Reznor YDSA Installation Manual

!
CQS
Form I-Y (Version .5)
Obsoletes I-Y (Version .4)
Installation / Operation
Applies to: Models YDHA, YDMA, and YDSA
Packaged Rooftop Equipment
P
R
O
Y
C
C
E
N
E
G
A
C
C
U
S
T
O
M
CQS
E
Q
R
U
P
R
O
D
Refrigerant
This unit contains R-410A high pressure refrigerant. Hazards exist that could result in
personal injury or death. Installation, maintenance, and service should only be performed by an HVAC technician qualied in R-410A refrigerant and using proper tools and equipment.
Due to much higher pressure of R-410A refrigerant, DO NOT USE service equipment or tools designed for R22 refrigerant.
S
R
E
G
S
V
E
N
N
O
T
M
Y
E
A
L
I
T
U
C
T
T
S
N
Y
Y
S
A
R
R
A
T
W
R-410A
P
U
-
T
R
A
T
S
DANGER:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
Be sure to read and understand the installation, operation, and service instructions in this manual.
Improper installation, adjustment, alteration, service, or maintenance can cause serious injury, death, or property damage.
Do not store or use gasoline or other ammable vapors and liquids in the vicinity
of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Leave the building immediately.
Immediately call your gas supplier from a phone remote from the building. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the re department.
Installation and service must be performed by a qualied installer, service agency,
or the gas supplier.
Form I-Y, P/N 273646R6, Page 1
Table of Contents
1.0 General .........................................................2
1.1 Cautions and Warnings ................................... 2
1.2 General Information ........................................ 3
1.3 Warranty ......................................................... 3
1.4 Installation Codes ........................................... 3
2.0 Location and Moving ...................................3
3.0 Receiving, Shipped Separate and Storage . 4
3.1 Receiving ........................................................ 4
3.2 Shipped Separate Accessories and Shipped
Loose Parts ..................................................... 4
3.3 Storage ........................................................... 6
4.0 Clearances and Dimensions .......................6
4.1 Clearances ..................................................... 6
4.2 Dimensions .................................................... 7
5.0 Mounting .....................................................10
5.1 Unit Weights.................................................. 10
5.2 Curb Cap Base and Mounting ...................... 10
5.3 Mounting on a Roof Curb ............................. 10
5.4 Rigging and Lifting ........................................ 19
6.0 Mechanical .................................................20
6.1 Install Hood(s) ............................................... 20
6.2 Duct Connections and Duct work ................ 22
6.3 Cooling Section Condensate Drain .............. 22
7.0 Electrical and Wiring .................................23
7.1 General ......................................................... 23
7.2 Supply Wiring................................................ 23
7.3 Wiring Diagram, Unit Wiring Requirements, and
Optional Convenience Electrical Outlet ......... 25
7.4 Electrical Compartment - Control Locations . 26
7.5 Control Wiring ............................................... 27
7.6 Supply Fan with Variable Frequency Drive .. 31
7.7 Condenser Fan Motors and Fans ................. 31
7.8 Compressors ................................................ 31
8.0 Controls ......................................................32
8.1 System Controller ......................................... 32
8.2 Supply Fan Control ....................................... 33
8.3 Other Optional Controls ................................ 34
9.0 Optional Equipment including Heat
Sections ......................................................35
9.1 Inlet Air and Exhaust Air Options .................. 35
9.2 Gas Heat Section .......................................... 37
9.3 Electric Heat Section .................................... 58
10.0 Commissioning and Startup ...................59
10.1 Preparation and Startup Requirements ...... 59
10.2 Checklist Prior to Startup ............................ 59
10.3 Unit Test Mode and Setting Fan CFM ......... 60
10.4 Other Control Settings ................................ 64
10.5 Checklist - Startup ...................................... 66
10.6 Checklist After Startup: ............................... 67
Appendix ..........................................................68
Cabinet Size 1, 2 or 3 by Model and Model Size
Cross-Referenced to Heat Section Size and Type
68
Wiring Diagram Option Identication .................. 68
Supply Fan Airow (cfm) / Pressure Drop (iwc) Tables
by Fan and Unit Size ..................................... 69
PE4 Airow (cfm) / Pressure Drop (iwc) Tables by Fan
and Unit Size ................................................. 71
PE5 Airow (cfm) / Pressure Drop (iwc) Tables by Fan
and Unit Size ................................................. 72
PE6 Airow (cfm) / Pressure Drop (iwc) Tables by Fan
and Unit Size ................................................. 73
Start-Up Information Form .................................. 74
References ......................................................... 75
Index .................................................................75
INSTALLATION RECORD - to be completed by
the installer: .................................................76
1.0 General
Denitions of Hazard Intensity Levels used in this Manual
Form I-Y, P/N 273646R6, Page 2
1.1 Cautions and Warnings
There are warning labels on the unit, on the front page, and throughout this manual. For your safety, comply with all warnings during installation, operation, and service of
this system. Denitions of the hazard intensity levels of the cautions, warnings, and
dangers are shown below.
HAZARD INTENSITY LEVELS
1. DANGER: Failure to comply will result in severe personal injury or death and/or property damage.
2. WARNING: Failure to comply could result in severe personal injury or death and/or property damage.
3. CAUTION: Failure to comply could result in minor personal injury and/or property damage.
Warnings for Units with a Gas Heat Section
WARNING
Gas-red appliances are not designed for use in hazardous atmospheres containing ammable vapors or combustible dust, in atmospheres containing chlorinated or halogenated hydrocarbons, or in applications with airborne silicone substances.
WARNING
Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve
to the appliance before shutting off the electrical supply.
WARNING
Do not use this appliance if any part has been under water. Immediately call a qualied service technician to inspect the appliance and replace any gas control that has been
under water.
1.2 General Information
1.3 Warranty
1.4 Installation Codes
This booklet includes installation and operation information. Before beginning any pro­cedure, carefully review the information, paying particular attention to the warnings.
If you do not have knowledge of local requirements, check with the local agencies who might have requirements concerning this installation. Become familiar with the require­ments of your particular installation and make preparations for necessary supplies, equipment, and manpower.
The installation instructions in this manual apply to Reznor® Model YDHA, Model
YDMA, and Model YDSA. Other manuals in the literature bag include:
Form O-Y, Maintenance/Service Manual
Form CP-Y D21, Manual for Makeup Air Control System Option D21; or
Form CP-Y D19, Manual for Space Temperature Control System Option D19
Refer to limited warranty information on the warranty form in the "Literature Bag" shipped with this system. If an optional extended warranty applies, keep the extended
warranty information for future reference and verication of warranty.
These packaged systems are certied by ETL to "Heating Cooling Equipment" (latest edition), UL 1995 / CAN/CSA C22.2 No. 236-05. Electrical characteristics are shown
on the system rating plate. All cooling and reheat circuits are factory-charged with R-410A refrigerant.
If the system has a gas heat section, it has an integral gas-red, power-vented duct
furnace. The furnace is certied by ETL to the latest editions of both ANSI Z83.8 and CSA 2.6 for use in the United States and Canada. The ETL label, type of gas, and the
ring rate are shown on the heat section rating plate.
California Warning
Label
Massachusetts Requirements
2.0 Location and
Moving
If a gas-red heat section is included and the system is being installed in the state of
California, the installer MUST attach the California warning label on the outside of the
heat section access panel. The California Warning label, P/N 196977, is shipped in
the "Literature Bag". Select a dry, clean location on the heat section access panel and adhere the label.
If being installed in the Commonwealth of Massachusetts, this unit must be installed by
a licensed plumber or licensed gas tter.
This outdoor unit is designed to be set on a matching Reznor® curb (See Paragraph
5.3.) that will provide either vertical or horizontal discharge airow. The system must be
level for proper operation. When selecting the location, check the following:
Installation location must comply with all applicable codes. Location on a roof depends on building structure. Refer to Paragraph 5.1 for
information on how to obtain unit weight data.
Comply with required clearances in Paragraph 4.1. Position the unit so that the outside air inlet will not be facing into the prevailing
wind.
Before moving the unit, refer to Paragraph 5.4 for rigging information.
Form I-Y, P/N 273646R6, Page 3
3.0 Receiving, Shipped Separate and Storage
3.1 Receiving
This system was test operated and inspected at the factory and was in operating condition. If the equipment has incurred any damage in shipment, document the
damage with the carrier and immediately contact your Reznor® distributor.
Check the entire unit for damage paying particular attention to the structural integrity of the lifting points and the condenser fan section. Check the condenser fan guards and the fan blades.
On the inside of the control access door, locate the system rating plate (See FIGURE 2 on page 7, FIGURE 3 on page 8 of FIGURE 4 on page 9). Check the rating plate
information for specications and the electrical characteristics and verify compatibility
with the installation site. If installing a unit with a heat section, check the rating plate on the inside of the
heat section door. For a gas heat section, be sure that the rating plate information is compatible with the altitude and the gas supply at the installation site.
3.2 Shipped Separate Accessories and Shipped Loose Parts
Check for shipped-separate accessories and shipped-loose parts. All systems will have a shipped-loose discharge air sensor. The roof curb which is shipped separately
(in most cases prior to the unit) requires eld assembly. The outside air hood is shipped with the unit in a separate carton for eld assembly and installation. (NOTE: Install the
hood after the unit is in place. See Paragraph 6.1.)
Listed in the tables below are shipped separately & their availability options.
Standard Efciency Vertical Flue Discharge Extension Options (pipe not included):
Model No Option PN’s Included Description H50 & H75
YDHA, YDMA CC3 235320
YDHA, YDMA, YDSA
YDHA, YDMA, YDSA
YDHA, YDMA, YDSA
YDHA, YDMA -- -- -- -- Yes
CC3D 235320
(small vent tube)
(small vent tube)
235321 (large vent tube)
Single furnace kit, Metal
Dual furnace kit, Metal
Yes -- -- -- --
-- Yes -- -- --
-- -- Yes -- --
-- -- -- Yes --
H100, H200,
H300, H400
H102, H125,
H150, H175
H202, H402,
H502, H602
H702 & H802
High Efciency Vertical Flue Discharge Extension Options (pipe not included):
Model No Option PN Description G150, G225, G300 G302, G372, G452 G525 & G602
YDHA
YDMA
YDSA
YDHA CC4D 273388 Dual furnace
YDMA -- Yes Yes
YDSA -- Yes --
CC4 273387 Single furnace
kit, PVC
kit, PVC
Yes
Yes
Yes
-- Yes Yes
-- --
-- --
--
--
High Efciency Flue Condensate Handling Options:
Model No Option PN Description G150, G225, G300, G302, G372, G452 G525 & G602
YDHA FB1 273277 Condensate Frost
YDMA Yes Yes
YDSA Yes --
YDHA CSP1 272512 Condensate Pump Yes Yes
YDMA Yes Yes
YDSA Yes --
YDHA CSN1 272511 Condensate
YDMA Yes Yes
YDSA Yes --
Form I-Y, P/N 273646R6, Page 4
Protection
Neutralizer
Yes Yes
Yes Yes
Controls Options:
Option PN Description
CL23 257338 24v 2-stage heating/cooling touch
screen prog thermostat
CL33 221038 Electronic 24v prog thermostat for up to
3 stages heating and or cooling
CL78 272631 Wall mounted DDC temperature moni-
tor and setpoint adjustment
BD5 42782 Firestat 200°F Yes Yes Yes
2
BE15 234820 Space CO
sensor (range 0-2000 ppm) Yes Yes Yes
BE17 259076 Smoke detector (photoelectric) Yes Yes Yes
Cabinet Size / Option Availability
1 (a) 2 3
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
RB5 260436 Wall mounted remote monitoring dis-
Yes Yes Yes
play
RB6 272407 Hand held remote display with cable Yes Yes Yes
(a) Cabinet size 1 not available with YDSA model
Curb Options:
Option Description Notes
CJ31 16”high full perimeter roof
curb, bottom duct connections, exposed external insulation.
Units with­out Energy Recovery
Cabinet Size / Option Availability & PN
1 (a) 2 3
Yes
Yes Yes
PN 272399 PN 272403 PN 284223
CJ48 36”high full perimeter curb for pad
mounting, horizontal discharge,
double wall insulation in air ple­num section.
CJ 34 16”high full perimeter roof curb
for units with ERM, bottom duct connections, exposed external insulation.
Units with­out Energy Recover
Units with Energy Recovery
Yes
Yes Yes
PN 272400 PN 272404 PN 284224
Yes Yes
PN 272401 PN 272405 PN 284223
Yes
CJ55 36”high full perimeter roof curb for
pad mounting for units with ERM,
horizontal discharge, double wall
Units with Energy Recovery
insulation in air plenum section.
(a) Cabinet size 1 not available with YDSA model
Yes Yes
Yes
PN 272402 PN 272406 PN 284224
Form I-Y, P/N 273646R6, Page 5
3.0 Receiving, Shipped Separate and Storage (cont’d)
3.2 Shipped Separate Accessories and Shipped Loose Parts (cont’d)
Outside Air Hood
Option Description
AS16 Outside air hood with
permanent prelters
1 2 3
273283 273373 284598
Exhaust Fan Control Option
Option Description
EFC4 Outside pressure pickup port
Room pressure port
234905 234906
Inlet Damper Control Option
Option Description
GF5 Outside pressure pickup port
Room pressure port
234905 234906
Fan Control Option
Option Description
VFC3 4”static pressure probe 234821 234821 234821
VFC4 Outside pressure pickup port
Room pressure port
Cabinet Size
Cabinet Size
1 2 3
234905 234906
234905 234906
Cabinet Size
1 2 3
234905 234906
234905 234906
Cabinet Size
1 2 3
-- 234905 234906
234905 234906
3.3 Storage
If this system is going to be stored, take precautions to prevent condensate formation inside the electrical compartments and motors. To prevent damage to the unit, do not store sitting on the ground.
4.0 Clearances and Dimensions
IMPORTANT: The area above the condenser fans MUST ALWAYS be totally open space to allow proper airow through the condenser
coils.
4.1 Clearances
FIGURE 1 - Minimum Clearances - All Sizes
48” (1219mm) - Service Clearance to Remove
84” (2134mm)
- Service
Clearance to
Remove the Heat
Exchanger in a
Unit w/Gas Heat
36” (914 mm)
- Service
Clearance for
Cooling Only or
Unit w/Electric Heat
Controls
Compressors, Coils, Filter Driers, etc.
Airflow
Outside
Air
Hood
24” 610mm
Top Clearance - 60” (1524mm)
Bottom Clearance - 0” (0mm)
Form I-Y, P/N 273646R6, Page 6
Service Clearance to Remove a Coil
72” (1829mm) -
4.2 Dimensions
FIGURE 2 - Cabinet Size 1 Dimensions - inches (mm)
Control End View with High Efficiency Gas Heat Section
(See dimensions below.)
82-11/16
(2100)
*Vent Outlet ­High Efficiency (condensing) Gas Heat Section
Control End View with Electric or
Non-Condensing Gas Heat Section
31-5/16
(795)
50
(1270)
Condenser
6-1/4 (159)
5-1/4 (133)
G
F
Utility Entrance Dimensions
* High-efficiency dual heat sections have two vent outlets. ** Two power supply entrances and two disconnect switches apply only to systems with dual disconnect Option BA7.
Optional Gas Heat Section
51-3/8 (1305)
Control Access
Section
Optional
Heat Section
44-7/16 (1128)
- Inside the Curb Cap
Y
X
6 (152) 8 (203)
**Optional Disconnect Switch
**Power Supply
Gas Inlet
5-1/8 (130)
std gas
heat only
Vent Outlet (gas heat)
7 (178)
B
36
(914)
Top
View
Vent Outlet - Standard (non-condensing) Gas Heat Section
Fan
Access
C - Inside the Curb Cap
A - Base Length
31-7/16
(799)
30
(762)
Supply Air
Bottom View showing Duct Openings
D
Side View
Discharge
Coil &
Filter
Access
Airflow
Optional
Wheel Access
1-1/4” Ø Condensate Drain Connection
16
(406)
E
Inlet
Return Air
Optional
Outside
Air Hood
32-7/16
(824)
Hood
Damper Access
23-7/8
(606)
7 (178)
36
(914)
5-15/16
(150)
**Power Exhaust w/Opt Wheel
14 (356)
Z
14-3/8
(365)
10-3/8
(254)
Power Exhaust
Box with
Points - 1-1/2 (38mm)
Optional Exhaust Dampers without an energy recovery
Inlet Air End View
23-3/8
(594)
Outside Air Inlet
Optional
Wheel
(4) Corner Lifting
80-7/8 (2238)
- Base Width
Opening Dimensions inches
(mm)
Supply Air Discharge
Return Air Inlet
Outside Air Inlet - Sizes by Option:
Option Z
AR7
AR25, AR2D, AR2H & all other models
36 x 30
(914) x (762)
36 x 16
(914) x (406)
8
(203)
19-7/8
(505)
Section
Condenser
Important NOTE: DO NOT use base dimensions for roof curb. See Paragraph 5.3.
Models and Cooling Sizes
YDMA and YDHA 060, 090 YDMA and YDHA 120, 150
YDMA and YDHA 060, 090 YDMA and YDHA 120, 150
Size
Cabinet
1A
1B
1A
1B
Gas Connection Location and Size for Systems with Optional Gas Heat Section Gas Heat Section (H=non-condensing; G=condensing heat section)
Single Furnace Dual Furnaces (one gas connection)
H50, H75, H100 H102, H125, H150, H175, H202
H200, G150 H402, G302 H300, H400, G225, G300 G372 3/4”
System without Energy Recovery Wheel System with Optional Energy Recovery Wheel
A1 B1 C1 D1 E1 F1 G1 A2 B2 C2 D2 E2 F2 G2
Dimensions - inches Dimensions - inches
53-1/32
128-1/2
120-11/16 127-19/32 20-1/2
63-1/32 49-21/32 57-21/32 63-1/32 49-21/32 57-21/32
41-31/32 46-31/32
136-27/32
53-1/32
129 135-15/16 28-13/16
Dimensions - mm Dimensions - mm
1347
3264
1601 1261 1464 1601 1261 1464
3065 3241 521
1066 1193
3476
X Y
10-15/16”
(278mm)
7-11/16”
(195mm)
1347
3277 3452 732
13-11/16”
(348mm)
14”
(356mm)
Diameter
(NPT)
1/2”
1/2”
Form I-Y, P/N 273646R6, Page 7
41-31/32 46-31/32
1066 1193
4.0 Clearances and Dimensions (cont’d)
4.2 Dimensions (cont’d)
FIGURE 3 - Cabinet Size 2 Dimensions - inches (mm)
Control End View with High
Efficiency Gas Heat Section
(See dimensions below.)
89-15/16
Vent Outlet (gas heat)
(2284)
5-1/8 (130)
w/std
gas heat only
66-1/2
(1689)
6-1/8 (155)
45
(1143)
Top
View
Side View
Supply Air
Discharge
C
Coil &
Filter
Access
Vent Outlet - Standard (non-condensing) Gas Heat Section
Fan
Access
B - Inside the Curb Cap
A - Base Length
31-7/16
(799)
Bottom View showing Duct Openings
30
(762)
Control Access
*Vent Outlets ­High Efficiency (condensing) Gas Heat Section
Control End View with Electric or
Non-Condensing Gas Heat Section
31-5/16
(795)
65-9/16
(1665)
Condenser
6-1/4 (159)
57-11/16
* High-efficiency dual heat sections have two vent outlets. ** Two power supply entrances and two disconnect switches apply only to systems with dual disconnect Option BA7.
5-1/4
(133)
(1468)
49-11/16
(1264)
Utility Entrance Dimensions
Optional Gas
Heat Section
58-5/8 (1489)
Control Access
Optional
Section
Heat Section
51-11/16 (1313)
- Inside the Curb Cap
6 (152)
8 (203)
**Optional Disconnect Switch
**Power Supply
Gas
Y
X
Inlet
Airflow
18
(457)
Inlet
Return Air
Optional
Outside
Air Hood
40-5/16
(1024)
Hood
Optional
Wheel Access
Damper Access
24
(610)
1-1/4” Ø Condensate Drain Connection
D
6-1/8 (155)
45
(1143)
24-9/16
(624)
14 (356)
Inlet Air End Views
Z
5-7/8 (149)
Y
Power Exhaust Box with Optional Wheel
X
Outside Air Inlet
Power Exhaust
Box with
Optional Wheel
(4) Corner Lifting
Points - 1-1/2 (38mm)
88-1/8 (2238)
- Base Width
Opening Dimensions
inches (mm)
Supply Air Discharge
Return Air Inlet
Outside Air Inlet - Sizes by Option:
Option X Y Z
AR1
AR7
AR25, AR2G, AR2H & all models with Wheel option
45 x 30
(1143) x (762)
45 x 18
(1143) x (457)
49-5/8
(1260)
25-5/8
(651)
45-3/4
(1162)8 (203)7 (178)
49-5/8
(1260)
25-5/8
(651)
Optional Exhaust Dampers without an energy recovery wheel
Section
Condenser
5-1/2
(140)
5-1/2
(140)
Important NOTE: DO NOT use base dimensions for roof curb. See Paragraph 5.3.
System without Energy Recovery
Wheel
A1 B1 C1 D1 A2 B2 C2 D2
Models and Cooling Sizes
Cabinet
Size
Dimensions - inches Dimensions - inches
YDMA & YDHA 180, 210, 240 and YDSA 120, 150
2 132-17/32 124-21/32 131-19/32 24-7/16 140-27/32 133 139-31/32 32-25/32
Dimensions - mm Dimensions - mm
YDMA & YDHA 180, 210, 240 and YDSA 120, 150
2 3366 3167 3342 621 3577 3378 3555 833
Gas Connection Location and Size for Systems with Optional Gas Heat Section Gas Heat Section (H=non-condensing; G=condensing heat section)
Single Furnace Dual Furnaces (one gas connection)
H75, H100 H125, H150, H175, H202
H200, G150 H402, G302 H300, H400, G225, G300 G372 3/4”
Form I-Y, P/N 273646R6, Page 8
X Y
10-15/16” (278 mm)
7-11/16”
(195 mm)
System with Optional Energy
Recovery Wheel
13-11/16” (348 mm)
14-1/8”
(359 mm)
Diameter
(NPT)
1/2”
1/2”
FIGURE 4 - Cabinet Size 3 Dimensions - inches (mm)
Control End View with High Efficiency Gas Heat Section
(See dimensions below)
Control Access
Optional Gas Heat Section
101-5/32
(2569)
Top View
Optional
Outside Air
Hood
ERV Wheel Access
Optional Exhaust Damper
Damper Access
*Vent Outlets High
Efficiency (condensing)
Gas Heat Section
Control End View with Electric or Non-Condensing Gas Heat Section
83-3/64
(2109)
Section
Condenser
12-5/64
(307)
**Optional
Disconnect
Switch
62-1/64
(1575)
55-5/64
(1399)
Utility Entrance Dimensions
* High efficiency dual heat sections have two vent outlets. ** Two power supply entrances and two disconnect switches apply only to systems with dual disconnect Option BA7
Y
70-11/16
(1795)
Control Access
Optional Heat
Section
64-23/32 (1644)
(Inside Curb Cap)
X
**Power
Supply
Gas Inlet
5
(127)
Vent Outlet
(gas heat)
6-9/64
(156)
57
(1448)
83-31/32
(2133)
161-11/32
Vent Outlet - Standard (non-condensing) Gas Heat Section
Access
32-43/64
(830)
Bottom View showing Duct Openings
(4098)
Side View (with power exhaust)
Fan
155-23/32
(Inside the Curb Cap)
(3955)
164-9/32
(Base Length)
(4173)
31
(787)
Supply Air
Discharge
Coil Access
21
(533)
Filter Access
Inlet
Return Air
Optional
Wheel Access
Damper
Access
32-57/64
(835)
49-25/64
(1255)
Hood
23-15/16
(608)
1” PVC Female Condensate Drain Pan Adapter Fitting
6-9/64
(156)
57
(1448)
Side View
(with ERV Wheel Option)
7-29/64
5-27/32
(148)
Z
Power
Exhaust Box with Optional
Wheel
Inlet Air End View
(189)
Power Exhaust
Optional Wheel
59-5/8 (1514)
Outside Air
Inlet
Box with
78-61/64
(2005)
(with Optional Exhaust Damper)
Opening Dimensions
inches (mm)
Supply Air Discharge
Return Air Inlet
Outside Air Inlet - Sizes by Option:
Option Z
AR1, AR25, AR2G & all other models
AR7
57 x 31
(1448) x (787)
57 x 21
(1448) x (533)
30-5/8
(778)
8-1/16
(205)
Side View
Section
Condenser
12-1/2
(317)
Important NOTE: DO NOT use base dimensions for roof curb. See Paragraph 5.3.
Gas Connection Location and Size for Systems with Optional Gas Heat Section
Gas Heat Section (H=non-condensing; G=condensing heat section)
Single Furnace Dual Furnaces (one gas connection)
G150, H200 G302, H402
-- H150, H175, H202 12-21/32”
G225, G300, H300, H400 G372, G452, H502, H602
-- G525, G602, H702, H802 1-1/4”
X Y
9-35/64”
(242 mm)
9-13/32”
(239 mm)
Diameter
(NPT)
19-5/32”
(487 mm)
19-5/32”
(487 mm)
19-37/64”
1/2”
1/2”
3/4”
(497 mm)
Form I-Y, P/N 273646R6, Page 9
5.0 Mounting
MUST be sealed between curb cap rail and roof curb.
Optional or Field-Supplied Roof Curb fits under and inside the curb cap.
Base of curb cap edge Edge of curb cap extends down over the roof curb.
Cabinet Wall
Curb Cap Rail
5.1 Unit Weights
For unit weights and or corner weights, refer to www.ReznorHVAC.com or call 1-800-695-1901. Specic unit weights will be supplied by order number which will include the weights of the options specied for that specic unit.
5.2 Curb Cap Base and Mounting
These packaged systems have a curb cap base designed for use with a full perimeter curb. When on a roof, either a manufacturer-designed roof
curb or a eld-supplied roof curb is
required.
NOTE: A Reznor® designed roof
curb with integral vertical duct work supports is recommended to provide a weatherproof installation.
Base design varies by cabinet size.
5.3 Mounting on a Roof Curb
Two types of fully enclosed curbs are available with these systems.
Optional Energy Recovery Wheel
Roof
Curbs
Option
CJ31 No 16” (406mm), Down Discharge with CJ34 Yes CJ48 No CJ55 Yes
If the application is sound sensitive, consider installing a eld-supplied vibration iso­lation curb or specialty sound attenuation curb. Whether using an optional roof curb
available with the system or a eld-supplied speciality curb, the curb must be secured,
on square, and level. When the unit is being placed on a roof, location depends on the roof structure and is the responsibility of the installer. For condensate drainage and proper operation, it is important that the installation be level.
When positioning the curb, always comply with the required clearances in Paragraph
4.1. Check the dimensions carefully, remembering that the condenser section will extend 30” (762mm) beyond the edge of the curb. (See orientation in FIGURE 13, page 19). Position the curb so that the outside air inlet of the unit will not be facing into the prevailing wind.
Duct Connections - Optional down discharge roof curbs are designed for duct work to be inserted in the duct connection opening(s) from above the curb prior to setting the unit on the curb.
Description
Duct Supports in the Curb
36” (914mm), Horizontal Discharge
with Duct Connections in the Curb
Curb Cap
Section View
Form I-Y, P/N 273646R6, Page 10
5.3.1 Down ow Roof
Curbs
Both Option CJ31 and CJ34 are 16" (406mm) high roof curbs designed for vertical (down) discharge. These curbs include integral cross supports for supply air and optional return air duct work.
FIGURE 5 - Layout, Dimensions, and Weights of Option CJ31 & CJ34 Roof Curbs
Curb
Layout
Wood
Nailer
Insulation
(Inlet Hood End)
2x6
16”
(406mm)
(Condenser Side of Unit - Base extends
30” / 761mm beyond this side of curb.)
Cross-Section
Downflow Curb Options CJ31 and CJ34
Return
Air
View
Supply
Air
of Unit)
(Control End
Dimensions - inches (mm)
Option Model and Size
YDHA & YDMA 060,
CJ31
No Energy
Wheel
090, 120, 150
YDHA & YDMA 180, 210, 240 YDSA 120, 150
YDHA & YDMA, 300, 360 YDSA 180, 210
YDHA & YDMA 060,
CJ34
With Energy
Wheel
090, 120, 150
YDHA & YDMA180, 210, 240 YDSA 120, 150
YDHA & YDMA, 300, 360 YDSA 180, 210
Cabinet
Size
1
2
3
1
2
3
A B C D
(Outside of Curb Rails) (Area Inside the Curb*)
119-11/16
(3040)
123-11/16
(3141)
154-11/16
(3929)
128
(3251)
132
(3353)
154-11/16
(3929)
* Area enclosed by the roof curb must comply with clearance to combustible materials. If the roof is constructed of combustible materials, area within the roof curb must be ventilated, left open, or covered with non-combustible material which has an “R” value of at least 5. If area within curb is left open, higher radiated sound levels may result. NOTE: If installing a unit with a high efciency,
condensing gas-red heat section, the area within the curb must be
left open.
** When cutting only duct openings, cut “E” & “F” dimensions 1/4”
(6.4mm) in from duct opening to allow clearance. Cut the curb rail sides of the duct opening(s) parallel to the curb rail. For Cabinet
Size 1, measure a maximum of 1-1/2” (38mm) in from the side rail. For Cabinet Size 2, measure a maximum of 3/4” (19mm) in from
the side rail.
*** See chart on page 68 for cross-reference by Model Size or Model and Heat Size to Cabinet Size.
D
G H
43-7/16
(1103)
50-11/16
(1287)
63-11/16
(1618)
43-7/16
(1103)
50-11/16
(1287)
63-11/16
(1618)
Return
(DxF)
115-15/16
(2945)
119-15/16
(3046)
150-15/16
(3834)
124-1/4
(3156)
128-1/4
(3257)
150-15/16
(3834)
Air
Weights of Downow Roof Curb Option CJ31 and CJ34 by Cabinet Size
Roof
Curb
Option CJ31 Option CJ34
Cabinet 1 Cabinet 2 Cabinet 3
lbs kg lbs kg lbs kg
237 108 257 117 322 146
248 11 2 268 122 322 146
Top View
Unit
Airflow
39-11/16
(1008)
46-15/16
(1192)
59-15/16
(1522)
39-11/16
(1008)
46-15/16
(1192)
59-15/16
(1522)
C A
E** F** G H
31
(787)
31
(787)
31
(787)
31
(787)
31
(787)
31
(787)
Supply
Air
(DxE)
EF
17
(432)
19
(483)
21
(483)
17
(432)
19
(483)
21
(483)
25-3/4
(654)
25-13/16
(656)
28-7/32
(717)
25-3/4
(654)
25-13/16
(656)
28-7/32
(717)
B
14-29/32
(379)
18-13/16
(478)
28
(711)
23-1/4
(591)
27-1/8
(689)
28
(711)
Form I-Y, P/N 273646R6, Page 11
5.0 Mounting (cont'd)
5.3 Mounting on a Roof Curb (cont'd)
5.3.1 Down ow Roof Curbs (cont’d)
CAUTION: Before installation, recheck to be sure that the correct curb has been ordered. Be sure that the curb selected matches the unit ordered. Verify the dimensions of the curb received with the appropriate dimension table.
FIGURE 6 - Components (CJ31 & CJ34)
B
A
E
Inlet Air End of Unit
B
(Condenser section base extends
30” / 762mm beyond the roof curb.)
Item
Cross Supports
A
(for duct work)
B Side Assy (inlet air end)
C Side Assy (control end)
D End Assembly
E Splice Plates for Sides
Description
Package P/N 272399 272403 284223 272401 272405 284223
D
Return Air Opening
Condenser Side of Unit -
Cabinet 1 Cabinet 2 Cabinet 3 Cabinet 1 Cabinet 2 Cabinet 3
271350
(Qty 4)
271413
(Qty 2)
271414
(Qty 2)
271415
(Qty 2)
271690
(Qty 2)
C
A
A
E
A
Air Opening
Supply (Discharge)
Control End of Unit
C
Option CJ31 Option CJ34
271689
(Qty 4)
272034
(Qty 2)
271392
(Qty 2)
271393
(Qty 2)
271690
(Qty 2)
284134
(Qty 4)
284189
(Qty 2)
284188
(Qty 2)
284187
(Qty 2)
271690
(Qty 2)
271350
(Qty 4)
271424
(Qty 2)
271414
(Qty 2)
271415
(Qty 2)
271690
(Qty 2)
271689
(Qty 4)
271391
(Qty 2)
271392
(Qty 2)
271393
(Qty 2)
271690
(Qty 2)
D
284134
(Qty 4)
284189
(Qty 2)
284188
(Qty 2)
284187
(Qty 2)
271690
(Qty 2)
Qty P/N Description Use
28 16243 Lag Screw
28 1333 Lock Washer
32 16247 Cap Screw 32 1333 Lock Washer 32 1035 Hex Nut
Form I-Y, P/N 273646R6, Page 12
Hardware in Options CJ31 and CJ34
For top level screws (1 each corner; 4 each splice; 2 each cross support). Insert screws from inside the curb so that they extend into the wood nailer on the outside.
For attaching at all points below the wood nailer. Insert screws from outside the curb.
Installation Instructions for Down Discharge Roof Curbs, Option CJ31 and Option CJ34
1. Refer to FIGURE 6 shown on page 12 and layout the
two curb ends (letter D) and four side pieces (letters B &C). Verify the side pieces are in the correct positions (inlet air end vs control end).
2. Attach Curb Corners.
Using the hardware provided, create the corners by attaching the ends to the side pieces.
FIGURE 7 - Curb Detail and Corner







   

3. Attach the Splice Plates.
Use the hardware provided to attach splice plates to join the side rail pieces and create the perimeter of the curb.
  
 
FIGURE 8 - Attaching Spice Plates
(4) Lag Screws with
washers - top row
(into the nailer)
}
(12) Cap Screws with washers and nuts
- bottom three rows (cap screw heads should be on insulation side of rail)
4. Attach the four Cross Supports.
At the holes in curb sides, line up the cross supports in the orientation illustrated in FIGURE 6 shown on page 12. Since the cross supports form the duct con­nections, be certain that the vertical side of each cross support is toward the duct opening.
Using two lag screws with washers, at each end of a cross support, attach the support to the sides. Insert the screws through the side and into the wood nailer. Repeat for the other three cross supports.
5. Check the roof curb for squareness. Adjust the curb so that the diagonal measurements
are equal within a tolerance of ±1/8”(3mm).
6. Level the roof curb.
To ensure a good weatherproof seal between the
cabinet curb cap and the roof curb, the curb must be leveled in both directions with no twist end to end. Shim as required and secure the curb to the roof deck
before installing ashing.
7. Install eld-supplied ashing.
FIGURE 9 - Installed
Curb
Counter Flashing
(by installer)
Cant Strip
(by installer)
Roofing Felts (by others)
8. Before placing the unit on the curb:
Curb
Wall
Cabinet
Cap
2 x 6 Wood Nailer
Insulation
Weld, bolt, or lag screw curb to deck structure.
Apply 1/4” x 1-1/4” foam sealant tape to both the top
surface of the curb rails and the top surface of the cross supports, being sure to make good butt joints at all corners. The sealant tape must be applied to prevent water leakage into the curb area due to blown rain and capillary action.
□ Slide the duct work down into the supply (discharge)
and optional return air openings. See dimensions in FIGURE 5, page 11. Duct work should have a
minimum 2” (51mm) duct ange.
□ When it is time to lift the unit onto the curb, comply
with rigging and lifting information in Paragraph 5.4.
IMPORTANT: Verify that the unit will be placed in the
correct airow orientation to mate properly with the
discharge and return air openings. See FIGURE 13, page 19.
MUST be sealed between curb cap and roof curb.
}
Roof Curb
Form I-Y, P/N 273646R6, Page 13
2x6 Wood Nailer
36”
(914mm)
Curb Side
Cross-Section
Installation NOTES:
Plenum ducts in the curb have insulated bottom and side panels. Always install all four side panels. If the system does not have return air, attach a field-fabricated cover over the return air opening in the curb. (Without return air, the bottom of the unit is solid.)
Horizontal Airflow Curb Options CJ48 and CJ55
(Inlet Hood End of Unit)
(Control End
of Unit)
Return Air
Plenum
Supply
Air Plenum
(Condenser Side of Unit - Condenser base will be
above the duct connections and extends
30”/762mm beyond the curb side.)
5.0 Mounting (cont'd)
5.3 Mounting on a Roof Curb (cont'd)
5.3.2 Curbs for Horizontal Airow
CAUTION: Before installation, recheck to be sure that the correct curb has been ordered. Be sure that the curb selected matches the unit ordered. Verify the dimensions of the curb received with the appropriate dimension table.
Options CJ48 and CJ55 are 36" (914mm) high roof curbs designed for horizontal discharge. The curbs include plenum
sections for ducting supply air and optional return air to the duct connections in the side of the curb.
FIGURE 10 - Layout, Dimensions, and Weights of Option CJ48 and CJ55 Horizontal Roof
Curbs
Dimensions - inches (mm)
Option Description
Horizontal Discharge
Curb for YDHA, YDMA, or YDSA
CJ48
without an energy
recovery wheel
Horizontal Discharge
Curb for YDHA, YDMA, or YDSA with
CJ55
an energy recovery wheel
* See chart on page 68 for cross-reference by Model
Size or Model and Heat Size to Cabinet Size.
Weights by Cabinet Size - Horizontal Airow Roof Curb Option CJ48 and CJ55
Roof Curb
Option CJ48 Option CJ55
* See chart on page 68 for cross-reference by Model Size or Model and Heat Size to Cabinet Size.
Form I-Y, P/N 273646R6, Page 14
*Cabinet 1 *Cabinet 2 *Cabinet 3
lbs kg lbs kg lbs kg
555 252 599 272 686 3 11 570 259 615 279 686 3 11
Cabinet
Size*
(Outside of Curb Rails)
119-11/16
1
123-11/16
2
154-11/16
3
1
2
154-11/16
3
A Dim B Dim
43-7/16
(3040)
(3141)
(3929)
128
(3251)
132
(3353)
(3929)
(1103)
50-11/16
(1287)
63-11/16
(1618)
43-7/16
(1103)
50-11/16
(1287)
63-11/16
(1618)
Unit
Airflow
24
(610)
Return
Air
Plenum
Duct
in the
Curb
Duct Connection Side View of Curb
Duct
18 (457)
Top View of Curb
- Return Air
Connection
A Dim
Supply Air
Plenum
Duct in
the Curb
Horizontal
Duct
Connection
- Supply Air
33 (838)
B
Dim
24
(610)
5.3.2 Curbs for Horizontal Airow (cont’d)
FIGURE 11 - Cabinet Sizes 1 & 2 Components (Horizontal Curb Options CJ48 and CJ55)
(12) each -
16243 Lag Screw
1333 Lock Washer -
through panel
into wood nailer
D
F
B
* Insulated double-wall
A
panel.
E
M
F
L
Item
Description
Package P/N 272400 272404 272402 272406
A End Assembly
B Side Assy (solid/control end)
C Side Assy w/Supply Air Opening
D Side Assy (solid/inlet air end)
E Side Assy w/Return Air Opening
F Splice Plates for Sides
G* “Outer” Sides - Plenum Ducts
H* Plenum Duct Bottom
J* “Inner” Sides - Plenum Ducts
K* Air Bafe for Supply Air Plenum
L Supply Air Duct Flange
M Return Air Duct Flange
G*
J*
J*
K*
G*
A
(40) each ­16247 Cap Screw 1333 Lock Washer 1035 Hex Nut
C
H*
Sheetmetal Screws P/N 11813
Curb Option CJ48 Curb Option CJ55*
Cabinet 1 Cabinet 2 Cabinet 1 Cabinet 2
271419
(Qty 2)
271396
(Qty 1)
271399
(Qty 1)
271418
(Qty 1)
271417
(Qty 1)
261887
(Qty 2)
271421
(Qty 2)
271420
(Qty 1)
271422
(Qty 2)
268606
(Qty 1)
271403
(Qty 1)
271404
(Qty 1)
271397
(Qty 2)
271396
(Qty 1)
271399
(Qty 1)
272036
(Qty 1)
272035
(Qty 1)
271379
(Qty 2)
271400
(Qty 2)
271401
(Qty 1)
271402
(Qty 2)
271386
(Qty 1)
271403
(Qty 1)
271404
(Qty 1)
271419
(Qty 2)
271396
(Qty 1)
271399
(Qty 1)
271427
(Qty 1)
271426
(Qty 1)
261887
(Qty 2)
271421
(Qty 2)
271420
(Qty 1)
271422
(Qty 2)
268606
(Qty 1)
271403
(Qty 1)
271404
(Qty 1)
271397
(Qty 2)
271396
(Qty 1)
271399
(Qty 1)
271395
(Qty 1)
271398
(Qty 1)
271379
(Qty 2)
271400
(Qty 2)
271401
(Qty 1)
271402
(Qty 2)
271386
(Qty 1)
271403
(Qty 1)
271404
(Qty 1)
* For a unit with an energy recovery wheel
Qty P/N Description Use
12 16243 Lag Screw 12 1333 Lock Washer 40 16247 Cap Screw 40 1333 Lock Washer 40 1035 Hex Nut
90 11813
Sheet metal Screws
Hardware in Options CJ48 & CJ55
For top level screws (1 each corner; 4 each splice plate). Insert screws from inside the curb so that they extend into the wood nailer on the outside.
For attaching corners and splice plates below the wood nailer (4 each corner; 12 each splice plate). Insert screws from outside the curb.
For attaching duct plenum sides, bottom, and bafe; and duct anges.
Form I-Y, P/N 273646R6, Page 15
5.0 Mounting (cont'd)
5.3 Mounting on a Roof Curb (cont'd)
5.3.2 Curbs for Horizontal Airow (cont’d)
Installation Instructions for Cabinet Sizes 1 & 2 Horizontal Airow Roof Curbs, Option CJ48 and
Option CJ55
1. Refer to FIGURE 11 shown on page 15 and position the two curb ends (letter A) and four side pieces (letters B, C, D, E). Verify the side pieces are
positioned correctly (shorter piece at the inlet air end and longer piece at the control end of the unit).
2. Attach Curb Corners.
Using the hardware provided (lag screw and washer in top holes; cap screw, washer, and nut in the 4 holes below the wood nailer), create the four corners by attaching the ends to the side pieces.
3. Attach the two Side Splice Plates (letter F).
Use the hardware provided (lag screw and washer in top holes; cap screw, washer, and nut in the 4 holes below the wood nailer) to attach splice plates (letter F) joining the side pieces (letters B&D and letters C&E) to complete the perimeter of the curb.
4. Attach the Two Outer Plenum Side Panels (letter G).
Position each insulated panel with the wide bottom
ange toward the center. Align the panel with the holes
in the curb sides and attach with sheet metal screws.
5. Install the Plenum Duct Bottom Panel (letter H).
Lower the insulated bottom panel into the curb, resting
it on the anges of the two panels installed in Step 4.
Attach the bottom panel with sheet metal screws.
6. Install the Two Inner Plenum Side Panels (letter J).
Position one insulated side panel as illustrated and align the holes. Attach with sheet metal screws. Repeat to install the other side panel.
7. Install the Bafe in the Supply Air Plenum (letter K).
Position the bafe between the insulated side pan­els (letters G & K) as illustrated and align the holes. Attach with sheet metal screws.
8. Attach the Duct Flanges (letters L & M).
Using sheet metal screws, attach the duct ange
(letter L) around the supply opening and the smaller
duct ange (letter M) around the return air opening. If the installation does not have return air, attach a eld-
fabricated cover over the return air opening.
9. Check the Squareness, Level the Curb, and Install the Flashing.
Adjust the curb so that the diagonal measurements are
equal within a tolerance of ±1/8”(3mm).
To ensure a good weatherproof seal between the cabinet curb cap and the perimeter of the curb, the curb must be leveled in both directions with no twist end to end. Shim as required and secure the curb to the roof deck.
Install eld-supplied ashing.
10. Before placing the unit on the curb, apply 1/4” x
1-1/4” foam sealant tape to both the top surface of
the curb rails and the top surface of the duct sides.
Form I-Y, P/N 273646R6, Page 16
5.3.2 Curbs for Horizontal Airow (cont’d)
FIGURE 12 - Cabinet Size 3 Components (Horizontal Curb Options CJ48 and CJ55)
Lag Screw P/N 16243 Lock Washer P/N 1333 (Qty 12 each) Wood nailer side - screw head towards panel
G
A
E
L
K
F
Item
A End Assembly
B Side Assy (solid/control end)
C Side Assy w/Supply Air Opening
D Side Assy (solid/inlet air end)
E Side Assy w/Return Air Opening
F Splice Plates for Sides
G Sides for Plenum Ducts
H Plenum Duct Bottom
J Air Bafe for Supply Air Plenum
K Return Air Duct Bottom
L Return Air Duct Flange
M Supply Air Duct Flange
Qty P/N Description Use
12 16243 Lag Screw 12 1333 Lock Washer 40 16247 Cap Screw 40 1333 Lock Washer 40 1035 Hex Nut
98 11813
Sheet metal Screws
G
G
D
F
J
B
Return Air
Supply Air
Cap Screw P/N 16247 Lock Washer P/N 1333
A
Hex Nut P/N 1035 (Qty 40 each) Cap screw to be on insulation side
G
M
H
C
Sheetmetal Screw P/N 11813 (Qty 98)
Description
Package P/N 284224
Hardware in Options CJ48 & CJ55
For top level screws (1 each corner; 4 each splice plate). Insert screws from inside the curb so that they extend into the wood nailer on the outside.
For attaching corners and splice plates below the wood nailer (4 each corner; 12 each splice plate). Insert screws from outside the curb.
For attaching duct plenum sides, bottom, and bafe; and duct anges.
Curb Option
CJ48 or CJ55
Cabinet 1
284173
(Qty 2)
284137
(Qty 1)
284139
(Qty 1)
284135
(Qty 1)
284171
(Qty 1)
271379
(Qty 2)
284175
(Qty 4)
284181
(Qty 1)
284184
(Qty 1)
284207
(Qty 1)
284185
(Qty 1)
271403
(Qty 1)
Form I-Y, P/N 273646R6, Page 17
5.0 Mounting (cont'd)
5.3 Mounting on a Roof Curb (cont'd)
5.3.2 Curbs for Horizontal Airow (cont’d)
Installation Instructions for Cabinet Size 3 Horizontal Airow Roof Curbs, Option CJ48 and Option CJ55
1. Refer to FIGURE 12 shown on page 17 and position the two curb ends (letter A) and four side pieces (letters B, C, D, E). Verify the side pieces are positioned correctly (shorter piece at the inlet air end and longer piece at the control end of the unit).
2. Attach Curb Corners.
Using the hardware provided (lag screw and washer in top holes; cap screw, washer, and nut in the 4 holes below the wood nailer), create the four corners by attaching the ends to the side pieces.
3. Attach the two Side Splice Plates (letter F).
Use the hardware provided (lag screw and washer in top holes; cap screw, washer, and nut in the 4 holes below the wood nailer) to attach splice plates (letter F) joining the side pieces (letters B&D and letters C&E) to complete the perimeter of the curb.
4. Assemble the Return Air Plenum.
Position two sides (letter G) between the return air duct bottom (letter K) align the holes in each and using the sheet metal screws, assemble these three sheet metal pieces. Then using the holes in the curb sides (letters D & E), align the return air plenum sub assembly holes on each end with the holes in the curb sides and attach using the sheet metal screws.
5
Assemble the Supply Air Plenum.
(letter G) between the supply air duct bottom (letter H) align the holes in each and using the sheet metal
Position two sides
screws, assemble these three sheet metal pieces. Then using the holes in the curb sides (letters D & E), align the supply air plenum sub assembly holes on each end with the holes in the curb sides and attach using the sheet metal screws.
6. Attach the Duct Flanges (letters L & M).
Using sheet metal screws, attach the supply air duct
ange (letter M) around the supply opening and the smaller return air duct ange (letter L) around the
return air opening. If the installation does not have
return air, attach a eld-fabricated cover over the
return air opening.
7. Check the Squareness, Level the Curb, and Install the Flashing.
Adjust the curb so that the diagonal measurements
are equal within a tolerance of ±1/8”(3mm).
To ensure a good weatherproof seal between the cabinet curb cap and the perimeter of the curb, the curb must be leveled in both directions with no twist end to end. Shim as required and secure the curb to the roof deck.
Install eld-supplied ashing.
8. Before placing the unit on the curb, apply 1/4” x
1-1/4” foam sealant tape to both the top surface of
the curb rails and the top surface of the duct sides.
Form I-Y, P/N 273646R6, Page 18
5.4 Rigging and
Optional Return Air
Discharge (Supply) Air
16” High
Curb with
Cross Supports
for Discharge
and Supply Air
Ductwork
Lifting
DANGER
If there is any visible damage or any question about the integrity
of a lifting point, DO NOT LIFT the system. Consult the factory.
Refer to Paragraph 5.1 for information on obtaining unit or corner weights. IMPOR­TANT NOTE: ALL systems MUST be loaded and unloaded by lifting. DO NOT attempt
to move with a fork lift. Lifting lugs for attaching rigging are provided at each corner of the base. ALL lifting
points MUST always be used. Spreader bars MUST be used to prevent cabinet dam- age and to allow the unit to be lifted straight up with vertical force only on the lifting points. Using ALL lifting points is mandatory.
Failure to lift by the manufacturer's instructions could cause damage to the equipment
and/or personal injury or death. The equipment manufacturer is not responsible for
unsafe rigging or lifting procedures.
In addition to checking the rigging, before lifting the unit, verify the following:
□ If the unit is being set on a down discharge curb and duct work is being installed
from the top, verify that the duct work is installed.
IMPORTANT: Verify that the lift operator knows the correct placement of the unit
so that the airow orientation will be correct. To match to the duct openings in the
curb, the unit must be positioned as illustrated in FIGURE 13, shown below.
Note that the condenser section does not set on the curb.
FIGURE 13 - Correct Orientation when Placing the Unit on either a Down ow Curb with Duct Supports or a Curb with Plenum Sections and Duct Connections for Horizontal Airow
36” High Horizontal
Horizontal
Duct
Connection
in the Curb
for Discharge
(Supply) Air
Horizontal Duct Connection in the Curb for Optional Return Air
(If not used, cover the opening.)
Airflow Curb with Plenum Sections with Duct Connections for Supply and Return Air
Down ow Roof Curb,
Options CJ31 and CJ34
Horizontal Airow Curb, Options CJ48 and CJ55
Form I-Y, P/N 273646R6, Page 19
Optional
Wheel Access
Damper Access
Coil &
Filter
Access
Supply
Fan
Access
Optional
Heat Section
Control Access
Condenser
Section
Spreader bars are REQUIRED.
After test lift, adjust cable length as needed so that the unit will remain horizontal throughout the lift.
(4) Corner Lifting Points - 1-1/2” (38mm) diameter
Lift straight up with vertical force only.
5.0 Mounting (cont'd)
5.4 Rigging and Lifting (cont’d)
DANGER
To prevent death, injury, or equipment damage caused by inadequate or improper rigging, test lift the unit before attempting to install it on the roof. To prevent injury, death, or
equipment damage when lifting, use ALL lifting points.
Test lift the unit to be sure that it is secure and the weight is balanced. Lift the unit slowly, following safe lifting procedures.
FIGURE 14 - Rigging and Lifting a Cabinet using four lifting points and spreader bars
6.0 Mechanical
6.1.1 Inlet Air Hood, Option AS16
Application and
Components by Model
and Size
Form I-Y, P/N 273646R6, Page 20
6.1 Install Hood(s)
To avoid possible damage, it is recommended that the hood(s) be installed after the system has been placed on the roof. Install the hood(s) before the blower is operated. Do not install the hood(s) while the system is in operation. All screw ends should be to the inside of the hood or cabinet.
Model YDSA N/A 120,150 180,210
Models YDHA, YDMA
Pkg P/N 273283 273373 284598
Air Hood Components:
Top 272476 271116 284449 Right Side 272477 271117 284450 Left Side 272478 271118 284451 Front Cover 272479 271119 284454 Filter Support Assy 272482 268702 284452 Sheet metal
Screws Self-Drilling SM Screws
Filters
060, 090, 120,
150
(4) 101607,
16x20x1
180, 210, 240 300, 360
(16) 11813, 1/2”
(8) 37661, 1/2”
(4) 101610,
20x25x1
(8) 101609,
16x25x1
NOTE: Select screws carefully. Use sheet metal screws (slotted head with straight tip) when holes in the cabinet are provided. Use self­drilling screws (head is not slotted with drill-type tip) when cabinet holes are not provided.
1a) Remove screw in cabinet top.
Hood Top (edge must go under cabinet top)
1b) Slide the edge of the ‘Hood Top’ under the edge of the ‘Cabinet Top’ and reinsert the screw.
ref. Cabinet Top
FIGURE 14A - Installation Instructions and Dimensions - Inlet Air Hood Option AS16
opening and onto the installed filter support.
head and standard point.
STEP 1 – Attach top
STEP 4 – Install lters and attach the
front cover. of outside air hood.
Front Cover
Prepare to attach sides.
STEP 2 – Attach sides of outside air hood.
2a) Position the ‘Side Panels’ inside
Hood Top
(see Step 1)
Left Side
2c) Repeat the procedure to install the ‘Right Side’.
STEP 3 – Attach lter support.
Right Side
the ‘Hood Top’ and attach with a sheet­metal screw. Each side panel requires (3) three screws; 1/2” with slotted head and standard point.
2b) Attach the ‘Side Panels’ to the ‘Cabinet’ with self tapping screws. Use the 1/2” hex head/no-slot screws with the drill point. Each side panel requires (3) three screws.
3a) Position the filter support assembly within the hood with filter opening out as indicated. 3b) Attach filter support assembly with sheetmetal screws. Each side requires three screws; 1/2”with slotted head and standard point
4b) Position the ‘Front Cover’ and attach with sheetmetal screws. Each side requires (1) one screw; 1/2” with slotted
Length Dimension
Dim “A”
(in / mm)
of Installed Hood
Option AS16
Air Hood
Cabinet Size Dim “A”
4a) Slide filters through the front
1 32.44 / 824 2 40.31 / 1024 3 49.39 / 1255
6.1.2 30% Inlet Air Hood in Inlet Air Conguration Option AR7
FIGURE 14B - Installing 30% Inlet Air Hood
6.1.3 Exhaust Air Hood - applies to all units with Power Exhaust (Option PE_) or Energy Recovery Wheel (Option EW__)
The 30% inlet air hood included in Option AR7 is assembled at the factory and shipped with the unit for eld installation. Follow the instructions in FIGURE 14B, shown below.
Remove
Instructions:
1) At the center of the cabinet top, remove the screw.
2) Slide the hood under the cabinet top.
4) Re-insert the screw.
5) Attach both sides of the hood with sheetmetal screws.
screw.
30% Inlet Air Hood,
P/N ______
The exhaust air hood parts are shipped separately for installation at the site. The exhaust location is different depending on whether or not the unit has an energy recovery wheel; the parts are the same. See FIGURE 14C shown or FIGURE 14D, page 22.
(Note complete list of hood
components listed in table in section 6.1 on page 20)
FIGURE 14C - Installing Exhaust Hood with Energy Recovery Wheel Option EW__.
Installing the Exhaust Hood on a Unit with Option EW__ Energy Recovery Wheel
The exhaust fan opening is in the side of the box under the outside air hood.
1) Attach the Hood Top - Above the exhaust opening, remove the screws holding the top of the box. Slide the edge of the hood top under the exhaust fan box top. Align the holes and re-insert the screws.
2) Attach the Hood Sides - Position a side panel to the inside of the hood top, line up with the holes in the box, and attach the side panel. Repeat to attach the other side. On each side of the hood top, insert screws to attach the top to the hood sides.
Form I-Y, P/N 273646R6, Page 21
Remove screws.
6.0 Mechanical (cont’d)
FIGURE 14D ­Installing Exhaust Hood for Power Exhaust Option PE__ without a wheel
6.2 Duct Connections and Duct work
CAUTION: An external duct system static pressure not within the limits on the rating plate may overload the motor.
Installing the Exhaust Hood on a Unit with Option PE_ Power Exhaust
The exhaust opening is in the door panel.
1) Position the hood side to align with the holes in the door panel. Attach with sheetmetal screws.
2) Repeat to attach the other side.
3) Slide the top in place over the side panels.
Attach the top to the door and the side panels.
Requirements and Suggestions for Installing Ducts
Duct connections are in the roof curb designed for the unit; see FIGURE 2 on page 7, FIGURE 3 on page 8 or FIGURE 4 on page 9 for duct connection sizes. Down ow roof
curbs are designed for installing duct work from the top before setting the unit on the
curb. Horizontal curbs have return air and supply air duct anges on the side under the
condenser section. See Figure 5, page 11 or FIGURE 10, page 14 in Paragraph 5.3. NOTE: All installations require a discharge air temperature sensor. See Paragraph
7.5.3 for placement of the discharge air sensor in the duct work.
FIGURE 15 - When installing a unit with a dual heat section, avoid an immediate “T” in the
Control Access
discharge (supply) duct.
An immediate “T” in the discharge duct
may allow stratication of the air resulting
in hot air only moving down one segment of the duct.
Avoid this supply duct conguration. If the conguration is not avoidable, provide air
mixing devices in the duct work.
Hot
Air
Dual Gas Heat
Section
Cool
Air
• Type of Duct work - The type of duct installation to be used depends in part on the construction of the roof (whether wood joist, steel bar joist, steel truss, pre-
cast concrete) and the ceiling (whether hung, ush,
etc.).
• Duct work Material - Rectangular duct should be
constructed of not lighter than No. 26 U.S. gauge galvanized steel or No. 24 B & S gauge aluminum.
• Duct work Structure - All duct sections 24 inches (610mm) or wider, and over 48 inches (1219mm) in length, should be cross broken on top and bottom and should have standing seams or angle-iron braces. Joints should be S and drive strip, or locked.
• Through Masonry Walls - No supply air duct should
come in contact with masonry walls. Insulate around all air ducts through masonry walls with not less than
1/2” (13mm) of insulation. 1” (25mm) is recommended.
• Through Uncooled/Unheated Space - Insulate all exposed supply air ducts passing through an uncooled
6.3 Cooling Section
Condensate Drain
NOTE: For condensate
drain for high-efciency
gas heat section, see Paragraph 9.2.
Form I-Y, P/N 273646R6, Page 22
The cooling section drain pan is below the coil access door in the cooling section. The
1-1/4” drain connection is through the side of the cabinet.
Follow the instructions below to install a trap in the drain. Do not reduce the drain diameter. Pitch the drain line at least 1/2” (13mm) for every 10 feet (3M) of horizontal
run. Drain lines must not interfere with access panels or doors. An obstruction in the drain or a poorly designed drain can cause the condensate pan to
over ow. Overow could result in damage to the unit and/or the building.
If the installation or local code requires, run drain into a waste water system.
or unheated space with at least 1/2” (13mm) of
insulation. 1” (25mm) is recommended.
• Duct Supports - Suspend all ducts securely from buildings members. Do not support ducts solely by the unit duct connections.
• Duct Sizing - Proper sizing of the supply air duct work
is necessary to ensure a satisfactory installation. The
recognized authority for such information is the Air
Conditioning Contractors Association, 2800 Shirlington Road, Suite 300, Arlington, VA 22206 (www.acca.
org). A manual covering duct sizing in detail may be
purchased directly from them.
• Duct Connections - To minimize sound and vibration transmission, use exible duct connections. Ducts
must be attached and sealed to provide airtight connections.
• Return Air Duct/Grill Size - Make certain that return air ducting or grill has a free area equal to the return
duct size connection.
   


6.3 Cooling Section Condensate
Drain (cont’d)
FIGURE 16A - Condensate Drain Trap Dimensions
Condensate Drain Trap in Cooling Coil Drain
The design of the drain trap is important. Since the condensate drain pan is on the blower inlet side, there is a negative pressure at the drain relative to the ambient. The trap height must account for this static pressure difference. Maximum negative static can be determined by reading the negative pressure at the blower inlet and adding .2”
iwc to allow for dirty lters.
If dimension "B" in FIGURE 16A shown below is not tall enough, the water seal will not hold, and air will be drawn through the drain pipe into the unit. If the outlet leg of the trap is too tall, water will back up into the drain pan. As condensate forms during normal
operation, the water level in the trap rises until there is a constant outow. FIGURE 16A
shown below illustrates the appropriate dimensions for trapping a negative pressure system.


A = 1" (25mm) for each 1"
(25mm) of maximum static pressure plus 1" (25mm)
B = A + A/2
7.0 Electrical and Wiring
7.2 Supply Wiring
7.2.1 Disconnect
Switch


FIGURE 16B - Drain Trap with
Clean out
7.1 General
All electrical wiring and connections including electrical grounding MUST be made in accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition). In addi­tion, the installer should be aware of any local ordinances or electric company require­ments that might apply.
Check the rating plate for the supply voltage and current requirements. Run a separate line voltage supply directly from the main electrical panel, making connection at the disconnect switch. See FIGURE 2 on page 7, FIGURE 3 on page 8 or FIGURE 4 on page 9 for location of supply wiring entrance.
If the system has dual disconnect switches (Option BA7), two supply wires are required (See FIGURE 17A, page 24 and FIGURE 17B, page 24).
The system must have a remote disconnect switch, a built-in disconnect switch, or both.
If ordered with a built-in disconnect switch, the system will be factory equipped with one or two built-in non-fusible, lockable disconnect switch(es). The built-in disconnect switch(es) (Option BA6 or BA7) require copper wiring with amp capacity based on 75°C maximum temperature rating at the line side terminals.
If the system does not have a built-in disconnect switch, a eld-provided or optional
shipped-separate, wall-mounted disconnect switch is required. It is recommended that there is at least four feet (1.2M) of service room between the switch and system access panels. All external wiring must be within approved conduit and have a mini­mum temperature rise rating of 60°C. Run conduit so that it does not interfere with the system access panels. When providing or replacing fuses in a fusible disconnect,
use dual element time delay fuses and size according to the rating plate.
WARNING
To prevent injury or death due to electrocution or contact with moving parts, lock an open disconnect switch.
WARNING
If the unit includes a gas furnace, always turn off the gas when you turn off the power supply.
Form I-Y, P/N 273646R6, Page 23
Loading...
+ 53 hidden pages