Reznor Q6SD User Manual

INSTALLATION
INSTRUCTIONS
WARNING: BEFORE INSTALLING READ ALL OF THE MANUFACTURERS
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Step 1:
Check for the correct number of parts. See list below:
1 ea. CO2 Sensor 1 ea. CO2 Sensor Base 1 ea. 0-10 VDC Potentiometer Signal Converter
(Honeywell Q769C) 1 ea. 4” Violet Wire 1 ea. 4” Red Wire
Step 2:
Mount CO2 Sensor base on wall. Route wires (raw end) through square hole in base and connect per wiring diagrams.
INSTALLATION OF CO2 SENSOR WITH HONEYWELL
M7415A MOTOR & W7459A LOGIC MODULE
547848
GR4GM 072, P6SD, Q6SD, R6GD 024-060 UNITS
FORM# 602A-0808 (602A-0298)
Step 3:
Attach CO2 Sensor.
Step 4:
If the unit has a W7459 Economizer Control, install the Honeywell Q769C potentiometer signal converter.
Step 5:
Make sure to secure the Q769C device using the included wire ties. Disconnect the (P-P1) jumper from the economizer control located on the actuator and connect the Q769C per wiring Diagram # 01CO201.
Step 6:
For W7459 Economizer Controller applications power the CO2 device via a properly protected, field supplied, non-grounded transformer of the appropriate primary and secondary voltage per the attached Diagram # 01CO201. Program the CO2 sensor per the specifications, provided with the accessory, to suit the application.
Q769C BOX
CO2 SENSOR
CO2 SENSOR BASE
SUPERSEDES 01-30-04 AUGUST 26, 2008
NEICO202
W7459 - Economizer Logic ModuleP# - Plug ConnectorS# - Socket ConnectorTransformer must not be grounded
Note: The socket and plug numbers change per unit.
Date: January 30, 2004
Su per cedes: 06-03-03
Dia gram# 01CO201