Please read this information thoroughly and become familiar with the capabilities and
use of your appliance before attempting to operate or maintain this unit. Keep this
literature where you have easy access to it in the future. If a problem occurs, check the
instructions and follow recommendations given. If these suggestions don’t eliminate
your problem, call your servicing contractor.
These instructions are primarily intended to assist qualifi ed individuals experienced in
the proper installation of this appliance. Some local codes require licensed installation/
service personnel for this type of equipment. Please read all instructions carefully before
starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
2
USER INFORMATION
IMPORTANT SAFETY INFORMATION .......................4
ABOUT THE HEAT PUMP ...........................................4
Safety markings are used frequently throughout this
manual to designate a degree or level of seriousness and
should not be ignored. WARNING indicates a potentially
hazardous situation that if not avoided, could result in
personal injury or death. CAUTION indicates a potentially
hazardous situation that if not avoided, may result in minor
or moderate injury or property damage.
ABOUT THE HEAT PUMP
Your heat pump is a unique, all weather comfort-control
appliance that will heat and cool your home year round
and provide energy saving comfort. It’s an unknown fact
that heat is always in the air, even when the outside
temperature is below freezing. The heat pump uses this
basic law of physics to provide energy saving heat during
the winter months. For example, If the outdoor temperature
is 47° F (8° C), your heat pump can deliver approximately
3.5 units of heat energy per each unit of electrical energy
used, as compared to a maximum of only 1 unit of heat
energy produced with conventional heating systems.
In colder temperatures, the heat pump performs like an air
conditioner run in reverse. Available heat energy outside
the home is absorbed by the refrigerant and exhausted
inside the home. This effi cient process means you only
pay for “moving” the heat from the outdoors to the indoor
area. You do not pay to generate the heat, as is the case
with more traditional furnace designs.
During summer, the heat pump reverses the fl ow of the
heat-absorbing refrigerant to become an energy-effi cient,
central air conditioner. Excess heat energy inside the
home is absorbed by the refrigerant and exhausted
outside the home.
OPERATING INSTRUCTIONS
Please refer to the thermostat manufacturer’s User manual
for detailed programming instructions.
Cooling Operation
1. Set the thermostat’s system mode to COOL or AUTO
and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired
temperature level. The outdoor fan, compressor, and
blower motor will all cycle on and off to maintain the
indoor temperature at the desired cooling level.
NOTE: If the temperature level is re-adjusted, or the
system mode is reset, the fan and compressor in the
outdoor unit may not start immediately. A protective
timer circuit holds the compressor and the outdoor
fan off for approximately three minutes following a
previous operation or the interruption of the main
electrical power.
Heating Operation
1. Set the thermostat’s system mode to HEAT or AUTO
and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired
temperature level. The compressor, outdoor fan, and
blower motor will cycle on and off to maintain the
indoor temperature at the desired heating level.
NOTE: If the temperature level is re-adjusted, or the
system mode is reset, the fan and compressor in the
outdoor unit may not start immediately. A protective
timer circuit holds the compressor and the outdoor
fan off for approximately three minutes following a
previous operation or the interruption of the main
electrical power.
Emergency Heat
Some thermostats may include a system mode called EM
HT or AUX HT, etc. This is a back-up heating mode that
should only be used if a problem is suspected. With the
mode set to EM HT, etc., the compressor and outdoor fan
will be locked off and supplemental heat (electric resistance
heating) will be used as a source of heat. Sustained use
of electric resistance heat in place of the heat pump will
result in an increase in electric utility costs.
Defrost Operation
During cold weather heating operation, the outdoor unit
Fan
Mode
Figure 1. Digital Thermostat
4
System
Mode
Temperature
Selector
will develop a coating of snow and ice on the heat transfer
coil. This is normal and the unit will defrost itself. This unit
features Demand Defrost that monitors ambient and coil
temperatures to regulate the defrost function accordingly.
USER INFORMATION
At the beginning of the defrost cycle, both the outdoor
condenser fan and compressor will turn off. After
approximately 30 seconds, the compressor will turn on
and begin to heat the outdoor coil causing the ice and
snow to melt.
NOTE: While the ice and snow is melting, some steam
may rise from the outdoor unit as the warm coil causes the
melting frost to evaporate. When defrost is completed, the
outdoor fan motor will start, and the compressor will turn
off again. In approximately 30 seconds the compressor
will start up again and continue normal operation.
Operating the Heat Pump for Automatic Cooling
and Heating
1. Set the thermostat system mode to AUTO and the
thermostat fan mode to AUTO. See Figure 1.
NOTE: Thermostat styles vary. Some models will
not include the AUTO mode and others will have the
AUTO in place of the HEAT and COOL. Others may
include all three. Refer to the instructions supplied
with your thermostat for specifi c instructions.
2. Set the thermostat's temperature selector to the
desired heating and cooling temperature level(s).
The outdoor unit and the indoor blower will then cycle
on and off in either the heating or cooling mode of
operation as required to automatically maintain the
indoor temperature within the desired limits.
Operating the Indoor Blower Continuously
The continuous indoor blower operation is typically used to
circulate the indoor air to equalize a temperature unbalance
due to a sun load, cooking, or fi replace operation.
Set the thermostat fan mode to ON (Figure 1). The indoor
blower starts immediately, and will run continually until
the fan mode is reset to AUTO.
The continuous indoor blower operation can be obtained
with the thermostat system mode set in any position,
including OFF.
Shutting the Heat Pump Off
Change the thermostat’s system mode to OFF and the fan
mode to AUTO. See Figure 1. NOTE: The system will not
operate, regardless of the temperature selector setting.
HEAT PUMP MAINTENANCE
CAUTION:
Shut off all electrical power to the unit before
performing any maintenance or service on the
system. Failure to comply may result in personal
injury or death.
Proper maintenance is most important to achieve the best
performance from the appliance and should be performed
by a qualifi ed service technician at least once a year.
Follow the maintenance schedule and the instructions
below for years of safe, trouble free operation.
Regular Cleaning
• Clean or replace the indoor air fi lter at the start of each
heating and cooling season, and when an accumulation
of dust and dirt is visible on the air fi lter.
• Remove any leaves and grass clippings from the coil
in the outdoor unit, being careful not to damage the
aluminum fi ns.
• Check for obstructions, such as twigs, sticks, etc.
TROUBLESHOOTING
If the unit fails to operate, check the following:
• The thermostat is properly set. See Cooling Operation
for air conditioning or Heating Operation for furnace or
air handler.
• The unit disconnect fuses are in good condition and
the electrical power to the unit is turned on.
WARRANTY INFORMATION
A warranty certifi cate with full details is included with the
heat pump. Carefully review these responsibilities with
your dealer or service company. The manufacturer will not
be responsible for any costs found necessary to correct
problems due to improper setup, improper installation,
adjustments, improper operating procedure on the part
of the user, etc. Some specifi c examples of service calls
which are not included in the limited warranty are:
• Correcting wiring problems in the electrical circuit
supplying the heat pump.
• Resetting circuit breakers or other switches.
• Adjusting or calibrating of thermostat.
5
INSTALLER INFORMATION
IMPORTANT SAFETY INFORMATION
Please read all instructions before servicing this equipment.
Pay attention to all safety warnings and any other special
notes highlighted in the manual. Safety markings are
used frequently throughout this manual to designate a
degree or level of seriousness and should not be ignored.
WARNING indicates a potentially hazardous situation that
if not avoided, could result in personal injury or death.
CAUTION indicates a potentially hazardous situation that
if not avoided, may result in minor or moderate injury or
property damage.
WARNING:
Unless noted otherwise in these instructions,
only factory authorized parts or accessory
kits may be used with this product. Improper
installation, service, adjustment, or maintenance
may cause explosion, fi re, electrical shock or
other hazardous conditions which may result in
personal injury or property damage
WARNING:
Shut off all electrical power to the unit before
performing any maintenance or service on the
system. Failure to comply may result in personal
injury or death.
WARNING:
Improper installation, service, adjustment, or
maintenance may cause explosion, fi re, electrical
shock or other hazardous conditions which may
result in personal injury or property damage.
Unless otherwise noted in these instructions,
only factory authorized kits or accessories may
be used with this product.
WARNING:
Q6SD units are fully charged with R-410A
refrigerant and ready for installation. When
a system is installed according to these
instructions, no refrigerant charging is required.
If repairs make it necessary for evacuation
and charging, it should only be attempted by
qualifi ed, trained personnel thoroughly familiar
with this equipment. Some local codes require
licensed installation service personnel to
service this type of equipment. Under no
circumstances should the homeowner attempt
to install and/or service this equipment. Failure
to comply with this warning could result in
equipment damage, personal injury, or death.
WARNING:
The safety information listed below must be
followed during the installation, service, and
operation of this unit. Unqualifi ed individuals
should not attempt to interpret these instructions
or install this equipment. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious per
injury or death
• The installer must comply with all local codes and
regulations which govern the installation of this type
of equipment. Local codes and regulations take
precedence over any recommendations contained in
these instructions. Consult local building codes and
the National Electrical Code (ANSI CI) for special
installation requirements.
• This equipment contains liquid and gaseous refrigerant
under high pressure. Installation or servicing should only
be performed by qualifi ed trained personnel thoroughly
familiar with this type equipment.
• All electrical wiring must be completed in accordance
with local, state and national codes and regulations
and with the National Electric Code (ANSI/NFPA 70)
or in Canada the Canadian Electric Code Part 1 CSA
C.22.1.
• Install this unit only in a location and position as specifi ed
on page 7. This unit is designed only for outdoor
installations and should be located with consideration
of minimizing the length of the supply and return ducts.
Consideration should also be given to the accessibility
of fuel, electric power, service access, noise, and shade.
• Follow all precautions in the literature, on tags, and
on labels provided with the equipment. Read and
thoroughly understand the instructions provided with
the equipment prior to performing the installation and
operational checkout of the equipment..
.
sonal
6
GENERAL INFORMATION
The Q6SD series heat pump is designed only for outdoor
rooftop or ground level installations. This unit has been
tested for capacity and effi ciency in accordance with
A.R.I. Standards and will provide many years of safe
and dependable comfort, providing it is properly installed
and maintained. Abuse, improper use, and/or improper
maintenance can shorten the life of the appliance and
create unsafe hazards.
Before you install this unit
The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected.
It is recommended that the area to be conditioned be
completely insulated and vapor sealed.
Check the electrical supply and verify the power supply
is adequate for unit operation. If there is any question
concerning the power supply, contact the local power
company.
All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage
prior to installing the equipment at the job site. Verify
coil fi ns are straight. If necessary, comb fi ns to remove
fl attened or bent fi ns. Claims for damage (apparent or
concealed) should be fi led immediately with the carrier.
Please consult your dealer for maintenance information
and availability of maintenance contracts. Please read
all instructions before installing the unit.
Locating the Heat Pump
• Survey the job site to determine the best location for
mounting the outdoor unit.
• Choose an appropriate location that minimizes the
length of the supply and return air ducts.
• Overhead obstructions, poorly ventilated areas, and
areas subject to accumulation of debris should be
avoided.
• Suffi cient clearance for unobstructed airfl ow through the
outdoor coil must be maintained in order to achieve rated
performance. See Figure 2 for minimum clearances to
obstructions.
Field Connections for Electrical Power Supply
• All wiring must comply with current provisions of the
National Electrical Code (ANSI/NFPA 70) and with
applicable local codes having jurisdiction.
• The minimum size of electrical conductors and circuit
protection must be in compliance with information listed
on the outdoor unit data label.
• Electrical power supplied to the unit must be adequate
for proper operation of the equipment. The system
must be wired and provided with circuit protection in
accordance with local building codes.
Air Ducts
This unit is designed only for use with a supply and return
duct. Air ducts must be installed in accordance with the
standards of the National Fire Protection Association
Standard for Installation of Air Conditioning Systems
36” For Coil Only
36"
36"
Clearances to Obstructions
0"
36"
TO BE
TOP OF UNIT
UNOBSTRUCTED
Minimum Required
Figure 2. Clearance Requirements
(NFPA 90A), Standard for Installation of Residence Type
Warm Air Heating and Air Conditioning Systems (NFPA
90B), and all applicable local codes. NFPA publications
are avaialable by writing to: National Fire Protection
Association, Batterymarch Park, Quincy, ME 02269 or
visit www.NFPA.org on the web.
• Design the duct work according to methods described
by the Air Conditioning Contractors of America (ACCA).
• The ducts must be properly sized not to exceed .2”
W.C. pressure drop at 400 scfm per nominal ton of
cooling capacity.
• Duct work should be attached directly to the unit fl anges
for horizontal applications.
• If roof curb is installed, the ducts must be attached to
the curb hangers, not the unit.
Unconditioned Spaces
All duct work passing through unconditioned space must
be properly insulated to minimize duct losses and prevent
condensation. Use insulation with an outer vapor barrier.
Refer to local codes for insulation material requirements.
Acoustical Duct Work
Certain installations may require the use of acoustical
lining inside the supply duct work.
• Acoustical insulation must be in accordance with the
current revision of the Sheet Metal and Air Conditioning
Contractors National Association (SMACNA)
application standard for duct liners.
• Duct lining must be UL classifi ed batts or blankets with
a fi re hazard classifi cation of FHC-25/50 or less.
• Fiber duct work may be used in place of internal duct
liners if the fi ber duct work is in accordance with the
current revision of the SMACNA construction standard
on fi brous glass ducts. Fibrous duct work and internal
acoustical lining must be NFPA Class 1 air ducts when
tested per UL Standard 181 for Class 1 ducts.
7
Air Filter Requirements
WARNING:
Never operate the unit without a fi lter in place.
Dust and lint could accumulate on internal parts,
resulting in loss of effi ciency, equipment damage
and possible fi re. Replace disposable fi lters with
the same type and size.
• Air fi lter(s) are not supplied and must be installed in
the return air system by the installer.Only three phase
units are equipped with an internal fi lter rack assembly.
• All return air must pass through the fi lters before
entering the unit. Recommended fi lter sizes are listed
in Table 1. NOTE: It is important that all fi lters be
kept clean and replaced frequently to ensure proper
operation of unit. Dirty or clogged fi lters will reduce
the effi ciency of the unit and result in unit shutdowns.
• Air fi lter pressure drop must not exceed 0.08 inches
WC.When replacing the air fi lters, a suitable air fi lter
must be installed upstream of the evaporator coil of
the return air system.
• Downflow Installations require an internal filter
accessory kit to be installed.
• Horizontal Installations require the air fi lter system be
installed in the return air ductwork.
Unit SizeInternal Filter Size
Q6SD-X36
Q6SD-X48 / X60
Table 1. Internal Filter Sizes
(2) 16” x 25” x 1”
or
(2) 16” x 25” x 2”
(2) 18” x 25” x 1”
or
(2) 18” x 25” x 2”
HEAT PUMP INSTALLATION
Packaging Removal
Remove the shipping carton and User’s Manual from the
equipment. Take care not to damage the tubing connections
when removing the carton. For rooftop installations, remove
and discard the two supports attached beneath the unit.
Rigging and Hoisting
WARNING:
To avoid the risk of property damage, personal
injury, or death, it is the rigger’s responsibility
to ensure that whatever means are used to hoist
the unit are safe and adequate:
• The lifting equipment must be adequate for the
load. Refer to Table 4 (page 15) for unit weights.
• The unit must be lifted from the holes in the
base rails using cables or chains.
• Spreader bars are required to protect the unit
and ensure even loading.
• Keep the unit in an upright position at all times.
The rigging must be located outside the units
center of gravity. Refer to Figure 7 (page 15)
for locating the center of gravity.
• All panels must be securely in place during
rigging and hoisting.
Minimum Clearance Requirements
Q6SD units are certifi ed as combination heating and
cooling equipment for outdoor installation only. Figure 2
(page 7) displays the minimum clearances to obstructions
for both downfl ow and horizontal discharge.
Units may be installed on wood fl ooring or on Class A, B,
or C roof covering material when used with bottom supply
and return air ducts as long as the following requirements
are met:
• If using horizontal supply and return air ducts, the
horizontal roof curb kit and return air kit must be
installed prior to unit installation. Horizontal roof curb
is required.
• If using bottom discharge with return air ducts a roof
curb must be installed prior to unit installation. See
Rigging and Hoisting section for setting of the unit.
2”
Figure 3. Ground Level Installation
8
Ground Level
Ground level installations must be located according to
local building codes or ordinances and these requirements:
• Clearances must be in accordance with those shown
in Figure 2. Also consider clearances for access to the
internal fi lter.
• A suitable mounting pad (Figure 3) must be provided
and separate from the building foundation. The pad
must be level to ensure proper condensate disposal
and strong enough to support the unit’s weight. The
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.