This unit contains R-410A high pressure refrigerant. Hazards exist that could result in
personal injury or death. Installation, maintenance, and service should only be performed by
an HVAC technician qualied in R-410A refrigerant and using proper tools and equipment.
Due to much higher pressure of R-410A refrigerant, DO NOT USE service equipment or
tools designed for R22 refrigerant.
S
R
E
G
S
V
E
N
N
O
T
M
Y
E
A
L
I
T
U
C
T
T
S
N
Y
Y
S
A
R
R
A
T
W
R-410A
P
U
-
T
R
A
T
S
DANGER:
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or
property damage.
Be sure to read and understand the installation, operation, and service instructions in
this manual.
Improper installation, adjustment, alteration, service, or maintenance can cause
serious injury, death, or property damage.
— Do not store or use gasoline or other ammable vapors and liquids in the vicinity
of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a phone remote from the building. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a qualied installer, service agency,
or the gas supplier.
Form I-Y, P/N 273646R6, Page 1
Table of Contents
1.0 General .........................................................2
1.1 Cautions and Warnings ................................... 2
1.2 General Information ........................................ 3
Index .................................................................75
INSTALLATION RECORD - to be completed by
the installer: .................................................76
1.0 General
Denitions of Hazard
Intensity Levels used in
this Manual
Form I-Y, P/N 273646R6, Page 2
1.1 Cautions and Warnings
There are warning labels on the unit, on the front page, and throughout this manual.
For your safety, comply with all warnings during installation, operation, and service of
this system. Denitions of the hazard intensity levels of the cautions, warnings, and
dangers are shown below.
HAZARD INTENSITY LEVELS
1. DANGER: Failure to comply will result in severe personal injury or
death and/or property damage.
2. WARNING: Failure to comply could result in severe personal injury
or death and/or property damage.
3. CAUTION: Failure to comply could result in minor personal injury
and/or property damage.
Warnings for Units with a Gas Heat Section
WARNING
Gas-red appliances are not designed for use in hazardous atmospheres containing
ammable vapors or combustible dust, in atmospheres containing chlorinated or
halogenated hydrocarbons, or in applications with airborne silicone substances.
WARNING
Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve
to the appliance before shutting off the electrical supply.
WARNING
Do not use this appliance if any part has been under water. Immediately call a qualied
service technician to inspect the appliance and replace any gas control that has been
under water.
1.2 General
Information
1.3 Warranty
1.4 Installation
Codes
This booklet includes installation and operation information. Before beginning any procedure, carefully review the information, paying particular attention to the warnings.
If you do not have knowledge of local requirements, check with the local agencies who
might have requirements concerning this installation. Become familiar with the requirements of your particular installation and make preparations for necessary supplies,
equipment, and manpower.
The installation instructions in this manual apply to Reznor® Model YDHA, Model
YDMA, and Model YDSA. Other manuals in the literature bag include:
• Form O-Y, Maintenance/Service Manual
• Form CP-Y D21, Manual for Makeup Air Control System Option D21; or
• Form CP-Y D19, Manual for Space Temperature Control System Option D19
Refer to limited warranty information on the warranty form in the "Literature Bag"
shipped with this system. If an optional extended warranty applies, keep the extended
warranty information for future reference and verication of warranty.
These packaged systems are certied by ETL to "Heating Cooling Equipment" (latest
edition), UL 1995 / CAN/CSA C22.2 No. 236-05. Electrical characteristics are shown
on the system rating plate. All cooling and reheat circuits are factory-charged with
R-410A refrigerant.
If the system has a gas heat section, it has an integral gas-red, power-vented duct
furnace. The furnace is certied by ETL to the latest editions of both ANSI Z83.8 and
CSA 2.6 for use in the United States and Canada. The ETL label, type of gas, and the
ring rate are shown on the heat section rating plate.
California Warning
Label
Massachusetts
Requirements
2.0 Location and
Moving
If a gas-red heat section is included and the system is being installed in the state of
California, the installer MUST attach the California warning label on the outside of the
heat section access panel. The California Warning label, P/N 196977, is shipped in
the "Literature Bag". Select a dry, clean location on the heat section access panel and
adhere the label.
If being installed in the Commonwealth of Massachusetts, this unit must be installed by
a licensed plumber or licensed gas tter.
This outdoor unit is designed to be set on a matching Reznor® curb (See Paragraph
5.3.) that will provide either vertical or horizontal discharge airow. The system must be
level for proper operation. When selecting the location, check the following:
Installation location must comply with all applicable codes.
Location on a roof depends on building structure. Refer to Paragraph 5.1 for
information on how to obtain unit weight data.
Comply with required clearances in Paragraph 4.1.
Position the unit so that the outside air inlet will not be facing into the prevailing
wind.
Before moving the unit, refer to Paragraph 5.4 for rigging information.
Form I-Y, P/N 273646R6, Page 3
3.0 Receiving, Shipped Separate and Storage
3.1 Receiving
This system was test operated and inspected at the factory and was in operating
condition. If the equipment has incurred any damage in shipment, document the
damage with the carrier and immediately contact your Reznor® distributor.
Check the entire unit for damage paying particular attention to the structural integrity of
the lifting points and the condenser fan section. Check the condenser fan guards and
the fan blades.
On the inside of the control access door, locate the system rating plate (See FIGURE 2 on page 7, FIGURE 3 on page 8 of FIGURE 4 on page 9). Check the rating plate
information for specications and the electrical characteristics and verify compatibility
with the installation site.
If installing a unit with a heat section, check the rating plate on the inside of the
heat section door. For a gas heat section, be sure that the rating plate information is
compatible with the altitude and the gas supply at the installation site.
3.2 Shipped
Separate
Accessories and
Shipped Loose
Parts
Check for shipped-separate accessories and shipped-loose parts. All systems will
have a shipped-loose discharge air sensor. The roof curb which is shipped separately
(in most cases prior to the unit) requires eld assembly. The outside air hood is shipped
with the unit in a separate carton for eld assembly and installation. (NOTE: Install the
hood after the unit is in place. See Paragraph 6.1.)
Listed in the tables below are shipped separately & their availability options.
Standard Efciency Vertical Flue Discharge Extension Options (pipe not included):
Model NoOptionPN’s IncludedDescriptionH50 & H75
YDHA, YDMACC3235320
YDHA, YDMA,
YDSA
YDHA, YDMA,
YDSA
YDHA, YDMA,
YDSA
YDHA, YDMA--------Yes
CC3D 235320
(small vent tube)
(small vent tube)
235321
(large vent tube)
Single furnace
kit, Metal
Dual furnace
kit, Metal
Yes--------
--Yes------
----Yes----
------Yes--
H100, H200,
H300, H400
H102, H125,
H150, H175
H202, H402,
H502, H602
H702 & H802
High Efciency Vertical Flue Discharge Extension Options (pipe not included):
Model NoOptionPNDescriptionG150, G225, G300G302, G372, G452G525 & G602
YDHA
YDMA
YDSA
YDHACC4D273388Dual furnace
YDMA--YesYes
YDSA--Yes--
CC4273387Single furnace
kit, PVC
kit, PVC
Yes
Yes
Yes
--YesYes
----
----
--
--
High Efciency Flue Condensate Handling Options:
Model NoOptionPNDescriptionG150, G225, G300, G302, G372, G452G525 & G602
YDHAFB1273277Condensate Frost
YDMAYesYes
YDSAYes--
YDHACSP1272512Condensate PumpYesYes
YDMAYesYes
YDSAYes--
YDHACSN1272511Condensate
YDMAYesYes
YDSAYes--
Form I-Y, P/N 273646R6, Page 4
Protection
Neutralizer
YesYes
YesYes
Controls Options:
OptionPNDescription
CL2325733824v 2-stage heating/cooling touch
screen prog thermostat
CL33221038Electronic 24v prog thermostat for up to
3 stages heating and or cooling
CL78272631Wall mounted DDC temperature moni-
tor and setpoint adjustment
BD542782Firestat 200°FYesYesYes
2
BE15234820Space CO
sensor (range 0-2000 ppm)YesYesYes
BE17259076Smoke detector (photoelectric)YesYesYes
Cabinet Size / Option Availability
1 (a)23
YesYesYes
YesYesYes
YesYesYes
RB5260436Wall mounted remote monitoring dis-
YesYesYes
play
RB6272407Hand held remote display with cableYesYesYes
for units with ERM, bottom duct
connections, exposed external
insulation.
Units without Energy
Recover
Units with
Energy
Recovery
Yes
YesYes
PN 272400PN 272404PN 284224
YesYes
PN 272401PN 272405PN 284223
Yes
CJ5536”high full perimeter roof curb for
pad mounting for units with ERM,
horizontal discharge, double wall
Units with
Energy
Recovery
insulation in air plenum section.
(a) Cabinet size 1 not available with YDSA model
YesYes
Yes
PN 272402PN 272406PN 284224
Form I-Y, P/N 273646R6, Page 5
3.0 Receiving, Shipped Separate and Storage (cont’d)
3.2 Shipped Separate Accessories and Shipped Loose Parts (cont’d)
Outside Air Hood
OptionDescription
AS16Outside air hood with
permanent prelters
123
273283273373284598
Exhaust Fan Control Option
OptionDescription
EFC4Outside pressure pickup port
Room pressure port
234905
234906
Inlet Damper Control Option
OptionDescription
GF5Outside pressure pickup port
Room pressure port
234905
234906
Fan Control Option
OptionDescription
VFC34”static pressure probe234821234821234821
VFC4Outside pressure pickup port
Room pressure port
Cabinet Size
Cabinet Size
123
234905
234906
234905
234906
Cabinet Size
123
234905
234906
234905
234906
Cabinet Size
123
--234905
234906
234905
234906
3.3 Storage
If this system is going to be stored, take precautions to prevent condensate formation
inside the electrical compartments and motors. To prevent damage to the unit, do not
store sitting on the ground.
4.0 Clearances and Dimensions
IMPORTANT: The area above the condenser fans MUST ALWAYS be
totally open space to allow proper airow through the condenser
Control End View with High
Efficiency Gas Heat Section
(See dimensions below.)
82-11/16
(2100)
*Vent Outlet High Efficiency
(condensing)
Gas Heat Section
Control End View with Electric or
Non-Condensing Gas Heat Section
31-5/16
(795)
50
(1270)
Condenser
6-1/4 (159)
5-1/4
(133)
G
F
Utility Entrance Dimensions
* High-efficiency dual heat sections have two vent outlets.
** Two power supply entrances and two disconnect switches apply
only to systems with dual disconnect Option BA7.
Optional Gas
Heat Section
51-3/8
(1305)
Control Access
Section
Optional
Heat Section
44-7/16 (1128)
- Inside the Curb Cap
Y
X
6 (152)
8 (203)
**Optional
Disconnect
Switch
**Power
Supply
Gas
Inlet
5-1/8
(130)
std gas
heat
only
Vent
Outlet
(gas heat)
7 (178)
B
36
(914)
Top
View
Vent Outlet - Standard (non-condensing) Gas Heat Section
Fan
Access
C - Inside the Curb Cap
A - Base Length
31-7/16
(799)
30
(762)
Supply Air
Bottom View showing Duct Openings
D
Side View
Discharge
Coil &
Filter
Access
Airflow
Optional
Wheel Access
1-1/4” Ø Condensate
Drain Connection
16
(406)
E
Inlet
Return Air
Optional
Outside
Air Hood
32-7/16
(824)
Hood
Damper Access
23-7/8
(606)
7 (178)
36
(914)
5-15/16
(150)
**Power
Exhaust
w/Opt
Wheel
14 (356)
Z
14-3/8
(365)
10-3/8
(254)
Power Exhaust
Box with
Points - 1-1/2 (38mm)
Optional Exhaust
Dampers
without an
energy recovery
Inlet Air End View
23-3/8
(594)
Outside
Air Inlet
Optional
Wheel
(4) Corner Lifting
80-7/8 (2238)
- Base Width
Opening Dimensions inches
(mm)
Supply Air
Discharge
Return Air
Inlet
Outside Air Inlet - Sizes by Option:
OptionZ
AR7
AR25, AR2D,
AR2H & all
other models
36 x 30
(914) x (762)
36 x 16
(914) x (406)
8
(203)
19-7/8
(505)
Section
Condenser
Important NOTE: DO NOT use base dimensions for roof curb. See Paragraph 5.3.
Models
and Cooling
Sizes
YDMA and
YDHA 060, 090
YDMA and
YDHA 120, 150
YDMA and
YDHA 060, 090
YDMA and
YDHA 120, 150
Size
Cabinet
1A
1B
1A
1B
Gas Connection Location and Size for Systems with Optional Gas Heat Section
Gas Heat Section (H=non-condensing; G=condensing heat section)
Vent Outlet - Standard (non-condensing)
Gas Heat Section
Fan
Access
B - Inside the Curb Cap
A - Base Length
31-7/16
(799)
Bottom View showing Duct Openings
30
(762)
Control Access
*Vent Outlets High Efficiency
(condensing)
Gas Heat Section
Control End View with Electric or
Non-Condensing Gas Heat Section
31-5/16
(795)
65-9/16
(1665)
Condenser
6-1/4 (159)
57-11/16
* High-efficiency dual heat sections have two vent outlets.
** Two power supply entrances and two disconnect switches apply
only to systems with dual disconnect Option BA7.
5-1/4
(133)
(1468)
49-11/16
(1264)
Utility Entrance Dimensions
Optional Gas
Heat Section
58-5/8
(1489)
Control Access
Optional
Section
Heat Section
51-11/16 (1313)
- Inside the Curb Cap
6 (152)
8 (203)
**Optional
Disconnect
Switch
**Power
Supply
Gas
Y
X
Inlet
Airflow
18
(457)
Inlet
Return Air
Optional
Outside
Air Hood
40-5/16
(1024)
Hood
Optional
Wheel Access
Damper Access
24
(610)
1-1/4” Ø Condensate
Drain Connection
D
6-1/8 (155)
45
(1143)
24-9/16
(624)
14 (356)
Inlet Air End Views
Z
5-7/8 (149)
Y
Power
Exhaust
Box with
Optional
Wheel
X
Outside
Air Inlet
Power Exhaust
Box with
Optional Wheel
(4) Corner Lifting
Points - 1-1/2 (38mm)
88-1/8 (2238)
- Base Width
Opening Dimensions
inches (mm)
Supply Air
Discharge
Return Air
Inlet
Outside Air Inlet - Sizes by Option:
OptionXYZ
AR1
AR7
AR25, AR2G,
AR2H & all
models with
Wheel option
45 x 30
(1143) x (762)
45 x 18
(1143) x (457)
49-5/8
(1260)
25-5/8
(651)
45-3/4
(1162)8 (203)7 (178)
49-5/8
(1260)
25-5/8
(651)
Optional
Exhaust
Dampers
without
an energy
recovery
wheel
Section
Condenser
5-1/2
(140)
5-1/2
(140)
Important NOTE: DO NOT use base dimensions for roof curb. See Paragraph 5.3.
Control End View with High
Efficiency Gas Heat Section
(See dimensions below)
Control Access
Optional Gas
Heat Section
101-5/32
(2569)
Top View
Optional
Outside Air
Hood
ERV Wheel Access
Optional
Exhaust
Damper
Damper
Access
*Vent Outlets High
Efficiency (condensing)
Gas Heat Section
Control End View with Electric or
Non-Condensing Gas Heat Section
83-3/64
(2109)
Section
Condenser
12-5/64
(307)
**Optional
Disconnect
Switch
62-1/64
(1575)
55-5/64
(1399)
Utility Entrance Dimensions
* High efficiency dual heat sections have two vent outlets.
** Two power supply entrances and two disconnect switches apply only
to systems with dual disconnect Option BA7
Y
70-11/16
(1795)
Control Access
Optional Heat
Section
64-23/32 (1644)
(Inside Curb Cap)
X
**Power
Supply
Gas
Inlet
5
(127)
Vent Outlet
(gas heat)
6-9/64
(156)
57
(1448)
83-31/32
(2133)
161-11/32
Vent Outlet - Standard (non-condensing)
Gas Heat Section
Access
32-43/64
(830)
Bottom View showing Duct Openings
(4098)
Side View (with power exhaust)
Fan
155-23/32
(Inside the Curb Cap)
(3955)
164-9/32
(Base Length)
(4173)
31
(787)
Supply Air
Discharge
Coil Access
21
(533)
Filter Access
Inlet
Return Air
Optional
Wheel
Access
Damper
Access
32-57/64
(835)
49-25/64
(1255)
Hood
23-15/16
(608)
1” PVC Female
Condensate Drain Pan
Adapter Fitting
6-9/64
(156)
57
(1448)
Side View
(with ERV Wheel Option)
7-29/64
5-27/32
(148)
Z
Power
Exhaust
Box with
Optional
Wheel
Inlet Air End View
(189)
Power Exhaust
Optional Wheel
59-5/8
(1514)
Outside Air
Inlet
Box with
78-61/64
(2005)
(with Optional Exhaust Damper)
Opening Dimensions
inches (mm)
Supply Air
Discharge
Return Air Inlet
Outside Air Inlet - Sizes by Option:
OptionZ
AR1, AR25,
AR2G & all
other models
AR7
57 x 31
(1448) x (787)
57 x 21
(1448) x (533)
30-5/8
(778)
8-1/16
(205)
Side View
Section
Condenser
12-1/2
(317)
Important NOTE: DO NOT use base dimensions for roof curb. See Paragraph 5.3.
Gas Connection Location and Size for Systems with Optional Gas Heat Section
Gas Heat Section (H=non-condensing; G=condensing heat section)
Single FurnaceDual Furnaces (one gas connection)
G150, H200G302, H402
--H150, H175, H20212-21/32”
G225, G300, H300, H400G372, G452, H502, H602
--G525, G602, H702, H8021-1/4”
XY
9-35/64”
(242 mm)
9-13/32”
(239 mm)
Diameter
(NPT)
19-5/32”
(487 mm)
19-5/32”
(487 mm)
19-37/64”
1/2”
1/2”
3/4”
(497 mm)
Form I-Y, P/N 273646R6, Page 9
5.0 Mounting
MUST be sealed
between curb cap
rail and roof curb.
Optional or
Field-Supplied
Roof Curb fits
under and inside
the curb cap.
Base of curb cap edge
Edge of curb cap
extends down over
the roof curb.
Cabinet Wall
Curb
Cap Rail
5.1 Unit Weights
For unit weights and or corner weights, refer to www.ReznorHVAC.com or call 1-800-695-1901. Specic unit weights
will be supplied by order number which will include the weights of the options specied for that specic unit.
5.2 Curb Cap Base
and Mounting
These packaged systems have a
curb cap base designed for use with
a full perimeter curb. When on a roof,
either a manufacturer-designed roof
curb or a eld-supplied roof curb is
required.
NOTE: A Reznor® designed roof
curb with integral vertical duct
work supports is recommended to
provide a weatherproof installation.
Base design varies by cabinet size.
5.3 Mounting on a Roof Curb
Two types of fully enclosed curbs are available with these systems.
Optional Energy
Recovery Wheel
Roof
Curbs
Option
CJ31No16” (406mm), Down Discharge with
CJ34Yes
CJ48No
CJ55Yes
If the application is sound sensitive, consider installing a eld-supplied vibration isolation curb or specialty sound attenuation curb. Whether using an optional roof curb
available with the system or a eld-supplied speciality curb, the curb must be secured,
on square, and level. When the unit is being placed on a roof, location depends on the
roof structure and is the responsibility of the installer. For condensate drainage and
proper operation, it is important that the installation be level.
When positioning the curb, always comply with the required clearances in Paragraph
4.1. Check the dimensions carefully, remembering that the condenser section will
extend 30” (762mm) beyond the edge of the curb. (See orientation in FIGURE 13,
page 19). Position the curb so that the outside air inlet of the unit will not be facing into
the prevailing wind.
Duct Connections - Optional down discharge roof curbs are designed for duct work
to be inserted in the duct connection opening(s) from above the curb prior to setting
the unit on the curb.
Description
Duct Supports in the Curb
36” (914mm), Horizontal Discharge
with Duct Connections in the Curb
Curb Cap
Section
View
Form I-Y, P/N 273646R6, Page 10
5.3.1 Down ow Roof
Curbs
Both Option CJ31 and CJ34 are 16" (406mm) high roof curbs designed for vertical
(down) discharge. These curbs include integral cross supports for supply air and
optional return air duct work.
FIGURE 5 - Layout, Dimensions, and Weights of Option CJ31 & CJ34 Roof Curbs
Curb
Layout
Wood
Nailer
Insulation
(Inlet Hood End)
2x6
16”
(406mm)
(Condenser Side of Unit - Base extends
30” / 761mm beyond this side of curb.)
Cross-Section
Downflow Curb Options CJ31 and CJ34
Return
Air
View
Supply
Air
of Unit)
(Control End
Dimensions - inches (mm)
OptionModel and Size
YDHA & YDMA 060,
CJ31
No Energy
Wheel
090, 120, 150
YDHA & YDMA 180,
210, 240 YDSA 120, 150
YDHA & YDMA, 300,
360 YDSA 180, 210
YDHA & YDMA 060,
CJ34
With Energy
Wheel
090, 120, 150
YDHA & YDMA180, 210,
240 YDSA 120, 150
YDHA & YDMA, 300,
360 YDSA 180, 210
Cabinet
Size
1
2
3
1
2
3
ABCD
(Outside of Curb Rails) (Area Inside the Curb*)
119-11/16
(3040)
123-11/16
(3141)
154-11/16
(3929)
128
(3251)
132
(3353)
154-11/16
(3929)
* Area enclosed by the roof curb must comply with clearance to
combustible materials. If the roof is constructed of combustible
materials, area within the roof curb must be ventilated, left open,
or covered with non-combustible material which has an “R” value
of at least 5. If area within curb is left open, higher radiated sound
levels may result. NOTE: If installing a unit with a high efciency,
condensing gas-red heat section, the area within the curb must be
left open.
** When cutting only duct openings, cut “E” & “F” dimensions 1/4”
(6.4mm) in from duct opening to allow clearance. Cut the curb rail
sides of the duct opening(s) parallel to the curb rail. For Cabinet
Size 1, measure a maximum of 1-1/2” (38mm) in from the side rail.
For Cabinet Size 2, measure a maximum of 3/4” (19mm) in from
the side rail.
*** See chart on page 68 for cross-reference by Model Size or
Model and Heat Size to Cabinet Size.
D
GH
43-7/16
(1103)
50-11/16
(1287)
63-11/16
(1618)
43-7/16
(1103)
50-11/16
(1287)
63-11/16
(1618)
Return
(DxF)
115-15/16
(2945)
119-15/16
(3046)
150-15/16
(3834)
124-1/4
(3156)
128-1/4
(3257)
150-15/16
(3834)
Air
Weights of Downow Roof
Curb Option CJ31 and CJ34
by Cabinet Size
Roof
Curb
Option
CJ31
Option
CJ34
Cabinet 1Cabinet 2Cabinet 3
lbskglbskglbskg
237108257117322146
24811 2268122322146
Top View
Unit
Airflow
39-11/16
(1008)
46-15/16
(1192)
59-15/16
(1522)
39-11/16
(1008)
46-15/16
(1192)
59-15/16
(1522)
C
A
E**F**GH
31
(787)
31
(787)
31
(787)
31
(787)
31
(787)
31
(787)
Supply
Air
(DxE)
EF
17
(432)
19
(483)
21
(483)
17
(432)
19
(483)
21
(483)
25-3/4
(654)
25-13/16
(656)
28-7/32
(717)
25-3/4
(654)
25-13/16
(656)
28-7/32
(717)
B
14-29/32
(379)
18-13/16
(478)
28
(711)
23-1/4
(591)
27-1/8
(689)
28
(711)
Form I-Y, P/N 273646R6, Page 11
5.0 Mounting (cont'd)
5.3 Mounting on a Roof Curb (cont'd)
5.3.1 Down ow Roof Curbs (cont’d)
CAUTION: Before installation, recheck to be sure that the correct curb has been ordered.
Be sure that the curb selected matches the unit ordered. Verify the dimensions of the curb
received with the appropriate dimension table.
3216247 Cap Screw
321333 Lock Washer
321035 Hex Nut
Form I-Y, P/N 273646R6, Page 12
Hardware in Options CJ31 and CJ34
For top level screws (1 each corner; 4 each splice; 2 each
cross support). Insert screws from inside the curb so that
they extend into the wood nailer on the outside.
For attaching at all points below the wood nailer. Insert
screws from outside the curb.
Installation Instructions for Down Discharge Roof Curbs, Option CJ31 and Option CJ34
1. Refer to FIGURE 6 shown on page 12 and layout the
two curb ends (letter D) and four side pieces (letters B
&C). Verify the side pieces are in the correct positions
(inlet air end vs control end).
2. Attach Curb Corners.
Using the hardware provided, create the corners by
attaching the ends to the side pieces.
Use the hardware provided to attach splice plates to
join the side rail pieces and create the perimeter of the
curb.
FIGURE 8 - Attaching Spice Plates
(4) Lag Screws with
washers - top row
(into the nailer)
}
(12) Cap Screws
with washers and nuts
- bottom three rows (cap screw heads
should be on insulation side of rail)
4. Attach the four Cross Supports.
At the holes in curb sides, line up the cross supports
in the orientation illustrated in FIGURE 6 shown on
page 12. Since the cross supports form the duct connections, be certain that the vertical side of each cross
support is toward the duct opening.
Using two lag screws with washers, at each end of a
cross support, attach the support to the sides. Insert
the screws through the side and into the wood nailer.
Repeat for the other three cross supports.
5.Check the roof curb for squareness.
Adjust the curb so that the diagonal measurements
are equal within a tolerance of ±1/8”(3mm).
6. Level the roof curb.
To ensure a good weatherproof seal between the
cabinet curb cap and the roof curb, the curb must be
leveled in both directions with no twist end to end.
Shim as required and secure the curb to the roof deck
before installing ashing.
7. Install eld-supplied ashing.
FIGURE 9 -
Installed
Curb
Counter Flashing
(by installer)
Cant Strip
(by installer)
Roofing
Felts (by others)
8. Before placing the unit on the curb:
Curb
Wall
Cabinet
Cap
2 x 6
Wood
Nailer
Insulation
Weld, bolt, or lag screw
curb to deck structure.
□Apply 1/4” x 1-1/4” foam sealant tape to both the top
surface of the curb rails and the top surface of the
cross supports, being sure to make good butt joints
at all corners. The sealant tape must be applied to
prevent water leakage into the curb area due to blown
rain and capillary action.
□ Slide the duct work down into the supply (discharge)
and optional return air openings. See dimensions
in FIGURE 5, page 11. Duct work should have a
minimum 2” (51mm) duct ange.
□ When it is time to lift the unit onto the curb, comply
with rigging and lifting information in Paragraph 5.4.
IMPORTANT: Verify that the unit will be placed in the
correct airow orientation to mate properly with the
discharge and return air openings. See FIGURE 13,
page 19.
MUST be
sealed
between
curb cap and
roof curb.
}
Roof Curb
Form I-Y, P/N 273646R6, Page 13
2x6
Wood
Nailer
36”
(914mm)
Curb Side
Cross-Section
Installation NOTES:
Plenum ducts in the curb have
insulated bottom and side
panels. Always install all four
side panels. If the system does
not have return air, attach a
field-fabricated cover over the
return air opening in the curb.
(Without return air, the bottom of
the unit is solid.)
Horizontal Airflow Curb Options CJ48 and CJ55
(Inlet Hood End of Unit)
(Control End
of Unit)
Return Air
Plenum
Supply
Air Plenum
(Condenser Side of Unit - Condenser base will be
above the duct connections and extends
30”/762mm beyond the curb side.)
5.0 Mounting (cont'd)
5.3 Mounting on a Roof Curb (cont'd)
5.3.2 Curbs for Horizontal Airow
CAUTION: Before installation, recheck to be sure that the correct curb has been ordered. Be sure
that the curb selected matches the unit ordered. Verify the dimensions of the curb received with the
appropriate dimension table.
Options CJ48 and CJ55 are 36" (914mm) high roof curbs designed for horizontal discharge. The curbs include plenum
sections for ducting supply air and optional return air to the duct connections in the side of the curb.
FIGURE 10 - Layout,
Dimensions, and
Weights of Option
CJ48 and CJ55
Horizontal Roof
Curbs
Dimensions - inches (mm)
Option Description
Horizontal Discharge
Curb for YDHA,
YDMA, or YDSA
CJ48
without an energy
recovery wheel
Horizontal Discharge
Curb for YDHA,
YDMA, or YDSA with
CJ55
an energy recovery
wheel
* See chart on page 68 for cross-reference by Model
Size or Model and Heat Size to Cabinet Size.
Weights by Cabinet Size - Horizontal Airow
Roof Curb Option CJ48 and CJ55
Roof Curb
Option CJ48
Option CJ55
* See chart on page 68 for cross-reference by Model Size
or Model and Heat Size to Cabinet Size.
(40) each 16247 Cap Screw
1333 Lock Washer
1035 Hex Nut
C
H*
Sheetmetal Screws
P/N 11813
Curb Option CJ48Curb Option CJ55*
Cabinet 1Cabinet 2Cabinet 1Cabinet 2
271419
(Qty 2)
271396
(Qty 1)
271399
(Qty 1)
271418
(Qty 1)
271417
(Qty 1)
261887
(Qty 2)
271421
(Qty 2)
271420
(Qty 1)
271422
(Qty 2)
268606
(Qty 1)
271403
(Qty 1)
271404
(Qty 1)
271397
(Qty 2)
271396
(Qty 1)
271399
(Qty 1)
272036
(Qty 1)
272035
(Qty 1)
271379
(Qty 2)
271400
(Qty 2)
271401
(Qty 1)
271402
(Qty 2)
271386
(Qty 1)
271403
(Qty 1)
271404
(Qty 1)
271419
(Qty 2)
271396
(Qty 1)
271399
(Qty 1)
271427
(Qty 1)
271426
(Qty 1)
261887
(Qty 2)
271421
(Qty 2)
271420
(Qty 1)
271422
(Qty 2)
268606
(Qty 1)
271403
(Qty 1)
271404
(Qty 1)
271397
(Qty 2)
271396
(Qty 1)
271399
(Qty 1)
271395
(Qty 1)
271398
(Qty 1)
271379
(Qty 2)
271400
(Qty 2)
271401
(Qty 1)
271402
(Qty 2)
271386
(Qty 1)
271403
(Qty 1)
271404
(Qty 1)
* For a unit with an energy recovery wheel
QtyP/N DescriptionUse
12 16243 Lag Screw
121333 Lock Washer
40 16247 Cap Screw
401333 Lock Washer
401035 Hex Nut
90 11813
Sheet metal
Screws
Hardware in Options CJ48 & CJ55
For top level screws (1 each corner; 4 each splice plate). Insert screws
from inside the curb so that they extend into the wood nailer on the outside.
For attaching corners and splice plates below the wood nailer (4 each
corner; 12 each splice plate). Insert screws from outside the curb.
For attaching duct plenum sides, bottom, and bafe; and duct anges.
Form I-Y, P/N 273646R6, Page 15
5.0 Mounting (cont'd)
5.3 Mounting on a Roof Curb (cont'd)
5.3.2 Curbs for Horizontal Airow (cont’d)
Installation Instructions for Cabinet Sizes 1 & 2 Horizontal Airow Roof Curbs, Option CJ48 and
Option CJ55
1. Refer to FIGURE 11 shown on page 15 and position the two curb ends (letter A) and four side pieces
(letters B, C, D, E). Verify the side pieces are
positioned correctly (shorter piece at the inlet air end
and longer piece at the control end of the unit).
2. Attach Curb Corners.
Using the hardware provided (lag screw and washer
in top holes; cap screw, washer, and nut in the 4 holes
below the wood nailer), create the four corners by
attaching the ends to the side pieces.
3. Attach the two Side Splice Plates (letter F).
Use the hardware provided (lag screw and washer in
top holes; cap screw, washer, and nut in the 4 holes
below the wood nailer) to attach splice plates (letter F)
joining the side pieces (letters B&D and letters C&E)
to complete the perimeter of the curb.
4. Attach the Two Outer Plenum Side Panels (letter G).
Position each insulated panel with the wide bottom
ange toward the center. Align the panel with the holes
in the curb sides and attach with sheet metal screws.
5. Install the Plenum Duct Bottom Panel (letter H).
Lower the insulated bottom panel into the curb, resting
it on the anges of the two panels installed in Step 4.
Attach the bottom panel with sheet metal screws.
6. Install the Two Inner Plenum Side Panels (letter J).
Position one insulated side panel as illustrated and
align the holes. Attach with sheet metal screws.
Repeat to install the other side panel.
7. Install the Bafe in the Supply Air Plenum (letter K).
Position the bafe between the insulated side panels (letters G & K) as illustrated and align the holes.
Attach with sheet metal screws.
8. Attach the Duct Flanges (letters L & M).
Using sheet metal screws, attach the duct ange
(letter L) around the supply opening and the smaller
duct ange (letter M) around the return air opening. If
the installation does not have return air, attach a eld-
fabricated cover over the return air opening.
9. Check the Squareness, Level the Curb, and Install
the Flashing.
Adjust the curb so that the diagonal measurements are
equal within a tolerance of ±1/8”(3mm).
To ensure a good weatherproof seal between the
cabinet curb cap and the perimeter of the curb, the
curb must be leveled in both directions with no twist
end to end. Shim as required and secure the curb to
the roof deck.
Install eld-supplied ashing.
10.Before placing the unit on the curb, apply 1/4” x
1-1/4” foam sealant tape to both the top surface of
the curb rails and the top surface of the duct sides.
Lag Screw P/N 16243
Lock Washer P/N 1333
(Qty 12 each)
Wood nailer side - screw
head towards panel
G
A
E
L
K
F
Item
AEnd Assembly
BSide Assy (solid/control end)
CSide Assy w/Supply Air Opening
DSide Assy (solid/inlet air end)
ESide Assy w/Return Air Opening
FSplice Plates for Sides
GSides for Plenum Ducts
HPlenum Duct Bottom
JAir Bafe for Supply Air Plenum
KReturn Air Duct Bottom
LReturn Air Duct Flange
MSupply Air Duct Flange
QtyP/N DescriptionUse
12 16243 Lag Screw
121333 Lock Washer
40 16247 Cap Screw
401333 Lock Washer
401035 Hex Nut
98 11813
Sheet metal
Screws
G
G
D
F
J
B
Return Air
Supply Air
Cap Screw P/N 16247
Lock Washer P/N 1333
A
Hex Nut P/N 1035
(Qty 40 each)
Cap screw to be on
insulation side
G
M
H
C
Sheetmetal Screw P/N 11813
(Qty 98)
Description
Package P/N284224
Hardware in Options CJ48 & CJ55
For top level screws (1 each corner; 4 each splice plate). Insert screws
from inside the curb so that they extend into the wood nailer on the outside.
For attaching corners and splice plates below the wood nailer (4 each
corner; 12 each splice plate). Insert screws from outside the curb.
For attaching duct plenum sides, bottom, and bafe; and duct anges.
Curb Option
CJ48 or CJ55
Cabinet 1
284173
(Qty 2)
284137
(Qty 1)
284139
(Qty 1)
284135
(Qty 1)
284171
(Qty 1)
271379
(Qty 2)
284175
(Qty 4)
284181
(Qty 1)
284184
(Qty 1)
284207
(Qty 1)
284185
(Qty 1)
271403
(Qty 1)
Form I-Y, P/N 273646R6, Page 17
5.0 Mounting (cont'd)
5.3 Mounting on a Roof Curb (cont'd)
5.3.2 Curbs for Horizontal Airow (cont’d)
Installation Instructions for Cabinet Size 3 Horizontal Airow Roof Curbs, Option CJ48 and Option CJ55
1. Refer to FIGURE 12 shown on page 17 and position
the two curb ends (letter A) and four side pieces
(letters B, C, D, E). Verify the side pieces are
positioned correctly (shorter piece at the inlet air end
and longer piece at the control end of the unit).
2. Attach Curb Corners.
Using the hardware provided (lag screw and washer
in top holes; cap screw, washer, and nut in the 4 holes
below the wood nailer), create the four corners by
attaching the ends to the side pieces.
3. Attach the two Side Splice Plates (letter F).
Use the hardware provided (lag screw and washer in
top holes; cap screw, washer, and nut in the 4 holes
below the wood nailer) to attach splice plates (letter F)
joining the side pieces (letters B&D and letters C&E)
to complete the perimeter of the curb.
4. Assemble the Return Air Plenum.
Position two sides (letter G) between the return air
duct bottom (letter K) align the holes in each and
using the sheet metal screws, assemble these three
sheet metal pieces. Then using the holes in the curb
sides (letters D & E), align the return air plenum sub
assembly holes on each end with the holes in the curb
sides and attach using the sheet metal screws.
5
Assemble the Supply Air Plenum.
(letter G) between the supply air duct bottom (letter
H) align the holes in each and using the sheet metal
Position two sides
screws, assemble these three sheet metal pieces.
Then using the holes in the curb sides (letters D & E), align the supply air plenum sub assembly holes on
each end with the holes in the curb sides and attach
using the sheet metal screws.
6. Attach the Duct Flanges (letters L & M).
Using sheet metal screws, attach the supply air duct
ange (letter M) around the supply opening and the
smaller return air duct ange (letter L) around the
return air opening. If the installation does not have
return air, attach a eld-fabricated cover over the
return air opening.
7. Check the Squareness, Level the Curb, and Install
the Flashing.
Adjust the curb so that the diagonal measurements
are equal within a tolerance of ±1/8”(3mm).
To ensure a good weatherproof seal between the
cabinet curb cap and the perimeter of the curb, the
curb must be leveled in both directions with no twist
end to end. Shim as required and secure the curb to
the roof deck.
Install eld-supplied ashing.
8.Before placing the unit on the curb, apply 1/4” x
1-1/4” foam sealant tape to both the top surface of
the curb rails and the top surface of the duct sides.
Form I-Y, P/N 273646R6, Page 18
5.4 Rigging and
Optional
Return Air
Discharge
(Supply) Air
16” High
Curb with
Cross Supports
for Discharge
and Supply Air
Ductwork
Lifting
DANGER
If there is any visible damage or any question about the integrity
of a lifting point, DO NOT LIFT the system. Consult the factory.
Refer to Paragraph 5.1 for information on obtaining unit or corner weights. IMPORTANT NOTE: ALL systems MUST be loaded and unloaded by lifting. DO NOT attempt
to move with a fork lift.
Lifting lugs for attaching rigging are provided at each corner of the base. ALL lifting
points MUST always be used. Spreader bars MUST be used to prevent cabinet dam-
age and to allow the unit to be lifted straight up with vertical force only on the lifting
points. Using ALL lifting points is mandatory.
Failure to lift by the manufacturer's instructions could cause damage to the equipment
and/or personal injury or death. The equipment manufacturer is not responsible for
unsafe rigging or lifting procedures.
In addition to checking the rigging, before lifting the unit, verify the following:
□ If the unit is being set on a down discharge curb and duct work is being installed
from the top, verify that the duct work is installed.
□ IMPORTANT: Verify that the lift operator knows the correct placement of the unit
so that the airow orientation will be correct. To match to the duct openings in the
curb, the unit must be positioned as illustrated in FIGURE 13, shown below.
Note that the condenser section does not set on the curb.
FIGURE 13 - Correct Orientation when Placing the Unit on either a Down ow Curb with Duct
Supports or a Curb with Plenum Sections and Duct Connections for Horizontal Airow
36” High
Horizontal
Horizontal
Duct
Connection
in the Curb
for Discharge
(Supply) Air
Horizontal Duct
Connection in the Curb
for Optional Return Air
(If not used, cover the opening.)
Airflow Curb
with Plenum
Sections with
Duct Connections
for Supply and
Return Air
Down ow Roof Curb,
Options CJ31 and CJ34
Horizontal Airow Curb, Options CJ48 and CJ55
Form I-Y, P/N 273646R6, Page 19
Optional
Wheel Access
Damper Access
Coil &
Filter
Access
Supply
Fan
Access
Optional
Heat Section
Control Access
Condenser
Section
Spreader bars
are REQUIRED.
After test lift, adjust cable length as needed so that
the unit will remain horizontal throughout the lift.
To prevent death, injury, or equipment damage caused by inadequate or improper rigging,
test lift the unit before attempting to install it on the roof. To prevent injury, death, or
equipment damage when lifting, use ALL lifting points.
Test lift the unit to be sure that it is secure and the weight is balanced. Lift the unit
slowly, following safe lifting procedures.
FIGURE 14 - Rigging and Lifting a Cabinet
using four lifting points and spreader bars
6.0 Mechanical
6.1.1 Inlet Air Hood,
Option AS16
Application and
Components by Model
and Size
Form I-Y, P/N 273646R6, Page 20
6.1 Install Hood(s)
To avoid possible damage, it is recommended that the hood(s) be installed after the
system has been placed on the roof. Install the hood(s) before the blower is operated.
Do not install the hood(s) while the system is in operation. All screw ends should be to
the inside of the hood or cabinet.
Model YDSAN/A120,150180,210
Models YDHA, YDMA
Pkg P/N273283273373284598
Air Hood Components:
Top272476271116284449
Right Side272477271117284450
Left Side272478271118284451
Front Cover272479271119284454
Filter Support Assy272482268702284452
Sheet metal
Screws
Self-Drilling SM
Screws
Filters
060, 090, 120,
150
(4) 101607,
16x20x1
180, 210, 240300, 360
(16) 11813, 1/2”
(8) 37661, 1/2”
(4) 101610,
20x25x1
(8) 101609,
16x25x1
NOTE: Select screws
carefully. Use sheet
metal screws (slotted
head with straight
tip) when holes
in the cabinet are
provided. Use selfdrilling screws (head
is not slotted with
drill-type tip) when
cabinet holes are not
provided.
1a) Remove screw
in cabinet top.
Hood Top
(edge must go
under cabinet top)
1b) Slide the edge of the
‘Hood Top’ under the edge
of the ‘Cabinet Top’ and
reinsert the screw.
ref. Cabinet Top
FIGURE 14A - Installation Instructions and Dimensions - Inlet Air Hood Option AS16
opening and onto the
installed filter support.
head and standard point.
STEP 1 –
Attach top
STEP 4 – Install lters and attach the
front cover.
of outside
air hood.
Front Cover
Prepare
to attach
sides.
STEP 2 – Attach sides of outside air hood.
2a) Position the ‘Side Panels’ inside
Hood Top
(see Step 1)
Left
Side
2c) Repeat the procedure to install the ‘Right Side’.
STEP 3 – Attach lter support.
Right
Side
the ‘Hood Top’ and attach with a sheetmetal screw. Each side panel requires
(3) three screws; 1/2” with slotted head
and standard point.
2b) Attach the ‘Side Panels’ to the ‘Cabinet’
with self tapping screws. Use the 1/2” hex
head/no-slot screws with the drill point.
Each side panel requires (3) three screws.
3a) Position the filter support
assembly within the hood with
filter opening out as indicated.
3b) Attach filter support assembly
with sheetmetal screws. Each side
requires three screws; 1/2”with
slotted head and standard point
4b) Position the ‘Front Cover’ and attach with sheetmetal
screws. Each side requires (1) one screw; 1/2” with slotted
Length
Dimension
Dim “A”
(in / mm)
of Installed
Hood
Option AS16
Air Hood
Cabinet SizeDim “A”
4a) Slide filters
through the front
132.44 / 824
240.31 / 1024
349.39 / 1255
6.1.2 30% Inlet Air
Hood in Inlet Air
Conguration
Option AR7
FIGURE 14B - Installing
30% Inlet Air Hood
6.1.3 Exhaust Air
Hood - applies to
all units with Power
Exhaust (Option PE_)
or Energy Recovery
Wheel (Option EW__)
The 30% inlet air hood included in Option AR7 is assembled at the factory and shipped
with the unit for eld installation. Follow the instructions in FIGURE 14B, shown below.
Remove
Instructions:
1) At the center of the cabinet
top, remove the screw.
2) Slide the hood under
the cabinet top.
4) Re-insert the screw.
5) Attach both sides
of the hood with
sheetmetal screws.
screw.
30% Inlet Air Hood,
P/N ______
The exhaust air hood parts
are shipped separately
for installation at the site.
The exhaust location is
different depending on
whether or not the unit has
an energy recovery wheel;
the parts are the same.
See FIGURE 14C shown
or FIGURE 14D, page 22.
(Note complete list of hood
components listed in table
in section 6.1 on page 20)
FIGURE 14C - Installing Exhaust Hood with
Energy Recovery Wheel Option EW__.
Installing the Exhaust Hood on a Unit with
Option EW__ Energy Recovery Wheel
The exhaust fan opening is in the side
of the box under the outside air hood.
1) Attach the Hood Top - Above the
exhaust opening, remove the screws
holding the top of the box. Slide the
edge of the hood top under the
exhaust fan box top. Align the holes
and re-insert the screws.
2) Attach the Hood Sides - Position a
side panel to the inside of the hood
top, line up with the holes in the box,
and attach the side panel. Repeat to
attach the other side. On each side of
the hood top, insert screws to attach
the top to the hood sides.
Form I-Y, P/N 273646R6, Page 21
Remove screws.
6.0 Mechanical (cont’d)
FIGURE 14D Installing Exhaust
Hood for Power
Exhaust Option
PE__ without a
wheel
6.2 Duct
Connections
and Duct work
CAUTION: An
external duct system
static pressure not
within the limits on
the rating plate may
overload the motor.
Installing the Exhaust Hood on a Unit with
Option PE_ Power Exhaust
The exhaust opening is in the door panel.
1) Position the hood side to align with the
holes in the door panel. Attach with
sheetmetal screws.
2) Repeat to attach the other side.
3) Slide the top in place over the side panels.
Attach the top to the door and the side
panels.
Requirements and Suggestions for Installing Ducts
Duct connections are in the roof curb designed for the unit; see FIGURE 2 onpage 7,
FIGURE 3 on page 8 or FIGURE 4 on page 9 for duct connection sizes. Down ow roof
curbs are designed for installing duct work from the top before setting the unit on the
curb. Horizontal curbs have return air and supply air duct anges on the side under the
condenser section. See Figure 5, page 11 or FIGURE 10, page 14 in Paragraph 5.3.
NOTE: All installations require a discharge air temperature sensor. See Paragraph
7.5.3 for placement of the discharge air sensor in the duct work.
FIGURE 15 - When installing a
unit with a dual heat section,
avoid an immediate “T” in the
Control Access
discharge (supply) duct.
An immediate “T” in the discharge duct
may allow stratication of the air resulting
in hot air only moving down one segment
of the duct.
Avoid this supply duct conguration. If the
conguration is not avoidable, provide air
mixing devices in the duct work.
Hot
Air
Dual Gas Heat
Section
Cool
Air
• Type of Duct work - The type of duct installation to be
used depends in part on the construction of the roof
(whether wood joist, steel bar joist, steel truss, pre-
cast concrete) and the ceiling (whether hung, ush,
etc.).
• Duct work Material - Rectangular duct should be
constructed of not lighter than No. 26 U.S. gauge
galvanized steel or No. 24 B & S gauge aluminum.
• Duct work Structure - All duct sections 24 inches
(610mm) or wider, and over 48 inches (1219mm) in
length, should be cross broken on top and bottom and
should have standing seams or angle-iron braces.
Joints should be S and drive strip, or locked.
• Through Masonry Walls - No supply air duct should
come in contact with masonry walls. Insulate around
all air ducts through masonry walls with not less than
1/2” (13mm) of insulation. 1” (25mm) is recommended.
• Through Uncooled/Unheated Space - Insulate all
exposed supply air ducts passing through an uncooled
6.3 Cooling Section
Condensate
Drain
NOTE: For condensate
drain for high-efciency
gas heat section, see
Paragraph 9.2.
Form I-Y, P/N 273646R6, Page 22
The cooling section drain pan is below the coil access door in the cooling section. The
1-1/4” drain connection is through the side of the cabinet.
Follow the instructions below to install a trap in the drain. Do not reduce the drain
diameter. Pitch the drain line at least 1/2” (13mm) for every 10 feet (3M) of horizontal
run. Drain lines must not interfere with access panels or doors.
An obstruction in the drain or a poorly designed drain can cause the condensate pan to
over ow. Overow could result in damage to the unit and/or the building.
If the installation or local code requires, run drain into a waste water system.
or unheated space with at least 1/2” (13mm) of
insulation. 1” (25mm) is recommended.
• Duct Supports - Suspend all ducts securely from
buildings members. Do not support ducts solely by the
unit duct connections.
• Duct Sizing - Proper sizing of the supply air duct work
is necessary to ensure a satisfactory installation. The
recognized authority for such information is the Air
Conditioning Contractors Association, 2800 Shirlington
Road, Suite 300, Arlington, VA 22206 (www.acca.
org). A manual covering duct sizing in detail may be
purchased directly from them.
• Duct Connections - To minimize sound and vibration
transmission, use exible duct connections. Ducts
must be attached and sealed to provide airtight
connections.
• Return Air Duct/Grill Size - Make certain that return
air ducting or grill has a free area equal to the return
The design of the drain trap is important. Since the condensate drain pan is on the
blower inlet side, there is a negative pressure at the drain relative to the ambient. The
trap height must account for this static pressure difference. Maximum negative static
can be determined by reading the negative pressure at the blower inlet and adding .2”
iwc to allow for dirty lters.
If dimension "B" in FIGURE 16A shown below is not tall enough, the water seal will not
hold, and air will be drawn through the drain pipe into the unit. If the outlet leg of the
trap is too tall, water will back up into the drain pan. As condensate forms during normal
operation, the water level in the trap rises until there is a constant outow. FIGURE 16A
shown below illustrates the appropriate dimensions for trapping a negative pressure
system.
A = 1" (25mm) for each 1"
(25mm) of maximum
static pressure plus 1"
(25mm)
B = A + A/2
7.0 Electrical and
Wiring
7.2 Supply Wiring
7.2.1 Disconnect
Switch
FIGURE 16B -
Drain Trap with
Clean out
7.1 General
All electrical wiring and connections including electrical grounding MUST be made in
accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition). In addition, the installer should be aware of any local ordinances or electric company requirements that might apply.
Check the rating plate for the supply voltage and current requirements. Run a separate
line voltage supply directly from the main electrical panel, making connection at the
disconnect switch. See FIGURE 2 on page 7, FIGURE 3 on page 8 or FIGURE 4 on
page 9 for location of supply wiring entrance.
If the system has dual disconnect switches (Option BA7), two supply wires are required
(See FIGURE 17A, page 24 and FIGURE 17B, page 24).
The system must have a remote disconnect switch, a built-in disconnect switch, or
both.
If ordered with a built-in disconnect switch, the system will be factory equipped with
one or two built-in non-fusible, lockable disconnect switch(es). The built-in disconnect
switch(es) (Option BA6 or BA7) require copper wiring with amp capacity based on
75°C maximum temperature rating at the line side terminals.
If the system does not have a built-in disconnect switch, a eld-provided or optional
shipped-separate, wall-mounted disconnect switch is required. It is recommended
that there is at least four feet (1.2M) of service room between the switch and system
access panels. All external wiring must be within approved conduit and have a minimum temperature rise rating of 60°C. Run conduit so that it does not interfere with the system access panels. When providing or replacing fuses in a fusible disconnect,
use dual element time delay fuses and size according to the rating plate.
WARNING
To prevent injury or death due to electrocution or contact
with moving parts, lock an open disconnect switch.
WARNING
If the unit includes a gas furnace, always turn off the gas
when you turn off the power supply.
Form I-Y, P/N 273646R6, Page 23
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.