RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTTION!
!
DO NOT DESTROY THIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
WARNING
!
ANT SAFETY INFORMA
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO
QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER
INSTALLAT I ON, ADJUSTMENT AND OPERATION OF THIS
UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE
AT TEMPTING INSTALLATION OR OPERATION. FA ILURE TO
FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER
INSTALLAT I ON, ADJUSTMENT,SERVICE OR MAINTENANCE
POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK,
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read
these instructions thoroughly before attempting installation or operation.
Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
WARNING
!
The manufacturer’s warranty does not cover any damage or defect to the air
conditioner caused by the attachment or use of any components, accessories
or devices (other than those authorized by the manufacturer) into, onto or in
conjunction with the air conditioner. You should be aware that the use of
unauthorized components, accessories or devices may adversely affect the
operation of the air conditioner and may also endanger life and property. The
manufacturer disclaims any responsibility for such loss or injury resulting
from the use of such unauthorized components, accessories or devices.
WARNING
!
Disconnect all power to unit before starting maintenance. Failure to do so can
cause electrical shock resulting in severe personal injury or death.
WARNING
!
Do not use oxygen to purge lines or pressurize system for leak test. Oxygen
reacts violently with oil, which can cause an explosion resulting in severe personal injury or death.
WARNING
!
Turn off electric power at the fuse box or service panel before making any
electrical connections.
Also, the ground connection must be completed before making line voltage
connections. Failure to do so can result in electrical shock, severe personal
injury or death.
WARNING
!
The unit must be permanently grounded. Failure to do so can cause electrical
shock resulting in severe personal injury or death.
WARNING
!
Secure elevated unit and elevating stand in order to prevent tipping. Failure to
do this may result in severe personal injury or death.
CAUTION
Wh e n coil is ins t alled ove r a f inished c e iling an d / or livin g a r ea, it is
recommended that a secon d a r y sheet metal c o n d e ns a t e pa n be
constructed and installed under entire unit. Failure to do so may result
in property damage.
CAUTION
Single-pole contactors are used on all standard single-phase units up through
5 tons. Caution must be exercised when servicing as only one leg of the power
supply is broken with the contactor. Two pole contactors are used on some
three phase units.
CAUTION
Dual fuel (fossil fuel) applications require the use of a high pressure control in
the heat pump section. If a high pressure control was not originally provided
with the heat pump section from the factory, a factory approved high pressure
control kit must be purchased from the manufacturer and installed in the heat
pump. Dual fuel (fossil fuel) applications in which a high pressure control is
not installed in the outdoor heat pump section will void the safety approval of
the product.
3
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL/METERING DEVICE
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
2.0 GENERAL
WARNING
!
The manufacturer’s warranty does not cover any damage or defect to the
air conditioner caused by the attachment or use of any components.
Accessories or devices (other than those authorized by the manufacturer) into, onto or in conjunction with the air conditioner. You should be
aware that the use of unauthorized components, accessories or devices
may adversely affect the operation of the air conditioner and may also
endanger life and property. The manufacturer disclaims any responsibility
for such loss or injury resulting from the use of such unauthorized compo-
ents, accessories or devices.
n
The information contained in this manual has been prepared to assist in the proper
installation, operation and maintenance of the heat pump equipment. Improper
installation, or installation not made in accordance with these instructions, can result
in unsatisfactory operation and/or dangerous conditions, and can cause the related
warranty not to apply.
Read this manual and any instructions packaged with separate equipment required
to make up the system prior to installation. Retain this manual for future reference.
To achieve optimum efficiency and capacity, the indoor cooling coils listed in the
heat pump specification sheet should be used.
2.1 CHECKING PRODUCT RECEIVED
Upon receiving unit, inspect it for any shipping damage. Claims for damage, either
apparent or concealed, should be filed immediately with the shipping company.
Check heat pump model number, electrical characteristics and accessories to
determine if they are correct. Check system components to make sure they are
properly matched.
2.2 APPLICATION
Before installing any heat pump equipment, a duct analysis of the structure and a
heat gain calculation must be made. A heat gain calculation begins by measuring
all external surfaces and openings that gain heat from the surrounding air and
quantifying that heat gain. A heat gain calculation also calculates the extra heat
load caused by sunlight and by humidity removal.
There are several factors that installers must consider.
•Outdoor unit location•Indoor unit blower speed
•Proper equipment evacuation •Supply and return air duct design and sizing
•Refrigerant charge•System air balancing
•Indoor unit air flow•Diffuser and return air grille location and sizing
The metal parts of this unit may be subject to rust or deterioration if exposed to a
corrosive environment. This oxidation could shorten the equipment’s useful life.
Corrosive elements include, but are not limited to, salt spray, fog or mist in seacoast
areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petroleum refineries.
If the unit is to be installed in an area where contaminants are likely to be a problem, special attention should be given to the equipment location and exposure.
•Avoid having lawn sprinkler heads spray directly on the unit cabinet.
•In coastal areas, locate the unit on the side of the building away from the waterfront.
•Shielding provided by a fence or shrubs may give some protection, but cannot
violate minimum airflow and service access clearances.
•Elevating the unit off its slab or base enough to allow air circulation will help
avoid holding water against the basepan.
Regular maintenance will reduce the build-up of contaminants and help to protect
the unit’s finish.
hipping
S
Lbs. [kg]
WARNING
!
Disconnect all power to unit before starting maintenance. Failure to do so
can cause electrical shock resulting in severe personal injury or death.
•Frequent washing of the cabinet, fan blade and coil with fresh water will remove
most of the salt or other contaminants that build up on the unit.
•Regular cleaning and waxing of the cabinet with an automobile polish will provide some protection.
•A liquid cleaner may be used several times a year to remove matter that will not
wash off with water.
Several different types of protective coil coatings are offered in some areas. These
coatings may provide some benefit, but the effectiveness of such coating materials
cannot be verified by the equipment manufacturer.
6
3.2 HEAT PUMP LOCATION
onsult local and national building codes and ordinances for special installation
C
equirements. Following location information will provide longer life and simplified
r
ervicing of the outdoor heat pump.
s
NOTE: These units must be installed outdoors. No ductwork can be attached, or
other modifications made, to the discharge grille. Modifications will affect performance or operation.
3.3 OPERATIONAL ISSUES
•IMPORTANT: Locate the unit in a manner that will not prevent, impair or com-
promise the performance of other equipment horizontally installed in proximity
to the unit. Maintain all required minimum distances to gas and electric meters,
dryer vents, exhaust and inlet openings. In the absence of National Codes, or
manaufacturers’ recommendations, local code recommendations and requirements will take presidence.
•Refrigerant piping and wiring should be properly sized and kept as short as
possible to avoid capacity losses and increased operating costs.
•Locate the unit where water run off will not create a problem with the equip-
ment. Position the unit away from the drip edge of the roof whenever possible.
Units are weatherized, but can be affected by the following:
o Water from the junction of rooflines, without protective guttering, entering the
heat pump while in operation, can impact fan blade or motor life. Coil damage may occur to a heat pump if moisture cannot drain from the unit under
freezing conditions.
o Freezing moisture, or sleeting conditions, can cause the cabinet to ice-over
prematurely and prevent heat pump operation, requiring backup heat, which
generally results in less economical operation.
•Closely follow clearance recommendations (see Figure 1).
o 24” to the service panel access
o 60” above heat pump fan discharge (unit top) to prevent recirculation
o 6” to heat pump coil grille air inlets (per heat pump).
3.4 FOR UNITS WITH SPACE LIMITATIONS
In the event that a space limitation exists, we will permit the following clearances:
Single Unit Applications: Heat pump grille side clearances below 6 inches will
reduce unit capacity and efficiency. Do not reduce the 60-inch discharge, or the 24inch service clearances.
Multiple Unit Applications: When multiple heat pump grille sides are aligned, a 6inch per unit clearance is recommended, for a total of 12 inches between multiple
units. Two combined clearances below 12 inches will reduce capacity and efficiency. Do not reduce the 60-inch discharge, or 24-inch service clearances.
•Do not obstruct the bottom drain opening in the heat pump base pan. It is
essential to provide defrost condensate drainage to prevent possible refreezing
of the condensation. Provide a base pad for mounting the unit, which is slightly
pitched away from the structure. Route condensate off the base pad to an area
which will not become slippery and result in personal injury.
•Where snowfall is anticipated, the heat pump must be elevated above the base
pad to prevent ice buildup that may crush the tubing of the heat pump coil or
cause fin damage. Heat pump units should be mounted above the average
expected accumulated snowfall for the area.
7
FIGURE 2
ECOMMENDED ELEVATED INSTALLATION
R
ELEVATION ABOVE
ANTICIPATED SNOW’FALL IS NECESSARY.
O NOT BLOCK
D
PENINGS IN BASE
O
AN. REFER TO
P
IGURE 1.
F
3.5 CUSTOMER SATISFACTION ISSUES
•The heat pump should be located away from the living, sleeping and recreational spaces of the owner and those spaces on adjoining property.
•To prevent noise transmission, the mounting pad for the outdoor unit should
not be connected to the structure, and should be located sufficient distance
above grade to prevent ground water from entering the unit.
3.6 UNIT MOUNTING
If elevating the h eat pum p, either on a flat ro of or on a slab, o bser ve the
following guidelines. (See Figure 2.)
•The base pan provided elevates the heat pump 3/4” above the base pad.
•If elevating a unit on a flat roof, use 4” x 4” (or equivalent) stringers positioned
to distribute unit weight evenly and prevent noise and vibration.
NOTE: Do not block drain openings shown in Figure 1.
•If unit must be elevated because of anticipated snow fall, secure unit and elevating stand such that unit and/or stand will not tip over or fall off.
CAUTION
!
Secure elevated unit and elevating stand in order to prevent tipping.
Failure to do this may result in minor or moderate injury.
3.7 FACTORY-PREFERRED TIE-DOWN METHOD
INSTRUCTIONS
IMPORTANT: These instructions are intended as a guide to securing equipment for
wind-load ratings of “120 MPH sustained wind load” and “3-second, 150 MPH gust.”
While this procedure is not mandatory, the Manufacturer does recommend that
equipment be properly secured in areas where high wind damage may occur.
STEP 1: Before installing, clear pad of any dirt or debris.
IMPORTANT: The pad must be constructed of industry-approved materials,
and must be thick enough to accommodate the concrete fastener.
STEP 2: Center base pan on pad, ensuring it is level.
STEP 3: Using basepad as a guide, mark spots on concrete where 4 holes will be
drilled (see Figure 3).
8
STEP 4: Drill four pilot holes in pad, ensuring that the hole is at least 1/4” deeper
than the concrete screw being used.
STEP 5: Center basepan over pre-drilled holes and insert concrete screws.
STEP 6: Tighten concrete screws.
NOTE: Do not over-tighten the concrete screws. Doing so can weaken the
integrity of the concrete screw and cause it to break.
STEP 7: Finish unit assembly per unit’s installation instructions.
All units are factory charged with Refrigerant 410A. All models are supplied with
service valves. Keep tube ends sealed until connection is to be made to prevent
system contamination.
5.0 REPLACEMENT UNITS
To prevent failure of a new heat pump unit, the existing tubing system must be correctly sized and cleaned or replaced. Care must be exercised that the expansion
device is not plugged. For new and replacement units, a liquid line filter drier should
be installed and refrigerant tubing should be properly sized. Test the oil for acid. If
positive, a liquid line filter drier is mandatory.
9
6.0 INDOOR COIL
REFER TO INDOOR COIL MANUFACTURER’S INSTALLATION INSTRUCTIONS.
IMPORTANT: The manufacturer is not responsible for the performance and opera-
tion of a mismatched system, or for a match listed with another manufacturer’s coil.
6.1 LOCATION
Do not install the indoor coil in the return duct system of a gas or oil furnace.
Provide a service inlet to the coil for inspection and cleaning. Keep the coil pitched
toward the drain connection.
CAUTION
When coil is installed over a finished ceiling and/or living area, it is
recomm e n d e d t h a t a s e co n da r y s h e et m e t al c o n de ns a te p a n b e
constructed and installed under entire unit. Failure to do so may result
in property damage.
7.0 INTERCONNECTING TUBING
7.1 VAPOR AND LIQUID LINES
Keep all lines sealed until connection is made.
Make connections at the indoor coil first.
Refer to Line Size Information in Table 3 and 4 for correct size and multipliers to be
used to determine capacity for various vapor line diameters and lengths of run. The
losses due to the lines being exposed to outdoor conditions are not included.
The factory refrigeration charge in the outdoor unit is sufficient for 15 feet of interconnecting lines. The factory refrigeration charge in the outdoor unit is sufficient for
the unit and 15 feet of standard size interconnecting liquid and vapor lines. For different lengths, adjust the charge as indicated below.
1/4” ± .3 oz. per foot
5/16” ± .4 oz. per foot
3/8” ± .6 oz. per foot
1/2” ± 1.2 oz. per foot
7.2 MAXIMUM LENGTH OF LINES
The maximum length of interconnecting line is 150 feet. Always use the shortest
length possible with a minimum number of bends. Additional compressor oil is not
required for any length up to 150 feet.
NOTE: Excessively long refrigerant lines cause loss of equipment capacity.
7.3 VERTICAL SEPARATION
Keep the vertical separation to a minimum. Use the following guidelines when
installing the unit:
1.DO NOT exceed the vertical separations as indicated on Table 4.
2.It is recommended to use the smallest liquid line size permitted to minimize system charge which will maximize compressor reliability.
3.Table 4 may be used for sizing horizontal runs.
7.4 TUBING INSTALLATION
Observe the following when installing correctly sized type “L” refrigerant tubing
between the condensing unit and evaporator coil:
•If a portion of the liquid line passes through a hot area where liquid refrigerant
can be heated to form vapor, insulating the liquid line is required.
•Always keep tubing sealed until tubing is in place and connections are to be
made.
10
•Blow out the liquid and vapor lines with dry nitrogen before connecting to the
outdoor unit and indoor coil. Any debris in the line set will end up plugging the
expansion device.
•As an added precaution, a high quality, bi-directional filter drier is recommend-
ed to be installed in the liquid line, if not factory installed.
Do not allow the vapor line and liquid line to be in contact with each other. This
•
causes an undesirable heat transfer resulting in capacity loss and increased
power consumption. The vapor line must be insulated.
•If tubing has been cut, make sure ends are deburred while holding in a position
to prevent chips from falling into tubing. Burrs such as those caused by tubing
cutters can affect performance dramatically, particularly on small liquid line
sizes.
•For best operation, keep tubing run as short as possible with a minimum num-
ber of elbows or bends.
•Locations where the tubing will be exposed to mechanical damage should be
avoided. If it is necessary to use such locations, the copper tubing should be
housed to prevent damage.
•If tubing is to be run underground, it must be run in a sealed watertight chase.
•Use care in routing tubing and do not kink or twist. Use a good tubing bender
on the vapor line to prevent kinking.
•Route the tubing using temporary hangers, then straighten the tubing and
install permanent hangers. Line must be adequately supported.
•The vapor line must be insulated to prevent dripping (sweating) and prevent
performance losses. Armaflex and Rubatex are satisfactory insulations for this
purpose. Use 1/2” minimum insulation thickness, additional insulation may be
required for long runs.
•Check Table 3 for the correct vapor line size. Check Table 4 for the correct liq-
uid line size.
7.5 TUBING CONNECTIONS
Indoor coils have only a holding charge of dry nitrogen. Keep all tube ends sealed
until connections are to be made.
•Use type “L” copper refrigeration tubing. Braze the connections with accepted
industry practices.
•Be certain both refrigerant shutoff valves at the outdoor unit are closed.
•Clean the inside of the fittings before brazing.
•Remove the cap and schrader core from service port to protect seals from heat
damage.
•Use an appropriate heatsink material around the copper stub and the service
valves before applying heat.
•IMPORTANT: Do not braze any fitting with the TEV sensing bulb attached.
•Braze the tubing between the outdoor unit and indoor coil. Flow dry nitrogen
into a service port and through the tubing while brazing.
•The service valves are not backseating valves. To open the valves, remove the
valve cap with an adjustable wrench. Insert a 3/16” or 5/16” hex wrench into the
stem. Back out counterclockwise.
•Replace the valve cap finger tight then tighten an additional 1/2 hex flat for a
SUCTION LINE LENGTH/SIZE VS. CAPACITY MULTIPLIER (R-410A)
OTES:
N
*Standard Line Size
sing suction line larger than shown in chart will result in poor oil return and is not recommended.
U
12
7.6 LEAK TESTING
•Pressurize line set and coil through service fittings with dry nitrogen to 150
PSIG maximum. Leak test all joints using liquid detergent. If a leak is found,
relieve pressure and repair.
WARNING
!
Do not use oxygen to purge lines or pressurize system for leak test.
Oxygen reacts violently with oil, which can cause an explosion resulting in
severe personal injury or death.
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.