REMKO RVS 130 DC, RVS 80 DC, RVS 180 DC, RVS 50 DC Operating And Installation Instructions

Page 1
Operating and installation instructions
REMKO RVS series
Chiller
RVS 50 DC, RVS 80 DC, RVS 130 DC, RVS 180 DC
Edition EN - N12 Read the instructions prior to performing any task!
Page 2
Page 3
Content
Safety notes
Environmental protection and recycling
Guarantee
Transportation and packaging
Unit description
Cooling cycle
Service limits
Operation
Installation instructions for qualified personnel
Installation
Care and maintenance
Shutdown
Electrical wiring
4
4
4
5
5
6
7
8-18
19
20-25
26
26
27-28
R410A
Refrigerant
Electrical drawings
Leak testing
Before commissioning
Commissioning
Overhaul and repair
Troubleshooting and customer service
Resistance table
Dimensions
Technical data
Carefully read this original operating manual prior to commissioning/ using the units! This operating manual is a translation of the German original. This manual is an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
Subject to modifications. No liability accepted for errors or misprints!
29-32
33
33-34
35
36
37-40
40
41
42
3
Page 4
REMKO series RVS
Safety notes
Carefully read the operating manual before placing the unit in service for the first time. It contains useful tips and notes as well as hazard warnings to prevent injury to persons or material damage the directions in this manual can endanger persons, the environment and the equipment itself and will void any claims for liability.
■
Keep this manual and the refrigerant data sheet near the unit.
■ Only qualified personnel may
set up and install the units and components.
■ The set-up, connection, and
operation of the unit and its components must take place in accordance with the operating conditions stipulated in this manual and comply with all applicable local regulations.
■ Stationary units must be
permanently installed for operation.
■ Modification of the units
and components supplied by REMKO is not permitted and can cause malfunctions.
■ Units and components may
not be operated in areas where there is an increased risk of damage. Observe the minimum clearances.
■ The electrical power
supply is to be adapted to the requirements of the units.
■ The operational safety of
the units and components is only assured if they are fully assembled and used as intended. Safety devices may not be modified or bypassed.
. Failure to follow
■ Do not operate units or
components if there are obvious defects or signs of damage.
■ All housing parts and unit
openings, e.g. air inlets and outlets, must be free from foreign objects, liquids, or gases.
■ The units and components must
be kept at an adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
■ Contact with some parts of
the unit or components can result in burns or other injuries.
■ Installation, repair and
maintenance work may only be carried out by authorised specialists. Visual inspections and cleaning can be performed by the operator as long as the unit is disconnected from the power.
■ Take appropriate precautions
when performing installation, repair or maintenance work or cleaning the unit to make sure the unit does not pose a danger to persons.
■ The units and components
should not be exposed to any mechanical load or extreme levels of humidity.
Environmental protection and recycling
Disposal of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved collection points.
Disposing of the units and their components
Only recyclable materials are used in the manufacture of the units and components. Help protect the environment by ensuring that the units or components (for example batteries) are not disposed of in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. using authorised disposal and recycling specialists or council collection points.
Guarantee
In order to make warranty claims, it is essential that the ordering party or their representative complete and return the "certificate of warranty" and “commissioning report” to REMKO GmbH & Co. KG at the time when the equipment was purchased and commissioned. The warranty conditions are listed in the "General terms and conditions". Furthermore, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.
4
Page 5
Transportation and packaging
The units are shipped in sturdy transport packaging. Immediately check the units on delivery and make a note of any damage or missing parts on the delivery note. Inform the forwarding agent and contractual partner.
Claims under guarantee made at a later date will not be accepted.
Unit description
In cooling mode, the unit (an air-cooled chiller) takes heat out of the operating medium to be cooled, water or a mixture of water and glycol, within a closed medium cycle in the evaporator (plate heat exchanger) and passes it on to the closed cooling cycle. As a consequence of the heat exchange, the medium cools and the refrigerant in the cooling cycle vaporises under low pressure. The gaseous refrigerant enters an electric compressor (scroll construction) which increases the pressure and the temperature of the refrigerant. The gaseous refrigerant is led into a finned condenser, which, as a consequence of the heat exchange, condenses the refrigerant under high pressure to a liquid. The air emerging at the condenser heats the environment. The liquid refrigerant is fed by means of a variable injector valve back to the evaporator where the circuit begins again. A return temperature dependent, seamless controller, which ensures the unit's operation and all of the safety functions, is used
to control the cooling capacity. A potential-free contact provides for remote enabling. The unit is designed for outdoor installation. Under certain circumstances, it can also be used in indoor areas. The unit cooling cycle comprises an evaporator, compressor, electronic injection valve, condenser, condenser fan, pressure transducer, high and low pressure switches and a 4-way changeover valve for heating mode. The medium cycle comprises a tube bundle heat exchanger, a circulation pump and a flow switch.
Vibration dampers, cabled remote controls and glycol concentrate are available as accessories.
Intended use
Depending on the model and the unit, the units are only intended to be used as a chiller for the cooling of the operating medium water or a water-glycol mixture within a closed medium cycle. Any different or additional use is a non-intended use. The manufacturer/supplier assumes no liability for damages arising from non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
Proper handling
Insofar as intervention is required in the refrigerant circuit of the unit during maintenance or repair work, all work shall be carried out exclusively by persons and companies who have a certificate in accordance with the prerequisites of EC ordinance no. 517/2014 of the European Council.
Applicability
Within the course of continuous further development of all products, REMKO GmbH & Co. KG reserve the right to carry out technical changes to the units as well as updates to the documentation. The documentation on the unit (name plates, wiring diagrams, etc.) shall be considered as part of the overall documentation.
Ecological design directive
The regulation (EU) 2016/2281 (LOT 21) approved by the European Commission is the enforcement action for the ecological design directive 2009/125/EC, whose principal objective is to reduce the primary energy demand in the European Union by 2030 and to reduce the emissions of hazardous substances associated with this.
The chillers from REMKO comply with the applicable energy requirements from the ecological design directive. The product datasheet required per the ordinance, to verify ERP conformity is attached as a separate document and is also available for download from www.remko.de.
5
Page 6
REMKO series RVS
Cooling cycle
6
Legend:
1 Compressor 2 Schrader valve 3 High-pressure switch 4 4-way changeover valve 5 Low-pressure switch
3
4
5
2
2
7
6 Tube bundle heat exchanger 7 Filter dryer 8 Electronic expansion valve 9 Fin condenser
2
2
9
1
8
7
6
Page 7
Service limits
Wassereintrittstemperatur
Wassereintrittstemperatur
RVS DC units are chillers with heat pump function. The primary purpose of the units here is cooling operation, whilst the heating function represents an additional function by means of reverse circulation.
For trouble-free unit operation and compliance with the legal warranty conditions, it is essential that the unit is be used within its respective operational limits. These are shown in the following diagram. Further information on this can likewise be found in the technical data.
Service limits
30
25
20
15
10
5
0
-5
-20 -15 -10 -5 0 10 15 20 25 30 35
-25
Umgebungstemperatur
A
B
5
Ambient temperature
40 45
55
50
60
55
50
45
40
35
30
Water inlet temperature Water inlet temperature
25
-20 -15 -10 -5 0 10 15 20 25 30 35
-25
Legend
A Standard version B Low-temperature version
A
A
5
Umgebungstemperatur
Ambient temperature
40 45
55
50
7
Page 8
REMKO series RVS
Operation
Display/control unit
The controller of the chiller is to be operated with the touch pad, which is located right on the unit in a housing protected from splashed water. To open the housing, press the "PRESS" button on the right-hand side of the housing. After operating the controller, close the housing again in order to prevent water ingress. If there is no activity on the controller for longer than 60 seconds, the display switches to stand-by mode and no values are displayed. The display can be activated by touching any part of the display.
Button symbol Designation Description
Mode key
On/off key
Up arrow key Values can be adjusted and pages scrolled through with the up arrow key
Operating modes can be changed, temperature settings changed and parameters set by pressing the mode key
The system can be switched on and off with the On/Off key. In addition, it is also possible to cancel the current operation and return to the previous operating stage
Down arrow key Values can be adjusted and pages scrolled through with the down arrow key
Clock key The clock key is used to set up and execute timer functions
8
Page 9
Button symbol Designation Description
Cooling mode Is displayed when the system is in cooling mode
Heating mode Is displayed when the system is in heating mode
Defrosting operation
Compressor Appears when the compressor is running
Circulation pump Appears when the circulation pump is running
Fan Appears when the fan is running
Timer Is displayed with the activation of a timer
Water outlet Appears when the digital display shows the water outlet temperature
Water inlet Appears when the digital display shows the water inlet temperature
Malfunction Is displayed if there is a fault present
Temperature (°C) Appears when the digital display shows the a temperature in °C
Appears during the defrosting procedure (only in heating mode)
Temperature (°F) Appears when the digital display shows the a temperature in °F
Setting Is displayed if the value is set
Seconds Appears when the digital display shows seconds
Minutes Appears when the digital display shows minutes
Hours Appears when the digital display shows hours
Pressure Appears when the digital display shows a pressure
Medium flow rate Appears when the digital display shows a medium flow rate
9
Page 10
REMKO series RVS
Switching the unit on
The unit is switched on by pressing the key for 1 second.
A further 1 second press of the without being used, the display darkens.
key in the start screen will switch the unit back off again. After one minute
Setting the operating mode
Before setting the operating mode, this must be implemented by installing/removing a wire jumper on the corresponding terminals (see chapter Electrical connection).
To set the operating mode, press the key on the start screen for 1 second. The mode can thus be set to either
cooling
or heating .
Setting the setpoint (return temperature)
To set the setpoint for the return temperature, briefly press the or key in the start screen. The display
flashes. Now the setpoint can be changed in steps of 0.5 with the same keys. Once the desired temperature is set,
confirm the input with the
If there is no activity for 20 seconds during the set-up process, the system automatically returns to the start screen
without changing any of the settings.
In order to cancel the adjustment process, press the
any of the values.
10
key. The value set will be saved and you are returned to the start screen.
key to return to the start screen without changing
Page 11
Setting the time
To set the system time, briefly press the and keys simultaneously.
The
to flash. The hours can now be adjusted with the and keys.
Confirm the hours with the
The minutes can now be adjusted with the
Confirm again by briefly pressing the
If there is no activity for 20 seconds during the set-up process, the system automatically returns to the start screen
without changing any of the settings.
In order to cancel the adjustment process, press the
of the values.
key appears on the right-hand side of the screen. Press this briefly and the display for the hours starts
key and the minute display starts to flash.
and keys.
key. The settings are saved and you are returned to the start screen.
key to return to the start screen without changing any
11
Page 12
REMKO series RVS
Saving timer programs
To save a timer program, briefly press the and keys simultaneously.
The
Press this for 2 seconds.
Now you can select a switch-on or switch-off point with the
ON 1 = Switch-on point for the first timer program
OFF 1 = Switch-off point for the first timer program
ON 2 = Switch-on point for the second timer program
OFF 2 = Switch-off point for the second timer program
Use the
The hours can now be adjusted with the
Confirm the hours with the
with the and keys.
Confirm again by briefly pressing the
To exit the timer menu, press the
In order to cancel the adjustment process press the
of the values.
key appears on the right-hand side of the screen.
and keys.
key to confirm your selection. The display for the hours starts to flash.
and keys.
key and the minute display starts to flash. The minutes can now be adjusted
key and the settings are saved.
key briefly
key to return to the start screen without changing any
12
Page 13
If the system is deactivated and the time set for a switch-on point (ON1, ON2) is reached, the system activates autonomously. It then carries out the operation with the settings before deactivating again.
If the system is activated and the time set for a switch-off point (OFF1, OFF2) is reached, the system de-activates autonomously.
13
Page 14
REMKO series RVS
Deleting timer programs
To delete a timer program, briefly press the and keys simultaneously.
The
Now you can select a switch-on or switch-off point that you wish to delete with the
ON 1 = Switch-on point for the first timer program
OFF 1 = Switch-off point for the first timer program
ON 2 = Switch-on point for the second timer program
OFF 2 = Switch-off point for the second timer program
Use the
The switch-on or switch-off point can now be deleted with a brief press of the
If the switch-on or switch-off point has been successfully deleted, the display shows - - : - - .
To return to the start screen, press the
key appears on the right-hand side of the screen. Press this for 2 seconds.
and keys.
key to confirm your selection. The display for the hours starts to flash.
key.
key briefly.
14
Page 15
Malfunction indication
If a fault arises on the unit, the controller reports this automatically. The screen shifts to the fault display and displays a fault code. The meanings of the various codes are listed in the Faults and fault causes chapter.
If multiple faults arise at the same time it is possible to switch between the fault displays with the keys.
You can return to the start screen by briefly pressing the If there is no activity for 10 seconds, the display automatically returns to the fault display.
If the fault is rectified, the controller will detect this and the fault display will disappear automatically. If a major fault arises 3 times within a 30 minute period, the fault message must be manually reset after the cause of the fault has been successfully removed.
A listing and definition of the major faults can be found in the Faults and fault causes chapter.
Once the cause of the fault has been removed the fault message must be manually reset by pressing the
for 2 seconds.
key.
and
key
15
Page 16
REMKO series RVS
Calling up operating parameters
To display the operating parameters, briefly press the key on the start screen. Now the sensor values and other operating conditions can be called up here. The operating parameters. The meaning of the individual parameters can be found in the list below.
and keys can be used to navigate between the different
ID Designation
U01 Water inlet temperature
U02 Water outlet temperature
U03 Suction gas temperature
U04 Heat gas temperature
U05 Ambient temperature
U06 Finned heat exchanger temp.
U07 Low pressure
U08 High pressure
U09 Throttle setting
Defrosting operation
ID Designation
U10 Current compressor frequency
U11 Required compressor frequency
U12 Suction gas overheating
U13 Heat gas overheating
U14 Current fan speed
U15 Not used
U16 Not used
U17 Driver status
In heating mode, condensate forms on the finned heat exchanger and this can freeze under certain conditions
and thus have an insulating effect. Because this can significantly impair the operation of the unit, the system
can switch to defrosting mode if required. The symbol for defrosting
the defrosting process. Once the defrosting process has ended, the symbol disappears and the system carries
on with normal operation.
16
is shown on the system display during
Page 17
Anti-freeze protection
The anti-freeze protection is based primarily on 3 parameters:
ID Designation Factory setting
C01 Anti-freeze protection temperature 4 °C
C02 Anti-freeze protection low pressure 0 bar
C03 Anti-freeze protection temperature difference 2 °C
Cooling mode: If the water outlet temperature (U02) is less than or equal to the anti-freeze protection temperature (C01) or if the suction pressure (U07) is less than the anti-freeze protection low pressure (C02) for 10 seconds, the system switches to anti-freeze protection.
Heating mode: If the water outlet temperature (U02) is less than the water inlet temperature (U01) -2°C or less than the anti­freeze protection temperature (C01), the system switches to anti-freeze protection.
In both cases, the system only carries on with normal operation once the water outlet temperature rises by the anti-freeze protection temperature difference or the suction pressure is higher than the anti-freeze protection low pressure parameter.
The anti-freeze protection temperature is set to 4°C at the factory.
If glycol is used, it is possible to change the parameters to operate at lower temperatures, depending on the glycol concentration. The table below can be helpful for this.
Adjustment is only possible after password input. For this purpose, please contact REMKO.
Glycol
content
Vol. % °C K
0 0 1 1 1 1
20 -9 0.960 0.995 1.040 1.19
35 -21 0.950 0.990 1.090 1.35
40 -26 0.925 0.985 1.105 1.51
Anti-freeze
protection
+-2°C
Correction factors when using a mixture of glycol* and
water
Cooling
capacity
L
Power
consumption
K
PE
Medium flow
rate
K
V
Pressure
loss
K
D
* We recommend using an ethylene glycol mixture. Observe the safety and product data sheets
for the type of glycol used.
! CAUTION
Use the required type and mix ratio appropriate for the application area to ensure the freezing point.
! CAUTION
The product and safety data sheets of the glycol type used must be observed during use and disposal.
17
Page 18
REMKO series RVS
Setting the anti-freeze protection parameters
Press the key on the start screen briefly to access the operating parameters level.
Then press the
will be required for this. Now enter the password with the
Press the
Select the C01 parameter with the
The value can now be adapted to the glycol concentration with the help of the
A short press of the
key in the operating parameters level for 2 seconds to access the next level down. A password
and keys and confirm with the key.
key again on the next and next again windows.
and keys and confirm the selection with the key.
and keys.
key saves the setting.
18
Page 19
Installation Instructions for qualified personnel
■
Important notes prior
to installation
■
Observe the manuals for the indoor units and chillers when installing the entire system.
■
The indoor units and chillers work independently. A connecting line between the two is not necessary.
■
Select an installation location which allows air to flow freely through the inlet and outlet. See section "Minimum clearances".
■
Do not install the unit in the immediate vicinity of devices which generate intensive thermal radiation. Installation in the vicinity of thermal radiation reduces the unit output.
■
Lift the unit only at intended lifting points. Never apply loads to the medium piping.
■
The medium connection lines, valves and connections must be insulated impervious to vapour diffusion.
■
Seal off open lines to prevent dirt getting in.
Comply with all regulations
governing structural and building requirements and conditions with regard to the installation site.
■
In the selection of the installation site, pay attention to the site itself and to any possible acoustic reflection from surrounding units.
■
To avoid the transmission of vibrations to the installation site, the units must be installed on vibration absorbing material or on vibration decoupled foundations. In doing so, make sure that the lines are also vibration decoupled.
■
If the installation site must fulfil special sound emission requirements, these must be realised on-site when appropriate adjustments can be made. In these cases, please consult an appropriate acoustics expert.
■
The units are tested in the factory and require only electrical and hydraulic installation by a suitable specialist.
■
The unit must be kept upright when transporting to a higher elevation:
■
Check the contents of the packaging for completeness and check the unit for visible transport damage. Report any damage immediately to your contractual partner and the shipping company.
■
If necessary, also insulate the condensate drainage line (only units with HP-function). In dual systems with cooling and heating modes, the requirements of the current Energy-Savings-Ordinance (EnEV) are to be complied with.
Transport
■
Transport the unit in its original packaging as close as possible to the installation location. You avoid transport damage by doing so.
■
The units may only be moved as installed (upright) using appropriate transport gear
(Figure 1).
Secure against tipping!
■
Make all electrical connections in accordance with applicable DIN and VDE standards.
■
Always ensure the electrical cables are properly connected to the terminals. Otherwise there is a risk of fire.
1 Standing transport
19
Page 20
REMKO series RVS
Installation materials
The unit is fastened on vibration dampers (accessories) to the floor by means of bolts. The carrying capacity of the bracket and the wall must be taken into account when fastening to the wall.
Definition of the Danger Area
Access to the unit is only permitted for authorised and trained persons. If unauthorised persons can approach the danger areas, these areas must be identified with corresponding signs, barriers, etc.
■
The external danger area surrounds the unit up to a distance of 2 m, measured in all directions from the unit housing.
■
The external danger area on­site can differ as a result of the setup. The specialist company performing the installation work bears the responsibility for this.
■
The internal danger area is located inside the machine and can only be reached with the use of an appropriate tool. Access is prohibited for unauthorised persons!
Installation
NOTE
Installation should only be performed by authorised specialists.
Disassembly of the transport pallets
The units are supplied with transport pallets for the purpose of transportation. Remove these before installation.
Transport packaging
Transport pallet
Unit installation
1. Install the vibration dampers (accessories) under the unit (accessories).
4. Ensure that structure-borne sound is not transferred to parts of the building.
5. Connect the medium piping.
6. Connect the unit electrically.
NOTE
The electrical connection of the unit is to be established by suitable specialist personnel and in compliance with all electrical safety regulations. Compliance with VDE regulations is essential.
NOTE
The dimensioning of the supply line and the selection of the customer-side unit safeguard(s) is the responsibility of the specialist company carrying out the work. The unit manufacturer provides no information regarding the dimensioning of pipework or the selection of fuses/breakers as these are subject to local conditions. All of the data required for the selection can be found in the technical data for the unit.
NOTE
20
2. Attach the unit to the building where structurally permitted. Refer to the Selecting the installation location chapter for this.
3. When installing the unit, ensure that the minimum clearances described hereafter are complied with. Any infringement of these stipulated clearances can result in a functional impairment of the unit operation.
The selection of the RCD breaker is the responsibility of the specialist company carrying out the work. Based on theprovisions per VDE 0160, E VDE 0100 Part 530 as well as the guidelines of VdS 3501 and the safety regulations from BGI 608, the use of an AC/ DC-sensitive, type-B RCD is recommended for ensuring standards-compliant personnel and fire protection.
Page 21
Selecting the installation location
The unit is designed for horizontal installation on a base in outdoor areas. The installation site must be level, flat and firm. The unit should also be secured to prevent it from tipping over.
For external installation, please observe the following instructions to protect the unit from the influence of the weather.
It is also possible to install the unit in the interior of the building. However, in this case the circulation of the required air flow volume (see technical data) must be assured. Any change to the air flow volume can result in faults or damage to the unit.
Rain
Sun
The finned condenser gives off heat in cooling mode.
Exposure to sunlight further increases the temperature of the fins and reduces the heat released by the finned heat exchanger.
The unit should, whenever possible, be installed on the north side of the building.
If necessary, take measures to provide sufficient shade (responsibility of customer). This could be a small roof.
However, the discharging warm air flow must not be affected by the measures.
NOTE
Cooling capacity changes as a consequence of ambient conditions influenced by rain, sun, wind, and snow, for example.
2 Minimum clearance to snow
Snow
20 cm
The unit should be at least 10 cm off the ground when mounted on the roof or ground.
Snow
The unit should be wall-mounted in areas of heavy snowfall.
Installation should be at least 20 cm above the expected level of snow to prevent snow from entering the outdoor unit
(Figure 2).
Sun
The finned condenser gives off heat in cooling mode.
Wind
3 Windbreak
If the unit is being installed inwindy areas, ensure that the warm outlet air is discharged in the prevailing wind direction. If this is not possible, it may be necessary to install a windbreak on-site (Figure 3).
Ensure that the windbreak does
Wind
not adversely affect the air intake to the unit.
4 Installation inside buildings (cooling mode)
Warm air
Additional fan
Light well
Warm air
Cold fresh air
Light well
Exposure to sunlight further increases the temperature of the fins and reduces the heat released by the finned heat exchanger.
Chiller
21
Page 22
REMKO series RVS
Connection of the medium piping
■
The connection of the lines on-site takes place on the front side of the unit (operating side).
■
For the purpose of servicing, connections must be equipped with shut-off valves and flow volumes adjusted using valves for hydronic balancing.
■
Additional automatic bleed valves are to be provided in the supply and return at the installation's highest point.
■
The medium piping may not exert any structural load on the unit.
■
The line connections may not generate any thermal or mechanical stresses on the unit (cool lines or hold in place with a second tool if required).
■
If the unit is at first to be operated with only a part of the entire system, the medium flow for the missing system components is to be simulated using valves for hydronic balancing.
■
The pipe sizing is to be designed such that the stipulated minimum flow volume is achieved.
Observe minimum flow volume of the chiller. The lines are to be insulated against vapour diffusion and, if necessary, the current German energy-saving ordinance (EnEV) must be observed. UV resistance must be realised outdoors
Minimum/maximum flow volume
The cold water generator's circulation pump generates a constant medium flow. The result is a loss of pressure in the system and in the cold water generator. The differential pressure or flow switch in the chiller measures the pressure loss over the evaporator or the flow of the medium and switches the unit off if the flow rate drops below the minimum medium volume. The medium flow rate limit may likewise not be exceeded (maximum flow volume). A 3-way valve with bypass and a hydraulic compensator to establish a primary and secondary circuit or a volume dependent bypass are necessary to ensure a constant flow volume.
Pressure and temperature displays
The pressure and temperature displays to be installed on-site at the intake and outlet serve to set the medium flow rate.
The display should be able to be shut off. Temperature sensors are located in the chiller's medium inlet and outlet. Sensor values can be queried via the controller.
Valves for hydronic balancing
The calculated individual pressure losses in the pipeline network layout for each individual unit are adjusted to the entire system with valves for hydronic balancing to be provided on-site. The nominal flow rates for the medium adjust to the necessary values as a consequence of the pressure loss.
NOTE
To adjust the circulation pump, we recommend that a main hydronic balancing valve is provided in the vicinity of the unit.
Fill and drain connection
A connection should be provided in an area safe from frost for the draining of pipe lines (especially if water is used as a medium). Applicable local disposal ordinances must be observed if glycol is used.
Medium piping
Medium piping can be made of copper, steel or plastic. To minimise pressure losses, only streamlined fittings should be used. When designing the layout, the large flow volumes in cold water systems, high pressure losses in connection with water­glycol mixtures and the cold water generator's minimum flow volume must be taken into account.
22
Ensuring the minimum flow volume
Incorrect
installation
2-way valve 3-way valve
Correct
installation
Page 23
Diaphragm expansion vessel (MAG)
Air bleeding valves
External medium storage tank
To avoid pressure fluctuations during standstill because of temperature changes, diaphragm expansion vessels filled with nitrogen (moisture neutral) must be integrated in the system.
The unit's standard equipment includes one diaphragm expansion vessel. The preliminary pressure must be set on the system; an increase in volume or, in the event of the realisation of a cooling-heating system, the installation of another diaphragm expansion vessel may be necessary.
Compensators
Compensators are used to connect lines to the unit to prevent vibration in the chiller from transmitting to other system components.
Compensators
Shut-off valve Compensator
Static fasten­ing
Unit connection
Safety valve
Safety valves limit excess operating pressure due to excess warming or overfilling of the operating medium. The valve outlet requires unobstructed draining into a drain line. Applicable local disposal ordinances must be observed if glycol is used. The standard scope of delivery for the unit includes a safety valve; an additional valve may be necessary at a suitable point.
The unit has manual air bleeding valves. The unit can be bled here after the system has been filled. Automatic bleeding valves must also be installed at the highest point in the collector line.
CAUTION
!
Glycol-tolerant air bleeding valves are necessary when using media that contain glycol.
Shut-off valves
As a rule, in cold water systems, shut-off valves with full admission should be used. For the purpose of servicing, medium inlet and medium outlet must be equipped with shut-off valves (if necessary safety valves).
Dirt trap
A rinsable dirt trap must be installed upstream from the unit intake. The mesh size should not be less than 10 mesh/cm². Shut­off valves should be installed upstream and downstream from the dirt trap.
CAUTION
!
Improperly installed or missing dirt traps can cause fouling of the plate heat exchanger.
If, for example, the required capacity of the cold water consumer is significantly less than the cooling capacity generated by the chiller, an increase in the medium content is recommended. As an example, the medium piping can be oversized or an additional storage tank installed to increase compressor operating time. A storage tank should, as a rule, be provided if the minimum medium volume is not reached.
Anti-freeze protection (accessories)
As a medium for a cold water system, a water-glycol mixture is used as a rule. Depending on the use to which the glycol type and quantity is put, the viscosity changes, the loss in pressure increases and the unit's cooling or heating capacity reduces. All system components must be approved for use with glycol. As a rule, the addition to the water of ethylene glycol, in a proportion of 34%, with inhibitors for corrosion protection is recommended.
CAUTION
!
During use and disposal, product and safety data sheets for the glycol type being used as well as applicable local ordinances (e.g. Water Resources Act) must be observed.
CAUTION
!
Use the required type and mix ratio appropriate for the application area to ensure the freezing point.
23
Page 24
+
+
+
+
REMKO series RVS
Condensate drainage connection and secure discharge
Condensate drainage connection
If the temperature falls below the dew point, condensation will form on the finned condenser during heating mode.
A condensate tray should be installed on the underside of the unit to drain any condensate.
■
The condensate drainage line should have an incline of min. 2%. This is the responsibility of the customer. If necessary, fit vapour­diffusion-proof insulation.
■
When operating the unit at outdoor temperatures below 4 °C, care must be taken that the condensate drainage line is anti-freeze protected. The lower part of the housing and condensate tray is also to be kept frost free in order to ensure permanent draining of the condensate. If necessary, fit a pipe heater.
Condensate drain
+
+
Condensate tray
Condensate drainage
NOTE
Cumulative ice formation in the lower part of the finned heated exchanger can develop under certain weather conditions. To prevent this ice formation, we recommend keeping the heat exchanger frost free on both sides using a heating band for example.
5 Minimum clearances
RVS 50 - 180 DC
1000mm
Minimum clearances
Fig. 5 shows the minimum clearances for trouble-free operation of the units. The protective zones serve to provide unhindered air intake and outlet, as well as providing sufficient room for performing maintenance and repairs and preventing the unit from being damaged.
NOTE
Failure to comply with the minimum clearances is considered a breach of intended use. The manufacturer assumes no liability for damage or malfunctions arising from this.
500mm
■
Following installation, check that the condensate drain is unobstructed and ensure that the line is permanently leak tight.
Safe drainage in the event of leakages
Local regulations or environmental laws, for example the German Water Resource Act (WHG), can require suitable precautions to protect against uncontrolled drainage in case of leakage to provide for safe disposal of escaping air conditioning fluid or hazardous media.
500mm
1500mm
24
Page 25
Necessary system components
6
System components
3
1
Legend:
1 Expansion pipe coupling 2 Safety valve 3 Manometer
1
1
4 Shut-off valve 5 Dirt trap 6 Diaphragm expansion vessel
2
4
3
4
8
3
5
4
7 Fill and drain device 8 Valve for hydronic balancing
7
NOTE
The system layout shown above shows the recommended pipework components to be established on­site. The detailed planning, layout and design of all components as well as the complete hydraulic system is the responsibility of the specialist company carrying out the work.
Medium storage tank
The units have integrated high-efficiency components, which adapt the cooling capacity of the unit to the respective load situation in accordance with the internal controller logic. This prevents cycled operation of the compressor, which can be caused through too little water in the complete system.
As a result, the use of a medium storage tank is not absolutely essential with RVS DC type units. However, the use of an external medium storage tank serves to increase the total water volume and thus contributes to an increase in the quality of regulation. For this reason, a system layout with an external medium storage tank is advisable as a matter of principle.
25
Page 26
REMKO series RVS
Care and maintenance Shutdown
Regular care and observation of some basic points will ensure trouble-free operation and a long service life.
CAUTION
!
Prior to performing any work, ensure that the equipment is isolated from the power supply and secured to prevent accidental switch-on!
Care
■
Ensure the unit is protected against dirt, mould and other deposits.
■
Clean the unit using a damp cloth. Do not use a jet of water.
■
Do not use any caustic, abrasive or solvent-based cleaning products.
■
Clean the fins on the unit prior to long shutdown periods.
Type of task
Checks / Maintenance/Inspection
Maintenance/leak testing
■ We recommend that you take
out a maintenance contract with an annual service from an appropriate specialist firm.
■ The legally stipulated
maintenance intervals are defined in EC ordinance no. 517/2014 of the European Council.
! CAUTION
Wearing appropriate protective clothing is necessary when working on the units.
NOTE
Statutory regulations require a leak test for the cooling cycle dependent on the GWP value. Inspection and documentation of the work performed is to be carried out by specialist technicians.
Commis-
sioning
Monthly
Half-yearly
Yearly
Temporary shutdown
1.
Shut down the cold water
consumers connected to the system.
2. Switch the unit off via the internal controller in the chiller (or using the remote control).
3. Check the percentage concentration of glycol.
4. Check the unit for visible signs of damage and clean it as described in the "Care and maintenance" chapter.
5. As much as possible, cover the unit with a plastic foil to protect it against the weather.
CAUTION
!
If only water and not a mixture of water and glycol is used, in regions subject to freezing, water must be drained from components when these are at standstill. The drained water volume must be replaced when components are put back into operation!
General Clean dirt traps
Check medium filling
Check circulation pump
Dirt/damage condenser
Check quality of the glycol
Measure voltage and current
Check direction of rotation
Check compressor
Check fan
Check the refrigerant volume
Check condensate drainage
Check insulation Sealing test for cooling cycle
1) see note
26
•
• •
• •
• •
• •
• •
• •
• •
• •
• •
• •
• •
• •
• •
Permanent shutdown
Ensure that units and components are disposed of in accordance with local regulations, e.g. through authorised disposal and recycling specialists or at collection points.
REMKO GmbH & Co. KG or your contractual partner will be pleased to provide a list of certified firms in your area.
1)
Page 27
Electrical wiring
CAUTION
!
All electrical installation work is to be performed by specialist companies. Disconnect the power supply when connecting the electrical terminals.
■
The power supply is made at the chiller; a control cable to the interior unit is not necessary.
■
An all-pole isolating switch,
which trips in the event of a failure of any of the individual phase conductors, must be installed in the supply line upstream of the unit.
■
Electric connections must be
carried out as fixed connections in accordance with the applicable regulations.
■
Check all terminal points for
stability.
■
The supply line must be
adequately insulated on-site and the voltage drop may not exceed permissible values.
■
Make sure that the electrical
system is adequate for the operation of the unit and can supply the operating current necessary for other already operated units.
■
Determine before installation,
when connecting to existing system components, whether the unit's supply line is adequately dimensioned for the unit's rated power consumption.
■ The connection of the units
must always be carried out with adequately dimensioned, low­resistance earth conductors, and, if necessary, carried out several times (especially with plastic pipes).
■
When installing the units on
flat roofs, lightning protection measures may be necessary.
■
All electrical connections
such as network supply, cable remote control etc. must be carried out in the unit's switch cabinet.
■
The lines to be installed are to
be fed into the switch cabinet through the cable glands provided.
■
An electrician must determine
the sizing and selection of the fuses and the cross section of the lines to be installed. Note that starting current may be up to 10 times nominal current.
Carry out the following electrical connections:
■
Connection of the power
supply.
■
Possible enabling contact for
the set mode or stand-by.
■
Possible operating mode
contact for cooling or heating mode.
■
Possible connection of cabled
remote control (accessory).
■
Possible connection of the
GLT to the unit controller via Modbus.
NOTE
The selection of the RCD breaker is the responsibility of the specialist company carrying out the work. Based on the provisions per VDE 0160, E VDE 0100 Part 530 as well as the guidelines of VdS 3501 and the safety regulations from BGI 608, the use of an AC/DC-sensitive, type-B RCD is recommended for ensuring standards­compliant personnel and fire protection.
Power supply
The units require a fixed AC or three-phase current connection. The power supply line must be connected in accordance with the wiring diagram.
CAUTION
!
Check all plug and terminal connections to verify that they are tight and make a permanent contact. Tighten as required.
Proceed as follows to connect:
1. Open the control panel and switch cabinet cover by removing the screws and lifting off the cover.
2. Feed the voltage-free cable through the glands into the switch cabinet and clamp the cable to the strain relief.
3. Then connect the cable in accordance with the connection diagram.
4. Ensure a correct rotating field.
5. Mount all removed parts.
NOTE
We recommend the use of safety fuses.
27
Page 28
REMKO series RVS
External enabling contact Operation/Standby
In addition to being operated with the controller or the cabled remote control, the unit can be switched on (normal operation) and switched off (Stand-By) via an external potential-free contact (normally-closed).
The contact is equipped with a wire jumper in the factory. The unit is enabled in this condition.
If the contact is opened, the unit is disabled and OFF is shown in the display.
Terminal blocks
RVS 80 DC
RVS 50, 130, 180 DC
General alarm signal ALARM 230V
The connection of a general alarm signal, for example, for signalling or for further processing to a building control system is possible as standard equipment. 230V is output here.
There is no voltage present at this contact during normal unit operation. As soon as a fault is diagnosed on the unit, 230V is present on the respective terminals of the alarm contact.
Modbus interface RS485
The unit has a Modbus interface RS485 as standard. This enables the querying or stipulation of setpoints, system temperatures, operating modes etc. A detailed list of all necessary information can be obtained on request.
Changeover cooling/heating mode
This changeover contact enables the unit to be switched to cooling mode or heating mode from a remote location.
The changeover of operating mode must be implemented both through the connection/ disconnection of the external changeover contact and through the setting in the controller display.
If the contact is closed and the unit is switched to heating mode (sun) via the setting in the controller display, the unit operates in heating mode.
28
If the contact is open and the unit is switched to cooling mode (snowflake) via the setting in the controller display, the unit operates in cooling mode.
Page 29
Electrical drawings RVS 50 DC
A
L
N
7
8
N
N
N
N
N
5
6
01
L
L
H C
L
MTS
N
N
PH
N
N
1 3
2 4
L
L1
2A
FU
B
7
8
NNN
N
5
6
02
1 3
2 4
N
K2
K2
N
4V
4V
CH
N
CH
EEV
N
P
P
K2
33
BRN
31
PUMPE
BLU
Y/G
C
N
N
L
L
RO 01
RO 02
K2
RO 03
4V
RO 04
RO 05
RO 06
RO 07
CH
RO 08
RO 09
17
RO 10
20
Ha uptp lat ine
RO 11
RO 12
RO 13
RO 14
RO 15
RO 16
RO 17
RO 18
CN3 CN4
5
CN1 CN2
12V
12V
WHT
12V
GND
GND
485-B3
485-A3
485-B2
485-A2
BLK
BLU
YEL
YEL
RED
BLK
4
4
30
485-A1
D
GND
AI 01
IT
5K
t
GND
OT
AI 02
AI 03 (50K)
AI 04 (50K) AI 05 AI 06 AI 07 AI 08 AI 09 AI 10 AI 11 AI 12 AI 13 AI 14 AI 15 AI 16 AI 17 AI 18 AI 19 AI 20 AI 21 AI 22 DI 01 DI 02 DI 03 DI 04 DI 05 DI 06 DI 07 DI 08 DI 09 DI 10
D01- PWM
A01 DI1- PWM
D02- PWM
A02
DI2- PWM
D03- PWM DI3- PWM D04- PWM DI4- PWM
D05- PWM
DI5- PWM
12V
GND
CAN-L
CAN-H
485-B1
5K
t
GND
4
1
GND GND
SUT
5K
t
SUT
GND
CT
5K
t
CT
GND
AT
5K
t
AT
GND GND
GND GND
GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND
GND GND GND GND GND GND GND GND GND GND GND GND
5V
GND
GND
33
31
HP HP LP LP FS FS
12 11 6 14
16
17
20
E
4 1
5
10 9 8
26
21 22
23 24
A B
23 24
21 22
20
17
16
14
12
11
10
8 9
6
5
1 4
22 2 3
21
19 20
N
17 18
16 24 25
A
15
B
13 14
12
11
10
8 9
7
6
5
4
3
1 2
F
485B-
485A+
Remote
Heat/Cool
Remote
ON/OFF
out
Alarm
220V~
220V~
relay coil
Electric hea t
WHT
4
YEL
BLK RED
BLK RED RED WHT WHT BLK
EP
EP
ET
ET
Controller
(ET)
Pressure sensor
(SUT)
Pressure sensor
ET EP
t
50K
30
4
WHT
YEL
BLK
12V
GND
485A1
485B1
CN4
In vert er- Pla tine
L2
CN1
L
N
Pl atin e Dre hzah lre gel ung
L
L
L
Ge räte sch utz scha lte r
Q
0 1 2 3 4 5 6 7 8
P02P01P00
ACN-IN
AC-N
AC-N
AC-L
ACL-IN
ACN-OUT
ACL-OUT
CN2
Fi lter pla tin e
A
N
N
N
N
L
CN1
B
FM1
黄/绿
Y/G
N
BLU
L N
L
RED
230V~/50Hz
L1
CN607
L2L1
Ver dic hter -
Gl eich ric hte r
C
B
A
12V
GND
CN708
W UV
AC-N
AC-L
CN604
AC-NAC-L
U V W
W
V
COMP
U
U V W
Y/G
D
/Outlet wat er temperature
Sammels törm eld. potentialfrei/Alar m out
Umschalt kontakt K/H p otentia lfrei/REM OTE HEAT/COOL
Freigab ekontakt potenti alfrei/REMOTE ON/OF F
OT:Sen sor Medium Aust ritt
COMP:Kom pressor/Com pressor
CH:KW-H eizung/Compres sor heater
E
IT:Sen sor Mediu m Eintritt/ Inlet water tempe rature
FS:Ström ungswächter/F low switch
LP:ND-Sc halter/Low pres sure protection
HP:HD-Sc halter/High pres sure protect ion
FU:Sicheru ngen/Fuse
CT:Sen sor Verflüssiger/C oil temperature
K2: R elais Umwälzpumpe /Relay of Pump
EP:Überhit zungsschutz Kompressor /Ex haust protection
MTS:T ermperaturregler Abtaueizung/ Tem perature switch
PS:Druc kaufnehmer/Pre ssure sensor
SUT:Sau ggaste mperatur
TC:Trans formator/Transf ormer
PH:Abtauh eizung / Def rost heater
F
Relaiss pule der elektrische n Zusatzh eizung/Elec tric heat rela y coil
4V: Um kehrventil / 4 way valve
29
Page 30
REMKO series RVS
Electrical drawings RVS 80 DC
A
L
N
7
8
N
N
N
5
6
01
L
L
H C
L
MTS
N
PH
N
1 3
2 4
L
L1
2A
FU
B
7
8
NNN
N
5
6
02
1 3
2 4
N
N
N
N
N
K2
K2
N
4V
4V
N
CH
EEV
N
P
P
K2
33
BRN
31
PUMPE
BLU
Y/G
C
N
N
L
L
RO 01
RO 02
K2
RO 03
4V
RO 04
RO 05
RO 06
RO 07
CH CH
RO 08
RO 09
17
RO 10
20
RO 11
Hau ptp lat ine
RO 12
RO 13
RO 14
RO 15
RO 16
RO 17
RO 18
CN3 CN4
5
CN1 CN2
12V
WHT
12V
12V
GND
GND
485-B3
485-A3
485-B2
485-A2
BLK
BLU
YEL
YEL
RED
BLK
4
4
30
D
GND
AI 01
IT
5K
t
GND
OT
AI 02
AI 03 (50K)
AI 04 (50K) AI 05 AI 06 AI 07 AI 08 AI 09 AI 10 AI 11 AI 12 AI 13 AI 14 AI 15 AI 16 AI 17 AI 18 AI 19 AI 20 AI 21 AI 22 DI 01 DI 02 DI 03 DI 04 DI 05 DI 06 DI 07 DI 08 DI 09 DI 10
D01- PWM
A01 DI1- PWM
D02- PWM
A02
DI2- PWM
D03- PWM DI3- PWM D04- PWM DI4- PWM D05- PWM
DI5- PWM
12V
GND
CAN-L
CAN-H
485-A1
485-B1
5K
t
GND
4
1
GND GND
SUT
5K
t
SUT
GND
CT
5K
t
CT AT
GND
5K
t
AT
GND GND
GND GND
GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND
GND GND GND GND GND GND GND GND GND GND GND GND
5V
GND
33
31
HP HP
LP LP FS FS
GND
12 11 6 14
16
17
20
E
4 1
5
10 9 8
22 21 24 23
23 24
21 22
20
17
16
14
12
11
10
8 9
6
5
1 4
26
A B
22 23
21
19 20
N
17 18
16 24 25
A
15
B
13 14
12
11
10
8 9
7
6
5
4
3
1 2
F
485B-
485A+
Remote
Heat/Cool
Remote
ON/OFF
out
Alarm
220V~
220V~
relay coil
Electric heat
WHT
4
YEL
BLK RED
BLK RED RED WHT WHT BLK
Controller
(ET)
Pressure sensor
(SUT)
Pressure sensor
EP
EP
ET
ET EP
t
ET
50K
30
30
4
WHT
YEL
BLK
12V
GND
485B1
485A1
CN4
CN1
L
N
Pla tin e Dre hzah lre gel ung
L
L
L
Ger äte sch utz scha lte r
Q
0 1 2 3 4 5 6 7 8
P02P01P00
ACN-IN
AC-N
AC-N
AC-L
ACL-IN
ACN-OUT
ACL-OUT
CN2
Fil ter pla tin e
A
N
N
N
N
L
CN1
B
FM1
黄/绿
Y/G
N
BLU
L N
L
RED
Inv ert er- Pla tine
L2
L1
CN607
AC-NAC-L
L2L1
Ver dic hter -
Gle ich ric hte r
230V~/50Hz
C
B
A
12V
GND
CN708
W UV
AC-N
AC-L
CN604
U V W
W
V
COMP
U
U V W
Y/G
EP:Überhit zungsschutz Kompressor /Exhaus t protection
CT:Sen sor Verflüssiger/Coil temperature
COMP: Kompressor/C ompressor
FS:St römungswäc hter/Flow swi tch
CH:KW- Heizung/Compres sor heater
D
E
/Outlet wat er temperat ure
Sammels törmeld. potentialf rei/Alarm out
Umsc haltkontakt K/H poten tialfrei/R EMOTE HEAT/COO L
Freigab ekontakt potenti alfrei/REMOTE ON/OF F
K2: R elais Umwälz pumpe/Relay o f Pump
LP:ND-Sc halter/Low pres sure protection
SUT:Sa uggaste mperat ur
FU:Sicheru ngen/Fuse
IT:Sen sor Medium Eintr itt/ Inlet water tempe rature
HP:HD-Sc halter/High pres sure protect ion
TC:Trans formator/Transf ormer
PS:Druc kaufnehmer/Pre ssure sensor
MTS:T ermperaturregler Abtauheizung/ Temperature s witch
OT:Sen sor Mediu m Au stritt
PH:Abt auheizung / Def rost heater
F
Relaiss pule der elektrisc hen Zusatzh eizung/Elec tric heat rela y coil
4V: U mkehrventil / 4 way valv e
Page 31
Electrical drawings RVS 130 DC
A
B
C
D
E
F
9
GND
AI 01
IT
5K
N
N
L
L
8
N
N
4V
L
RO 01
RO 02
K2
K2
K2
4V
RO 03
4V
RO 04
RO 05
RO 06
RO 07
CH
7
7
8
N
N
N
N
N
5
6
02
1 3
2 4
6
L
L
7
N
N
5
H C
PH
N
1 3
MTS
5
L
4
L
L
FU
30
4
WHT
YEL
BLK
12V
GND
485B1
485A1
CN4
CN1
L
N
Pl atin e Dre hzah lre gel ung
L
N
N
CH
8
N
N
N
6
01
N
N
N
2 4
N
P
L1
3.15A
PUMPE
K2
Y/G
FM2
FM1
CH
RO 08
RO 09
13
RO 10
16
RO 11
Ha uptp lat ine
RO 12
RO 13
RO 14
RO 15
RO 16
RO 17
RO 18
CN3 CN4
5
EEV
CN1 CN2
12V
12V
GND
485-B3
485-A3
YEL
YEL
BLK
RED
WHT
4
30
AI 02
AI 03 (50K)
AI 04 (50K) AI 05 AI 06 AI 07 AI 08 AI 09 AI 10 AI 11 AI 12 AI 13 AI 14 AI 15 AI 16 AI 17 AI 18 AI 19 AI 20 AI 21 AI 22 DI 01 DI 02 DI 03 DI 04 DI 05 DI 06
DI 07 DI 08 DI 09
DI 10
D01- PWM
A01 DI1- PWM
D02- PWM
A02
DI2- PWM
D03- PWM
DI3- PWM
D04- PWM
DI4- PWM
D05- PWM
DI5- PWM
12V
12V
GND
GND
485- A2
485-B2
CAN-H
485-A1
485-B1
BLK
BLU
4
3
L
t
GND
OT
5K
t
GND
ET
50K
t
ET
GND GND
SUT
5K
t
SUT
GND
CT
5K
t
CT
AT
GND
5K
t
AT
GND
GND GND
GND GND GND GND GND GND GND GND GND GND GND GND GND
HP HP
GND
LP LP
GND
FS FS
GND
GND
GND GND
GND GND GND
GND GND GND GND
GND GND GND
GND GND GND GND GND
5V
GND
GND
CAN-L
1
6 5 4
485B-
22
17 18
19 20
8 7 2
10
12
13
16
A B
19 20
18
17
16
N
13
12
A
10
B
8
7
6
4 5
2
1
485A+
21
Remote
19 20
17 18
13 14 15 16
12
11
10
8 9
7
6
5
4
3
1 2
Heat/Cool
Remote
ON/OFF
out
Alarm
220V~
220V~
relay coil
Electric heat
WHT
4
YEL
BLK RED
BLK RED RED WHT WHT BLK
Controller
(ET)
Pressure sensor
(SUT)
Pressure sensor
2
Ge räte sch utz scha lte r
Q
N
N
N-in
N-out
L
L
N N
L-in
L-out
L
Fi lter pla tin e
Y/G
N
BLU
L
L N
RED
230V~/50Hz
0 1
A
B
CN617
In vert er- Pla tine
CN618
PE ACN ACL L1 L2
CN607
P2
P1
CN608
B
A
12V
GND
CN614
W UV
CN604
C
N
L
L1 L2
Ver dic hter -
Gl eich ric hte r
L4
L
PTC
L4
L
L4
K1
P2
N
P2
P1
U
V
W
N
N
P1
K1
D
W
W
V
V
U
COMP
U
/Outlet wat er temperature
:Luf tschalter /Air switc h
CT:Sen sor Verflüssiger/Coil temperature
HP:HD-Sc halter/High pres sure protect ion
FU:Sicheru ngen/Fuse
COM P:Kompre ssor/Compres sor
CH:KW-H eizung/Com pressor heater
FS:Ström ungswächter/F low switch
E
PH:Abtauh eizung / Def rost heater
K2: R elais Umwälzpum pe/Relay of Pum p
SUT:Sau ggastemperat ur
OT:Sen sor Medium Aust ritt
LP:ND-Sc halter/Low pres sure protec tion
IT:Sen sor Mediu m Eintr itt/ Inlet wat er tempera ture
Freigab ekontakt potenti alfrei/REMOTE ON/OF F
Umsc haltkont akt K/H poten tialfrei/R EMOTE HEAT/C OOL
4V: Um kehrventil / 4 way valve
Q
TC:Trans formator/Transf ormer
PS:Druc kaufnehmer/Pre ssure sensor
MTS:T ermperaturregler Abtauheizung/ Tem perature swi tch
Sammels törm eld. potentialfrei/Alar m out
F
Relaiss pule der elekt rische n Zusatzheizung/Elec tric heat rela y coil
31
Page 32
REMKO series RVS
Electrical drawings RVS 180 DC
A
B
C
D
E
F
9
N
L1
8
L2
L3
L1
7
N
N
L1
6
5
4
L1
N
L3
L2
3
L1
L1
L2
L3
N14
N
14
12
L2(B)
L1(A) 11
L3(C)
L1
1A
FU
L2L3
Pha sen fol ger elai s
N
N14
L
L1
RO 01
N
N1
K2
K2
7
8
N
H C
L1
MTS
N
N
N
5
6
01
PH
1 3
2 4
FR
N
4V
4V
N
CH
9
16
RO 02
K2
RO 03
4V
RO 04
RO 05
RO 06
RO 07
CH CH
RO 08
RO 09
Hau ptp lat ine
RO 10
RO 11
RO 12
RO 13
30
4
WHT
YEL
BLK
12V
GND
485A1
485B1
CN4
CN1
L
N
Pla tin e Dre hzah lre gel ung
L1
N
L3
L2
L1
K2
FR
FM2
FM1
5
EEV
W
V
3
U
PUMPE
BRN BLK BLU
Y/G
RO 14
RO 15
RO 16
RO 17
RO 18
CN3 C N4
12V
12V
CN1 CN2
12V
GND
GND
485-B3
485-B2
485- A2
485- A3
BLU
BLK
YEL
YEL
RED
BLK
WHT
4
4
30
GND
AI 01
IT
5K
t
IT
GND
OT
AI 02
AI 03 (50K) AI 04 (50K)
AI 05 AI 06 AI 07 AI 08 AI 09 AI 10 AI 11 AI 12 AI 13 AI 14 AI 15 AI 16 AI 17 AI 18 AI 19 AI 20 AI 21 AI 22 DI 01 DI 02 DI 03 DI 04 DI 05 DI 06
DI 07 DI 08 DI 09
DI 10
D01- PWM
A01
DI1- PWM
D02- PWM
A02
DI2- PWM
D03- PWM DI3- PWM
D04- PWM
DI4- PWM
D05- PWM
DI5- PWM
12V
GND
CAN-L
CAN-H
485-A1
485-B1
5K
t
OT
GND
ET
50K
t
ET
GND GND
SUT
5K
t
SUT
GND
CT
5K
t
CT
GND
AT
5K
t
AT
GND
GND GND
GND GND GND GND GND GND GND GND GND GND GND GND GND
GND GND GND
GND
GND GND
GND GND GND
GND GND GND GND
GND GND GND
GND GND GND GND GND
5V
GND
3
6
5 4
HP HP
LP LP
FS FS
17 18
19 20
GND
10 7 1
8
12
485B-
485A+
19 20
17 18
16
N9
485B-
10 12
485A+
6
3 4 5
1 7 8
485B-
22
485A+
21
20
Remote
19
18
17
16
15
14
13
7 8 9 1 0 1 1 1 2
6
2 3 4 5
1
Heat/Cool
Remote
ON/OFF
out
Alarm
220V~
220V~
relay coil
Electric heat
RED
4
Controller
BLK
WHT
BLK BLK WHT YEL
RED RED WHT
(ET)
Pressure sensor
(SUT)
Pressure sensor
32
B
A
2
N
Ger äte sch utz scha lte r
1
Q
L3N
L1L2
Y/G
BLU
L3 N
WHT
L3 N
L2
BLK
0
L1
L2
C B A
L3
Fil ter pla tin e
N
N
N- C- B- A-
A
L2
L1
RED
400V/3N~/50Hz
L1
B
CN602
Inv ert er- Pla tine
CN613
DCN-IN
CN614
DCP-IN
39K
39K
N
1 3
2 45678
C
5V
12V
GND
GND
CN605
JP601
CN617
DCP-OUT
U V W
L3
L2
L1
R S T
CN615
DCN-OU T
W
WHT
V
BLK
RED
COMP
U
/Outlet wat er temperature
02
Electronic expand valve
FR:M otorschu tzscha lter/Ther mal relay
EEV:
ET:Exhaus t temperature
CH:KW-H eizung/Compres sor heater
Ver dich ter -
Gle ich ric hte r
D
COMP:Kom pressor/Com pressor
FU:Sicheru ngen/Fuse
CT:Sen sor Verflüssiger/Coil temperature
FS:Ström ungswächter/F low switch
E
MTS:T ermperaturregler Heizung/ Tem perature switch
HP:HD-Sc halter/High pres sure protect ion
IT:Sen sor Medium Eint ritt/ Inlet water temperature
LP:ND-Sc halter/Low pres sure protection
SUT:Suc tion temperat ure
OT:Sen sor Medium Aust ritt
K2:Schüt z Umwälzpump e /Contactor Circ ulation Pump
Sammels törm eld. potentialfrei/Alar m out
Umschalt kontakt K/H p otentialfrei/REM OTE HEAT/C OOL
Freigab ekontakt potenti alfrei/REMOTE ON/OF F
4V: Um kehrventil / 4 way valve
PH:Abtauh eizung / Def rost heater
F
Relaiss pule der elektrische n Zusatzheizu ng/Electric heat rela y coil
Page 33
Leak testing
Before commissioning
The leak test is carried out after the connection has been made.
1. Flush the system twice with clean tap water.
2. Clean the sieve insert of the dirt trap provided by customer.
3. Fill the system with water again and bleed the unit at the manual bleed valves.
4. Adjust the test pressure to at least 250 kPa (2.5 bar).
5. Check the connections for leaking water after a period of at least 24 hours . If leaks are visible, the connection has not been properly made. Tighten the connection or establish a new connection.
6. After a successful leak test, remove the excess pressure from the medium piping if a water-glycol mixture is used or adjust the non-circulating pressure to the required system pressure.
6 Unit preliminary pressure
Filling the system
The system is filled at the customer-provided filling and draining connections.
Anti-freeze protection for the medium
If a water-glycol mixture is used, it is to be pre-mixed before being put in the system. The desired concentration is then to be checked.
Unit preliminary pressure for the medium
The preliminary pressure of the medium (without operation of the circulation pump) varies within the system. From the highest point, the pressure increases by approx.10 kPa (0.1bar) per metre difference in altitude (geodetic altitude). The value measured at the highest point is identified as the non-circulating pressure.
The position of the unit in the system is decisive in the calculation of the unit's preliminary pressure (pressure of the manometer on the unit installed by the customer). The pressure must be set to at least 70 kPa (0.7 bar)
.
■
If the unit is positioned at the lowest point in the system, the unit preliminary pressure (=non-circulating pressure+geodetic system altitude) must be set to at
least 70 kPa (0.7 bar) + 10 kPa (0.1bar) x geodetic system altitude.
■
If the unit is positioned at the highest point in the system, the unit preliminary pressure (=non-circulating pressure) to at least 70 kPa (0.7 bar). Please note that the system pressure at the lowest point is increased by the geodetic system altitude!
Bleeding the system
■
Air may still be in the pipe lines after the leak test. The operation of the circulation pump transports this to the next highest point or to the cold water consumer. Here it is necessary to vent again (Figure 7).
■
Also vent the pump if necessary.
■
The non-circulating pressure must then be adjusted to the required system pressure.
Unit preliminary pressure
Non-circulating pressure
7 Manual bleeding
Unit preliminary pressure
Geodetic system altitude
Manual bleeding
33
Page 34
REMKO series RVS
Diaphragm expansion vessel
■ The preliminary pressure for
the diaphragm expansion vessel must be adjusted individually to the system layout, the volume of the medium and the installation site.
■
If necessary, change the installation site. For this, the manufacturer's authorisation is required.
■
For cooling and heating systems, the volume and the preliminary pressure for the diaphragm expansion vessel must be adjusted to both operating modes; integrate an additional diaphragm expansion vessel in the system if necessary.
Valves for hydronic balancing
■
The calculated excess pressure in the pipe network layout at the individual cold water outlets must be adjusted at the valves for hydronic balancing.
Additional checks
General checks
■
Checking that minimum clearances are correct.
■
Checking the transfer of cooling and heating capacity via the cold or hot water consumer (indoor unit).
Electrical checks
■
Checking electrical connections for correct phase sequencing.
■
Functional check of the cooling mode/heating mode enable (option).
■
Functional check of the enable mode/Stand-By (option).
Checking the medium cycle
NOTE
The units are equipped with a phase sequence relay which prevents the operation of the controller if the direction of rotation of the electric power supply is wrong. The rotary field must be replaced if the controller is not activated during commissioning of the unit.
NOTE
During manual bleeding, any glycol mixtures which escape must be disposed of separately.
Safety valve
■
The safety valves and their correct function must be checked.
■
The drain line for the valves is to be checked for function and leak tightness.
■
If necessary, change the installation site. For this, the manufacturer's authorisation is required.
■
Checking the circulation pump for freedom of movement.
■
Checking whether all valves are open.
■
Checking the medium circuit.
■
Setting the circulation pump's nominal flow rate.
Checking the cooling circuit
■
Checking the cooling circuit for adequate oil/refrigerant.
■
Checking the cooling circuit for leak tightness.
34
Page 35
Commissioning
NOTE
Commissioning should only be performed by specially trained personnel and documented after the certificate has been issued.
■
Observe the manuals for the unit and all other components when commissioning the entire system.
Functional test for Cooling mode:
1. Switch the power supply on.
2. Open all shut-off valves if necessary.
3. Switch the unit and the corresponding circulation pump on to the highest level. The outlet temperature must be between +4 and +18°C.
4. Switch the unit on and select the cooling operating mode. If the return temperature is warmer than the setting, the compressor display will flash and the compressor will begin to work after approx. 3 to 5 minutes.
- The circulation pump starts and the controller checks the medium flow rate via the differential pressure/flow switch. If the volume is insufficient, a fault shut-off will be carried out and the cooling cycle will not be enabled.
6. Measure and record all the required values in the commissioning report and check the safety functions.
7. Check the unit control system using the functions described in the "Operation" chapter.
Functional test for Heating mode
1. Switch the power supply on.
2. Open all shut-off valves if necessary.
3. The voltage supply is made at the chiller; a control cable to the interior unit is not necessary. The outlet temperature must be between +35 and +45°C.
- The circulation pump starts and the controller checks the medium flow rate via the differential pressure/flow switch. If the volume is insufficient, a fault shut-off will be carried out and the cooling cycle will not be enabled.
6. Measure and record all the required values in the commissioning report and check the safety functions.
7. Check the unit control system using the functions described in the "Operation" chapter.
Final tasks
■
Reassemble all disassembled parts.
■
Familiarise the operator with the system.
5. Please note that the inlet temperature at the nominal flow rate of the medium lies approx. 5 K below the return temperature.
- If the supply temperature falls
below the factory setting of 4°C, a fault triggers. If this is the case, a higher return temperature must be selected. If the spread is too great or too small, the medium flow rate must be checked.
4. Switch the unit on and select the heating operating mode. If the return temperature is colder than the setting, the compressor display will flash and the compressor will begin to work after approx. 3 minutes.
5. Please note that the supply temperature at the nominal flow volume of the medium lies approx. 5 K above the return temperature.
35
Page 36
REMKO series RVS
Overhaul and repair
NOTE
Overhaul and repairs should only be performed and documented by specially trained personnel.
Cooling circuit
Repairs on the cooling cycle are to be documented in the operating manual. The following measures must be observed:
■
Environmentally correct
collection and disposal of refrigerant and defective components
■
Repairs carried out properly and
permanently with original spare parts and connecting materials appropriate to the task
■
Long-lasting leak-testing
with the maximum occurring pressure
■
Long-lasting and properly
implemented evacuation and drying of the refrigerant circuit
■
Proper filling with pure
refrigerant and corresponding quantity per operating instructions/name plate
■
Functional check of safety
components
! CAUTION
Wear protective clothing when handling refrigerant.
! CAUTION
Only refrigerant in a liquid state may be used to fill the cooling cycle.
Medium cycle
Repairs on the medium cycle are to be carried out and documented in accordance with the current regulations and/or regional guidelines. The following measures must be observed:
■
Environmentally correct
collection and disposal of operating medium and defective components
■
Repairs carried out properly and
permanently with original spare parts and connecting materials appropriate to the task
■
Long-lasting leak-testing
with the maximum occurring pressure
■
Functional check of safety
components
■
Proper filling with pure
operating medium
NOTE
The escape of refrigerant contributes to climatic change. In the event of escape, refrigerant with a low greenhouse potential has a lesser impact on global warming than those with a high greenhouse potential. This unit contains refrigerant with a greenhouse potential of 2088. That means the escape of 1 kg of this refrigerant has an effect on global warming that is 2088 times greater than 1 kg CO2
based on 100 years. Do not conduct any work on the cooling cycle or dismantle the unit - always enlist the help of qualified experts.
Electrical components
Repairs on electrical components and parts are to be carried out and documented in accordance with the current regulations and/or regional guidelines. The following measures must be observed:
■
Environmentally correct disposal
of defective components
■
Repairs carried out properly and
permanently with original spare parts
■
Inspection of the unit or system
in accordance with the currently applicable regulations and guidelines, e.g. protection against direct contact, damage to components, defective components, changes to factory-delivered components, etc.
■
Testing of the unit or system
in accordance with the currently applicable regulations and guidelines, e.g. devices for protection against electric shock/overvoltage/incorrect rotating field, overcurrent protection devices, display and fault devices, interlocks, etc.
■
Measurement and assessment
of the unit or system in accordance with the currently applicable regulations and guidelines, e.g. insulation resistance, loop impedance, residual current protective devices, low-resistance connection of the earth conductor, earthing resistance, incorporation into the lightning protection system, etc.
! CAUTION
All overhaul/repairs to be carried out in electrically de­energised condition.
36
Page 37
Troubleshooting and customer service
The unit has been manufactured using state-of-the-art production methods and has been tested several times to ensure that it works properly. If malfunctions should occur, please check the unit as detailed in the list below. Please inform your dealer if the unit is still not working correctly after all the function checks have been performed.
Operational malfunctions
Malfunction Possible cause Checks Remedial measures Major
P01 Medium inlet probe defective
P02
P04
P07
P08
PP1 "Low-pressure probe fault"
PP2 "High-pressure probe fault"
E01
Medium outlet sensor defective
Probe defective, ambient temperature probe
Probe defective, suction gas temperature probe
Probe defective, heat gas temperature probe
High-pressure switch, high­pressure alarm
- Check:
- Probe resistance
- Connections of the probe cable
- Check:
- Probe resistance
- Connections of the probe cable
- Check:
- Probe resistance
- Connections of the probe cable
- Check:
- Probe resistance
- Connections of the probe cable
- Check:
- Probe resistance
- Connections of the probe cable
- Check:
- Probe resistance
- Connections of the probe cable
- Check:
- Probe resistance
- Connections of the probe cable
In cooling mode: Finned heat exchanger blocked, dirty or exposed to excessive sunlight? Condenser fan or high-pressure switch defective?
In heating mode: Medium flow rate too low, Medium temperature on the plate heat exchanger too high, High-pressure switch defective.
- Replace defective probe
- Renew connections
- Replace defective probe
- Renew connections
- Replace defective probe
- Renew connections
- Replace defective probe
- Renew connections
- Replace defective probe
- Renew connections
- Replace defective probe
- Renew connections
- Replace defective probe
- Renew connections
In cooling mode: Clear finned heat exchanger, clean, shade, have condenser fan checked by specialist personnel, check high­pressure switch.
In heating mode: Check medium flow rate and medium temperature, check high-pressure switch
X
In cooling mode: Insufficient refrigerant, Medium flow rate too low, low-pressure switch defective.
In heating mode: Insufficient refrigerant, Finned heat exchanger blocked or dirty? Evaporator fan or low-pressure switch defective?
E02
Low-pressure probe low-pres­sure alarm
Please note that this troubleshooting table continues on the next pages
In cooling mode: Insufficient Refrigerant, check medium flow rate and low­pressure switch.
In heating mode: Clear and clean finned heat exchanger, have evaporator fan checked by specialist personnel, check low-pressure switch.
X
37
Page 38
REMKO series RVS
Malfunction Possible cause Checks Remedial measures Major
E03 Medium flow disturbance
E07 Frost protection triggered
P81 Heat gas overtemperature
E44
E21 Low voltage fuse triggered
E22/23 Overflow protection
Heating system dropped below bottom operating limit
Check:
- Air in the medium piping
- Open shut-off devices
- Medium pressure
- Circulation pump capacity
- Medium flow rate
- Flow monitor
Is the supply temperature greater than or less than 4°C?
Check:
- Heat gas temperature (U04)
- Heat gas temperature probe, probe resistance
- Refrigerant quantity
Outside temperature below
-20°C?
Check:
- Voltage on R/S/T on the inverter board (min 300V)
Check:
- Current consumption of the complete system
- Bleed medium cycle
- Open shut-off valves
- Increase medium pressure
- Have circulation pump, medium flow rate and flow monitor checked by a specialist company.
Raise return flow temperature, increase medium flow rate, adjust anti-freeze temperature to the operating medium.
- Replace heat gas temperature probe
- Fill refrigerant to operational levels after rectifying
the cause of the problem
Establish stable power supply on the supply line
- Replace inverter board
- Restart system
X
X
X
E24
E25
E27 IPM overcurrent protection
E28 IPM overheating protection
E30 / E31
DC bus overvoltage protection triggered
Inverter board low voltage protection device triggered
Overheating of the control electronics
Check:
- Voltage at R/S/T on the inverter board (max 500V)
- Voltage between DCP-IN and DCN-IN on the inverter board (max 800V)
Check:
- Voltage at R/S/T on the inverter board (min 210V)
- Voltage between DCP-IN and DCN-IN on the inverter board (min 300V)
Check: Compressor current draw, Pressure difference, high/low pressure
Check:
- Function of the fan
- Air throughput
Check:
- Function of the fan
- Air throughput
Establish stable power supply on the supply line
- Replace inverter board
Establish stable power supply on the supply line
- Replace inverter board
- Reduce pressure difference by raising the low pressure or lowering the high pressure
- Ensure that there is adequate distance at the fan inlet and outlet
- Clean the finned heat exchanger
- Ensure that there is adequate distance at the fan inlet and outlet
- Clean the finned heat exchanger
38
Page 39
Malfunction Possible cause Checks Remedial measures Major
Check:
E32 IPM current probe
E33 / E34
E35 Faulty input voltage
E36 Compressor start-up fault
E37 DSP communications fault - Replace inverter board
Compressor overcurrent protection
Compressor current draw, Pressure difference, high/low pressure
Check: Compressor current draw, Pressure difference, high/low pressure
Check:
- Voltage between U&V, U&W and V&W (380V (+-10%))
Check:
- U/V/W connections on compressor
- U/V/W connections on the inverter board
- Voltage between U&V, U&W and V&W (380V (+-10%))
- Compressor motor windings
- Operating pressures in the refrigerant circuit
- Reduce pressure difference by raising the low pressure or lowering the high pressure
- Replace inverter board
- Reduce pressure difference by raising the low pressure or lowering the high pressure
Establish stable power supply on the supply line
- Replace inverter board
- Renew connections
- Replace compressor
- Replace inverter board
E38 PFC communications fault - Replace inverter board
E39 Supply voltage check
E40 EEPROM error
E41
E45 PFC communications fault - Replace inverter board
E46 Fan motor 1 defective
E47 Fan motor 1 defective
EE8
Faulty compressor start-up voltage
Communication fault between motherboard and inverter board
Check:
- Voltage on the supply line
Check: Correct seating of the EEPROM
Check:
- Voltage between U&V, U&W and V&W (380V (+-10%))
Check:
- Fan motor operation
- Fan motor current draw
Check:
- Fan motor operation
- Fan motor current draw
Check:
- Connections between motherboard and inverter board
Establish stable power supply on the supply line
- Replace inverter board
- Correct the seating of the EEPROM
- Replace inverter board
Establish stable power supply on the supply line
- Replace inverter board
- Replace the fan motor.
- Replace the fan motor.
- Renew connections
- Replace inverter board
- Replace motherboard
E08
Communication fault between motherboard and display
Check:
- Communications between motherboard and display
- Renew connections
- Replace display
- Replace motherboard
39
Page 40
REMKO series RVS
Malfunction Possible cause Checks Remedial measures Major
Check:
F032 Fan motor 1 defective
- Fan motor operation
- Fan motor current draw
- Replace the fan motor. X
Check:
- Connections between motherboard and fan speed controller
- Replace fan speed controller
- Replace motherboard
E081
Communication fault between motherboard and fan speed controller
Resistance table
The resistance values for the probes: AT (ambient), CT (register), SUT (suction gas), OT (medium outlet), IT (medium inlet) are shown in the following table. The ET (compressor outlet) probe is an NTC 50.
Temperature
[°C]
-30 63.73
-29 60.32
-28 57.12
-27 57.12
-26 51.27
-25 48.60
Resistance
(kΩ)
Temperature
Resistance
[°C]
-5 17.91
-4 17.10
-3 16.32
-2 15.59
-1 14.89
0 14.23
(kΩ)
Temperature
Resistance
[°C]
20 6.09
21 5.85
22 5.62
23 5.40
24 5.20
25 5.00
(kΩ)
-24 46.09
-23 43.72
-22 41.49
-21 39.38
-20 37.40
-19 35.53
-18 33.76
-17 32.09
-16 30.52
-15 29.03
-14 27.62
-13 26.29
-12 25.03
-11 23.84
-10 22.72
-9 21.65
1 13.60
2 13.01
3 12.44
4 11.90
5 11.39
6 10.90
7 10.44
8 10.00
9 9.58
10 9.18
11 8.80
12 8.44
13 8.09
14 7.76
15 7.45
16 7.15
26 4.81
27 4.63
28 4.46
29 4.29
30 4.13
31 3.98
32 3.83
33 3.70
34 3.56
35 3.43
36 3.31
37 3.19
38 3.08
39 2.97
40 2.97
41 2.77
-8 20.64
-7 19.68
-6 18.77
40
17 6.87
18 6.59
19 6.33
42 2.67
43 2.58
44 2.49
Page 41
Dimensions
Unit dimensions
RVS 50 DC
RVS 130 DC
RVS 80 DC
RVS 180 DC
41
Page 42
REMKO series RVS
Technical data
Series RVS 50 DC RVS 80 DC RVS 130 DC RVS 180 DC
Operating mode
Nominal cooling output kW 4.7
1)
(1.6 - 5.6) 7.6 1) (2.0 - 10.0) 13.5 1) (5.0 - 14.5) 16.9 1) (7.0 - 20.0)
Compact air-cooled chiller for external installation
with seamless power regulation for cooling and heating
SEER 3.88 4.33 5.01 4.15 Annual room cooling efficiency n
s,c
Setting range return temp. Cooling °C
% 152 170 195 163
+10 to +20 / +3 to +20
4)
Setting range return temp. Heating °C +30 to +50 Operating range, cooling °C -15 to +45 Operating range, heating °C -20 to +52 Cooling circuits, number 1
Refrigerant R410A
7)
GWP value 2088 Refrigerant filling quantity CO
equivalent 5.22 5.01 6.68 9.19
2
6)
kg 2.5 2.4 3.2 4.4
Compressor, number/type 1/Rotary piston Air flow rate, max. m³/h 3,900 3,900 7,800 8,600 Nominal airflow volume m³/h 3,650 3,650 7,300 8,100 Number of fans 1 2 Power consumption, fan kW 0.11 0.11 0.22 0.25 Current consumption, fan A 0.5 0.5 1.0 1.1 Sound pressure level
3)
dB(A) 37.3 37.3 41.7 46.2 Sound power level dB(A) 68.5 68.5 73.1 77.6 Power supply V/Hz 230/1~/50 400/3~N / 50 Enclosure class IP X4 Electr. power consumption, max. Elec. current consumption, max. Electr. rated power consumption
Cooling Electr. rated current consumption
Cooling
1)
1)
4)
4)
kW 2.1 3.4 5.6 9.0
A 9.2 18.0 27.0 14.0
kW 1.3 2.3 4.5 5.5
A 5.6 10.4 20.7 9.5
Electr. starting current, max. A Not applicable as the unit starts with min. frequency Operating medium Water; max. 35% ethylene glycol, max. 35% propylene glycol Operating pressure, medium, max. kPa 600 Nominal flow rate, medium
Cooling
m³/h 1.0 1.6 2.8 4.2
Minimum flow volume, medium m³/h 0.62 1.00 1.75 2.63 Maximum flow volume, medium m³/h 1.68 2.70 4.70 7.00 Pressure loss, indoor kPa 10.0 24.0 105.0 71.0 Nominal pump pressure, max. kPa 60.8 122.6 206.0 220.7 Equipment pressure, available kPa 50.8 98.6 101.0 149.7 Power consumption, pump kW 0.05 0.18 0.50 0.65 Current consumption, pump A 0.4 0.7 2.8 1.7 Medium connection, inlet Inches 1 1 1 1/4 1 1/4 Medium connection, outlet Inches 1 1 1 1/4 1 1/4 Dimensions - Height mm 790 910 1320 1592
Width mm 1008 953 996 1175
Depth mm 463 445 395 400 Weight kg 95 110 148 219 Standard colour similar to RAL 9018
1) Air inlet temperature TK 35°C, medium inlet 12°C, medium outlet 7°C, 0% glycol concentration
3) Distance 10 m free field
4) With low temperature accessories
6) The refrigerant filling quantity is subject to continuous optimisation. Therefore, the exact filling quantity can be found on the name plate
42
Page 43
43
Page 44
REMKO QUALITY WITH SYSTEMS
Air-Conditioning | Heating | New Energies
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 32791 Lage
Telephone +49 (0) 5232 606-0 Telefax +49 (0) 5232 606-260
E-mail [email protected] URL www.remko.de
Hotline within Germany
+49 (0) 5232 606-0
Hotline International
+49 (0) 5232 606-130
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
Loading...