charge Adjustment = (Line Set (oz./ft.) x Total Length) – Factory Charge for Line Set
Example: A three ton air conditioner unit with factory installed 3/8” liquid service valve requires 75 ft. of line set with a liquid line diameter of 1/2”.
Factory Charge for Line Set = 15 ft. x .6 oz. = 9 oz. Charge Adjustment = (1.2 oz. x 75 ft.) – 9 oz. =
+ 81 oz.
Page 13
Interconnecting Tubing (cont�)
INSTALLATION
Interconnecting Tubing and Fitting Losses
Refrigerant tubing is measured in terms of actual length and equivalent length� Actual length is used for refrigerant charge applications� Equivalent length takes into account pressure losses from
Equivalent Length for Fings ()
90° Short
Line Size
(in)
3/8 1.3 0.8 0.3 6 4 0.4 6 1/2 1.4 0.9 0.4 9 5 0.6 6 5/8 1.5 1 0.5 12 6 0.8 6 3/4 1.9 1.3 0.6 14 7 0.9 6 7/8 2.3 1.5 0.7 15 8 1 6
1-1/8 2.7 1.8 0.9 22 12 1.5 6
Radius
Elbow
90° Long
Radius Elbow
45°
Elbow
Liquid Line Selection
The purpose of the liquid line is to transport warm sub-cooled liquid refrigerant from the outdoor unit to the indoor unit in cooling mode� In heating mode the liquid line returns sub-cooled liquid from the indoor unit to the outdoor unit� It is important not to
allow the refrigerant to ash any superheated vapor
prior to the expansion device of the indoor coil� The ashing of refrigerant can occur for the follow­ing reasons:
• Low refrigerant charge
• Improperly selected liquid line size
• Absorption of heat prior to expansion device
• Excessive vertical rise between the condenser
and evaporator
Table 2 lists the equivalent length per 25’ of liquid
tubing length, ttings, vertical separation, acces­sories, and lter dryers. The table below references dierent commonly used equivalent lengths.
Table 1
Solenoid
Valve
line at various diameters up to 300’� The total pres­sure drop allowed for the liquid line is 50 PSI� The procedure for selecting the proper liquid line is as follows:
• Measure the total amount of vertical rise
• Measure the total amount of liquid line needed
• Add all of the equivalent lengths associated with any ttings or accessories using the table above.
• Add the total length and tting pressure drop.
This will equal your total equivalent length�
• Round-down the total equivalent length to the
closest value in Table 2�
• Reference Table 2 to verify the rounded-down
value of the calculated equivalent length is com­patible with the required vertical rise and diam­eter of liquid line�
Check
Valve
Site
Glass
Filter
Dryer
Tubing
Note: Elevaon is defined as the
highest point of the line set to the
lowest
13
Page 14
INSTALLATION
DimensionalData
()A20
24
36
48
60
Height“H”inches(mm)
39(991)
39(991)
51(1295)
51(1295)
LengthLinches(mm)
33.75(857)
33.75(857)
35.75(908)
35.75(908)
WidthWinches(mm)
33.75(857)
33.75(857)
35.75(908)
35.75(908)
InterconnectingTubing
Pg14.Replacethetablewiththefollowing:
Interconnecting Tubing (cont�)
Example: A 3-Ton air conditioner unit is installed 50’ below the ID unit, requires a 75’ of 1/2” diam­eter liquid line, and 4 90° LR elbows�
• Fitting Equivalent Length (ft.) = 4 x .9 = 3.6’
• Total Equivalent Length (ft.) = 75’ + 3.6’ = 78.6’
• Rounded-down value (ft.) = 75’
Liquid Line
R-410A System
Capacity
Model
37 3/8" [9.53]
(Exerpt from Table 2, page 17)
Tubing
Long Line Set Applications
Size
Connection
Size (Inch I.D.) [mm]
Liquid Line
Size (Inch
O.D.) [mm]
1/4 [6.35] 25 [7.62]
5/16 [7.94] 25 [7.62] 50 [15.24] 60 [18.29] 45 [13.72] 35 [10.67] 20 [6.1] 5 [1.52]
3/8 [9.53] 25 [7.62] 50 [15.24] 75 [22.86] 80 [24.38] 80 [24.38] 75 [22.86] 70 [21.34] 65 [19.81] 60 [18.29] 55 [16.76] 50 [15.24] 45 [13.72]
7/16 [11.12] 25 [7.62] 50 [15.24] 75 [22.86] 95 [28.96] 90 [27.43] 90 [27.43] 85 [25.91] 85 [25.91] 85 [25.91] 80 [24.38] 80 [24.38] 80 [24.38]
1/2 [12.71] 25 [7.62] 50 [15.24] 75 [22.86] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 90 [27.43] 90 [27.43] 90 [27.43]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [45.72] 150 [45.72] 175 [53.34] 200 [60.96] 225 [68.58] 250 [76.20] 275 [83.82] 300 [91.44]
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
Long line set applications are dened as applica­tions that require accessories or alternate construc­tion methods� The following are special consider­ations that need to be addressed when installing a long line set application:
• Additional refrigerant charge
• Fitting losses and maximum equivalent length
considerations
• Refrigerant migration during the o cycle
• Oil return to the compressor
• Capacity losses
• System oil level adjustment
This application is acceptable because the 50’ vertical rise is less than the maximum rise of 75’ for this application� The application is also considered to have a long line set� Reference the long line set section of the I&O for detail�
Liquid Line Size
Elevation (Above or Below) Indoor Coil
Total
Maximum
Length - Feet [m]
Equivalent
Vertical Separation - Feet [m]
N/R N/R N/R N/R N/R
ODModel Compressor NameplateOil
Charge(oz) ()A2024 ()A2036
ZPV0212EZE9130 40
()A2048 ZPV0342EZE9130 40 ()A2060 ZPV038CEZE9130 40
Table 2 is used to determine if the application is
considered to have a long line set� The region of
the chart that is shaded grey is considered to be a long line set application.
Oil Level Adjustments for Long Line Set Applications
Additional oil will need to be added for long line set applications� (Ref� Table 2)� Below is the equation for the oil level adjustment and the compressor name
plate oil charge for the dierent od units.
Oil to be Added = [(Charge Adjustment + OD
Unit Name Plate Charge (oz.)) x (0.022) – [(0.10) x (Compressor Name Plate Oil Charge (oz.))]
Example: An application requires 125ft of line set
with a liquid line diameter of 3/8”, Charge Adjust-
ment = 52.4 oz., Name Plate Charge = 107 oz., Name Plate Oil Charge = 25 oz., Oil to be Added = ((52.4 oz. +107 oz.) x .022) – (.10 x 25 oz.) = 1.0 oz.
14
Page 15
Interconnecting Tubing (cont�)
INSTALLATION
Suction Line Selection
Purpose of the suction line is to return superheated vapor to the condensing unit from the evaporator in cooling mode� While in heating mode the suction line transports discharge vapor to the indoor unit from the outdoor unit� Proper suction line sizing is important because it plays an important role in returning oil to the compressor to prevent potential damage to the bearings, valves, and scroll sets� Also, an improperly sized suction line can dra­matically reduce capacity and performance of the system� The procedure for selecting the proper suction line is as follows:
• The total amount of suction line needed
• Add all of the equivalent lengths associated with any ttings or accessories using the table on
previous page�
• Add the total length and tting pressure drop.
This will equal your total equivalent length�
• Reference Table 2 to verify that the calculated
equivalent length falls within the compatibility region of the chart�
• Verify Table 3 to verify the capacity dierence is
compatible with the application�
Outdoor Unit Level or Near Level to Indoor Section Line Set
Refrigerant Migration During Off Cycle
Long line set applications can require a consider­able amount of additional refrigerant� This addition­al refrigerant needs to be managed throughout the entire ambient operating envelope that the system will go through during its life cycle. O-Cycle mi­gration is where excess refrigerant condenses and migrates to the lowest part of the system� Exces­sive build-up of refrigerant at the compressor will result in poor reliability and noisy operation during startup� This section demonstrates the required accessories and unit conguration for dierent ap­plications�
Tubing
REFERENCE TABLE 2 FOR
MAXIMUM LENGTH LIMITATIONS
IDEALLY, LINE SET SLOPES AWAY
SUB-COOLING PRIOR TO
THROTTLEING DEVICE, INSULATED
FROM OUTDOOR. VERIFY
LIQUID LINE.
ST-A1219-01-01
15
Page 16
INSTALLATION
OUTDOOR UNIT BELOW INDOOR SECTION LINE SET
Interconnecting Tubing (cont�)
Tubing
For applications that are considered to have a long line set with the outdoor unit and indoor unit on the same level the following is required:
• EXV on the indoor unit (standard equipment)
• Insulated liquid and suction line for in uncondi-
tioned space
Outdoor Unit Below Indoor Section Line Set
INSULATE LIQUID
AND SUCTION
LINE
• Vapor line should slope toward the indoor unit
• Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments spelled out in this document and the outdoor units I&O
• Verify at least 5°F sub-cooling at the ID unit prior
to throttling device
INVERT TRAP
EVEN WITH TOP
OF THE COIL
REFERENCE TABLE 2 FOR
MAXIMUM LENGTH LIMITATIONS
For applications that are considered to have a long line set with the outdoor unit below the indoor unit the following is required:
• EXV at the IDunit (standard equipment)
• Inverted vapor-line trap (Reference Figure 3)
• Insulated liquid and suction line
• Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments spelled out in this document and the outdoor units I&O
16
ST-A1219-02-01
Figure 4
• Measure pressure at the liquid line service valve
and prior to expansion device� Verify that it is not greater than 50 PSI
• For elevations greater that 25’ can expect a
lower sub-cooling
Page 17
Interconnecting Tubing (cont�)
p
g
Outdoor Unit Above Indoor Unit
Outdoor Unit Above Indoor Unit
INSTALLATION
Tubing
Verify sub-cooling prior
to throlin
device
Insulated liquid and
sucon line
TXV or EEV at indoor
eva
Figure 5
Reference Table 2
for elevaon
limitaons
orator
For applications that are considered to have a long line set with the outdoor unit above the indoor unit the following is required:
• EXV at the indoor unit (standard equipment)
• Insulated liquid and suction line
• Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments spelled out in this document and the outdoor units I&O
• Verify at least 5°F sub-cooling at the ID unit prior
to throttling device
17
Page 18
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
Grey=Thisapplicationisacceptable,butthelonglineguidelinesmustbefollowed.ReferenceLongLineSetsectionintheI&O.
INSTALLATION
Liquid Line Size
NOTES:
N/R = Application not recommended.
60 3/8" [9.53]
48 3/8" [9.53]
36 3/8" [9.53]
R-410A System
Capacity Model
Size (Inch I.D.)
3/8" [9.53]24
Connection
[mm]
Interconnecting Tubing
Liquid Line
Tubing
7/16 [11.12] 25 [7.62] 50 [15.24] 60 [18.29] 55 [16.76] 50 [15.24] 45 [13.72] 40 [12.19] 35 [10.67] 35 [10.67] 30 [9.14] 25 [7.62] 20 [6.1]
1/2 [12.71] 25 [7.62] 50 [15.24] 65 [19.81] 65 [19.81] 60 [18.29] 60 [18.29] 55 [16.76] 55 [16.76] 55 [16.76] 50 [15.24] 50 [15.24] 45 [13.72]
3/8 [9.53] 25 [7.62] 50 [15.24] 40 [12.19] 30 [9.14] 20 [6.1] 10 [3.05] N/R N/R N/R N/R N/R N/R
5/16 [7.94] 25 [7.62] 10 [3.05] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1/4 [6.35]
7/16 [11.12] 25 [7.62] 50 [15.24] 75 [22.86] 80 [24.38] 75 [22.86] 75 [22.86] 70 [21.34] 70 [21.34] 65 [19.81] 65 [19.81] 60 [18.29] 60 [18.29]
1/2 [12.71] 25 [7.62] 50 [15.24] 75 [22.86] 85 [25.91] 85 [25.91] 80 [24.38] 80 [24.38] 80 [24.38] 80 [24.38] 75 [22.86] 75 [22.86] 75 [22.86]
3/8 [9.53] 25 [7.62] 50 [15.24] 70 [21.34] 65 [19.81] 60 [18.29] 55 [16.76] 50 [15.24] 40 [12.19] 35 [10.67] 30 [9.14] 25 [7.62] 20 [6.1]
5/16 [7.94] 25 [7.62] 50 [15.24] 35 [10.67] 20 [6.1] N/R N/R N/R N/R N/R N/R N/R N/R
1/2 [12.71] 25 [7.62] 50 [15.24] 75 [22.86] 95 [28.96] 95 [28.96] 90 [27.43] 90 [27.43] 90 [27.43] 90 [27.43] 90 [27.43] 85 [25.91] 85 [25.91]
1/4 [6.35] 20 [6.1]
7/16 [11.12] 25 [7.62] 50 [15.24] 75 [22.86] 90 [27.43] 90 [27.43] 85 [25.91] 85 [25.91] 80 [24.38] 80 [24.38] 80 [24.38] 75 [22.86] 75 [22.86]
5/16 [7.94] 25 [7.62] 50 [15.24] 60 [18.29] 45 [13.72] 30 [9.14] 20 [6.1] 5 [1.52] N/R N/R N/R N/R N/R
3/8 [9.53] 25 [7.62] 50 [15.24] 75 [22.86] 80 [24.38] 75 [22.86] 70 [21.34] 65 [19.81] 60 [18.29] 55 [16.76] 50 [15.24] 50 [15.24] 45 [13.72]
1/2 [12.71] 25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 100 [30.48] 100 [30.48] 100 [30.48] 100 [30.48] 100 [30.48] 100 [30.48] 95 [28.96] 95 [28.96]
1/4 [6.35] 25 [7.62]
7/16 [11.12] 25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 90 [27.43] 90 [27.43]
5/16 [7.94] 25 [7.62] 50 [15.24] 75 [22.86] 80 [24.38] 75 [22.86] 70 [21.34] 60 [18.29] 55 [16.76] 50 [15.24] 45 [13.72] 40 [12.19] 35 [10.67]
3/8 [9.53] 25 [7.62] 50 [15.24] 75 [22.86] 95 [28.96] 90 [27.43] 90 [27.43] 90 [27.43] 85 [25.91] 85 [25.91] 80 [24.38] 80 [24.38] 80 [24.38]
(Inch O.D.)
1/4 [6.35] 25 [7.62] 50 [15.24] 35 [10.67] 15 [4.57] N/R N/R N/R N/R N/R N/R N/R N/R
[mm]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [45.72] 150 [45.72] 175 [53.34] 200 [60.96] 225 [68.58] 250 [76.20] 275 [83.82] 300 [91.44]
Maximum Vertical Separation - Feet [m]
Elevation Above or Below Indoor Coil
Total Equivalent Length - Feet [m]
Liquid Line Size
18
Page 19
N/R N/R N/R N/R N/R N/R
Allcalculationsaccumea3/8"liquidline
INSTALLATION
R-410A System
NOTES:
N/R = Application not recommended.
60 3/4" [19.06]
48 3/4" [19.06]
36 3/4" [19.06]
24 3/4" [19.06]
Capacity Model
Connection Size
(Inch I.D.) [mm]
Vapor Line
Interconnecting Tubing (cont.)
1-1/8 [28.58] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1 [25.4] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
7/8 [22.23] 1.00 0.99 0.99 0.98 0.98 0.97 N/R N/R N/R N/R N/R N/R
3/4 [19.05] 0.97 0.93 0.89 0.87 0.84 0.83 N/R N/R N/R N/R N/R N/R
5/8 [15.88] 0.99 0.98 0.96 0.95 0.94 0.92
1-1/8 [28.58] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1 [25.4] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
7/8 [22.23] 1.00 0.99 0.99 0.98 0.98 0.97 0.98 0.97 0.97 0.96 0.95 0.95
3/4 [19.05] 0.98 0.94 0.91 0.89 0.87 0.84 0.83 0.81 0.8 0.82 0.81 0.83
5/8 [15.88] 0.99 0.98 0.98 0.96 0.95 0.94 0.93 0.92 0.91 0.9 0.89 0.88
1-1/8 [28.58] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1 [25.4] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
7/8 [22.23] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
3/4 [19.05] 1.00 0.99 0.98 0.98 0.97 0.96 0.95 0.94 0.94 0.93 0.93 0.92
5/8 [15.88] 0.98 0.96 0.94 0.92 0.9 0.89 0.87 0.85 0.84 0.83 0.84 0.82
1-1/8 [28.58] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1 [25.4] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
7/8 [22.23] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
3/4 [19.05] 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.98 0.98 0.98 0.97 0.97
5/8 [15.88] 0.99 0.99 0.98 0.97 0.96 0.96 0.94 0.93 0.92 0.91 0.9 0.9
Vapor Line Size
(Inch O.D.)
[mm]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [45.72] 150 [45.72] 175 [53.34] 200 [60.96] 225 [68.58] 250 [76.20] 275 [83.82] 300 [91.44]
Total Equivalent Length - Feet [m]
Capacity Multiplier Table
Tubing
Vapor Line Selection Chart
19
Page 20
INSTALLATION
Interconnecting Tubing (cont�)
Tubing Installation
Observe the following when installing correctly sized type “L” refrigerant tubing between the condensing unit and evaporator coil:
• Check the tables on pages 18 and 19 for the
correct suction line size and liquid line size�
If a portion of the liquid line passes through a very hot area where liquid refrigerant can be heated to form vapor, insulating the liquid line is required.
• Use clean, dehydrated, sealed refrigeration-
grade tubing�
• Always keep tubing sealed until tubing is in place
and connections are to be made�
Tubing
• A high-quality biflow filter drier is included with
all R-410A air conditioner units and must be installed in the liquid line upon unit installation�
• When replacing an R-22 system with an R-410A
system and the line set is not replaced, use a flush kit available through aftermarket stores such as Prostock�
• If tubing has been cut, make sure ends are
deburred while holding in a position to prevent chips from falling into tubing� Burrs such as those caused by tubing cutters can affect performance dramatically, particularly on small liquid line sizes�
• For best operation, keep tubing run as short as
possible with a minimum number of elbows or bends�
• Locations where the tubing will be exposed to
mechanical damage should be avoided� If it is necessary to use such locations, the copper tubing should be housed to prevent damage�
20
Page 21
INSTALLATION
TEMPORARY
HANGER
PERMANENT
HANGER
ST-A1226-05-00
Interconnecting Tubing
• If tubing is to be run underground, it must be run
in a sealed watertight chase�
• Use care in routing tubing and do not kink or
twist� Use a good tubing bender on the vapor line to prevent kinking�
• Route the tubing using temporary hangers; then
straighten the tubing and install permanent hangers� Line must be adequately supported�
• If the vapor line comes in contact with inside
walls, ceiling, or flooring, the vibration of the vapor line in the heating mode will result in noise inside the structure�
(cont�)
• Be certain both refrigerant shutoff valves at the
outdoor unit are closed�
Remove the caps and Schrader cores from the pressure ports to protect seals from heat damage� Both the Schrader valves and the service valves have seals that may be damaged by excessive heat�
Tubing
• Blow out the liquid and vapor lines with dry
nitrogen before connecting to the outdoor unit and indoor coil� Any debris in the line set will end
up plugging the expansion device�
Tubing Connections
Indoor coils have only a holding charge of dry nitrogen� Keep all tube ends sealed until connections are to be made�
• Use type “L” copper refrigeration tubing. Braze
the connections with the following alloys:
– copper to copper, 5% silver minimum – copper to steel or brass, 15% silver minimum
Clean the inside of the fittings and outside of the tubing with a clean, dry cloth before soldering� Clean out debris, chips, dirt, etc�, that enters tubing or service valve connections�
Wrap valves with a wet rag or thermal barrier compound before applying heat�
21
Page 22
INSTALLATION
ST-A1226-06-00
Tubing
Interconnecting Tubing
Braze the tubing between the outdoor unit and
indoor coil� Flow dry nitrogen into a pressure port and through the tubing while brazing, but do not allow pressure inside tubing which can result in leaks� Once the system is full of nitrogen, the nitrogen regulator should be turned off to avoid pressuring the system�
(cont�)
The three stage inverter driven air conditioners are equipped with OD EXVs and matched to ID units that are also equipped with EXVs� During shipment, vibration has been found to move the EXV stem valve to a near closed position despite being set to a fully open position in the factory� Prior to leak testing it is recommended to apply 24VAC low voltage power to the ID and outdoor units making sure there is no call for operation by disconnecting the EcoNetTM control center or two stage legacy thermostat� By doing this, each control will immediately close their respective EXVs followed immediately by opening them to the wide open position, therefore, permitting free flow of nitrogen through the system�
22
• A
fter brazing, use an appropriate heatsink material
to cool the joint�
• Reinstall the Schrader cores into both pressure
ports�
• Do not allow the vapor line and liquid line to
be in contact with each other� This causes an undesirable heat transfer resulting in capacity loss and increased power consumption�
Leak Testing
Indoor coils have only a holding charge of dry nitrogen� Keep all tube ends sealed until connections are to be made�
WARNING: Do not use oxygen
to purge lines or pressurize system for leak test� Oxygen reacts violently with oil, which can cause an explosion resulting in severe personal injury or death�
ST-A1226-07-00
Pressurize line set and coil through service fittings with dry nitrogen to 150 PSIG maximum� Close nitrogen tank valve, let system sit for at least 15 minutes, and check to see if the pressure has dropped� If the pressure has dropped, check for leaks at the line set braze joints with soap bubbles and repair leak as necessary� Repeat pressure test� If line set and coil hold pressure, proceed with line set and coil evacuation (see page 21)�
• The vapor line must be insulated for its entire
length to prevent dripping (sweating) and prevent performance losses� Closed-cell foam insulation such as Armaflex and Rubatex® are satisfactory insulations for this purpose. Use 1/2" [12.7 mm] minimum insulation thickness� Additional insulation may be required for long runs�
Page 23
Control Wiring
WIRING
WARNING: Turn o electric power
at the fuse box or service panel before making any electrical connections� Also, the ground connection must be completed before making line voltage connections� Failure to do so can result in electrical shock, severe personal injury, or death�
EcoNet™ Control Communications
The EcoNet™ enabled (-)A20 series of air conditioners are designed to operate with conventional 24VAC Thermostat or an EcoNet™ communicating control center� If the (-)A20 outdoor unit is installed with a conventional 24VAC Thermostat some features and comfort settings will not be available�
Control Wiring
Running low-voltage wires in conduit with line voltage power wires is not recommended� Low­voltage wiring may be run through the insulated
bushing provided in the 7/8" [19 mm] hole in the
base panel, up to and attached to the pigtails from the bottom of the control box� Conduit can be run to the base panel if desired by removing the insulated bushing�
A thermostat and a 24-volt, 40 VA minimum transformer are required for the control circuit of the system� The furnace or the air handler transformer may be used if sufficient� See the wiring diagram for reference� Use “Wire Size” table on page 18 to size the 24-volt control wiring�
FIELD WIRE SIZE FOR 24-VOLT THERMOSTAT CIRCUITS
Thermo­stat Load (amps)
3.0
2.5
2.0
(1) Wire length equals twice the run distance� NOTICE: Do not use control wiring smaller than No� 18
AWG between thermostat and outdoor unit�
EcoNet™ Control Board Communication Wiring
The four 18 AWG low-voltage control wires must be installed from the control center to the indoor unit and from the indoor unit to the outdoor unit� The wire length between the control center and indoor unit should not be greater than 100 feet
SOLID COPPER WIRE – AWG
16 14 12 10 10 10 16 14 12 10 10 10 16 14 12 10 10 10
50 100 150 200 250 300
[15] [30] [46] [61] [76] [91] Length of Run – Feet [m] (1)
[30.5 m].
The wire length between the indoor unit and outdoor unit should not be greater than 125 feet
[38.1 m].
An EcoNet™ communicating HVAC system consists of these matched components:
EcoNet™ communicating air conditioner or
EcoNet™ communicating condensing unit�
EcoNet™ communicating air handler or
EcoNet™ communicating furnace�
EcoNet™ control center�
IMPORTANT: If the installed system
does not meet these requirements, the system must be wired using traditional control wiring� See “Conventional 24 VAC Thermostat Control Wiring” on page 24�
Do not use phone cord to connect indoor and outdoor units. This will damage the controls.
IMPORTANT: EcoNet™ require
systems continuous 18 AWG thermostat wire� The EcoNet™ Control requires four (4) control
wires for unit operation:
• R 24 VAC
• C 24 VAC common
• Data wire E1 Communications
• Data wire E2 Communications
Air Handler Furnace Air Conditioner Control Center Indoor Outdoor
E1 – – – – – – – – – – – E1– – – – – – – – – E1 E2 – – – – – – – – – – – E2 – – – – – – – – E2 R – – – – – – – – – – – – R – – – – – – – – – R C – – – – – – – – – – – – C – – – – – – – – – C
These wires need to be connected to each device control center, indoor air handler or furnace, and outdoor unit (air conditioner)�
Once all devices are connected, apply the line and low voltage to the system�
When all devices are powered, the control center should detect the indoor and outdoor units within 45 seconds�
Once the system is powered, the airflow settings will be configured for all devices�
Wiring
23
Page 24
WIRING
Line Voltage
Field-Installed
Factory Standard
(-)HMV
Air Handler
(-)A20
Air Conditioner
Outdoor Unit
Typical Two-Stage Thermostat
W1 W2 Y1 Y2
R C G
ODD
Y1
Y2
G
W2
C
R
DHM
Y
Y2
R C
W/BK W/BL
Y
Y/BL
R
BR
G
W1
Indoor
Unit
BR/WH
P
R
BR
Y/PK O/W
R
BR
E1
E2
C
R
Communicating
Thermostat
Outdoor
Unit
E1 E2
C
R
E1
E2
C
R
Line Voltage
Field-Installed
Factory Standard
Control Wiring (cont�)
Wiring
All adjustments for airflow are made at the control center from this point� Items that can be changed are airflow trim adjustment, dehumidification set point, cooling, heating airflow by tonage and electric heat airflow� The control center also has a wide range of fault and history information� To access any of the control center menus press the settings, status, or service icons at the bottom of the touch screen� Refer to the air handler or furnace installation manual and the communicating control center installation manual for further details on setting up the system and available adjustment options�
The communicating air handler or communicating furnace is equipped with a 24-volt, 50 VA transformer for proper system operation� See the
wiring diagram below for reference�
Conventional 24 VAC Thermostat Control Wiring
The (-)A20 series of air conditioners allow the installer to use conventional 24 VAC control wiring and a conventional thermostat for limited unit operation�
IMPORTANT: The preferred method
of unit installation and operation is by the EcoNet™ Communicating System, which allows access to
the fault history of the system� This diagnostic information is not available at the thermostat when the (-)A20 unit is using a conventional thermostat� See “EcoNet™ Control Board Communicating Wiring” on page 23�
Thermostat control wiring requires a minimum of six (6) wires for proper unit operation:
R – 24 VAC C – 24 VAC common Y – First-stage operation Y2 – Second-stage operation
24
Conventional 24VAC mode of Operation
When the variable speed (-)A20 outdoor unit is paired with a legacy thermostat, the unitary control will control the compressor speed based on the following logic:
If both Y2 + Y terminals are energized the
compressor will operate at the maximum speed permitted by the model data at the currently operating outdoor ambient temperature�
If the Y terminal ONLY is energized the compressor will run at the lowest compressor speed for 15 minutes� After this time, if the Y terminal ONLY is energized the compressor will be commanded to an intermediate compressor speed� (NOTICE: There will be no change in ID airflow at this time�)
When the outdoor ambient temperature rises above 100°F, but less than 110°F the unitary control has a function that will allow the compressor to be driven to a higher speed than when the outdoor ambient is below 100°F� This allows the unit to maintain a more comfortable space condition�
Typical Noncommunicating Thermostat Wiring Diagrams
The following figures show the typical wiring diagrams with (-)HMV air handler and (-)A20 air conditioner� Cooling airflows may need to be adjusted for homeowner comfort once the system is
operational�
WIRE COLOR CODE
BK – BLACK GY – GRAY W – WHITE BR – BROWN O – ORANGE Y – YELLOW BL – BLUE PR – PURPLE G – GREEN R – RED
TYPICAL 2-STAGE THERMOSTAT: (-)A20 AIR CONDI­TIONER WITH ELECTRIC HEAT USING A TWO-STAGE THERMOST A T WITH DEHUMIDIFICATION
Page 25
Line Voltage
Field-Installed
Factory Standard
(-)HMV
Air Handler
(-)A20
Air Conditioner
Outdoor Unit
Typical Two-Stage Thermostat
W1 W2 Y1 Y2
R C G
ODD
Y1
Y2
G
W2
C
R
DHM
Y
Y2
R C
W/BK W/BL
Y
Y/BL
R
BR
G
W1
Line Voltage
Field-Installed
Factory Standard
(-)HMV
Air Handler
(-)A20
Air Conditioner
Outdoor Unit
Typical Two-Stage Thermostat
W1 W2 Y1 Y2
B R C G
ODD
B
Y1
Y2
G
W1
W2
C
R
Y
Y2
B R C
Humidistat
W/BK
W/BL
Y
Y/BL
BL
R
BR
G
Control Wiring (cont�)
NOTES: (1) FOR PROGRAMMING THERMOSTAT IN DUAL-FUEL APPLICATION, SEE
THERMOSTAT INSTALLATION INFORMATION. (2) FOR REMOTE SENSOR INSTALLATION, SEE THERMOSTAT INSTALLATION INFORMATION. (3) OPTIONAL PLENUM SENSOR. (4) FOR TWO STAGES, CONNECT W2 ON THERMOSTAT TO W2 ON THE CONTROL BOARD. (5) EMERGENCY HEAT (E) CONNECTION MAY NOT BE ALLOWED BY LOCAL CODES. (6) 2-STAGE HEAT PUMP ONLY.
R C
W2 W/E
Y
(5)
(6)
Y2
G
V B + S –
R C Y
Y2
W2/V
R C
W
YL YH
G
Outdoor
Sensor
(2)
12 FT.
(3.7 M )
(-)A20
Air Conditioner
Outdoor Unit
Typical Two-Stage Thermostat
w/vs Blower Motor
Furnace
Control
B
WIRING
TYPICAL 2-STAGE THERMOSTAT: AIR CONDITIONER WITH ELECTRIC HEAT
TYPICAL 2-STAGE THERMOSTAT: (-)A20 AIR CONDI­TIONER WITH ELECTRIC HEAT USING A HUMIDISTAT FOR DEHUMIDIFICATION
TYPICAL 2-STAGE THERMOSTAT: AIR CONDITIONER
AND FURNACE
Wiring
Field wiring must comply with the National Electric Code (C�E�C� in Canada) and any applicable local code�
All wires are field installed� *Add jumper between W1 and W2 for maximum
temperature rise if desired�
Power Wiring
It is important that proper electrical power from a commercial utility is available at the air conditioner terminal block� Voltage ranges for operation are shown below�
VOLTAGE RANGES (60 HZ)
Nameplate
Voltage
208/230
(1 Phase)
Install a branch circuit disconnect within sight of the unit and of adequate size to handle the starting current (see “Electrical Data” on page 5�)
Operating Voltage Range at Copeland
Maximum Load Design Conditions for
Compressors
197–253
25
Page 26
WIRING
ST-A1241-02-X0
ST-A1241-01-X0
Control Wiring (cont�)
Power wiring must be run in a rain-tight conduit� Conduit must be run through the connector panel below the access cover (see page 6) and attached to the bottom of the control box�
Grounding
WARNING: The unit must be
permanently grounded� Failure to do so can cause electrical shock resulting in severe personal injury or death�
Wiring
Connect power wiring to line-voltage lugs located in the outdoor air conditioner unit electrical box� (See wiring diagram attached to unit access panel�)
Check all electrical connections, including factory wiring within the unit and make sure all connections are tight�
DO NOT connect aluminum field wire to the (-)A20
terminal block�
A grounding lug is provided near the line-voltage power entrance for a ground wire�
26
Page 27
Start-Up
Connect the communicating system according to the wiring diagram on pages 24 or 25� Once all devices are connected, power up the line and
Checking Airflow
START-UP
low voltage to the system� When all devices are powered, the thermostat should detect the indoor and outdoor units within 45 seconds�
Even though the unit is factory-charged with Refrigerant-410A, the charge must be checked to the charge table attached to the service panel and adjusted, if required� Allow a minimum of 15 minutes of run time before analyzing charge�
The air distribution system has the greatest effect on airflow� The duct system is totally controlled by the contractor� For this reason, the contractor should use only industry-recognized procedures�
The correct air quantity is critical to air conditioning systems� Proper operation, efficiency, compressor life, and humidity control depend on the correct balance between indoor load and outdoor unit capacity� Excessive indoor airflow increases the possibility of high humidity problems� Low indoor airflow reduces total capacity and causes coil icing� Serious harm can be done to the compressor by low airflow, such as that caused by refrigerant flooding�
Air conditioning systems require a specified airflow� Each ton of cooling requires between 320 and 450 cubic feet of air per minute (CFM)� See the manufacturer’s spec sheet for rated airflow for the system being installed�
Duct design and construction should be carefully done� System performance can be lowered dramatically through bad planning or workmanship�
The fully variable inverter driven systems have a dramatic variation between maximum and minimum airflow. For this reason only certain indoor air handlers and furnaces are approved as air moving matches to this product. When designing duct work this variation must be considered for optimal air delivery to all conditioned spaces. If the duct work is not adequately designed minimum airflow may not reach certain registers within the conditioned area.
Air supply diffusers must be selected and located carefully� They must be sized and positioned to deliver treated air along the perimeter of the space� If they are too small for their intended airflow, they become noisy� If they are not located properly, they cause drafts� Return air grilles must be properly sized to carry air back to the blower� If they are too small, they also cause noise�
The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home� This ensures a comfortable living space�
These simple mathematical formulas can be used to determine the CFM in a residential or light commercial system�
Electric resistance heaters can use:
CFM = volts x amps x 3.413
SHC x temp rise Gas furnaces can use:
CFM = Output Capacity in BTUH*
SHC x temp rise
*Refer to furnace data plate for furnace output capacity�
SHC = Sensible Heat Constant (see table below)
An air velocity meter or airflow hood can give a more accurate reading of the system CFM�
The measurement for temperature rise should be performed at the indoor coil inlet and near the outlet, but out of direct line of sight of the heater element or heat exchanger� For best results, measure air temperature at multiple points and average the measurements to obtain coil inlet and outlet temperatures�
Start-Up
Airflow
27
Page 28
START-UP
Evacuation and Leak Testing
ALTITUDE
(FEET)
Sea Level 1�08 6000 0�87
500
1000
2000
3000
4000
5000 0�90 20000 0�50
SENSIBLE HEAT
CONSTANT
(SHC)
1�07 7000 0�84
1�05 8000 0�81
1�01 9000 0�78
0�97 10000 0�75
0�94 15000 0�61
ALTITUDE
(FEET)
SENSIBLE HEAT
CONSTANT
(SHC)
Evacuation Procedure
Evacuation is the most important part of the entire service procedure� The life and efficiency of the equipment is dependent upon the thoroughness exercised by the serviceman when evacuating air and moisture from the system�
Air or nitrogen in the system causes high condensing temperatures and pressure, resulting in increased power input and nonverifiable performance�
Moisture chemically reacts with the refrigerant and oil to form corrosive hydrofluoric acid� This attacks motor windings and parts, causing breakdown�
• After adequate evacuation, open both service valves by removing both brass service valve
caps with an adjustable wrench. Insert a 3/16" [5 mm] or 5/16" [8 mm] hex wrench into the
stem and turn counterclockwise until the wrench stops�
• Gauges must be connected at this point to
check and adjust charge� Do not replace caps yet�
Evacuation
28
• After the system has been leak-checked and
proven sealed, connect the vacuum pump and evacuate system to 500 microns and hold 500 microns or less for at least 15 minutes� The vacuum pump must be connected to both the high and low sides of the system by connecting to the two pressure ports� Use the largest size connections available since restrictive service connections may lead to false readings because of pressure drop through the fittings�
IMPORTANT: Compressors
(especially scroll type) should never be used to evacuate the air conditioning system because internal electrical arcing may result in a damaged or failed compressor� Never run a scroll compressor while the system is in a vacuum or compressor failure will occur�
Final Leak Testing
After the unit has been properly evacuated and service valves opened, a halogen leak detector should be used to detect leaks in the system� All piping within the air conditioner, evaporator, and interconnecting tubing should be checked for leaks� If a leak is detected, the refrigerant should be recovered before repairing the leak� The Clean Air Act prohibits releasing refrigerant into the atmosphere�
Page 29
Checking Refrigerant Charge
START-UP
Charge for all systems should be checked against the Charging Chart inside the access panel cover�
WARNING:
compressor shell is hot� Touching the compressor top may result in serious personal injury�
The top of the scroll
IMPORTANT: Use factory-approved
charging method as outlined on the next page to ensure proper system charge�
NOTICE: The optimum refrigerant charge
for any outdoor unit matched with an indoor coil/air handler is affected by the application� Therefore, charging data has been developed to assist the field technician in optimizing the charge for all mounting configurations� Refer to the charging chart inside the access panel cover on the unit and choose the appropriate column for the specific application being installed or serviced� New installations utilizing either an RCF indoor coil installed on a gas furnace or an RH series air handler in the downflow or horizontal right-hand discharge may require removal of refrigerant since the factory charge could result in an overcharge condition�
Charging Units With R-410A Refrigerant
CAUTION:
approximately 60% higher (1�6 times) than R-22 pressures� Use appropriate care when using this refrigerant� Failure to exercise care may result in equipment damage or personal injury�
Charge for all systems should be checked against the Charging Chart inside the access panel cover�
R-410A pressures are
IMPORTANT: Do not operate the
compressor without charge in the system� Addition of R-410A will raise high-side pressures
(liquid and discharge)�
NOTICE: System maintenance is to be
performed by a qualified and certified technician� The following method is used for charging systems
in the cooling and heating mode� All steps listed should be performed to ensure proper charge has been set� For measuring pressures, the service valve port on the liquid valve (small valve) and the service valve port on the vapor valve (large valve) are to be used�
Confirm ID Airflow and Coils Are Clean
Confirm adequate indoor supply airflow prior to starting the system� See the Technical Specification Sheet for rated airflow for each ID/OD unit match� Air filter(s) and coils (indoor and outdoor) are to be clean and free of frost prior to starting the system� Supply airflow must be between 320 and 450 cfm per rated cooling ton prior to adjusting system charge� If a humidification system is installed, disengage it from operation prior to charge adjustment� Verify that the outdoor unit is operating
in high stage and the indoor air mover is delivering the high-stage airflow for this system size. Refer to
the “Checking Airflow” section of this manual for further instruction�
NOTICE: Verify system components
are matched according to the outdoor unit Specification Sheet�
Measurement Device Setup
1� With an R-410A gauge set, attach the high-
pressure hose to the access fitting on the liquid line (small) service valve at the OD unit�
2�
Attach the low-pressure hose to the vapor (large)
service valve at the OD unit
3. Attach a temperature probe within 6" [15.2 cm]
outside of the unit on the copper liquid line (small line)� For more accurate measurements, clean the copper line prior to measurement and use a calibrated clamp-on temperature probe or an insulated surface thermocouple�
Charging by Weight
NOTICE:
weight for the straight length of the refrigerant line set� For a new installation, evacuation of inter-
connecting tubing and indoor coil is adequate;
otherwise, evacuate the entire system� Use the factory charge shown in “Electrical and Physical Data” on page 5 of these instructions or on the unit data plate� Note that the charge value includes
charge required for 15 ft. [4.6 m] of standard-size
interconnecting liquid line without a filter drier� Calculate actual charge required with installed
liquid line size and length using:
1/4" [6.4 mm] O.D. = .3 oz./ft. [8.5 g/.30 m] 5/16" [7.9 mm] O.D. = .4 oz./ft. [11.3 g/.30 m] 3/8" [9.5 mm] O.D. = .6 oz./ft. [17.0 g/.30 m] 1/2" [12.7 mm] O.D. = 1.2 oz./ft. [34.0 g/.30 m]
Add 6 oz� for field-installed filter drier�
Adjust the system charge by
Refrigerant
29
Page 30
START-UP
Refrigerant
Checking Refrigerant Charge (cont�)
With an accurate scale (+/– 1 oz. [28.3 g]) or volumetric charging device, adjust charge difference between that shown on the unit data plate and that calculated for the new system installation� If the entire system has been evacuated, add the total calculated charge�
IMPORTANT: Charging by weight is
not always accurate since the application can affect the optimum refrigerant charge� Charging by weight is considered a starting point ONLY� Always check the charge by using the Charging Chart and adjust as necessary� CHARGING BY LIQUID SUBCOOLING MUST BE USED FOR FINAL CHARGE ADJUSTMENT�
With thermostat in the “Off” position, turn on the power to the furnace or air handler and the air conditioner� Start the air conditioner and the furnace or air handler with the thermostat� Verify that the outdoor unit is operating in high stage and the indoor air mover is delivering the correct airflow for the system size�
IMPORTANT: R-410A is a blended
refrigerant of R-32 and R-125 ( 50/50)� These two refrigerants have different saturation curves and therefore change state at different pressures and temperatures� If charge is added to the system in the vapor state, it is possible to have a disproportionate amount of each part of the R-410A blend which will cause unstable and inefficient operation� Therefore, it is critical to add R-410A in the liquid form only!
Setting Compressor Speed for Charge Adjustment
When operating the variable speed system in legacy mode, it is necessary to set the compressor speed by using the push buttons located on the control board in the outdoor unit� In order to set proper charge level the compressor speed must be operating at high speed/high stage� Use the following process to set the compressor speed for charge mode:
IMPORTANT: It is necessary to make
sure the ID unit is receiving a high stage operation
call (Y + Y2) from the thermostat before entering
this mode� Failure to do so can cause operating envelope, low pressure, or overcurrent faults causing the system to automatically shut down�
1� Depress the TEST & SW2 buttons at the same
time for 5 – 8 seconds�
2� After this time the dual seven segment LEDs
will show the first menu option (FC)�
3� Depress the TEST button one time and the
dual seven segment LEDs will show CS, which represents Compressor Speed�
4� Depress the SW2 button to enter the
Compressor Speed menu�
5� After entering the Compressor Speed menu the
dual seven segment will show a value of 3�
Note: If the dual seven segment LEDs show
a value of 1, the VS ODU does not have a
Y+Y2 signal. Check the wiring and thermostat
requested stage of operation before proceding�
6� At this point the control will send the
compressor to high stage based on the outdoor dry bulb temperature and model
data programed for the specific model being installed�
NOTICE: After Charge analysis is
complete the Test button must be pushed to exit the Compressor Speed menu and allow the thermostat to regain control of the outdoor unit� If this is not performed the unit will respond to operational calls from the thermostat, but will not reduce compressor speed for 24 hours� This will result in reduced efficiency for the variable speed system and may induce nuisance operating envelope, low pressure, or overcurrent faults�
Gross Charging by Pressures
1� Following airflow verification and charge weigh-
in, run the unit for a minimum of 15 minutes prior to noting pressures and temperature�
IMPORTANT: Indoor conditions
as measured at the indoor coil must be within
2°F [1.1°C] of the following during gross charge
(pressure) evaluation:
Cooling Mode: 80°F [26.7°C] Dry Bulb
NOTICE:
or below this range, run the system to bring the temperature down or run the electric heat/furnace
If the Indoor temperature is above
30
Page 31
Checking Refrigerant Charge (cont�)
START-UP
to bring the temperature within this range� System pressure values provided in the Charging Chart for outdoor dry bulbs corresponding to conditions outside of these ranges are provided as reference ONLY�
2� Note the Outdoor Dry Bulb Temperature,
ODDB° = _____°F [_____°C]. Unit charging is
recommended under the following outdoor conditions ONLY:
Cooling Mode ONLY: 55°F [12.8°C] outdoor dry bulb and above
3� Locate and note the design pressures� The
correct liquid and vapor pressures are found at the intersection of the installed system and the outdoor ambient temperature on the Charging Chart located inside the access panel cover�
Liquid Pressure: = ______psig; Vapor Pressure = ______psig
NOTICE:
provided are for gross charge check ONLY� These pressure values are typical, but may vary due to application� Evaporator load (indoor coil) will cause pressures to deviate� Note that all systems have unique pressure curves� The variation in the slope and value is determined by the component selection for that indoor/outdoor matched system� The variation from system to system seen in the table is normal� The values listed are for the applicable indoor coil match ONLY!
4� If the measured liquid pressure is below the
listed requirement for the given outdoor and indoor conditions, add charge� If the measured liquid pressure is above the listed requirement for the given outdoor and indoor conditions, remove charge�
The refrigerant pressures
Final Charge by Subcooling
1� After gross charging, note the designed
subcooling value� The correct subcooling value is found at the intersection of the installed system and the outdoor ambient temperature on the Charging Chart located inside the access panel cover�
SC° from Charging Chart = _____°F [_____°C].
IMPORTANT: Indoor conditions as
measured at the indoor coil are required to be
between 70°F [21.1°C] and 80°F [26.7°C] dry
bulb for fine-tuned unit charge adjustment� Unit charging is recommended under the following outdoor conditions ONLY:
Cooling Mode ONLY: 55°F [12.8°C] outdoor dry
bulb and above
NOTICE: If the indoor temperature is
above or below the recommended range, run the system to bring the temperature down or run the electric heat/furnace to bring the temperature up� System subcooling values provided in the Charging Chart for outdoor dry bulbs corresponding to conditions outside of the above range are provided as reference ONLY�
2. Note the measured Liquid Pressure, Pliq = ______psig, as measured from the liquid
(small) service valve� Use the Temperature Pressure Chart below to note the corresponding saturation temperature for R-410A at the measured liquid pressure�
Liquid Saturation Temperature, SAT°= _____°F [_____°C].
3. Note the liquid line temperature, Liq° = _____°F [_____°C], as measured from a temperature probe located within 6" [15.2 cm] outside of
the unit on the copper liquid line (small line)� It is recommended to use a calibrated clamp­on temperature probe or an insulated surface thermocouple�
4�
Subtract the liquid line temperature from the
saturation temperature to calculate subcooling�
SAT°_____°F SC°_____°F
5�
Adjust charge to obtain the specified subcooling
value� If the measured subcool is below the listed requirement for the given outdoor and indoor conditions, add charge� If the measured subcool is above the listed requirement for the given outdoor and indoor conditions, remove charge�
[_____°C]
[_____°C]
- Liq°_____°F
Finishing Up Installation
• Disconnect pressure gauges from pressure ports;
then replace the pressure port caps and tighten
adequately to seal caps� Do not overtighten.
• Replace the service valve caps finger-tight
and then tighten with an open-end wrench
adequately to seal caps� Do not overtighten.
• Replace control box cover and service panel and
install screws to secure service panel�
• Restore power to unit at disconnect if required.
[_____°C]
=
Refrigerant
31
Page 32
START-UP
Checking Refrigerant Charge (cont�)
• Configure indoor thermostat per the thermostat
installation instructions and set thermostat to desired mode and temperature�
NOTICE: Systems should not be fine-
tune charged below 50°F [13°C] outdoor dry bulb.
TEMPERATURE PRESSURE CHART
SATURATION
TEMP
(Deg. F) [Deg.
C]
-150 [-101]
-140 [-96]
-130 [-90]
-120 [-84]
-110 [-79]
-100 [-73]
R-410A
PSIG
-30 [-34]
-25 [-32]
-20 [-29]
-15 [-26]
-10 [-23]
-5 [-21]
SATURATION (Deg. F) [Deg.
TEMP
C]
R-410A
PSIG
17�9 35 [2] 107�5 100 [38] 317�4
22�0 40 [4] 118�5 105 [41] 340�6
26�4 45 [7] 130�2 110 [43] 365�1
31�3 50 [10] 142�7 115 [46] 390�9
36�5 55 [13] 156�0 120 [49] 418�0
42�2 60 [16] 170�1 125 [52] 446�5
IMPORTANT: Excessive use of
elbows in the refrigerant line set can produce excessive pressure drop� Follow industry best practices for installation� Installation and commissioning of this equipment is to be performed by trained and qualified HVAC professionals� For technical assistance, contact your Distributor Service Coordinator�
SATURATION
TEMP
(Deg. F) [Deg.
C]
R-410A
PSIG
SATURATION
TEMP
(Deg. F) [Deg.
C]
R-410A
PSIG
Refrigerant
-90 [-68]
-80 [-62]
-70 [-57]
-60 [-51] 0�4 15 [-9] 70�2 80 [27] 235�6 145 [63] 576�0
-50 [-46] 5�1 20 [-7] 78�5 85 [29] 254�5 150 [66] 612�8
-40 [-40] 10�9 25 [-4] 87�5 90 [32] 274�3
-35 [-37] 14�2 30 [-1] 97�2 95 [35] 295�3
0 [-18] 48�4 65 [18] 185�1 130 [54] 476�5
5 [-15] 55�1 70 [21] 201�0 135 [57] 508�0
10 [-12] 62�4 75 [24] 217�8 140 [60] 541�2
32
Page 33
COMPONENTS AND CONTROLS
Cooling Low
Pressure
(Operation)
95psig
Compressor Stator Heat (CSH)
CSH is standard on these models due to refrigerant migration during the off cycle that can result in a noisy start-up and compressor damage�
Stator Heat Operation:
Supplemental stator heat is required to prevent refrigerant migration in systems with relatively high system refrigerant charges�
Summary of operation:
• Stator heat is off whenever the compressor is
running�
At initial start-up or after extended shutdown periods the control board will automatically keep the system from operating if a flooded compressor condition is sensed�
Under specific conditions, the refrigerant in the system can condense to a liquid and collect in the sump of the compressor when the unit is not running� This will result in the compressor pumping liquid instead of gas on the next startup� Noisy startup and potential compressor damage can occur� To prevent this condition, an internal heat source is used to keep the compressor temperature elevated� The compressor temperature shall be checked in the OFF cycle for the proper temperature range�
If heat is required the control will energize the internal heater� Once the predetermined temperature has been reached the control will de-energize the heater�
Note: Compressor stator heat may only operate when the outdoor ambient temperature is less than 45°F� Upon initial install at temperatures less than this, the stator heat will keep the compressor from operating until the compressor shell is greater than 50°F�
Components
High- and Low-Pressure Controls (HPC and LPC)
These controls keep the compressor from operating in pressure ranges which can cause damage to the compressor� Both controls are in
the low-voltage control circuit� The high-pressure control (HPC) is an automatic-
reset which opens near 610 PSIG and closes near 420 PSIG�
The (-)A20 EcoNet™ enabled variable speed air conditioners are equipped with a pressure transducer for low pressure control, diagnostic, and refrigerant charging purposes� Algorithms exist to detect low/high refrigerant levels, and
detect/prevent unreliable compressor operation� The control will only indicate a low pressure
condition when a call for heat or cool is made� A low pressure condition will be declared per the
following table:
Cooling Low
Pressure
(No
Operation)
< 50psig
The control will respond when the pressure drops below the NO OPERATION levels as follows:
• Command the compressor to zero (0) RPM.
• The outdoor fan will remain operating for the
compressor off delay (5min)�
• Display the appropriate error code on the dual
seven segment LED and send an error status to the control center when operating with the EcoNet™ control center�
• If a demand persists after the delay and the
pressure has reached the operation level, then operation will be resumed� The seven segment display error code will be cleared and the unitary control will communicate the cleared error to the control center when operating in communicating mode�
33
Page 34
Components
COMPONENTS AND CONTROLS
High- and Low-Pressure Controls (HPC and LPC) (cont�)
• If a demand persists after the delay but the
suction pressure has not recovered, the outdoor fan will be turned off� If the pressure recovers any time after the delay then compressor operation will resume�
• If a pressure drops below the NO-operation
level 3 consecutive times during a single call for operation, the unitary control will keep the system from conditioning the space, and the appropriate error code will be displayed at the outdoor unit� The unitary control will also
Accumulator
All (-)A20 EcoNet™ enabled variable speed air conditioners are equipped with accumulators for the purpose of managing possible refrigerant
Outdoor Fan Motors
All (-)A20 air conditioners are equipped with fully variable outdoor fans controlled with a pulse width modulated signal (PWM) provided by the variable
communicate the lockout fault to the EcoNet™ control center when used in communicating mode�
• The suction pressure transducer (SPT) faults
will be recorded in historical data�
NOTICE: HPC and LPC are monitored by
the EcoNet™ System�
flood back issues that may occur at abnormal environmental conditions�
speed unitary control� The fan speed is selected to optimize the air conditioning performance based on compressor speed�
Outdoor Fan Blades
All (-)A20 air conditioners are equipped with swept fan blade designs� These fan blades allow for a reduced amount of vortex shedding over that of a standard paddle blade� The design also provides optimal scfm/watt efficiency which permit the (-)A20 models to operate as a low sound level
while delivering exceptional performance�
34
Page 35
COMPONENTS AND CONTROLS
Alternate Section Line Thermistor (OST)
The EcoNet™ enabled (-)A20 variable speed air conditioners are equipped with a suction line thermistor for the purposes of measuring suction gas temperature� The measured temperature is paired with the saturated suction temperature and used by the unitary control to calculate superheat and at the compressor for improved service diagnostics without requiring gage sets to be installed�
Figure 1: Thermister Location
IMPORTANT: The clamp on the vapor
line thermistor securely attaches to the alternate suction line at the 10 to 2 o’clock position with a corrosion resistant stainless steel clip� Insulation is factory installed over the suction line thermistor and suction line� This thermistor is provided with the coil thermistor as a single harness�
Components
Coil Thermistor (EVAPIN)
The EcoNet™ enabled (-)A20 variable speed air conditioners are equipped with a coil sensor that is used for the purposes of identifying low ambient cooling operational conditions� This thermistor is provided with the alternate suction line thermistor as a single harness�
Compressor Sump Thermistor (CPT)
The EcoNet™ enabled (-)A20 variable speed air conditioners utilize a sump thermistor to monitor the condition of the lower bearing in the compressor sump� As environmental variables change it is possible to have liquid refrigerant flood back to the compressor� Although the (-)A20 designs have been specified to minimize this from happening, occasions will occur where this may happen� During these times the EcoNet™ unitary control has been programmed with algorithms to slow the compressor speed until the liquid refrigerant exits the compressor shell�
The sump thermistor is also used to identify when compressor stator heat is needed during off cycles� See the compressor stator heat section for more details on this operation�
35
Page 36
Components
COMPONENTS AND CONTROLS
Suction Pressure Transducer (SPT)
The EcoNet™ enabled (-)A20 variable speed air conditioners are equipped with a 5vdc powered suction line pressure transducer� This device has an internal diaphragm that changes the resistance in line with the input voltage to return a modified voltage that is scalled from 0�5 to 4�5vdc� This range is linearly proportional to an absolute pressure range of 0 to 300psia�
Discharge Line Thermistor
The EcoNet™ enabled (-)A20 variable speed air conditioners are equipped with a discharge line thermistor� This thermistor is used to measure the discharge temperature at the compressor for the purposes of consistently operating the compressor within its designated operating envelope� At extreme environmental conditions the discharge temperature can rise to temperatures that may be unsafe for compressor operation� At these times the unitary control will automatically slow the compressor speed until a more reliable operating condition is obtained� Once this is done the unitary control will continually attempt to raise the compressor speed to maximize performance and conditioned space comfort�
NOTICE: This sensor is connected
directly to the power inverter�
Power Inverter Compressor Controls
The EcoNet™ enabled (-)A20 variable speed air conditioners are equipped with power inverter technology to vary the compressor speeds from as low as 1200RPM up to 7000RPM for maximum conditioned space comfort� Each inverter takes high voltage single phase incoming power and converts it to high voltage DC power� The output of each inverter is a simulated 3 phase AC signal that switches at just over 6500hz between each leg of the 3 phase compressor motor� There are 4 different power inverters (3�7kW, 5�5kW, 8�0kW and 8�0kW with back spin protection) that have been selected, designed, and qualified to meet the most extreme of conditions to insure continuous and reliable system operation� Each inverter is programmed to monitor compressor power consumption, motor torque, input current, input voltage, discharge pressure, and discharge temperature� When the inverter identifies a specific condition that may create a possible reliability risk it will automatically reduce the compressor speed until a more reliable
operating condition is obtained� Once this is done
36
Page 37
COMPONENTS AND CONTROLS
Power Inverter Compressor Controls (cont�)
the power inverter will continually attempt to raise the compressor speed to maximize performance and conditioned space comfort�
1. High voltage input (L1 – Black; L2 – Yellow)
2� Ground connection 3� Choke Connection
Choke/Inductor
For each power inverter used in the (-)A20 system there is a paired choke/inductor� The choke is designed as a low pass filter and increase inductance� By doing this the input power can be more efficiently used by the inverter and compressor�
4� High Pressure control connection (HPS) – with
automatic reset 5� Discharge line thermistor connection (Sensor) 6� Modbus communication connections (RS485)
7. Compressor connections (W-Black; V-Red;
U-Yellow)
Components
Filter & Ferrite Rings
For the (-)A20 model line there are 3 ferrite rings and one filter applied on all models� The ferrite rings are similar in purpose to the choke, whereas they create an inductive field around the assembled wires, but they do not filter the signals� The ferrite rings are applied only for the purpose of keeping the high voltage lines from cross contaminating one another and thereby
Filter
Ferrite Ring
creating unexpected operation and Electro Magnetic Interference� The single filter has been applied to eliminate high frequency “noise” from the incoming power line thereby making it more efficient for the inverter to convert the incoming high voltage single phase AC power into high voltage 3 phase DC power�
Ferrite Ring
37
Page 38
Components
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control
The EcoNet™ system is the next generation of the integrated compressor control (ICC) and is an integral part of the EcoNet™ communication network�
1� Thermostat Terminals 2� Communication wire terminals 3� Modbus unitary inverter communication
connection 4� Outdoor PSC Fan relay connections 5� Outdoor ambient thermistor connection 6� Coil Sensor (EVAPIN) and Alternate Suction
(OST) thermistor connections
7� Liquid line (OLT – for future use) and
compressor sump (CPT) connections 8� Outdoor ECM fan PWM output connection 9� Suction pressure transducer (SPT) connection 10� Liquid pressure transducer (LPT) connection 11� Electronic expansion valve connection 12� Reversing Valve Connections 13� 3 Amp fuse 14� Test and SW2 Button 15� Communications LEDs (ET – EcoNet™
communication is transmitting; RT –
EcoNet™communication is receiving)
16� Memory card connection
17� Dual seven segment LED – Displays status,
diagnostic codes, fault recall, compressor speed, superheat, and defrost menus
18. Dip Switches (Defrost [DFST] and EXV [EXV]
offset)
19. Dip Switches (EXV [1600/500] selection)
20� EXV Operational Lights (Green – EXV is
opening; Amber - EXV is closing)
CAUTION: UNIT MAY START
SUDDENLY AND WITHOUT WARNING�
TEST and SW2 Buttons
TEST and SW2 buttons are used to enter the following menus and modes:
• Test mode
• Forced Defrost
• Fault Code Recall Menu
• Compressor Speed Menu
• Superheat Menu
• Forced 6 hour defrost menu
38
15
4
3
2
1
17
5
14 13
76
16
98
18
19
10
11
12
20
Page 39
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
Memory Card
• The memory card stores all unit information.
• The unit information is called model data.
• The model data is all the information needed for
proper unit operation�
Components
39
Page 40
Components
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control
Installation Verification
• 24 VAC power on R and C must be present at
the ICC for it to operate�
• Line voltage must be present at the ICC for the
compressor and the outdoor fan to operate�
• The ICC displays a “0” for standby mode.
Standby mode indicates line voltage and 24 VAC are present at the ICC and there is not a call for unit operation from the serial communicating thermostat�
Zero (0) displayed� The unit is in standby�
Call for Compressor Operation
• If a call for compressor operation is received by
the ICC (high-stage/low-stage cooling�
• The ICC has an on/off fan delay of one (1)
second for each stage of heating or cooling�
• The ICC ignores the low-pressure control for the
first 90 seconds of compressor operation�
• The dual 7-segment LEDs display two (2)
operational status codes:
1) Low-Stage Cooling Operation – When the
ICC receives a call for first-stage cooling operation, a lower-case “c” is displayed on the dual 7-segment LEDs�
Lower-case “c” indicates Low-stage cooling operation�
2) High-Stage Cooling Operation – When the
ICC receives a call for second-stage cooling operation, an upper-case “C” is displayed on the dual 7-segment LEDs�
Upper-case “C” indicates high-stage cooling operation�
4-Minute Anti-Short-Cycle Timer
• The ICC has a built-in 4-minute time delay
between compressor operations to protect the compressor against short cycling� The dual 7-segment LEDs will flash “c” or “C” while the short-cycle timer is active and a call for unit operation is received�
Flashing lower-case "c"
A call for low-stage cooling has been received�
Flashing high-case "C"
A call for low-stage cooling has been received�
When a call for compressor operation is present, the 4-minute time delay can be bypassed by pressing the TEST button for 1 second and releasing� The compressor will begin operation and the dual 7-segment LEDs will stop flashing�
30-Second Minimum Run Timer
• The ICC has a built-in 30-second minimum unit
run time� If a call for compressor operation is received by the ICC and the call is removed, the compressor will continue to operate for 30 seconds� The dual 7-segment LEDs will flash “c” or “C” while the minimum run timer is active�
1-Second Compressor/Fan Delay
• The ICC starts/stops the outdoor fan one (1)
second after the start/stop of the compressor upon a call for compressor operation to minimize current inrush and/or voltage drop�
Compressor Operation
The (-)A20 series of EcoNet™ compatible outdoor air conditioners are equipped with legacy and communicating modes of operation� To maximize the performance and efficiency of these systems it is highly recommended to operate the (-)A20 systems in communicating mode� It is possible where communication signals are corrupted resulting in an application that may only utilize 24VAC legacy thermostat control� In these situations a 2 stage legacy thermostat is required�
Communicating Mode: Compressor Operation
When the (-)A20 series of outdoor air conditioners are installed with the EcoNet™ communicating control center the ICC will respond to building capacity demand� This demand is converted by the ICC into compressor RPMs which can vary in 1 RPM increments from a minimum speed to a maximum speed as defined by the outdoor
40
Page 41
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
unit model data� The magnitude of instantaneous compressor speed change will depend on the change in building load measured by the control center� Through this process the (-)A20 air conditioners only provide to the building the required amount of conditioning for optimal comfort and efficiency�
Legacy Mode: Low/Intermediate Speed Compressor Operation
When the (-)A20 series of outdoor air conditioners are installed in legacy mode with a 2 stage thermostat the low and intermediate compressor speed operation defaults to a time based logic� In this situation when a Y ONLY 24VAC signal is present, the ICC requests the inverter to run the minimum speed as defined by the model data for 15 minutes� After this time has passed and the Y ONLY 24VAC signal remains present the ICC will automatically increase the compressor speed to the intermediate speed as set by the model data� The ICC will keep the compressor at this speed until the call for compressor operation is removed
or a Y + Y2 signal is received from the legacy 2
stage thermostat�
IMPORTANT: This logic only occurs
for legacy installs� All compressor speeds will be requested discretely when the (-)A20 air conditioner is operating in communicating mode with the Rheem Control Center�
Indoor Airflow
Similar to the compressor operation outlined in the prior section, the Indoor airflow will be set by the control center based on the building load percentage� While operating in communicating mode after the ICC set the compressor speed it will transmit the necessary indoor airflow as identified by the outdoor unit model data to the control center where it will relay the information to the indoor air mover� When the (-)A20 air conditioner is matched with a constant CFM indoor air handler or furnace the ICC will request a discrete airflow for each compressor speed� Prior to the control center sending the requested air flow to the indoor air mover it will apply any offset or corrections as identified in the control center installer menu�
Outdoor Fan Control
The ICC can accommodate electronically commutated (ECM) or permanent start capacitor (PSC) outdoor fan motors� If the outdoor unit is equipped with a PSC motor, the model data will set the ICC firmware to energize the PSC fan relay when the outdoor fan motor is required to operate� If the outdoor unit is enabled with an ECM outdoor fan motor, the model data will set the ICC firmware
to utilize a pulse width modulated signal from the PWM terminal to control the outdoor fan motor� This output is a 80Hz pulse-width-modulated signal that can be varied from 0 to 100% duty cycle in 1% increments�
Secondary parameters such as rpm blocking ranges, startup mandatory ranges, shutdown ranges, fault induced rpm reduction, and low ambient cooling ranges can also impact the final calculated RPM value for the outdoor fan and compressor speeds.
Oil Circulation
During operation it is possible that an excess of refrigerant could be returned to the compressor causing a flooded compressor sump condition� If this event occurs the compressor reliability and/or life could be drastically reduced� For this reason the (-)A20 air conditioners are equipped with a sump thermistor (CPT) to monitor the sump temperature of the compressor� The ICC will evaluate the differential between the compressor sump temperature and the saturated suction temperature (aka sump superheat)� If the ICC concludes that the sump superheat is below the design limit, the ICC will request for the inverter to reduce the compressor RPM incrementally until the differential value has sufficiently increased� After the minimum sump superheat is obtained the ICC will request for the inverter to raise the compressor RPM a rate of no greater than 2000RPM per minute� During the ramp up period the ICC will continuously evaluate the sump superheat temperature and hold the compressor speed to a limit resulting in acceptable sump superheat�
Discharge Temperature (DLT) Fold back Protection
If the discharge line temperature, as read from the Modbus communication between the ICC and the inverter, reaches 235°F the ICC will request the inverter to reduce the compressor RPM incrementally until the discharge line temperature (DLT) reduces to 200°F� After the DLT reaches this level, the compressor RPM will be set to rise at a rate of no greater than 500RPM per minute until the compressor equals the requested speed from the requested capacity� During the ramp period the discharge line temperature will continue to be monitored�
Low Ambient Cooling
In some installations, a requirement exists for cooling a space when the outdoor ambient is below the normal range (<55°F), such as a computer room or other enclosed areas where a large heat load exists that must be kept cool� Low ambient cooling is a special cooling mode that allows the unit to provide cooling when
Components
41
Page 42
Components
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
the outdoor temperature is below 55°F� When necessary, the outdoor fan is cycled off to maintain condensing pressure and temperature in the system at an acceptable level�
Menu Structure
The (-)A20 product line is equipped with a dual 7-segment LED display and two push buttons (SW2 and TEST)� The display and push buttons work together to allow the technician access to fault recall, compressor speed locking, and current SH measurement (active for heat pumps only)�
The following process can be used to access any of these menus:
- Press the SW2 and TEST buttons for 5-8 seconds�
- After this time the dual seven segment LEDs will show the first menu option (FC)�
- To enter a menu, depress the SW2 button
- To toggle to the next menu depress the test button�
- No action for 5 seconds in the root menu structure will return the control to normal operation�
Menu Definition:
FC (Fault Codes) CS (Compressor Speeds)
• 3 (MAXIMUM Speed)
• 2 (INTSPEED Speed)
• 1 (MINIMUM Speed)
SH (Superheat Measurement) – Active for heat
pumps only�
• The display is to show the following options:
• HI = Superheat is ≥+5°F away from SH_SP
• hI = Superheat is between +5° and 1.5°F_away from SH_SP
• 00 = Superheat is between +1.5°F and -1.5°F away from SH_SP
• lo = Superheat is between -1.5°F and -5°F away from SH_SP
• LO = Superheat is ≤-5°F away from SH_SP.
dF (Defrost Mode) – Active for heat pumps only�
• 6 – Forced 6 hour defrost. When this mode
is selected the ICC will begin a 9 hour timer� During this time defrosts will be limited to 6 hour intervals between occurances�
Key:
FC = Fault Codes – by selecting this menu
the control will list the stored numerical fault codes in order of sequence by which they were stored� Depressing the SW2 button while a fault code is shown will increment to the next
fault� Depressing the TEST button will force the control back to the main menu�
CS = Compressor Speed – For this selection
menu to initiate the requested compressor speed, there must be an active call for compressor operation, the compressor must be operating, and the selection must be static for 5 seconds� The Compressor Start and Run, and Compressor Shut down algorithms will be used to obtain the requested compressor speed�
IMPORTANT: This mode should be
manually exited� If this menu is not exited manually the ICC will wait 24 hours before returning to normal operation� During this time the ICC will only request the selected compressor speed�
Active Compressor Protection Mode
Active Compressor Protection Mode
Active Envelope Management will be used to maintain the compressor within the specified operating envelope parameters� There are several boundaries of operation that must be recognized and respected for reliable compressor operation� Excursion beyond the specified boundaries will result in shortened compressor life or failure� These boundaries are over current, over/under voltages, over temperature, lubrication, and oil circulation� System and/or environmental conditions can force the compressor outside the safe operation area� Adjustments to the EXV, compressor speed, outdoor air flow, and indoor air flow can be used to modify operation and keep the compressor within limits while maintaining the highest possible capacity and efficiency� Operational algorithms for these adjustments are defined in the following sections�
L8 – Compressor Model Unknown – A900_O Inverter Identity Fault
If the inverter compressor model is not set, the inverter will keep the compressor from operation� The ICC will lock out the compressor to keep it from operating and flash an ”L” on the dual 7-segment LEDs followed by a 8�
IMPORTANT: This mode of active
protection must be manually reset
Active Protection – Code L8 – Open high-pressure control
42
Page 43
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
15- Compressor Overcurrent– T901_O Inverter Fault
If the inverter detects an output overcurrent condition to the compressor greater than the compressor/inverter envelope permits, the inverter will automatically begin to slow the compressor operation and reduce the output current� When operating with an ECM outdoor fan motor and in cooling mode the ICC will increase the OD fan speed� When operating in communicating and heating modes the ICC will request the indoor airflow to be increased to the maximum level permissible for the outdoor unit� If this fold back is not successful in bringing the compressor back into the designed operating envelope then the compressor will be kept from operating�
During either of the above conditions where the compressor has been stopped from operating the ICC will flash a “15” on the dual 7-segment LED�
L15 -Power Factor Correction Circuit Overcurrent – T903_O Inverter Fault
If the inverter detects an overcurrent condition in the power factor correction circuit the inverter will automatically shut the compressor off and keep it from operation� There is a 5 minute delay after this fault occurs before ICC will restart the compressor� If this fault occurs 3 times during a single call for operation the ICC will lock out the compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 15�
fault occurs 3 times in one hour the ICC will lock out the compressor to keep it from continuing to operate for one hour and flash an ”L” on the dual 7-segment LEDs followed by a 15�
IMPORTANT: This mode of active
protection must be manually reset�
L15 – DC Bus Under Voltage - A905_O Inverter Fault
If the inverter detects an under voltage condition in the DC bus circuit the inverter will automatically shut the compressor off and keep it from operation� The ICC will leave the compressor off until the DC bus voltage rises above 300Vdc� At this time the ICC will restart the compressor� If this fault occurs 3 times in one hour the ICC will lock out the compressor to keep it from continuing to operate for one hour and flash an ”L” on the dual 7-segment LEDs followed by a 15�
IMPORTANT: This mode of active
protection must be manually reset�
Components
IMPORTANT: This mode of active
protection must be manually reset
L15 - DC Bus Over Voltage – A904_O Inverter Fault
If the inverter detects an overvoltage condition in the DC bus circuit the inverter will automatically shut the compressor off and keep it from operation� The ICC will leave the compressor off until the DC bus voltage drops below 380Vdc� At this time the ICC will restart the compressor� If this
L15 – PIM Over-temp – T908_O Inverter Fault
If the inverter detects an over temperature condition in the Power Module circuit the inverter will automatically shut the compressor off and keep it from operation� The ICC will leave the compressor off until the circuit temperature is reduced to acceptable levels� At this time the ICC will restart the compressor� If this fault occurs 3 times during one call for operation the ICC will lock out the compressor to keep it from continuing to operate for one hour and flash an ”L” on the dual 7-segment LEDs followed by a 15
IMPORTANT: This mode of active
protection must be manually reset�
43
Page 44
Components
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
delay after this fault occurs before ICC will restart the compressor� If this fault occurs 3 times during a single call for operation the ICC will lock out the compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 15�
L15 – PFC Over-temp – T909_O Inverter Fault
If the inverter detects an over temperature condition in the Power Factor Correction circuit the inverter will automatically shut the compressor off and keep it from operation� The ICC will leave the compressor off until the circuit temperature is reduced to acceptable levels� At this time the ICC will restart the compressor� If this fault occurs 3 times during one call for operation the ICC will lock out the compressor to keep it from continuing to operate for one hour and flash an ”L” on the dual 7-segment LEDs followed by a 15�
IMPORTANT: This mode of active
protection must be manually reset�
L15 – Lost Rotor Position- A910_O Inverter Fault
If the inverter loses the rotor position in the compressor the inverter will automatically shut the compressor off and keep it from operation� There is a 5 minute delay after this fault occurs before ICC will restart the compressor� If this fault occurs 3 times during a single call for operation the ICC will lock out the compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 15�
IMPORTANT:This mode of active
protection must be manually reset�
IMPORTANT:This mode of active
protection must be manually reset�
L15 – DC Voltage Low – T914_O Inverter Fault
If the inverter detects an sustained low voltage condition in the DC bus circuit the inverter will automatically shut the compressor off and keep it from operation� The ICC will immediately restart the compressor� If this fault occurs 3 times during one call for operation the ICC will lock out the compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 15�
IMPORTANT: This mode of active
protection must be manually reset�
L15- PIM Temperature High – T917_O Inverter Fault
If the inverter identifies a high Power Module temperature thermistor reading the inverter will automatically shut the compressor off and keep it from operation� If this fault occurs 3 times during one call for operation the ICC will lock out the compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 15�
44
IMPORTANT: This mode of active
protection must be manually reset�
L15- Current Imbalance – T911_O Inverter Fault
If the inverter identifies an imbalanced current draw between the compressor 3 phase windings, the inverter will automatically shut the compressor off and keep it from operation� There is a 5 minute
Page 45
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
L15 – PFC & IGBT Temperature High – T918_O Inverter Fault
If the inverter identifies a high insulated-gate bipolar transistor (IGBT) temperature or power factor correction (PFC)circuit temperature reading the inverter will automatically shut the compressor off and keep it from operation� If this fault occurs 3 times during one call for operation the ICC will lock out the compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 15�
IMPORTANT: This mode of active
protection must be manually reset�
L16 – PIM Temp Sensor Open – A913_O Inverter Fault
If the inverter identifies an open power module temperature thermistor the inverter will automatically shut the compressor off and keep it from operation� The ICC will lock out the compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 16�
IMPORTANT: This mode of active
protection must be manually reset�
Components
L15- PIM Temperature Fold back – T922_O Inverter Fault
If the inverter detects a high Power Module temperature the inverter will automatically begin to slow the compressor operation� If this fold back is not successful in bringing the PIM temperature into the acceptable range then the compressor will be kept from operating� If this fault occurs 3 times during one call for operation ICC will lock out the compressor to keep it from continuing to operate and flash an “L” on the dual 7-segment LEDs followed by a 15�
IMPORTANT: This mode of active
protection must be manually reset�
L16- Microprocessor Fault – A912_O Inverter Fault
If the inverter identifies faulty microprocessor the inverter will automatically shut the compressor off and keep it from operation� The ICC will lock out the compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 16�
IMPORTANT: This mode of active
protection must be manually reset�
L16 – PFC MCU/DSP Communication Fault – A919_O Inverter Fault
If the inverter identifies a communication fault between the MCU (motor control unit) or DSP (digital signal processor), the inverter will automatically shut the compressor off and keep it from operation� If this fault occurs 3 times during one call for operation the ICC will lock out the compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 16�
IMPORTANT: This mode of active
protection must be manually reset�
L16 – Com/DSP Comm Fault – A920_O Inverter Fault
If the inverter identifies a communication with the DSP (digital signal processor), the inverter will automatically shut the compressor off and keep it from operation� If this fault occurs 3 times during one call for operation the ICC will lock out the
45
Page 46
Components
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 16�
IMPORTANT: This mode of active
protection must be manually reset�
L16 – PFC Temperature Sensor Open – A921_O Inverter Fault
If the inverter identifies an open power factor correction (PFC) temperature thermistor the inverter will automatically shut the compressor off and keep it from operation� The ICC will lock out the compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 16�
IMPORTANT: This mode of active
protection must be manually reset�
L16 – Discharge Line Temperature Fault – A927_O Inverter Fault
If the inverter identifies a faulty discharge line temperature thermistor the inverter will automatically shut the compressor off and keep it from operation� The ICC will lock out the compressor to keep it from continuing to operate and flash an ”L” on the dual 7-segment LEDs followed by a 16�
L16 – Discharge Temperature – T916_O Inverter Fault
If the ICC detects the compressor discharge temperature is greater 235°F the ICC will automatically begin to slow the compressor
operation until the temperature is ≤200°F. If
this fold back is not successful in bringing the compressor discharge temperature below 200°F prior to reaching the minimum compressor speed then the compressor will be kept from operating� After the compressor off delay is complete the ICC will return the compressor to operation� If this fault occurs 3 times during one call for operation the ICC will lock out the compressor to keep it from continuing to operate and flash an “L” on the dual 7-segment LEDs followed by a 16�
IMPORTANT: This mode of active
protection must be manually reset�
L16 – Communication Failure – A929_O Inverter Fault
If the inverter identifies a communication error with the ICC, the inverter will automatically shut the compressor off and keep it from operation� When this fault occurs the ICC will lock out the compressor to keep it from operating and flash an ”L” on the dual 7-segment LEDs followed by a 16�
IMPORTANT: This mode of active
protection must be manually reset�
46
IMPORTANT: This mode of active
protection must be automatic reset once the discharge line thermistor fault is corrected�
16 – HP Sensor Not Configured – T926_O
If the inverter is not configured or does not hold the configuration for the high pressure switch in the Modbus register, the inverter will provide this fault�
Page 47
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
L21 – Low Pressure Refrigerant – A/T 021_0 Low Refrigerant Pressure
• The ICC will display a flashing “21” followed by a
flashing “L” when a low-pressure control lockout occurs�
IMPORTANT: This mode of active
protection must be manually reset�
• The ICC addresses low-pressure control faults
differently depending on the mode of unit operation (cooling or heating mode)�
Cooling Mode
• If the LPC opens three (3) times during the same
call for cooling operation, the ICC will lock out the compressor to keep it from continuing to operate and flash a “21” on the dual 7-segment LEDs followed by an “L�”
IMPORTANT: This mode of active
protection is automatically reset�
L29 – High Refrigerant Pressure – A/T 923_O High Refrigerant Pressure
• If the HPC opens three (3) times during the same
call for unit operation, the ICC will lock out the compressor to keep it from continuing to operate and flash a “29” on the dual 7-segment LEDs followed by an “L�”
IMPORTANT: This mode of active
protection must be manually reset�
Components
Active Protection – Code 21L –
Open low-pressure
control
27- AC Input Under Voltage – A907_O_Inverter Fault
If the inverter detects input AC under voltage the ICC will automatically shut the compressor off and keep it from operation� The ICC will leave the compressor off until the input AC voltage
increases to ≥187VAC. At this time the ICC will
restart the compressor� While the compressor is off the ICC will display a 27 on the dual 7-segment LEDs�
IMPORTANT: This mode of active
protection is automatically reset�
28 – AC Input Over Voltage – A906_O Inverter Fault
If the inverter detects input AC over voltage the ICC will automatically shut the compressor off and keep it from operation� The ICC will leave the compressor off until the input AC voltage reduces
to ≤252VAC. At this time the ICC will restart the
compressor� While the compressor is off the ICC will display a 28 on the dual 7-segment LEDs�
Active Protection – Code 21L –
Open low-pressure
control
31 - Compressor Envelope Protection- T902_O Inverter Fault – Envelope Protection
If the inverter detects the calculated compressor torque is greater than the designed operating envelope permits the inverter will automatically begin to slow the compressor operation� If this fold back is not successful in bringing the compressor back into the designed operating envelope then the compressor will be kept from operating�
IMPORTANT: For a single stage or
two stage system it is very common during startup and shutdown for the compressor to venture outside the designed operating envelope� It is possible this fault can be seen on an installation when there is nothing globally wrong with the installation� For this reason the ICC will auto reset and return the system to operational condition after the compressor delay is complete�
Prior to restarting the compressor the ICC 7-segment display will flash a “31”�
47
Page 48
Components
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
35- Suction Temperature Thermistor Failure – A102_O
If the ICC identifies an issue with Outdoor Suction Thermistor (OST) sensor the ICC will flash a 35 on the dual 7-segment LEDs�
IMPORTANT: This mode of active
protection is automatically reset once the OAT sensor failure is corrected�
84 – Outside Ambient Thermistor Failure - T952 If the ICC identifies an issue with the Outdoor Ambient Thermistor (OAT) sensor the ICC will flash an 84 on the dual 7-segment LEDs�
IMPORTANT: This mode of active
protection is automatically reset once the OAT sensor failure is corrected�
36 – Suction Pressure Sensor Failure – A956_O
If the ICC identifies an issue with the Suction Pressure Transducer (SPT) sensor the ICC will flash a 36 on the dual 7-segment LEDs�
IMPORTANT: This mode of active
protection is automatically reset once the OAT sensor failure is corrected�
42- Compressor Temperature Thermistor Failure – T955_O
If the ICC identifies an issue with the Compressor Sump Thermistor (CPT) the ICC will flash a 42 on the dual 7-segment LEDs�
IMPORTANT: This mode of active
protection is automatically reset once the CPT sensor failure is corrected�
83 – Evaporator Temperature Thermistor Failure – T953_O
If the ICC identifies an issue with the Evaporator Temperature Thermistor (EVAPIN) sensor the ICC will flash an 83 on the dual 7-segment LEDs�
IMPORTANT: This mode of active
protection is automatically reset once the OAT sensor failure is corrected�
93 – Configuration Data Restore Failure – A950_O
If the ICC identifies issue(s) reading the model data from the memory card, the ICC will automatically shut the compressor off and keep it from operation� When this fault occurs the ICC will lock out the compressor to keep it from operating and flash an ”L” on the dual 7-segment LEDs followed by a 93�
IMPORTANT: This mode of active
protection must be manually reset�
D1 – Memory Card Configuration Data Write Failure – A951_O
If the ICC identifies issue(s) writing the model data from the memory card, the ICC will automatically shut the compressor off and keep it from operation� When this fault occurs the ICC will lock out the compressor to keep it from operating and flash an ”D1” on the dual 7-segment LEDs�
IMPORTANT: This mode of active
protection must be manually reset�
48
Page 49
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
Test and Fault Recall Modes
Test Mode (Test Button on the ICC)
• Enter TEST mode by pressing the TEST button
Exiting Active Compressor Protection Lockout
There are three methods to reset the ICC after an active protection lockout:
1) Cycle the line voltage to the unit�
2) Cycle 24 VAC to the ICC (remove the R or C connection to the ICC)�
Default Operations Upon Component Failure
If any of the following components on the (-)A20 air conditioner fail, there are multiple fail safe logic routines to keep the system conditioning the space while service is being sought� The following Table outlines the effect for each of these routines�
with an insulated probe for one (1) second and release�
• The TEST mode causes the ICC to do the
following:
1) Resets the 4-minute anti-short-cycle timer�
2) Energizes the unit without a call for unit operation�
• If the 4-minute anti-short-cycle timer or
30-second minimum run timer is active (a flashing “c,” “C,” “h,” or “H” is displayed on the dual 7-segment LEDs) and a call for unit operation is present, the TEST mode causes:
1) A “t” to display momentarily on the dual 7-segment display�
Components
FAILED
COMPONENT
OutdoorSensor
(OAT)
CoilSensor
(EVAPIN)
SuctionSensor
(OST)
EXVInletSensor
(LIQ)
Compressor
SumpSensor
(CPT)
Oneminutefanoffdelayon
PWMShiftabove104ºF
Suction Temp Measurement
Subcoolingverification NoSubCoolingverification
AEMLubricationProtection
FUNCTION
LowAmbientCooling NoLowAmbientfunction
COOLmode
LowAmbientCooling
&OilCirculationRatio
Protection
DEFAULTOPERATION
Nodelayfunctionsiffailureis
openorshort.Continuefunction
forathermistorrangeerror.
Shiftwillnotoccur
Nofunction
Default value reported to
the control center
function
Thecompressoroperation
outlinedintheapplicable
sectionswillbeperformedonce
anhour.
49
Page 50
Components
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
3� Once the compressor has started depress
2) The compressor will start and the outdoor fan will operate�
3) The display will change to a steady “c” or “C” to show the current demand for unit operation�
the SW2 and TEST buttons together for 5-8 seconds�
4� After this time the dual seven segment LEDs
will show the “FC” menu option�
5� Press the TEST button one time� The dual
7-segment display will show a “CS”, which refers to compressor speed�
6� To enter this menu, depress the SW2 button
once�
7� The LED display should now show a value
of “1”� This refers to 1st stage or low stage operation�
IMPORTANT: When testing in this
NOTICE: If a call for unit operation is
present at the end of the TEST mode, the unit will continue to operate�
• If no call for unit operation is present, the TEST
mode causes:
1) A steady “C” to appear on the dual 7-segment LEDs�
2) The compressor will start�
3) The compressor will turn off after 5 seconds�
NOTICE: Entering TEST mode
without a call for unit operation will cause the compressor to run for 5 seconds�
Agency Test Mode Instructions
The (-)A20 variable speed system by nature varies the compressor speed based on building load and thermostat call for operation� Therefore the following set of special instructions is necessary for agency testing ONLY� These modes should not be used for field installation use�
Low Compressor Speed Test Mode
To enter low compressor speed test mode where the ICC will keep the compressor speed at the minimum possible speed for the given/tested outdoor ambient temperature use the following procedure:
1� Supply a Y ONLY signal to the ICC� (NOTE: for
heating also supply a 24VAC signal to the “B” terminal)
2� Allow the 5min delay to expire and for the
compressor to start�
mode with an RHMV air handler, it is required to short the WIT or P12 pins to keep the ID blower supplying the rated low stage airflow� If this is not completed, the indoor airflow will move to intermediate stage cfm�
IMPORTANT: When operating in this
mode the ICC will stop compressor operation if the Y signal is removed for the purposes of completing the optional cycle tests� Upon the return of the Y signal the ICC will continue to operate in low compressor speed�
To exit this mode and return to standard thermostat signal control mode, depress the TEST button once and wait 5-10 seconds� The dual 7-segment display will display the current thermostat requested stage of operation�
Intermediate Compressor Speed Mode
To enter intermediate compressor speed test mode where the ICC will keep the compressor speed at the intermediate compressor speed for the given/tested outdoor ambient temperature use the following procedure:
1� Supply a Y ONLY signal to the ICC� (NOTE: for
heating also supply a 24VAC signal to the “B” terminal)
2� Allow the 5min delay to expire and for the
compressor to start�
3� Once the compressor has started depress
the SW2 and TEST buttons together for 5-8 seconds�
4� After this time, the dual seven segment LEDs
will show the “FC” menu option�
5� Press the TEST button one time� The dual
7-segment display will show a “CS”, which refers to compressor speed�
50
Page 51
COMPONENTS AND CONTROLS
EcoNet™ Variable Speed Unitary Control (cont�)
6� To enter this menu, depress the SW2 button
once�
7� The LED display should now show a value of
“1”� This refers to 1st stage or low compressor speed operation�
8� To toggle to the next compressor speed by
depressing the SW2 button once�
9� The LED display should now show a value of
“2”� This refers to the intermediate compressor speed operating stage�
IMPORTANT: When testing in this
mode with an RHMV air handler provide a Y2 thermostat signal only and the intermediate airflow will be provided immediately�
IMPORTANT: When operating in
this mode the ICC will stop compressor operation if the Y signal is removed� Upon the return of the Y signal the ICC will continue to operate in intermediate compressor speed�
To exit this mode and return to standard thermostat signal control mode, depress the TEST button once and wait 5-10 seconds� The dual 7-segment display will display the current thermostat requested stage of operation�
High/Maximum Compressor Speed Mode
To enter high/maximum compressor speed test mode where the ICC will keep the compressor speed at the intermediate compressor speed for the given/tested outdoor ambient temperature use the following procedure:
1. Supply a Y+Y2 signal to the ICC. (NOTE: for heating also supply a 24VAC signal to the “B” terminal)
2� Allow the 5min delay to expire and for the
compressor to start�
3� Once the compressor has started depress
the SW2 and TEST buttons together for 5-8 seconds�
4� After this time, the dual seven segment LEDs
will show the “FC” menu option�
5� Press the TEST button one time� The dual
7-segment display will show a “CS”, which refers to compressor speed�
6� To enter this menu, depress the SW2 button
once�
7� The LED display should now show a value
of “3”� This refers to the high/maximum compressor speed operating stage�
IMPORTANT: When testing in this
mode with an air handler or furnace provide
a Y1+Y2 thermostat signal only and the high/
maximum airflow will be provided immediately�
IMPORTANT: When operating
in this mode the ICC will stop compressor
operation if the Y+Y2 signal is removed. Upon the return of the Y+Y2 signal the ICC will
continue to operate in low compressor speed� To exit this mode and return to standard
thermostat signal control mode, depress the TEST button once and wait 5-10 seconds� The dual 7-segment display will display the current thermostat requested stage of operation�
Components
51
Page 52
ACCESSORIES
Accessories
at the fuse box or service panel for at least 1 minute before making any electrical connections� Also, the ground connection must be completed before making line voltage connections� Failure to do so can result in electrical shock, severe personal injury, or death�
Air Conditioner Thermostat Warning Light Kit RXPX-D01
This component senses a compressor lock out and tells the thermostat service light to come on� This will let the homeowner know that service is needed on the system�
NOTE: Warning light on thermostat will come on during a 5 minute compressor time delay and for 5 seconds during defrost while the compressor is off� Homeowner should only be concerned if light stays on for more than 5 minutes�
WARNING: Turn o electric power
Communicating 2-Wire Kit (Part No. RXME-A02)
This kit allows the outdoor unit to operate with only 2 control wires� A communicating air handler/ furnace and communicating thermostat must be used in conjunction with this kit�
52
Page 53
DIAGNOSTICS
IMPORTANT: The (-)A20 series units
with the ICC (Integrated Compressor Control) provide status and diagnostic information that greatly enhances the ability to quickly diagnose system faults� Use the following troubleshooting guides as another tool in system diagnostics�
NOTICE: In diagnosing common faults
in the cooling system, develop a logical thought pattern as used by experienced technicians� The charts which follow are not intended to be an answer to all problems but only to guide the technician’s troubleshooting� Through a series of yes and no answers, follow the logical path to a likely conclusion�
A novice technician should use these charts like a road map� Remember that the chart should clarify a logical path to the solution�
Replacement of EcoNet™ Variable Speed Unitary Control Board
Each control board in the EcoNet™ Communication Network needs information
specific to the unit the control is installed in� This information is called model data because it is model specific information required for the HVAC network to operate properly for the specific model installed� The data for a unit contains information that allows the unit to operate correctly�
When a control board requires replacement, it is important that the replacement board gets the model data from the old control� The primary way the replacement control gets this information is by the memory card that should be installed on the old control� Remove the memory card from the old control, replace the control, and reinstall the memory card on the new control�
The memory card from a different unit should never be used�
NOTE: See links to training and service manuals at MyRheem�com or MyRuud�com, or contact the
wholesale distributor selling this unit�
Diagnostics
53
Page 54
DIAGNOSTICS
ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below: NOTE: Codes must be read from correct side to avoid an error in reading codes�
Diagnostics
Dual 7-Segment
LEDs Display
Code
FLASHING
FLASHING
Diagnostic Description
c – First-Stage Cooling
cooling.
c – Anti-short-cycle timer (3 minutes) or minimum run timer (30 seconds) active
C – Second-Stage Cooling Unit has received a command for second-stage cooling.
C – Anti-short-cycle timer (3 minutes) or minimum run timer (30 seconds) active.
d1 – No Model Data • Replace memory card with correct system
0 – Standby No command for unit operation
Status/Possible Cause –
Troubleshooting Information
Normal operation
cooling during an active anti-short-cycle timer or minimum run timer.
• Wait until unit timer has expired or press the TEST button to defeat short-cycle delay.
Normal operation
• The unit has received a command for second­stage cooling during an active anti-short-cycle timer or minimum run timer.
• Wait until timer has expired or press the TEST button to defeat short-cycle delay.
information.
Normal operation
54
L8 – Compressor Model Unknown A900–O Inverter Identity Fault
09 – Low Secondary Volts The secondary voltage at R and C is below 18VAC.
L15 – T901, A903, A904, A905, A908, A909, A910, T911, T914, T917, T918 & T922
Inverter Fault
• Check model data card is properly connected
• Cycle power – remove power until all the lights
on the inverter have gone out. Then restore
power to inverter then ICC.
• Replace model data card
• Control transformer overloaded.
• Low line voltage
• Verify high voltage connections at the terminal
block, filter and inverter are all tight.
• Verify communication cable connection between
the inverter and ICC is complete.
• Check the U/V/W output wires are correct.
• Verify there is not a short in the filter or choke.
• Verify input voltage is within 187VAC and 252VAC.
• Check outdoor airflow and verify OD fan is
operating.
• Check the power inverter heat sync for debris.
• Replace model data card
• If none of the above corrects the issue,
replace drive.
Page 55
DIAGNOSTICS
Dual 7-Segment
LEDs Display
Code
Diagnostic Description
L16 – A912, A913, A919, A920, A921, & A929 Inverter Fault
Discharge line temperature – T916 Inverter Fault
Communication Failure – A915 Inverter Fault
Status/Possible Cause –
Troubleshooting Information
• Power cycle the system. Verify all lights on the
inverter are out prior to returning power to the
drive.
• Check the U/V/W output wires are correct.
• Check charge level. Reduce charge.
• Check continuity of discharge line thermistor
and connection at the drive. If issue persists,
replace the thermistor.
• If none of the above corrects the issue, replace
the drive.
• Outdoor ambient is above 125°F. Allow unit to cool and condensing pressure to reduce before
restarting.
• Outdoor ambient is below 0°F. Allow unit to heat up and evaporating pressure to increase before
restarting.
• Check charge level. Reduce charge.
• Check thermistor continuity. The discharge thermistor is a 10k thermistor. See the 10k thermistor chart for correct resistance value.
• Verify communication cable connection between the inverter and ICC is complete.
• Verify shielding on communication cable is adequately connected to the connector.
• Verify crimp terminals in the ICC to inverter communication cable are fully inserted and making good contact with the receptacle.
Diagnostics
FLASHING
21 – Low Pressure Control Open The ICC detects the LPC is open.
Notice: The low-pressure control is ignored for the
21L – Active Protection Low-Pressure Control Trip
• Unit has low refrigerant charge.
• Indoor coil is frozen (cooling mode).
• Indoor blower is not running (cooling mode).
• Outdoor coil is frozen (heating mode).
• Expansion valve is not operating correctly.
• LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor
55
Page 56
DIAGNOSTICS
Diagnostics
Dual 7-Segment
LEDs Display
Code
FLASHING
Diagnostic Description
27 – AC Input Under Voltage – A907 Inverter Fault
28 – AC Input Over Voltage – A906 Inverter Fault
29 – High-Pressure Control Open – T923 Inverter Fault The ICC detects the HPC is open.
29L – Active Protection High-Pressure Control Trip • HPC has opened 3 times in the same cooling
A923 Inverter Fault
Status/Possible Cause –
Troubleshooting Information
• Check incoming line voltage to the disconnect and unit.
• Check wiring connections.
• Check line voltage.
• Outdoor coil is dirty (cooling mode).
• Outdoor fan is not running (cooling mode).
• Indoor blower is not running (heating mode).
• Liquid line restriction
• Excessive refrigerant charge
operation; the ICC has locked out the compressor
31 – Compressor Envelope Protection – T902 Inverter Fault Inverter has recognized the compressor is operating outside the envelope
L31 – Compressor Envelope Protection
Lockout – T902 Inverter Fault
Inverter has recognized the compressor is operating outside the envelope
L32 – Compressor Temperature Thermistor
Failure – A902 Inverter Fault
L33 – Compressor Envelope Protection
Lockout – T902 Inverter Fault
Inverter has recognized the compressor is operating outside the envelope
• Check charge level. Reduce charge.
• Charge migration could have occurred resulting
in high compressor ratio.
• If ambient above 110°F compression ratio could
be too high for low speed operation. The demand
will automatically increase by the control center and the system will restart.
• ICC will clear this fault and restart independently
• Check charge level. Reduce charge.
• Outdoor ambient is above 125°F. Allow unit to
cool and condensing pressure to reduce
before restarting.
• Cycle power to restart.
• Check thermistor continuity. The compressor thermistor is a 10k thermistor. See the 10k thermistor chart for correct resistance value.
• Check thermistor continuity. The evaporator thermistor is a 10k thermistor. See the 10k thermistor chart for correct resistance value.
56
Page 57
DIAGNOSTICS
Dual 7-Segment
LEDs Display
Code
Diagnostic Description
Status/Possible Cause –
Troubleshooting Information
83 – Condenser Coil Temperature Fault The sensor detects an abnormally low or high coil temperature.
• Replace the sensor.
• Check sensor is installed correctly on control.
84 – Outdoor Ambient Temperature Fault The sensor detects an abnormally low or high
outdoor ambient temperature. T952
• Check unit placement. If the outdoor unit is in a high-temperature area, wait until the ambient temperature drops and check sensor reading.
• Replace the sensor.
• Check sensor is installed correctly on control.
93 – Configuration Data Restore Failure
A950
The control is not functioning properly.
• Check control for proper system operation.
• Replace control.
L42 – Compressor Temperature Thermistor Failure – T955
• Check thermistor continuity. The compressor
thermistor is a 10k thermistor. See the 10k
thermistor chart for correct resistance value.
L36 – Suction Pressure Sensor Failure –
A956
• Check pressure transducer wiring harness for
continuity while attached to sensor.
• Check 5Vdc is constant between black and red
at the sensor.
• Check return voltage between Black and Green
terminals on back of control board.
• Calculate the gauge pressure from the voltage
readings: PSIG = (375 * (Vout/Vin) - 22.8)-14.7
• On a legacy controlled system verify that the
voltage readings convert to the servicer gauge
readings.
• On a communicating system verify that the
voltage readings convert to the displayed
pressure listed on the control center.
• If all voltage measurements convert to a
similar pressure as displayed by the control
center or manual gauges replace the control.
If not replace the harness and/or pressure
transducer.
Diagnostics
57
Page 58
DIAGNOSTICS
YES
YES
YES
YES
NO
YES
NO
NO
NO
Outdoor Unit
Running
7-Segment
Display Lit?
Flashing Mode
Character
Alternating ``C
´´
and ``##´´ (Code)
Refer to the ICC Diagnostics Codes section from this manual for fault code troubleshooting.
Check fault history for other faults.
See the “ICC Diagnostic
Codes and the “Active
Compressor Protection
Mode” section from
this manual for fault code
troubleshooting.
Control in lockout mode.
Check fault history and refer to diagnostic chart and the ICC Diagnostic Codes section of this manual.
Waiting for anti-short-cycle delay to clear.
Notice: For solid comm. LED, check comm. wiring, term/bus switches at ICC and AH controls.
Check control voltage (R and C) to control. Check transformer or Check 3A fuse on
ICC Board
Bad control board or incorrect wiring – check wiring and replace control if bad.
NO
NO
Diagnostics
Electrical Checks Flowchart
THERMOSTAT CALL FOR COOLING, NO COOLING
58
Page 59
High Head Pressure or
Compressor Envelope
Protection
YES
NO
Pressure
Problems?
Low Liquid
Pressure
Low Suction
Pressure
Go to Electrical
Checks Flowchart
Dirty Filters
Dirty Indoor Coil
Inadequate Indoor
Airflow
Inoperative Indoor
Blower
Low on Charge
Low Ambient
Temperature
Bad
Compressor
Outdoor Check
Valve Closed
Restricted Indoor
Metering Device
Restricted Filter Drier
Dirty Outdoor
Coil
Inoperative Outdoor
Fan
Overcharge
Recirculation of
Outdoor Air
Noncondensibles
Higher Than Ambient Air
Entering Outdoor Coil
Wrong Outdoor
Fan Rotation
Inadequate Ducts
Outdoor Check
Valve Closed
Restricted Filter Drier
Outdoor Unit
Running?
Low on Charge
Restricted Indoor
Metering Device
Restriction in
System
Recirculation of
Indoor Air
Wrong Indoor
Blower Rotation
Cooling Mechanical Checks Flowchart
DIAGNOSTICS
Diagnostics
59
Page 60
DIAGNOSTICS
General Troubleshooting Chart
Diagnostics
WARNING:
unit before servicing� Contactor may break only one
Disconnect all power to
side� Failure to shut off power can cause electrical shock resulting in personal injury or death�
SYMPTOM POSSIBLE CAUSE REMEDY
Unit will not run • Power o or loose electrical connection
• Thermostat out of calibration – set too high.
Unit in active compresor protection
lockout mode
• Defective control board
• Blown fuses/tripped breaker
• Transformer defective
• High-pressure control open
• Miswiring of communications (communication
light on continuously)
Outdoor fan runs, compressor doesn't
Insucient cooling • Improperly sized unit
Compressor short cycles
Registers sweat • Low indoor airow • Increase speed of blower or reduce restriction.
High head, low vapor pressures
High head, high or normal vapor pressure – Cooling mode
Low head, high vapor pressures
Low vapor, cool compressor, iced indoor coil
High vapor pressure • Excessive load
Fluctuating head and vapor pressures
Gurgle or pulsing noise at expansion device or liquid line
• Loose connection
• Communication cable disconnected or failed
• Compressor stuck, grounded or open motor
winding, open internal overload�
• Low-voltage condition
• Improper indoor airow
• Incorrect refrigerant charge
• Air, noncondensibles, or moisture in system
• Incorrect voltage
• Improperly sized unit
• Refrigerant undercharge
• Restriction in liquid line, expansion device, or lter drier
• Stuck EXV
• Dirty outdoor coil
• Refrigerant overcharge
• Outdoor fan not running
• Air or noncondensibles in system
• EXV in bypass mode
• Bad compressor
• Low indoor airow
• Operating below 55°F outdoors
• Moisture in system
• Low ambient coding not operating (coil or
ambient thermister failure)
• Defective compressor
• EXV hunting
• Air or noncondensibles in system
• Air or noncondensibles in system • Recover refrigerant. Evacuate and recharge.
• Check for correct voltage at line voltage connections in
condensing unit�
• Reset – Power cycle high and low voltage to outdoor
unit
• Check control board diagnostic codes.
• Replace fuses/reset breaker.
• Check wiring. Replace transformer.
• Reset. Also see high head pressure remedy. The high-
pressure control opens at 610 PSIG�
• Check communication wiring.
• Check for correct voltage at lter and inverter. Check
and tighten all connections�
• Check control board diagnostic codes.
• Replace
• Recalculate load.
• Check airow. Should be approximately 400 CFM per
ton�
• Charge per procedure attached to unit service panel.
• Recover refrigerant. Evacuate and recharge. Replace lter drier.
• At inverter input terminals, voltage must be between
187-252VAC when unit is operating�
• Add refrigerant.
Replace air lter.
• Remove or replace defective component.
• Verify EXV operation.
• Clean coil.
• Correct system charge.
• Repair or replace.
• Recover refrigerant. Evacuate and recharge.
• Verify thermostat connections at EXV control
• Verify thermister and pressure transducer connection
and operation
• Replace compressor.
• Increase speed of blower or reduce restriction. Replace air lter.
• Recover refrigerant. Evacuate and recharge. Replace lter drier.
• Conrm outdoor thermister operation.
• Recheck load calculation.
• Replace compressor.
• Check thermistor to vapor line connection. Check air
distribution on coil�
• Check suction thermistor and pressure transducer
operation
• Recover refrigerant. Evacuate and recharge.
• Remove & conrm EXV movement. Clean EXV inside
with nitrogen to remove any debris then reinstall
60
Page 61
Service Analyzer Charts
COMPRESSOR OVERHEATING – HIGH DISCHARGE TEMP
SYMPTOM POSSIBLE CAUSE CHECK/REMEDY
High superheat (greater than 15°F [-9°C] at coil)
Low line voltage Loose wire connections Check wiring.
High line voltage Power company problem Have problem corrected.
High head pressure
Short cycling of com pressor
DIAGNOSTICS
Low charge Check system charge.
Verify suction thermistor operation (10k thermistor) Replace thermistor.
Verify pressure transducer operation input and output voltage
Faulty metering device, inadequate suction thermistor or pressure transducer operation.
High internal load Hot air (attic) entering return
Restriction in liquid line Drier plugged.
Low head pressure Low charge
Suction or liquid line subjected to high heat source
Power company problem, transformer Have problem corrected before diagnosis continues.
Undersized wire feeding unit Correct and complete diagnosis.
Overcharge Check system charge.
Dirty heat pump coil Clean coil.
Faulty or wrong size heat pump fan motor Replace fan motor.
Faulty fan blade or wrong rotation Replace fan blade.
Recirculation of air Correct installation.
Additional heat source Check for dryer vent near unit.
Noncondensibles Recover refrigerant. Evacuate and recharge system.
Equipment not matched Correct mismatch.
Faulty pressure control Replace pressure control.
Loose wiring Check unit wiring.
-
Thermostat Located in supply air stream
Replace thermistor and/or harness and/or control board.
Restricted cap tube, EXV
Heat source on; miswired or faulty control
Line kinked.
Operating in low ambient temperatures
Hot attic
Hot water line
Replace with correct rotation motor.
Check for recirculation from other equipment.
Diagnostics
Customer misuse
EXV Internal foreign matter
Pressure transducer failure
Suction thermistor failure
EXV control failure
EXV coil failure
Distributor tube/tubes restricted
Distributor tube Restricted with foreign matter
Kinked
I.D. reduced from previous compressor failure
61
Page 62
DIAGNOSTICS
Service Analyzer Charts
COMPRESSOR OVERHEATING – HIGH DISCHARGE TEMP (cont.)
SYMPTOM POSSIBLE CAUSE CHECK OR REMEDIES
Short cycling of compressor (cont.)
Low charge Check system charge.
Dirty coil
Duct too small or restricted
Diagnostics
Faulty internal overload Replace compressor.
ELECTRICAL
SYMPTOM POSSIBLE CAUSE CHECK OR REMEDIES
Voltage present on load side of inverter and compressor won't run
187 – 252VAC present at input to inverter
No voltage at input to inverter
Improper voltage High voltage Wrong unit
Communication failure from ICC to inverter. Check communication harness connectors and wire
Compressor windings Check for correct ohms.
Thermostat Check for control voltage to contactor coil.
Compressor control circuit High-pressure switch
Blown fuses or tripped circuit breaker Check for short in wiring or unit.
Improper wiring Recheck wiring diagram.
Low voltage Wrong unit
continuity.
Low-pressure cut-out
Ambient thermostat
Stater heat is active
Power supply problem
Power supply problem
Wiring undersized
Loose connections
62
FLOODED STARTS
SYMPTOM POSSIBLE CAUSE CHECK OR REMEDIES
Liquid in the com­pressor shell
Too much liquid in system
Faulty stator heat circuit (compressor thermistor or single leg output to compressor)
Incorrect piping Check piping guidelines.
Overcharge Check and adjust charge.
Replace compressor thermistor
Check inverter for single leg output power and correct wiring
Page 63
DIAGNOSTICS
Service Analyzer Charts
CONTAMINATION
SYMPTOMPOSSIBLE CAUSEREMEDY
Moisture Poor evacuation on installation or during service In each case, the cure is the same. Recover refrigerant.
High head pressure Noncondensibles air
Unusual head and suction readings
Foreign matter –
Wrong refrigerant or mixed refrigerants
Copper tubing cuttings
Copper oxide Dirty copper piping or nitrogen not used when
Welding scale Nitrogen not used during brazing
Excess soft solder Wrong solder material
brazing
LOSS OF LUBRICATION
SYMPTOM POSSIBLE CAUSEREMEDY
Compressor failures Line tubing too large Reduce pipe size to improve oil return.
Low suction pressure Low charge Check system charge.
Refrigerant leaks Repair and recharge.
Cold, noisy compressor – Slugging
Noisy compressor Migration Check stater heat and compressor thermistor.
Cold, sweating compressor
Low load
Short cycling of compressor
Dilution of oil with refrigerant Observe piping guidelines.
Flooding Check system charge.
Dirty coil
Wrong duct size
Restricted duct
Thermostat setting Advise customer.
Faulty high- or low-pressure control Replace control.
Loose wiring Check all control wires.
Thermostat In supply air stream, out of calibration
Customer misuse
Diagnostics
SLUGGING
SYMPTOM POSSIBLE CAUSEREMEDY
On start-up Incorrect piping Review pipe size guidelines.
EXV hunting when running
Faulty EXV components Check EXV, suction pressure transducer, and suction
thermistor for operation.
63
Page 64
DIAGNOSTICS
Service Analyzer Charts
FLOODING
Diagnostics
ELECTRONIC EXPANSION VALVES (INDOOR VALVE)
SYMPTOM POSSIBLE CAUSE REMEDY
Bad pressure reading Check transducer wiring.
Poor system control
using an EXV
Suction thermistor in wrong location Relocate thermistor.
Bad suction thermistor Replace thermistor.
Improper superheat setting (less than 5°F [-15°C])
Adjust EXV SH setpoint dipswitches and validate valve operation.
SYMPTOM POSSIBLE CAUSE REMEDY
High Superheat, Low
Suction Pressure
(superheat over
15°F [9°C])
Moisture freezing and blocking valve
Dirt or foreign material blocking valve
Low refrigerant charge Correct the charge.
Vapor bubbles in liquid line Remove restriction in liquid line. Correct the refrigerant
Undersized EXV
Incorrectly sensing vapor line temperature
Suction thermistor incorrectly calibrated.
Vapor pressure measured incorrectly.
Recover charge, replace filter-drier, evacuate system, recharge.
Recover charge, replace filter-drier, evacuate system, recharge
charge.
Remove noncondensible gases.
Size liquid line correctly.
Replace with correct valve.
Verify suction thermistor resistance is correct and properly attached and insulated to the vapor line.
Replace suction thermistor assembly.
After verifying lack of connectivity, replace the pressure transducer or harness.
64
EXV is stuck
ICC dc circuit failed
High superheat adjustment
If harness has a short, replace harness
If gauge pressure measurement and the converted voltage readings at the control are different replace pressure transducer
If gauge pressure measurement and the converted voltage readings at the control are the same, replace the control.
Remove EXV from the system and purge with nitrogen, replace filter drier, and recharge.
If EXV will not open, validate EXV wiring harness and rotor resistance between the black wire and the other 4 wires.
If none of the above rectifies the issue, replace EXV and filter drier and recharge.
Verify 5Vdc to pressure transducer is present. If not, replace ICC.
Change the superheat offset dip switches to lower superheat
Page 65
Service Analyzer Charts
ELECTRONIC EXPANSION VALVES (INDOOR VALVE) (cont.)
SYMPTOM POSSIBLE CAUSE REMEDY
EXV control dc circuit failed Verify 5Vdc to pressure transducer is present. If not,
replace EXV controller.
High superheat adjustment Change the superheat offset dip switches to increase
superheat.
Moisture causing valve to stick open. Recover refrigerant, replace filter-drier, evacuate
system, and recharge.
DIAGNOSTICS
Valve feeds too much
refrigerant, with low superheat, with low
superheat and
higher than normal
suction pressure.
Dirt or foreign material causing valve to stick open
Oversized EXV
Incorrect suction thermistor location Install suction thermistor with the provided stainless
Low superheat adjustment
Incorrectly sensing vapor line temperature
Suction thermistor incorrectly calibrated.
Vapor pressure measured incorrectly.
Recover refrigerant, replace filter-drier, remove EXV and purge with nitrogen, evacuate system, and recharge.
If EXV is completely clogged use the EXV control to open the EXV, and purge with nitrogen, replace filter drier, and recharge.
Install correct EXV
steel strap and an additional zip tie at the 10:00 or 2:00 position on suction line, with insulation.
Change the superheat offset dip switches to increase superheat.
Verify suction thermistor resistance is correct and properly attached and insulated to the vapor line.
Replace suction thermistor assembly.
After verifying lack of connectivity, replace the pressure transducer or harness.
If harness has a short, replace harness
If gauge pressure measurement and the converted voltage readings at the control are different replace pressure transducer
If gauge pressure measurement and the converted voltage readings at the control are the same, replace the control.
Diagnostics
Compressor flood
back upon
start-up
Refrigerant drainage from flooded evaporator
Inoperable stator heat
Any of the causes listed under Symptoms of Electrical Problems on page 62.
Install trap riser to the top of the evaporator coil.
Verify compressor thermistor (OST). Replace if needed.
Any of the solutions listed under Solutions of Electrical Problems on page 62.
65
Page 66
DIAGNOSTICS
Service Analyzer Charts
ELECTRONIC EXPANSION VALVES (INDOOR VALVE) (cont.)
SYMPTOM POSSIBLE CAUSE REMEDY
Superheat is low
to normal with low
suction pressure
Unequal evaporator circuit loading Ensure airflow is equally distributed through
evaporator.
Check for blocked distributor tubes.
Low load or airflow entering evaporator coil Ensure blower is moving proper air CFM.
Diagnostics
Superheat and
suction pressure
fluctuate (valve
is hunting)
Valve does not
regulate at all
Expansion valve is oversized.
Sensing bulb is affected by liquid refrigerant or refrigerant oil flowing through suction line
Unequal refrigerant flow through evaporator circuit
Moisture freezing and partially blocking EXV
Pressure transducer not connected or plugged
Suction line thermistor not connected, or installed on heat effected zone.
Suction line thermistor failed (continuity to control, wire damaged, resistance values incorrect)
Remove/Correct any airflow restriction.
Install correct EXV
Relocate sensing bulb in another position around the circumference of the suction line.
Ensure sensing bulb is located properly.
Check for blocked distributor tubes.
Recover refrigerant, change filter-drier, evacuate system, and recharge.
Connect pressure transducer in proper location, or remove any blockage.
Install suction line thermistor in correct horizontal clean section of copper pipe.
Replace suction line thermistor.
66
Page 67
SYSTEM
PROBLEM
Overcharge
Undercharge
Liquid Restriction
(Drier)
Low Indoor Airflow
Dirty Outdoor Coil
Low Outdoor
Ambient Temperature
Inefficient
Compressor
Indoor Suction
Pressure T ransducer
Faulty Measurement
Poorly Insulated
Indoor Vapor Line
Thermistor
DIAGNOSTICS
COOLING MODE
TROUBLESHOOTING TIPS
INDICATORS
DISCHARGE
PRESSURE
High High Low High High
Low Low High Low Low
Low Low High High Low
Low Low Low Low Low
High High Low Low High
Low Low High High Low
Low High High High Low
Low Low High High Low
High High Low Low High
SUCTION
PRESSURE
SUPERHEAT
Normal: 5°–15°F
[-15° – -9°C]
SUBCOOLING
Normal: See
Charging Chart
COMPRESSOR
AMPS
Diagnostics
67
Page 68
WIRING DIAGRAM
COMP
ODF
MODBUS
OAT
EVAPIN OST
OLT CPT
Memory Card
PWM
SPT
LPT
EXV
RVS
RVSC
RT E2 E1 C R Y Y2 B W UTIL24 UTIL
R
CGND
TEST SW2
ET ER
LED3 LED5
ACT
L1
L2
GND
H2
H1
U
V
W
Choke
Filter
IN
OUT
L1
L2
Power
In
Inverter
BK
BK
BK
G
G
Y
Y
R
Y
GY
GY
BK
Y G
HPC
SENSOR
RS485
OFM
G/Y
BL
Y
BR
BK
HPC
ETENOC
ODF
SPT
LPT
RVS
RVSC
MODBUS
Memory Card
MPW
OAT
C DGN
TEST
R
SW2
ET
RE
LED3 LE D5
ACT
OLT CPT
OIPANVE ST
UTIL 2
UTIL
C R YY2BWRT E2 E1
VXE
ETENOC
Comp.
Inverter
1L
2L
Filter
Power
Wiring Diagram
68
CM 1215
Loading...