This unit contains R-410A high pressure refrigerant. Hazards exist that could
result in personal injury or death. Installation, maintenance, and service should
only be performed by an HVAC technician qualied in R-410A refrigerant and
using proper tools and equipment. Due to much higher pressure of R-410A
refrigerant, DO NOT USE service equipment or tools designed for R22
refrigerant.
IMPORTANT: Do not release refrigerant to the atmosphere! If required service
procedures include the adding or removing of refrigerant, the service technician
must comply with all federal, state and local laws. The procedures discussed
in this manual should only be performed by a qualied HVAC technician.
IMPORTANT: Failure to maintain, misuse of the unit, use of replacement parts
not factory approved or wrong startup procedures will void the warranty.
Form I-ZQYRA P/N 260414R8, Page 1
Table of Contents
1.0 General .......................................................................... 2
1.1 Hazard Labels and Notices ....................................... 2
1.2 General Information .................................................... 3
There are warning labels on the condensing unit and throughout this manual. For
your safety, read the denitions below and comply with all boxes labeled CAUTION,
WARNING, and DANGER during installation, operation, maintenance, and service of
this system.
Denitions of Hazard Intensity Levels in this Manual
HAZARD INTENSITY LEVELS
DANGER: Failure to comply will result in severe personal injury
or death and/or property damage.
WARNING: Failure to comply could result in severe personal
injury or death and/or property damage.
CAUTION: Failure to comply could result in minor personal
injury and/or property damage.
WARNING
Improper installation, adjustment, alteration, service, or
maintenance can cause property damage, personal injury, or
death. A qualied installer or service agency must perform
installation and service.
DANGER
The heat pump in this ventilation unit is designed to use R-410A high pressure
refrigerant only. Hazards exist that could result in personal injury or death.
Installation, maintenance, and service should only be performed by an HVAC
technician qualied in R-410A refrigerant and using proper tools and equipment.
Due to much higher pressure of R-410A refrigerant, DO NOT USE service equipment
or tools designed for R22 refrigerant.
DANGER
Never use oxygen to pressurize a refrigeration system. Oxygen can explode on
contact with oil and result in personal injury or death. When using high pressure
gas such as nitrogen for pressurizing a refrigeration system, ALWAYS USE A
PRESSURE REGULATOR that can control the pressure down to 1 or 2 psig.
SAFETY WARNINGS
For your safety, wear eye protection, gloves, and protective clothing when handling
R-410A refrigerant or POE oil and when brazing. Have a re extinguisher nearby
when brazing.
DANGER
Before installing or servicing, always turn off the main power to the system and
install a lock out on the disconnect switch.
1.2 General
Information
1.3 Warranty
1.4 Installation
Codes
2.0 Location
This booklet includes installation, operation, maintenance, and service information.
Before beginning any procedure, carefully review the information, paying particular
attention to the warnings. All installations must be in compliance with all codes and
requirements of authorities having jurisdiction.
Refer to limited warranty information on the Warranty Form in the “Literature Bag”
shipped with this system.
All installations must be in compliance with the National Electric Code ANSI/NFPA No.
70 (latest edition) or, in Canada, the Canadian Electrical Code, Part I-C.S.A. Standard
C 22.1. Check any local ordinances or utility company requirements that apply. The
installation must be in compliance with all authorities having jurisdiction. Local code
requirements supersede national requirements.
This ventilation unit is designed to be mounted outdoors on a level surface but could
be mounted indoors. The supporting structure must be able to support the operating
weight of the unit and maintain a level plane during continued operation. Water
should drain away from the unit. Location must comply with free space clearances for
unrestricted airow
3.0 Receiving,
Moving, and
Uncrating
3.2 Storage and
Moving
3.1 Receiving
Check for any damage that may have happened during shipment. If damage is found,
document the damage with the transporting agency and immediately contact your
distributor. If you are an authorized Distributor, follow the FOB freight policy procedures.
With the shipping skid attached, the unit may be moved with a fork lift or an overhead
crane. After the shipping skid has been removed, the unit must be lifted from overhead.
The heavy gauge base of the ventilation unit has a lifting lug on each corner. Always
use spreader bars when rigging to prevent damage to the cabinet.
If the unit is going to be stored, take precautions to prevent condensation inside the
electrical compartment and motors. To prevent damage to the unit, do not store sitting
on the ground.
3.3 Uncrating and
Preparation
Immediately upon uncrating, check the electrical characteristics to verify that the unit
is suitable for the installation site.
Shipped-with and Shipped-separate Items - A carton shipped inside the unit
contains the vertical supply air opening cover and parts to assemble and install the
inlet and exhaust hoods. The hoods will be attached after the unit is in the installed
location.
Before beginning installation, be sure that all shipped-separate options ordered are
available at the site. Shipped-separate options could include a roof curb, a wallmounted control, and/or a disconnect switch.
Supply Air (Discharge) and Return Air Openings - To enable the installer to adapt
to either vertical or horizontal ductwork, the cabinet has both vertical and horizontal
supply and return air openings. Both the horizontal supply air and return air openings
are capped during shipping.
NOTE: There are no vertical duct connections on the unit; duct ange connections are
part of the roof curb. The curb is designed to slide the ductwork into the vertical duct
openings from the roof before the unit is lifted to the curb.
On each corner, the heavy gauge base of the ventilation unit has a lifting lug with a
1-1/2” diameter hole for rigging. When attaching rigging, insert a clevis in each lifting
lug. Use spreader bars in the rigging. Lift the unit straight up with vertical force.
Test lift the unit to be sure that it is secure. Adjust cables so that the unit will remain
horizontal throughout the lift. Lift slowly, following safe lifting procedures.
Rigging and lifting are the responsibility of the installer.
Approximate Operating
Weight
“Z” Size 812
Weight
Form I-ZQYRA P/N 260414R8, Page 5
858 lbs1003 lbs
389 kg455 kg
SIDE VIEW
of Unit
After test lift, adjust cable
length as needed so that the
unit will remain horizontal
throughout the lift.
To prevent damage to
the cabinet, spreader
bars are REQUIRED.
FRONT VIEW
of Unit
To prevent damage to
the cabinet, spreader
bars are REQUIRED.
Lifting Lug with
1-1/2” ( 38mm)
diameter hole (4) one on each
corner
5.0 Mounting
(cont’d)
5.2 Rigging and
Lifting (cont’d)
FIGURE 4 Rigging and
Lifting
5.3 Curb Cap Base
and Mounting
IMPORTANT NOTE:
Unit must be level.
5.3.1 Mounting
without a Roof Curb
This unit is equipped with a load-bearing curb cap. The curb cap has bolted seams
and is designed so that it may be set on perpendicular supports or over a roof curb. A
curb is required if the application uses vertical (down) discharge and or vertical (down)
return air.
Because of condensate drain requirements, setting this unit directly on a at surface
(cement slab) is not recommended.
Be sure to comply with clearances in FIGURE 2, page 5. It is recommended that this
ventilation unit be positioned so that the outside air inlet hood is not facing into the
prevailing wind.
Prior to installation, be sure that the method of support is in agreement with all local
building codes and is suited to the climate. If considering an installation without a roof
curb in snow areas, it is recommended that the support under the system be at least
12” (305mm) higher than the roof surface.
If setting cross supports on the roof surface and not decking, be sure to have sufcient
tread material under the supports to adequately spread the load and prevent “sinking”
into the roong material. The eld-supplied, weather resistant, cross-support structure
must be secure and adequate for the weight of the unit (Refer to Paragraph 5.1).
FIGURE 5 -
Locations for
Field-Supplied
Rail Cross
Supports
5.3.2 Mounting on a
Roof Curb
Form I-ZQYRA P/N 260414R8, Page 6
The curb, Option CJ3C, is a 16” (406mm) high, fully enclosed, insulated curb. If the
application is sound sensitive, consider installing a eld-supplied vibration isolation
curb or specialty sound attenuation curb. Whether using the optional roof curb available
with the system or a eld-supplied curb, the curb must be secure, square, and level.
When using a eld-supplied curb with vertical ductwork, eld-fabricated custom duct
connections will be required as there are no duct anges on the unit.
The top surface of the roof curb must be caulked with 1/4” x 1-1/4” sealant tape or two
1/4” beads of suitable sealant. The unit must be sealed to the curb to minimize sound
transmission, prevent air leakage, and to prevent water leakage into the curb area due
to wind blown rain and capillary action.
Roof Curb,
1
2
3
4
5
6
7
8
9
10
11
(Right End)
(Center
Support)
(Left End)
Top View (showing supply
and return airflow)
(Front Side)
(Rear Side)
L
A
J
E
G
C
F
M
B
D
H
K
Use 3/4” Cap Screw, P/N 16247,
with Lockwasher, P/N 1333, and Nut,
P/N 1035, in bottom two holes in each corner.
Use 1-1/4” Lag Screw, P/N 16243,
with Lockwasher, P/N 1333, in all
attachmentsmade into the wood
nailer around the top
of the curb.
Use sheetmetal screws, P/N 11813, for
attaching duct support parts to each
other and to the insulated portion of
the curb rails.
Assembled
Views
Slide vertical ductwork down from the top
and attach to duct flanges at bottom of curb.
See dimensions on page 8.
Bottom View (from inside the building showing flanges for
ductwork on the openings on the bottom of the curb)
Return Air
Duct Flange
Supply Air
Duct Flange
Return Air
Supply Air
Option CJ3C
Roof curb Option CJ3C, is shipped separately for eld installation. The roof curb
designed for this system includes integral duct connections for supply air and return air
making it very important to know the orientation of the unit when installing the
curb. See the illustrations in FIGURE 6 and the component list below. See dimensions
in FIGURE 8, page 8 and orientation in FIGURE 9, page 9.
The roof curb is designed for ductwork to be installed from the top prior to setting the
Components in Option
CJ3C, Pkg P/N 260418
unit. If ductwork is installed after the unit, eld-fabricated custom connections will be
required as the unit does not have duct anges.
Item QtyP/NDescription
Roof Curb Rail and Cross Support Parts, Items A, B, C, D, and E are ALWAYS used:
A1260215 Roof Curb Front Side
B1260216 Roof Curb Right End
C1260217 Roof Curb Left End
D1260218 Roof Curb Rear Side
E1259636 Roof Curb Center Support
Vertical Duct Support Parts (Items F-M) are required if the application has vertical supply and return air.
Installation of these parts is optional if installing a unit using the horizontal supply and return air openings.
F1259637 Roof Curb Cross Support (return air)
G1259638 Roof Curb Cross Support (discharge air)
H1259639 Roof Curb Cross Support (return air)
J1259640 Roof Curb Center Support (discharge air)
K1259641 Duct Angle Support (discharge air right end)
L1259642 Duct Angle Support (discharge air front side)
M1259643 Duct Angle Support (return air right end)
FIGURE 6 - Layout of Roof Curb Components listed above
Instructions and
Requirements for
Assembling and
Installing Roof Curb
Option CJ3C
The option package
includes the following
hardware:
Roof Curb
Hardware
Bag
includes:
1. Verify that the roof curb parts match those listed in the package component table
and the hardware bag component table above.
Verify that the location has adequate support for the weight (Paragraph 5.1).
QtyP/NDescription
1016243 Hex Hd Lag Bolt 5/16 X 1-1/4” lg
181333Lockwasher 5/16 In.
816247 Cap Screw 5/16 X 3/4” lg
81035Hex Nuts
3111813 S/M Screw #10-16x1/2 Ab Stalgd
166302 Roll of Sealant Tape, 1/4” x 1-1/4”
2. Position the roof curb end and side assemblies as shown in FIGURE 6. Fasten
each corner using lag screws with lockwashers in the top holes and cap screws
with lockwashers and nuts in each of the other holes. Install the center support.
Before continuing to Step 3, verify that the airow orientation is correct.
Form I-ZQYRA P/N 260414R8, Page 7
5.0 Mounting
Roofing Felts
(by others)
Cant Strip
(by installer)
Counter Flashing
(by installer)
MUST be sealed between
curb cap and roof curb.
2 x 6
Wood
Nailer
Insulation
Weld, bolt, or lag screw curb to deck structure.
Roof Curb
44-1/8”
(1121mm)
- inside
of curb
47-7/16”
(1205mm)
- outside
of rails
Rail Width
1-21/32”
(42mm)
Rail Width
1-21/32”
(42mm)
Outside Air Inlet Location
(on side of unit)
TOP VIEW of Assembled
ROOF CURB
Exhaust Air
Outlet Location
(on side of unit)
Supply Air Opening
18-7/32” x 8-11/64”
(463mm x 208mm)
64-5/32” (1629mm) - inside of curb
67-15/32” (1713mm) - outside of rails
21-1/2”
(546mm)
Return Air Opening
19-51/64” x 8-11/64”
(503mm x 208mm)
22-1/4” (565mm)
Horizontal Return
Air Opening
Location on
Side of Unit
Supply
Air Opening
Location on
Side of Unit
(cont’d)
5.3 Curb Cap Base
and Mounting
(cont’d)
5.3.2 Mounting on a
Roof Curb (cont’d)
FIGURE 7 - Crosssection of Roof Curb
showing Construction
Detail
Instructions and Requirements for Assembling and Installing Roof Curb
Option CJ3C (cont’d)
3. Identify the duct supports that create the integral supply and return air ductwork.
NOTE: If the system is not using the vertical duct openings, the duct support parts
are not required but may be installed.
Position the duct support parts as shown in FIGURE 6 and attach. Use 1-1/4” lag
screws with lockwashers when attaching supports to the top portion of the curb
rails with the wood nailer. Use sheetmetal screws in all other locations.
4. Check the roof curb for squareness. The curb must be adjusted so that the
diagonal measurements are equal within a tolerance of ±1/8" (3mm).
5. Level the roof curb. To ensure a good weatherproof seal between the cabinet curb
cap and the roof curb, the curb must be leveled in both directions with no twist end
to end. Shim as required and secure curb to the roof deck before installing ashing
(See Curb Detail in FIGURE 7).
6. Install eld-supplied ashing.
Form I-ZQYRA P/N 260414R8, Page 8
FIGURE 8 Option CJ3C
Roof Curb and
Duct Opening
Dimensions
Slide return
air and supply
ductwork down
from the top
and attach to
duct anges.
Apply sealant
tape to top of all
curb rails.
7. Before lifting and placing the unit on the curb, check the following:
□The curb is designed for ductwork to be installed from the top BEFORE the unit
is in place. Slide the ductwork down into the discharge and return air openings.
See dimensions in FIGURE 8. Ductwork should be sized slightly smaller with a
minimum 3/4" duct ange that will attach to all sides of the duct connection in the
curb. See Paragraph 6.2 for connecting ductwork.
□Apply 1/4" x 1-1/4" foam sealant tape to both the top surface of the curb rails and
the top surface of the duct connection supports, being sure to make good butt
joints at all corners. The sealant tape must be applied to the rails to prevent water
leakage into the curb area due to blown rain and capillary action.
□The unit has eld convertible (either vertical or horizontal) supply and return air
opening locations. Depending on whether the ductwork is vertical or horizontal,
Inlet
Air
Drain
Electrical
Entrance
Installed Option CJ3 Curb
Model ZQYRA
Return Air
Supply Air
*
Inlet Air Hoods
with Filters
(Size 8 - 2 hoods;
Size 12 - 3 hoods)
See assembly and
installation instructions
in Paragraph 6.2.3.
Condensate Drain Connection;
see Paragraph 6.4.
*
Vertical Discharge Air
Opening (In the bottom)
Vertical Return Air Opening
(in the bottom)
Inlet
Side
Post
Supply Fan Access
Inlet
Hoods
*
Exhaust Hood See assembly
and installation
instructions in
Paragraph 6.2.2.
Disconnect
Switch (Optional)
Controls
Compressor
Electric Heat (Optional)
High
Voltage
Entrance
Low
Voltage
Entrance
Exhaust Fan Acccess
Horizontal
Supply Air
Horizontal
Return Air
Opening
(Control Side)
Return Air
Filter Access
*
Inlet Air
Filter Access
Enthalpy Wheel Access
Control
Side
Post
*
Remove the inlet air filter access panel to find 1) the
carton that contains the inlet hood components and the
cover for the vertical supply duct opening; and 2) the
bundle of exhaust hood parts.
verify that the discharge and return air openings being used are uncovered and the
openings not being used are covered.
□When it is time to lift the unit onto the prepared curb (See Rigging and Lifting,
Paragraph 5.2), be sure that all of the above preparations have been made.
IMPORTANT:Verify that the unit is being placed on the curb in the correct
airow orientation. See FIGURE 9 for required orientation when installing a
unit with vertical ductwork.
FIGURE 9 - Correct Orientation
of Unit to Roof Curb when
using Vertical Ductwork
Reminder NOTES: Curb is
designed for ductwork to be
installed from the top prior to
setting unit on the curb.
Always apply sealant tape to top
of curb rails before placing unit.
6.0 Mechanical
FIGURE 10 - Identication of Locations referenced
in Paragraphs 6.2 - 6.4
6.2 Inlet Air and
Exhaust Air
Openings
6.1 Identity of Mechanical Procedure Locations
6.2.1 Field-Installed Inlet Air and Exhaust Hoods
All Model ZQYRA ventilation units require eld installation of the inlet air hood and the
exhaust hood. All hood components plus the vertical supply duct cover are shipped
inside the cabinet. Remove the inlet lter access panel (see FIGURE 10); a carton and
a bundle of parts are visible. First, slide out the carton and then remove the bundle of
parts that is attached to brackets. DO NOT remove the brackets or the carton stop.
The bundled parts are for the exhaust hood. Use screws from the hardware bag in the
carton and follow the instructions In Paragraph 6.2.2 below to install the exhaust hood.
Follow the instructions in Paragraph 6.2.3 to install the inlet air hood.
Form I-ZQYRA P/N 260414R8, Page 9
2
Right
Side
1
Left
Side
3
Top
Cover
4
Screws
(26 required)
6.0 Mechanical
(cont’d)
6.2 Inlet Air and Exhaust Air Openings (cont’d)
Use of the vertical supply air cover will be determined in Paragraph 6.3.
6.2.2 Exhaust Air Hood
Exhaust Hood Components and Installation
FIGURE 11 - Components and Assembly of the Exhaust Hood
CodeQty
11260210Hood Left Side
21260211Hood Right Side
31261138261855Hood Top Cover
42611813Screws*
* Screws are shipped in
is in the carton with the inlet hood parts. The bag includes
enough screws for both the inlet and exhaust hoods.
P/N
Size 8Size 12
hardware bag, P/N 260354, that
Description
Exhaust Hood Assembly and Installation Instructions
1. Undo the exhaust hood component bundle and identify the three parts illustrated above.
2. If the exhaust opening has a shipping cover, remove it.
If the exhaust opening has a factory-installed damper, check damper blade operation.
3. Position one of the hood side panels with the ange out as illustrated. Line the holes up with the holes in the
cabinet. Attach the side panel to the cabinet with the screws provided. Repeat with the opposite side.
4. Position the hood top UNDER the edge of the cabinet top and OVER the installed side panels.
Using six screws, attach the hood top to the cabinet. Attach the top to both sides as illustrated.
6.2.3 Inlet Air Hood
Inlet Air Hood Components
Components of the Inlet Air Hood - (qty) and P/N by Model ZQYRA Size
CODE (See
FIG 13B-D)
A(2) Strips of P/N 103604 Gasket strips are for across top and bottom; length of each is 23” (584mm) .
B(2) Strips of P/N 103604 Gasket strips are for sides - Size 8, 28-1/2” (724mm) length; Size 12, 32” (812mm) length
C(1) 262662(1) 262662
D(1) 262663(2) 262663For Middle and Bottom Hoods
E(2) 262665(3) 262664 Inlet Hood Right Side Panel
F(2) 262667(3) 262666 Inlet Hood Left Side Panel
(107) 11813Screws (in hardware bag, P/N 260354, for both the inlet hoods and the exhaust hood)
For Top Hood (top with wider ange across the back)
Description
Outside Inlet Air
Hood Assembly and
Installation Instructions
- Steps apply to both
sizes unless noted.
Form I-ZQYRA P/N 260414R8, Page 10
1. Identify the hood components from the list above and the assembly illustrations.
2. Prepare the Cabinet Inlet
a) Remove the shipping cover.
b) If the inlet has a factory-installed damper, check the damper for any damage.
(For additional information on the damper, see Paragraph 6.2.4.) If damper
blades are operating properly, remove the screws (listed in table below) holding
the damper frame.
Facing the Inlet OpeningSize 8Size 12
Across the Top4 screws4 screws
Right Side5 screws8 screws
Left Side1 screw2 screws (in oblong holes)
If the inlet does not have a damper, there are no screws to remove.
c) Determine gasket strip location, clean the surface, and carefully attach each
gasket strip in the order listed.
1st - BOTTOM Gasket Strip (A) - At the corner, measure up from the bottom of
the cabinet:
- Size 8 - 7-1/2” (191mm)
Refer to FIGURE 10,
D
Top for Bottom
& Middle Hood
E
Right Side
Panel
F
G
H
J
K
M
N
Front Cross
Bracket - 21-15/16”
(557mm) long
Filter
Front Filler Plate
(Size 8 only)
Filter Access
Rear Cross
Bracket -
22-13/16”
(579mm) long
Left Side
Panel
Side Filter
Bracket (2)
page 9, and FIGURE 12
below for appearance of
installed hoods.
FIGURE 12 - View
of installed hoods
showing that the
assembled inlet air
hoods attach to the
outside of the cabinet
corner post.
- Size 12 - 10” (254mm)
At that point starting at the corner,
mark a straight horizontal line.
Position one of the 23” (584mm)
FIGURE 13A - Attach
Gasket Strips
Top
A
gasket strips with the bottom edge on
the line. Adhere the gasket.
2nd - SIDE Gasket Strips (B) -
Left Side - Starting even with the
bottom of the horizontal gasket strip,
Left
Side
B
B
Right
Side
position the side strip on the edge of
the corner post (around the corner
from the opening). Clean the surface.
Starting at the bottom, adhere the
gasket strip.
Measure up from
the cabinet bottom.
Size 8 - 7-1/2” (191mm)
Size 12 - 10” (254mm)
A
Bottom
Right Side - On the post or damper
frame on the right of the opening, starting at the bottom, adhere the gasket
strip vertically up the side of the opening.
3rd - TOP Gasket Strip (A) - Position the top strip horizontally across the top
connecting the two side strips. Clean the surface and adhere the gasket.
3. Assemble and Install the Bottom Hood Using Screws from the Hardware Bag
a) Assemble the hood as illustrated in FIGURE 13B, except for installing the lter
(M) and the lter access panel (K).
FIGURE 13B - Assemble Bottom Hood
FIGURE 13C Attach Bottom
Hood
NOTE: Size 12 is illustrated. Size 12 does not have a
filler plate (N). Procedure is the same for both sizes.
b) Attach the assembled hood; refer to FIGURE 13C. Position the hood so
that the rear cross bracket is on the bottom gasket strip, the left side is
on the gasket strip on the corner post, and the right side on the other
gasket strip. On the right side, match the holes under the gasket strip
with the holes in the hood side panel. Adjust hood location slightly as
needed and attach with screws. Being sure the holes match, attach
the left side of the hood to the corner post.
c) Slide the lter (M) in place and attach the lter access panel (K).
4. Size 12 only - Repeat the procedure in Step 3a (FIGURE 13B) to
assemble the middle hood. Position it above the bottom hood. Line up
the holes on the right side and attach the hood. Attach the left side to
the corner post.
Slide the lter in place and attach the lter access panel.
5. Using the hood top with the longer ange, repeat the procedure in
Step 3a (FIGURE 13B) to assemble the last hood.
When positioning the hood on the cabinet (FIGURE 13D), slide the
Top was
already attached
to the hood sides
in Step 3a.
Filter
M
K
FIGURE 13D -
Attach Top
Hood
NOTE: Size 8
is illustrated.
Procedure is
the same
for Size 12.
Form I-ZQYRA P/N 260414R8, Page 11
Filter Access
When attaching
the top hood, slide
the hood flange
under the edge of
the cabinet top.
6.0 Mechanical
(cont’d)
6.2 Inlet Air and Exhaust Air Openings (cont’d)
6.2.3 Inlet Air Hood (cont’d)
hood top ange under the edge of the cabinet top. (If needed, loosen the screw
in the cabinet top.) Matching holes, attach the hood on both sides and across the
top.
To complete the installation, slide the lter (M) in place and attach the lter access
panel (K).
6.2.4 Inlet and
Exhaust Dampers,
Option AR2Y
6.3 Duct
Connections
and Ductwork
Indoor Installation
NOTE: If installing
this ventilation unit
indoors, exhaust and
supply airow will be
double. Ductwork and
louvers must be sized
accordingly.
(Size 8 - CFM Range is
500-1100; Size 12 - CFM
Range is 900-1500)
Example: A Model
ZQYRA 12 installed
indoors operating at
1500 cfm will require
supply and exhaust
ductwork sized for 3000
cfm.
If equipped with optional intake and exhaust dampers, the intake damper has a
motorized actuator and the exhaust damper has a barometric control.
The intake damper has a 24volt, two-position, spring return actuator directly
interlocked with the supply fan. The actuator opens the damper whenever the supply
fan is commanded to operate. When the supply fan is off, the actuator’s spring drives
the damper closed.
The exhaust hood features a low leak gravity operated back draft damper. The exhaust
damper starts to open at 0.03” w.c and is fully opened at 0.10” w.c.
Duct Connection Conguration
This unit has both vertical and horizontal supply and return air duct opening locations
so ductwork connection openings being used depend on the installation.
Installation using Horizontal Ductwork - See locations of the horizontal duct
openings in FIGURE 10, page 9, and dimensions in FIGURE 1, page 4. Remove
the cover from the horizontal return air opening and re-locate it to cover the vertical
return air opening in the bottom of the cabinet. Remove and discard the cover from the
horizontal supply (discharge) air opening. Shipped in the carton with the hood parts
(see Paragraph 6.2), nd the cover for the vertical supply air opening. Install the cover
to close the vertical supply air opening.
Installation using Vertical Ductwork - Vertical ductwork connection anges are in the roof curb; see dimensions in FIGURE 8, page 8. If vertical ductwork was not installed
from the top or a eld-supplied curb is used, a transition may be required for attaching
ductwork. When using vertical ductwork, the horizontal duct opening covers should not
be removed and the vertical supply duct cover shipped in the hood carton will not be
used.
Requirements and Suggestions for Ductwork Design and Installation
Before operating the unit, be sure that the unused supply and return air openings are
closed with the covers provided.
CAUTION: An external duct system static pressure not within the
limits shown on the rating plate may overload the motors. See
Hazard Levels, page 2.
• Type of Ductwork - The type of duct installation to be used depends in part on
the construction of the roof (whether wood joist, steel bar joist, steel truss, pre-cast
concrete) and the ceiling (whether hung, ush, etc.).
• Ductwork Material - Rectangular duct should be constructed of not lighter than
No. 26 U.S. gauge galvanized iron or No. 24 B & S gauge aluminum.
• Ductwork Structure - All duct sections 24 inches (610mm) or wider, and over 48
inches (1219mm) in length, should be cross broken on top and bottom and should
have standing seams or angle-iron braces. Joints should be S and drive strip, or
locked.
• Through Masonry Walls - No supply air duct should come in contact with
masonry walls. Insulate around all air ducts through masonry walls with not less
than 1/2" (13mm) of insulation. 1" (25mm) is recommended.
• Through Uncooled/Unheated Space - Insulate all exposed supply air ducts
passing through an uncooled or unheated space with at least 1/2" (1" is
recommended) of insulation.
• Duct Supports - Suspend all ducts securely from buildings members. Do not
support ducts solely by the unit duct connections.
the diameter of the
condensate drain piping.
3/4” PVC is required for
attaching to the drain
connection. See FIGURE 10, page 9, for drain
location.
Condensate Drain Trap
• Duct Sizing - Proper sizing of the supply air ductwork is necessary to ensure a
satisfactory installation. The recognized authority for such information is the Air
Conditioning Contractors Association, 2800 Shirlington Road, Suite 300, Arlington,
VA 22206 (www.acca.org). A manual covering duct sizing in detail may be
purchased directly from them.
• Duct Connections - To minimize sound and vibration transmission, use
exible duct connections. Ducts must be attached and sealed to provide airtight
connections.
• Return Air Duct/Grill Size - Make certain that return air ducting or grill has a free
area equal to the return duct size connection.
All systems require a condensate drain. A non-corrosive drain pan with a 3/4 Schedule
40 PVC socket adapter tting is located on the non-control side of the cabinet. When
connecting the drain line, provide a means of disconnecting the line at or near the
cabinet connection to allow for cleaning.
Ensure the system is level before connecting the drain line. Do not reduce the drain diameter.
Follow the instructions below to install a trap in the drain. Pitch the drain line at least
1/2" (13mm) for every 10 feet (3M) of horizontal run. Drain lines must not interfere with
drain pan or access panels.
An obstruction in the drain or a poorly designed drain can cause the condensate pan
to over ow. Do not reduce the drain piping diameter. Overow could result in damage
to the unit and/or the building.
If the installation or local code requires, run drain into a waste water system.
The design of the drain trap is important. The trap height must account for this static
pressure difference. Maximum negative static can be determined by reading the
negative pressure at the blower inlet and adding .2” w.c. to allow for dirty lters.
If dimension "B" in FIGURE 14A is not tall enough, the water seal will not hold, and
air will be drawn through the drain pipe into the system. If the outlet leg of the trap
is too tall, water will back up into the drain pan. As condensate forms during normal
operation, the water level in the trap rises until there is a constant outow. FIGURE
14A illustrates the appropriate dimensions for trapping a negative pressure system.
Improper trap design accounts for some condensate drainage system failures, but
incorrect use and maintenance of condensate drain trap can also cause problems.
The combination of airborne particles and moisture in the air handler can result in
algae formation in the drain pan and trap. The trap must be cleaned regularly to avoid
blockage that can slow or stop water ow, resulting in backup into the system.
If drain has a cleanout opening (FIGURE 14B), be sure to close the opening after
cleaning.
FIGURE 14A Condensate Drain Trap
Dimensions
A = 1" (25mm) for each 1"
(25mm) of maximum
static pressure plus 1"
(25mm)
B = A + A/2
Condensate Drain Use
FIGURE 14B -
Drain Trap
with Cleanout
At the beginning of the cooling and heating season, inspect and clean the condensate
drain pan and line. Thoroughly clean dirt, algae, grease, and other contaminants.
Inspect condensate drain pan, trap, and piping; ll trap with water to ensure proper
operation.
Since the heat pump operates year round, more frequent inspections of the condensate
drain may be required. Freeze protection of the trap will be required when the outside
temperature is below freezing.
Form I-ZQYRA P/N 260414R8, Page 13
7.0 Electrical
Connections
and Wiring
All electrical wiring and connections, including electrical grounding MUST be made
in accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition). In
addition, the installer should be aware of any local ordinances or electric company
requirements that might apply.
See FIGURE 1, page 4, to show the entrance locations for the high voltage and low
voltage wiring.
7.1 Supply Voltage
CAUTION: If this
unit is allowed
to operate on an
electric supply
that is not within
the specied
tolerances, the
product warranty
shall be void. See
Hazard Levels,
page 2.
CAUTION: Check
compressor
rotation to verify
correct phasing.
DO NOT use fan
rotation to check
phasing. ECM
fans cannot run
backwards.
Disconnect Switch
The system may be factory equipped with a built-in non-fusible, lockable disconnect
switch (See location in FIGURE 1, page 4). The built-in disconnect switch (Option BA6)
requires copper wiring with ampere rating based on 75°C maximum temperature rating
at the line side terminals.
If the system does not have a built-in disconnect switch, a eld-provided or optional
shipped-separate, wall-mounted disconnect switch is required. It is recommended that
there is at least four feet (1.2M) of service room between the wall-mounted switch and
unit access panels. All external wiring must be within approved conduit and have a
minimum temperature rise rating of 60°C. Run conduit so that it does not interfere with
unit access panels. When providing or replacing fuses in a fusible disconnect, use dual
element time delay fuses and size according to the rating plate.
Check the rating plate for the supply voltage and current requirements. The electric
supply to the unit must meet stringent requirements for the system to operate properly.
Voltage supply should be within ±10% or as stated on the rating plate. Maximum
imbalance on a 3-phase system is 2%. Follow instructions below to check.
If the power supply is not within these tolerances, contact the power company prior to
operating the system.
Check Voltage Supply - See voltage use range on the rating plate. Measure (and
record) each supply leg voltage at all line disconnect switches. Readings must fall
within the allowable range.
Check Voltage Imbalance - In a 3-phase system, excessive voltage imbalance
between phases will cause compressor motors to overheat and eventually fail.
Maximum allowable imbalance is 2%. To determine voltage imbalance, use recorded
voltage measurements taken above in the following formula.
Key:
Formula:
3-Phase Wiring Connection - There is a chance of unknowingly connecting
3-phase power in such a way as to cause compressor rotation in reverse. To
prevent damage to the components, it is important to check this on startup.
Checking the rotation of the compressor requires connecting pressure gauges
BEFORE startup. Connect refrigerant manifold pressure gauges rated for use with
R410-A refrigerant to the compressor suction and discharge lines.
At startup, observe the gauges. If the suction pressure rises and discharge pressure
drops, the compressor is operating in reverse and should be shut down. (After
several minutes of operation in reverse, the compressor’s internal protector will trip. If
compressors are repeatedly allowed to restart and run in reverse, the compressors will
be permanently damaged.)
To correct, shut down the unit and turn off the power. At the incoming power connection, switch the 3-phase line voltage wiring connections before restarting the unit.
Recheck the pressure gauges.
V1, V2, V3 = line voltages as measured
VA (average) =
VD = line voltage (V1, V2, or V3) that deviates farthest from average (VA)
% Line Voltage Imbalance =
(V1 + V2 + V3)
3
[100 x (VA - VD)]
VA
CAUTION: Connect pressure gauges to the suction and discharge lines BEFORE
startup so that compressor rotation can be checked immediately. Scroll compressors
will be destroyed if operated in the wrong direction. See Hazard Levels, page 2.
Form I-ZQYRA P/N 260414R8, Page 14
and C in the electrical compartment.)
7.2 Supply Wiring
FIGURE 15A illustrates supply wiring connections with or without Option BA6
disconnect switch.
Option BA6
60A LOCKABLE ON/OFF
DISCONNECT SWITCH
#6 BK
#6 Y
#6 R
Field installed wiring (If there is no Option BA
disconnect switch, connect field wires at A, B,
A
B
C
Supply Wiring
Connections
FIGURE 15A - Supply
Wiring Connections for
Options AK5, AK6 and
AK7
OPTIONAL FUSIBLE
DISCONNECT SWITCH
460/3/60
208 or 230/3/60
GND
Depending on option selection, the unit is wired for:
• 208v /3ph / 60Hz - Option AK5
• 230v / 3ph / 60Hz - Option AK6
• 460v / 3ph / 60Hz - Option AK7
Supply VoltageSupply Fan Motor Exhaust Fan MotorSupply Wiring and Connection (See FIGURE 15A)
To prevent injury or death due to electrocution or contact with moving parts, lock disconnect
switch open. See Hazard Levels, page 2.
Form I-ZQYRA P/N 260414R8, Page 15
7.0 Electrical Connections and Wiring (cont’d)
7.3 Electrical
Compartment
Locations of Components
Remove the electrical compartment access panel to view the controls and compressor
as illustrated in FIGURE 16. Some components in the electrical compartment are
common and some vary by options selected.
FIGURE 16 -
Control
Locations
Electrical
Panel
Contactor (fans)
Multi Voltage
Relay Module
(time
schedule
clock,
Opt CN7A)
Distribution
Blocks -
A, B, and C
Grounding
Lug
Contactor
(wheel)
Contactor
(heat pump)
Digital Controller
(Compressor)
Contactor (optional
electric preheat)
Terminal Blocks
Control
Transformers
Control Transformer
Control Compartment
with Access Panel
Removed
Transformer
(Size 8, 460V)
Supply &
Exhaust Fan
Overload Relays
Contactor
(supplemental
heating element)
Relay
(damper motor)
Field
(damper motor)
Connection
Terminal
Blocks
Unit Controller
(NOTE: If ordered
with a BACnet®
or LONworks®
communication
card, it is located
on the controller;
see Paragraph 8.7.)
Controls on either the side or
back wall of the Control
Compartment
Display
Module
Air Proving Switch
(supply side),
P/N 197031 set
at 0.35” w.c.
Air Proving Switch
(exhaust side),
P/N 197031 set
at 0.35” w.c.
Option BE18
Dirty Filter
Switch
7.4 Electrical
Components
7.4.1 Fan Motors
The supply and exhaust fans are centrifugal, backward curve fans with integral
electronically commutated motors (ECM) that are directly controlled by the unit interface
control. The unit uses a portion of the outside intake air as part of the return airow as
shown in FIGURE 17.
At startup, the speed of each fan must be set. See the instructions in Paragraph 9.3
FIGURE 17 - Diagram showing Airow through the Unit
NOTE: If installing this ventilation unit
indoors, exhaust and supply airow will be
double. Ductwork and louvers must be sized
accordingly.
(Size 8 - CFM Range is 500-1100;
Size 12 - CFM Range is 900-1500)
Example: A Model ZQYRA installed indoors
operating at 1500 cfm will require supply and
exhaust ductwork sized for 3000 cfm.
The energy recovery wheel is equipped with a motor and belt drive. When the unit
controller requires energy recovery, the wheel motor responds and rotates the wheel
through both the inlet and return airstreams.
Compressor - The heat pump has a digital scroll compressor providing quieter, more
efcient operation. The compressor has high and low pressure switches, a crankcase
heater, a thermistor to protect against too high temperature, and a modulating
solenoid valve for operation. The digital controller in the electrical compartment (See
FIGURES 18A and 19.) is the electronic interface between the compressor and the
system controller. The compressor controller is connected to the unit control to provide
protection and diagnostics for compressor operation.
After a compressor shutdown, a two-minute anti-short cycle timer in the compressor
controller delays the compressor restart. The unit controller has a ve-minute
compressor on/off time. The delay times are concurrent so total delay time is ve
minutes.
FIGURE 18A - Compressor Digital
Controller located in the control
compartment interfaces the
compressor with the unit controller.
LED
Color
Green Solid
Green Flashing
LED
State
Indicates
Power (24VAC present at
power terminals)
Anti-short cycle timer is
active
Unloader (Solenoid valve
Yellow Solid
is energized; compressor
capacity is 0.)
RedNot litNo abnormal operation alerts
RedFlashing See Paragraph 10.3.2.
The heat pump compressor and refrigerant piping with reversing valve shown in
FIGURE 18B are located directly under the control compartment and are accessed
through the same removable side panel.
FIGURE 18B -
Heat Pump
Compressor
and Piping
Compressor
Modulating
Solenoid Valve
High Pressure Switch (manual reset)
is on the discharge line
Reversing Valve
(enlarged view below)
When the controller calls
refrigerant flow.
Compressor
Thermistor
Crankcase Heater
CAUTION: Crankcase heater must be allowed to warm up for at least 24 hours prior to startup
or after a power outage of eight or more hours. Either turn the unit off with a CN option switch if
available or remove the jumper to break contact between Terminals 3 and 8, BEFORE turning on
power to warm up the crankcase heater.
The scroll compressor also has a belly band crankcase heater which straps around the
bottom half of the compressor. The crankcase heater must be allowed to warm up for
at least 24 hours prior to startup or after an 8-hour power outage.
Charge
Compensator
Low Pressure Switch (auto reset)
Form I-ZQYRA P/N 260414R8, Page 17
Accumulator
7.0 Electrical and
Wiring (cont’d)
Coils
7.4 Electrical Components (cont’d)
7.4.3 Heat Pump (cont’d)
The heat pump has highly efcient evaporator and condenser coils and a cleanable
condensate drain pan. When the heat pump is in a defrost state, electric heat coils (5kW
Size 8; 10kW Size 10) are activated to ensure the discharge air stays at a comfortable
temperature.
FIGURE 19 shows the locations of the evaporator and condenser coils and their
thermostatic expansion and check valves. The system is factory charged with
7.4.4 Optional Electric
Preheat, PH1A (5kW)
and PH2A (10kW)
Condenser Coil
Check Valve
Flow Direction
TXV Bulb Location
Thermostatic
Expansion
Valve
Thermostatic
Expansion
Valve
Flow Direction
Expansion Valve
Evaporator Coil
Flow Direction
Expansion Valve
Check Valve
TXV Bulb Location
Flow Direction
Condensate Drain
Side Opposite Controls View
(partial view)
If ordered with optional electric preheat, electric elements will be installed in the cabinet
between the inlet hood and the energy recovery wheel. Optional electric preheat
provides frost protection for the wheel in extremely cold temperatures. For more
detailed information on controls, see “Optional Preheat Control” in Paragraph 8.2.
Check the unit rating plate for the MCA and MOP of a unit with optional electric preheat.
FIGURE 20 - Location of Optional Electric Heating Elements
Model ZQYRA Size 12 with Option PH2A
Model ZQYRA Size 8 with Option PH1A
(one heating element)
NOTES: Both Model Sizes 8 and 12 could have either Option PH1A (5kW) or PH2A (10kW). If it is determined after
installation that electric preheat is needed, contact your distributor about eld installing heating elements.
7.5 Control Wiring
(eld-installed)
7.5.1 Control Wiring General Requirements
There are ve wall-mounted control options & one duct mounted temperature sensor
that require eld installation and wiring. Follow the manufacturer’s instructions for instal-
lation. Refer to Paragraph 7.5.2 for more detailed information about wiring and operation
for each control option.
Form I-ZQYRA P/N 260414R8, Page 18
(two heating elements)
Digital Control
4 x 12 x 24
3.14
4 x 305 x 610
3.14
Signal Wiring
Recommendations
and Requirements
24V Field Control Wiring Length and Size Requirements
The manufacturer recommends for optimum temperature control performance that the
analog and digital inputs (CO2 and air quality sensors) that are connected to the main
controller have a <3% wattage drop and be routed to the unit in one of the following
manners:
1) In separate conduits, isolated from 24 VAC controls and line voltage power to the
unit, OR
2) If the digital sensor wires are to be run in the same conduit as the 24 VAC control
wiring, the CO2, VOC, and display sensor wiring in Options CN7B, CN7C, and
RB5 must be completed using shielded cable and bundled separately from the
24 VAC control wiring. The shield must be drained at the unit and taped on the
opposite end.
Comply with the digital control sensor wire gauge and length requirements in the
table below.
Maximum
Sensor Wire
Length for less
than 1°F Signal
Error
Wire Gauge
AWG
14800244
16500152
1831094
Maximum Sensor Wire Length (Digital Control)
FeetMeters
7.5.2 Instructions for
Installing Discharge
Air Sensor in the
Ductwork
FIGURE 20A-
Discharge Air
Temperature
Sensor Probe and
Weatherproof Box,
P/N 222753
The discharge air temperature sensor (See FIGURE 20A.) is shipped with every unit
and must be eld installed in the ductwork. The location and position of the sensor are
important. Follow the instructions below.
1. Determine the appropriate distance from the unit. Be sure there is sufcient
distance from the outlet to have a good mixture of discharge air temperature.
According to the latest edition of AMCA Standard 201, in straight ducts, the air
is typically well mixed a minimum of ve equivalent duct diameters from the discharge of the unit with equivalent duct diameter dened as equal to the square
root of 4AB/3.14. "A" and "B" are the duct cross-sectional dimensions.
Example: Supply ductwork cross-sectional dimension is
24" x 12" (610mm x 305mm).
5 x
= 96" 5 x
= 2435mm
Locate the sensor a minimum of 96" (2435mm) from the
outlet of the unit.
NOTE: If the length of the discharge duct is less than 8 ft (2.4M), a mixing vane is
recommended for mixing the discharge air.
Do not mount the sensor in the ductwork after a split in the supply as that will
cause loss of control in the duct that does not house the sensor.
2. Determine the location and orientation of the sensor. The position of the sen-
sor in the duct is also important. In horizontal ductwork, locate the sensor assem-
bly in the top, middle of the duct with the sensor probe extending vertically down
into the center of the airstream.
In vertical ductwork, locate the sensor assembly in the middle of the side of the
duct that corresponds with the top middle of the discharge outlet.
3. Attach the sensor. Mark the selected location and drill a 7/16" hole. Insert the
probe into the hole. Be sure that the blue plastic tting holding the probe is centered in the hole. Attach with two No. 8 sheetmetal screws (do not overtighten).
Check to be certain that the hole is sealed.
4.Run the sensor wire to the unit. Use eld-supplied 2 to 3 pair of 16 to 22 ga
wire. Digital control inputs are low-current, resistance-based signals.
Form I-ZQYRA P/N 260414R8, Page 19
Multi-Voltage Relay Module, P/N 260189, used with
Option CN7A is mounted in the electrical
compartment at the factory; see FIGURE 16, page 16.
Time ClockWall Switch,
Leviton Model VPT24-1P,
P/N 260188
BK
BL
W
O
R
BK
W
Y/R
R
G/Y
(HOT) BK
(NEUT) W
}
115/1/60
LINE
PAM-1
TIMER
SWITCH
Y
22
23
BL
8
Multi-voltage
relay
(see below)
3
= field wiring
= field connection terminal block
7.0 Electrical and
Wiring (cont’d)
7.5 Control Wiring
(eld-installed)
(cont’d)
7.5.2 Specic
Wiring by Control
Option (cont’d)
Depending on which eld-installed control option was ordered, the unit will operate
whenever there is a call for fresh air (ventilation) from that control. Otherwise, the unit
is OFF.
The wall-mounted, manual two-position key switch in Option CN5 will start or stop
the unit. Mount the 2-wire, 24V switch in a eld-supplied, standard 2 x 4 electrical
box. Install the cover plate. Follow the wiring diagram to run the wires and make the
connections. Mount the start/stop switch on the wall.
Components and wiring
information for Option CN5.
START
STOP
Cover, P/N 260229
Label, P/N 260228
2-Position (start/stop)
Key Switch, P/N 260227
2 Key Positions
START
STOP
Reference
CN5
KEY LOCK
POWER SWITCH
83
= field wiring
= field connection terminal block in the
electrical compartment of the unit
The compact wall-mounted time clock with manual
ON/OFF override will start or stop the unit. The
24-hour time clock schedule allows exible weekday
and weekend start/stop times with a convenient
daylight savings update. A rechargeable battery
maintains the programming in a temporary power
outage. The unit requires a 2-wire, 120V power supply, external of the ventilation unit. As shown
in the wiring diagram, a switch relay converts the
time clock 120V output to a set of dry contacts. Two
FIGURE 22 Option CN7A,
Time Clock
Wall Switch
and Wiring
Connections
Form I-ZQYRA P/N 260414R8, Page 20
Time Clock Wall Switch, Option CN7A (cont’d)
dry contact wires are terminated to controller terminals 3 and 8 which activate the unit
when closed.
Install the time clock in a standard, eld-supplied 2 x 4 electrical box to be mounted in
the wall. Provide power to the time clock. Follow the wiring diagram to run the control
wires and make the connections. Add the supplied cover plate. For programming,
see the instruction sheet provided by the manufacturer. Follow the instructions for
programming Leviton Model VPT24-1P.
CO2 Sensor, Option
VOC and CO
Sensor, P/N 260192
Keyed, 3-Position Wall
Switch, P/N 260230
Cover, P/N 260229
Label, P/N 260231
3 Key Positions
HAND
OFF
AUTO
HAND
AUTO
OFF
Reference
11
SW2
AUTO & HAND
AUTOSW1
8
SHIELD
1
GROUND
3
SIGNAL
IAQ SENSOR
SHIELD
(OPT. CN7C)
1
POWER
2
GROUND
SWITCH
KEYED
3
9
3
= field wiring
CN7B
The CO2 sensor with manual HAND/OFF override will start or stop the unit. The
infrared beam technology provides reliable and accurate sensing of the CO2 level
(±50 ppm). When in AUTO, the CO2 sensor will activate the unit whenever the carbon
dioxide rises above the factory default value of 1000 ppm (0-2000 ppm range).
The manual key switch will allow the unit to be directly commanded HAND or OFF,
bypassing the sensor.
FIGURE 23 - Option CN7B, CO2 Sensor Switch and
Wiring Connections
(OPT. CN7B)
SHIELD
= field connection terminal
block in the electrical
compartment of the
ventilation unit
3
11
= field wiring
KEYED
SWITCH
AUTO & HAND
SW2
AUTOSW1
8
9
SHIELD
Follow the sensor manufacturer-provided instructions for mounting the sensor. Install the switch in a eld-supplied,
standard 2 x 4 electrical box to be mounted in the wall.
The sensor is powered from the control module 24VAC transformer. Follow the wiring diagram to run the wires and
make the connections. Use shielded 2/c cable for the 0-10V digital signal.
Attach the “HAND/OFF/AUTO” cover plate.
CO2 SENSOR
GROUND
2
SIGNAL
4
GROUND
2
POWER
1
HAND
OFF
AUTO
Cover, P/N 260229
Label, P/N 260231
CO2 Sensor,
P/N 234820
Keyed, 3-Position
Wall Switch,
P/N 260230
3 Key Positions
HAND
Reference
OFF
AUTO
Indoor Air Quality
(VOC and CO) Sensor,
Option CN7C
The volatile organic compound (VOC & CO) sensor with manual HAND/OFF override
will start or stop the unit. When in AUTO, the unit will start whenever the air quality in
the space environment exceeds the VOC level of the setpoint.
This option also provides a three-position keyed, manual switch that is wired to the
digital input. The three position switch provides “auto”, “hand (manual on)” and “off”
modes.
• When the switch is in the AUTO mode, the sensor is powered, the digital start/stop
input is open, and the system monitors the VOC levels.
• When the switch is in HAND mode, the contact is closed and the sensor is
disabled. When the input is closed, the unit is on.
FIGURE 24 - Option CN7C, Air Quality Sensor Switch and Wiring Connections
• When the switch is in the manual OFF mode, the contact is open and the sensor is
disabled. When the input is open, the unit is off
Follow the sensor manufacturer-provided instructions for adjusting the setpoint and for
mounting the sensor. Install the switch in a eld-supplied, standard 2 x 4 electrical box
to be mounted in the wall.
The sensor is powered from the control module 24VAC transformer. Follow the unit
wiring diagram to run wires and make connections. Use shielded 2/c cable for the
0-10V digital signal.
Attach the “HAND/OFF/AUTO” cover plate.
Form I-ZQYRA P/N 260414R8, Page 21
COM
RELAY
OUTPUT
COMM
INPUT
POWER
24V IN
N.O.
OCCUPANCY SENSOR
PW-100-24
OPT. CN7D
8
11
10
3
= field wiring
7.0 Electrical and Wiring (cont’d)
7.5 Control Wiring (eld-installed) (cont’d)
Space Mounted
Occupancy Switch,
Option CN7D
The space-mounted occupancy switch is well suited for small enclosed spaces with
clear line of sight of the occupants. In “Auto-On” mode, the unit will start or stop based
on occupancy. The passive infrared sensor features an adjustable 5 to 30 minute
sensing window to prevent nuisance switching. The sensor has a manual on/off
override feature providing manual on/off control.
Refer to the manufacturer’s instructions for mounting and operation. The sensor
requires a separate power supply, external of the ventilation unit.
Four wires are required from the ventilation unit control panel to the wall sensor. Follow
the wiring diagram provided with the ventilation unit to run the wires and make the
necessary connections.
(2) Cable Splitter and Signal
Booster Modules, P/N 260735
(2) 6-pin Connection
Cables, P/N 260175
Front and Side Views with Dimensions
Plug
A
Screw Terminals
Plug
B
Plug
C
6
5 432
1
0
1.125”
(29mm)
2.75” (70mm)
1.56”
(40mm)
3.13” (80mm)
Ø.219
(6mm)
Mounted Unit Display,
Option RB5
FIGURE 26 Components of Option
RB5, Field-Installed
Remote Display
The factory-installed display (Paragraph 8.1) allows complete access to unit test
features, schedules, discharge air setpoints, fan control, alarms, and other unit
operational setpoints. Option RB5 is a second, remote-mounted display that can be
eld-installed up to 1500 ft (457M) from the unit allowing the same unit access. To
install the remote-mounted display, follow the illustrated instructions below.
FIGURE 27A - Install
one of the cable
splitter and signal
booster modules on
the wall of the electrical
compartment.
Instructions to eld install Option RB5, Remote Mounted Display
Option RB5 is a remote unit interface display that provides the same access as the
unit interface module described in Paragraph 8.1. The remote unit interface module
is shipped separately or loose for eld mounting. Field-supplied 22 AWG to 18 AWG
twisted pair wire (EIA 485) and an electrical junction box are required. Follow the
instructions below for setup and installation.
1. Turn power off to the unit (lock the disconnect switch open).
2. Install one Cable Splitter and Signal Booster Module inside the Cabinet
a) Remove the electrical compartment access panel. Position one of the cable
splitter/signal booster modules (P/N 260735) on the wall of the electrical
compartment as illustrated. Attach it with the screws provided.
Main Controller
Unit Display
Attach cable
splitter/cable
booster
module for
Option RB5 to
the wall of the
control
compartment
b) In the electrical compartment, nd the unit display and the main controller (See
FIGURE 27A). At the main controller, locate and unplug the 6-pin connection
cable (the cable that connects from the unit display to the controller). Move the
disconnected end of the cable to the module installed in Step 2a) and connect it
to plug “A” (see illustration below).
c) Install one of the new 6-pin connection cables (P/N 260175), connecting one
end to the main controller and the other to plug “S” (see below) on the module
installed in Step 2a).
3. Install the second Cable Splitter/Signal Booster Module at the Remote
FIGURE 27B - Wiring
Connections on Cable
Splitter in Option RB5
Wiring Connections on Cable Splitter and Signal Booster Module, P/N 260735
6
5 432
Plug
A
Screw Terminals
Plug
B
Location
a) Determine the desired location for the remote display unit. It can be located up
FIGURE 28 - Wiring Connections for
Installing Option RB5
Pin Telephone
Connection
Meaning
Using eld-supplied 22 AWG to 18 AWG shielded
twisted pair wire (EIA 485), run dedicated wires
from that location to the unit. Two sets of twisted
pair wire are required -- one for the power and one
for communication. The communication wire should
be shielded to prevent noise.
On the cable splitter/signal booster module installed
in Step 2a), connect the shield to screw terminal 0.
Connect the power wires to screw terminals 1 and
2. Connect the communication wires to terminals 3
and 4.
On the cable splitter/signal booster module installed
in Step 2a), connect the power wires to screw
terminals 1 and 2. Connect the communication
wires to terminals 3 and 4.
Form I-ZQYRA P/N 260414R8, Page 24
b) Install the second cable splitter/signal booster
module (P/N 260735) in a eld-supplied junction
box to be recessed behind the remote display.
Connect the shield to screw terminal 0. Connect
the power wires to terminals 1 and 2 and
communication wires to terminals 3 and 4, making
sure that power and communication polarity is
maintained.
CAUTION: Improper wiring can damage
the remote unit interface display as well as
the main system controller.
c) Attach the second 6-pin connection cable (P/N
260175) in the kit to plug “A” on the remote cable
splitter/signal booster module.
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.