Remeha GAS 210 Technical Information

GAS 210 ECO PRO
High efficiency Low NOX gas boiler
Types:
210-80
210-120
210-160
210-200
EN
Technical
information
114494-04
Table of contents
GAS 210 ECO PRO
Table of contents
Preface 6
1. EC declaration 7
2. Introduction 8
2.1 Pictograms used 8
2.2 Important instructions 8
3. Safety 9
4. Installation 10
4.1 Scope of delivery and installation 10
4.2 Dimensions 11
4.3 Installation and service clearances 12
5. Water-side connections 13
5.1.1 Condensed water discharge 13
5.1.2 Water treatment 13
5.1.3 Pressure relief valve 14
5.1.4 Circulation pump 14
5.1.5 Water flow 14
6. Gas-side connections 15
6.1 Gas connection 15
6.2 Gas pressure 15
6.3 Gas/air ratio control 15
7. Connecting the flue gas discharge and air supply 16
7.1 General 16
7.2 Conventional open flue installation 16
7.2.1 Possible lengths for the flue gas discharge pipe 17
7.3 Room sealed installation 18
7.3.1 Possible lengths for the air supply and flue gas discharge 18
7.3.2 Discharge in different pressure areas 20
7.3.3 Connection of flue gas discharge and choice of material 21
7.3.4 Air supply connection and choice of material 21
7.3.5 Additional Directives 21
8. Control and electrical connections 22
8.1 General 22
8.1.1 Boiler control 22
8.1.2 Modulating controls general 22
8.1.3 Modulating room control 22
8.1.4 Modulating weather-compensated control rematic® 22
8.1.5 Modulating cascade controller MC4 23
8.2 Electrical specifications 23
8.2.1 Mains voltage 23
8.2.2 Control box 23
8.2.3 Fuse ratings 24
8.3 Electrical connection options 24
8.3.1 Connection options of standard control unit (PCU-01) 24
8.3.2 On/off control (OT) 24
8.3.3 Modulating controls (OT) 24
8.3.4 External interlock (BL) 24
8.3.5 Input release (RL) 25
8.3.6 Circulation pump (Pump) 25
8.3.7Connecting a PC 25
2
114494-03
GAS 210 ECO PRO
Table of contents
8.3.8 Connection options for the PCB - SCU - X01 25
8.4 Connection options for the optional 0 - 10 V control PCB (IF-01) 26
8.4.1 Connection status (Nc) 26
8.4.2 OTm connection 26
8.4.3 Analogue input (0 - 10 V) 27
8.4.4 Analogue output (0 - 10 V) 27
8.5 Connection options of the optional expanded control/protection PCB (SCU-S01) 28
8.5.1 Flue gas damper control (FgV) 28
8.5.2 Hydraulic valve control (HdV) 28
8.5.3 External gas valve control (EgV) 28
8.5.4 Operation signal and failure signal (Nc / No) 28
8.5.5 Water pressure sensor (Wps) 28
8.5.6 Outside temperature sensor (Tout) 29
8.5.7 Minimum gas pressure switch (Gps) 29
8.5.8 Gas leakage control (VPS; only for 210- 160 and 210- 200 boilers) 29
8.5.9 Wiring diagram 30
9 Commissioning 31
9.1 Control panel 31
9.1.1 Normal start-up procedure 31
9.1.2 Fault during start-up procedure 32
9.1.3 Reading current values 33
9.1.3.1 Status and sub status 34
9.1.4 Adjusting the boiler to the system 34
9.1.5 Changing parameters at user level (without access code) 35
9.1.6 Changing parameters at service level (with access code) 35
9.1.7 Resetting factory settings 38
9.1.8 Setting manual operation ( symbol) 39
9.2 Commissioning 39
9.3 Taking the boiler out of operation 42
9.3.1 Boiler with frost protection, out of operation for a long time 42
9.3.2 Boiler without frost protection, out of operation for a long time 42
10. Inspection and maintenance 43
10.1 General 43
10.2 Combustion check of the boiler 43
10.2.1 Corrective maintenance 43
10.2.2 Cleaning the fan 44
10.2.3 Cleaning the heat exchanger (flue gas side) 46
10.2.4 Cleaning the burner 47
10.3 Cleaning the trap 48
10.4 Checking the ignition electrode 48
10.5 Checking for leaks 48
10.6 Checking water pressure 48
10.7 Putting boiler back into operation 48
11. Control stops and faults 49
11.1 General 49
11.2 Control stops and faults 49
11.3 Control stop codes 49
11.4 Fault codes 51
11.5 Control stop - and fault memory 54
11.5.1 Reading faults 55
11.5.2 Deleting control stops or faults 55
114494-03
3
Table of contents
GAS 210 ECO PRO
12. Service parts 56
12.1 General 56
12.2 Exploded view 57
13. Regulations 58
13.1 General 58
13.2 Standards 58
13.3 Remeha factory test 58
13.4 Supplementary guidelines 59
14. Technical specifications 60
14.1 Technical data 60
15. Efficiency data and gas inspection labels 61
15.1 Unit usable efficiency (HR efficiency) 61
15.2 Water-side efficiency 61
15.3 Zero-load losses 61
15.4 Description of specifications 61
15.5 Accessories 62
15.6 Services 62
15.7 Type of unit 63
15.8 Operating principle 64
15.9 Boiler Control 64
15.9.1 Temperature control 64
15.9.2 Low water level protection 64
15.9.3 Maximum protection 65
15.9.4 Frost protection 65
16. Application data 66
16.1 General 66
16.2 Air and flue gas application options 66
16.3 Hydraulic application options 66
16.4 Cascade application 66
16.5 Control options 69
16.6 Gas application options 69
17. Checklists (records) 70
17.1 Checklist for commissioning (Commissioning record) 70
17.2 Checklist for annual inspection (inspection record) 70
17.3 Checklist for maintenance (maintenance record) 71
4
114494-03
GAS 210 ECO PRO
Table of contents
114494-03
5
Preface
Preface
GAS 210 ECO PRO
PREFACE
This technical information , which contains a lot of practical infor­mation about the Remeha Gas 210 ECO PRO, a High efficiency central heating unit, is mainly intended for installers. It contains important instructions for safe and trouble-free operation of the boiler before commissioning and during operation. Read these instructions carefully before putting the boiler into operation, familiarise yourself with its control functions, operation and strictly observe the instructions given. Failure to do so may invalidate warranty or prevent the boiler from operating. The boiler is available in the following types:
- Gas 210 ECO PRO 80 (3 sections; 87 kW)
- Gas 210 ECO PRO 120 (4 sections; 120 kW)
- Gas 210 ECO PRO 160 (5 sections; 166 kW)
- Gas 210 ECO PRO 200 (6 sections; 200 kW)
The installation, commissioning, inspection and servicing of the boiler must be carried out by a competent Corgi registered engi­neer who holds valid A.C.S. certification and in accordance with current gas safety (installation and use) regulations, the building regulations and all other relevant codes of practice. All electrical work must be carried out by a competent engineer and to be installed in accordance with the current IEE regulations.
If you have any questions, require an engineer to call on site, or if you need more information about specific subjects relating to this boiler, or it's installation please do not hesitate to contact our tech­nical help line 0118 978 3434.
When contacting Broag with a problem on the boiler, please have available the boiler type, Serial No (located on the bottom of the casing), and the symptoms or fault code (the fault code is a series of flashing digits in the display panel).
The data published in these technical instructions is based on the latest information (at date of publication) and may be subject to revisions. We reserve the right to continuous development in both design and manufacture, therefore any changes to the materials or tech­nology employed may not be retrospective nor may we be obliged to adjust earlier supplies accordingly.
6
114494-03
GAS 210 ECO PRO
1. EC declaration
EC - DECLARATION OF CONFORMITY
Manufacturer : Remeha B.V. Address : Kanaal Zuid 110 City, Country : Postbus 32, NL-7300 AA Apeldoorn, Holland
- this is to declare that the following product(s) : Remeha Gas 210 ECO PRO
is/are in conformity with the following EEC-directives:
EEC- Directive: 90/396/EEC tested and examined to the following norms:
EN 656 A1
15240
92/42/EEC 73/23/EEC DIN EN 50165
DIN EN 60335-1
, EN 15417
(2006)
(2006)
(2006)
, EN 50165
(2001)
, EN 60335-1
(2003)
(1997 + A1: 2001)
07
(2002)
1. EC declaration
89/336/EEC EN 55014-1
EN 61000-3-2
(2000+A1:2001)
(2000+A2:2005)
97/23/EEC (article 3, sub 3)
Apeldoorn, aug. 2007
W.F. Tijhuis Approval manager
, 55014-2
, 61000-3-3
(1997+A1:2001)
(1995+A1:2001)
114494-03
7
2. Introduction
2. Introduction
2.1 Pictograms used
2.2 Important instructions
GAS 210 ECO PRO
The following pictograms are used in this document to emphasise certain instructions. This is in order to increase your personal safety and to safeguard the technical reliability of the boiler. The pictograms used are:
Useful advice.Important instruction for carrying out an action. Possible risk of bodily injury or material damage to boiler,
building or environment.
Possible risk of electrical shocks. Serious bodily injury may
occur.
The boiler must be installed in a frost-free area.
Work on the boiler
Installation, commissioning, maintenance and repair work may only be carried out by suitably qualified specialist installers in accordance with the applicable national and local standards and guidelines.Always disconnect the mains supply and close the main gas cock when working on the boiler. Check the entire system for leaks after maintenance and servicing work.
Casing panels may only be removed for maintenance and servic­ing purposes. Refit all panels on completion of maintenance and servicing work.
Instruction and warning labels on the boiler must never be removed or covered and must be clearly legible throughout the entire service life of the boiler. Replace damaged or illegible instruction and warning labels immediately. Generally applicable safety instructions related to accident prevention must be con­sulted in addition to the information supplied in this technical docu­mentation.
Boiler modifications Modifications to the boiler require the written approval of Broag.
Keep this document near to the installation.
8
114494-03
GAS 210 ECO PRO
3. Safety
3. Safety
Adhere strictly to the specific safety instructions.
Can you smell gas? Proceed as follows:
• do not smoke and avoid fire and sparks
• do not operate electrical switches.
• close the gas cock.
• open doors and windows.
• trace possible leaks and seal them off.
• if the leak is upstream of the gas meter, notify National Gas
Emergency Service tel: 0800 1110999.
Can you smell flue or combustion gases? Proceed as follows:
• isolate the mains power supply from the boiler.
• open doors and windows.
• trace possible leaks and seal them off.
114494-03
9
4. Installation
4. Installation
4.1 Scope of delivery and installation
The boiler is supplied fully assembled and protected. The boiler is placed on a pallet (70 x 130 cm, 145 cm high), which can be transported with a pallet truck, hand truck, forklift truck or 4-wheel transport boards. The packaging passes through all standard doors (minimum width of 74.5 cm).
The boiler is installed as follows:
- Position the pallet with the boiler in the boiler room;
- Remove the fixing bands and all other packaging (some components are packaged in the polystyrene cap);
- Lift the boiler from the pallet;
- Slide the boiler into the required position, using the recessed handles in the boiler base;
- Cover the boiler and do not operate it whilst dust creating construction processes or insulation to the pipe work etc. are carried out in the plant room.
GAS 210 ECO PRO
10
114494-03
GAS 210 ECO PRO
4.2 Dimensions
4. Installation
1200
1070 125
305160 140140 121
61
A
1272
61
316
152
1190
fig. 01 Elevation drawings
Connection Gas 210 ECO PRO 80/120/160 Gas 210 ECO PRO 200
É Flow Ê Return
Gas connection
Ò Condensate drain Ð Combustion air supply Ñ Flue gas outlet
1¼” male thread 1½” male thread (fit supplied adapter 1¼” > 1½”)
1¼” male thread 1½” male thread (fit supplied adapter 1¼” > 1½”)
1¼” male thread 1¼” male thread
Ø 32 mm external Ø 32 mm external
Ø 150 mm Ø 150 mm
Ø 150 mm Ø 150 mm
Dimension “A 1309 mm 1324 mm Ì Second return (option)
1¼” male thread 1¼” male thread
114494-03
450
114492LTAL21H001b
11
4. Installation
4.3 Installation and service clearances
Clearance of at least 60 cm is required at the front of the boiler. However, we recommend a clearance of 1 m. We recommend a clearance of at least 40 cm above the boiler control panel, at least 5 cm on the left side and at least 25 cm on the right side in con­nection with condensed water discharge. Install a gas cock in the immediate vicinity of/above the boiler.
GAS 210 ECO PRO
1050
1
1490
250119050
450600
1050
2
450600
3 4
2100
600450 450600
2930
250119050 2501190
1890
2501190450
1690
1190
250 250
fig. 02 Boiler room installation options
12
4501190
1690
50
114492LTAL21H002a
114494-03
GAS 210 ECO PRO
5. Water-side connections
5.1.1 Condensed water discharge
Discharge the condensed water directly into a foul water drain. In view of the acidity level of condensate (pH between 3 and 5), only use plastic material for the discharge pipe. After assembly, fill the trap with clean water. Make an open connection with the drain. The discharge pipe must slope down by at least 30 mm/m. Condensed water must not be discharged into gutters or rain water down pipes.
5.1.2 Water treatment
• Use untreated tap water only to fill the CH system.
• The pH value of the system water must be between 7 and 9.
• Where inhibitors are being used, please refer to Broag recom-
mendations in this section and follow the manufactures instructi­ons given.
If used correctly water treatment can improve the boilers efficiency and increase the anticipated life expectancy of the boiler.
5. Water-side connections
For further information a special document “Remeha water quality regulations” is available from Broag. The regulations mentioned in this document must be followed.
As most systems contain a variety of metals, it is considered good practice to provide some form of water treatment in order to pre­vent or reduce the following:
• Metallic corrosion
• Formation of scale and sludge
• Microbiological contamination
• Chemical changes in the untreated system water
All scale deposits, however small, will reduce the efficiency of the boiler and should be prevented.
Suitable chemicals and their use should be discussed with a spe­cialist water treatment company prior to carrying out any work (environmental aspects, health aspects). The specification of the system and manufacturers recommendations must be taken into account, along with the age and condition of the system. New sys­tems should be flushed thoroughly to BS 7593(1992) to remove all traces of flux, debris, grease and metal swarf generated dur­ing installation. Care to be taken with old systems to ensure any black metallic iron oxide sludge and other corrosive residues are removed, again by power flushing, ensuring that the system is drained completely from all low points.
114494-03
Please ensure that the new boiler plant is not in circuit when the flushing takes place, especially if cleansing chemicals are used to assist the process.
13
5. Water-side connections
GAS 210 ECO PRO
It is important to check the inhibitor concentration after installa­tion, system modifications, filling the system and every service in accordance with these instructions.
For the correct dosage and the suitability of inhibitors for use with our boilers and for further information on water treatment or sys­tem cleaning we advise direct contact with either of the following companies:
‘Copal®’ manufactured by: Fernox, Cookson Electronics Forsyth Road Sheerwater Woking Surrey GU21 5RZ Tel No: 01483 793200 Fax No: 01483 793201 Email: sales@fernox.com Website: www.fernox.com or:
Sentinal ‘X100®’ manufactured by: Sentinel Performance Solutions The Heath Business & Technical Park Runcorn Cheshire, WA7 4QX Tel No: 0800 389 4670 Fax No: 0800 389 4677 Email: info.uk@sentinel-solutions.net Website: www.sentinel-solutions.net
5.1.3 Pressure relief valve
Install an pressure relief valve in the system, in accordance with NEN 3028, between any valves and the boiler and in the flow pipe within 0.5 m of the boiler.
5.1.4 Circulation pump
The boiler is equipped with a pump switch to connect an external circulation pump. This pump is run once every 24 hours to prevent sticking (24 hour pump operation). Only on/off pumps can be con­trolled. For connections, see Section 8.3.6.
P (%)
V
D
0 10 20 30 40
35
T (°C)
114492LTAL21H031
fig. 03 Output control characteristic
V = full load P = heat output D = part load ∆T = temperature difference
14
The hydraulic resistance for the various output options of the boiler is as follows:
Boiler type
210-80 210-120 210-160 210-200
Hydraulic resistance at a dT of 20°C
mbar kPa mbar kPa
165 16,5 545 54,5 135 13,5 446 44,6 170 17,0 562 56,2 180 18,0 595 59,5
Hydraulic resistance at a dT of 10°C
5.1.5 Water flow
The maximum temperature difference between flow and return, and the maximum rate of rise of the flow temperature and boiler block temperature are limited by the boiler's modulating controls. As a result, the boiler is virtually unaffected by low water flow. However for a continuous supply of heat, the boiler requires a minimum flow of 30 % of the nominal flow at the relevant design temperatures.
114494-03
GAS 210 ECO PRO
114492LTAL21H003a
6. Gas-side connections
6.1 Gas connection
The boiler is suitable for use with natural gas and propane* cat­egory II department. All gas appliances must, by law, be installed by com­petent persons (e.g. Corgi). Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the law is complied with.
The gas connection is at the top of the boiler. We recommend installing a gas filter in the gas supply pipe to avoid pollution of the gas multiblock. The gas filter's resistance must not be so high that the minimum inlet gas pressure can no longer be achieved.
* Refer to Broag for using propane.
6.2 Gas pressure
6. Gas-side connections
. For other types of natural gas, consult our Technical
2H3P
5+6 L3+4 L
fig. 04 Gas multiblocks
6.3 Gas/air ratio control
The boiler has been factory set and tested by Remeha to natural gas (G20) - with an inlet pressure of 17 mbar. The boiler is suitable for 17 - 30 mbar inlet gas pressure. For propane (LPG), an inlet pressure of 37 - 50 mbar is required.
The boiler has a zero governor gas valve. This gas valve main­tains the ratio between the gas and air quantities in the burner at a constant level under variable loads. This ensures clean and reli­able combustion and high efficiency across the entire load range.
114494-03
15
7. Connecting the flue gas discharge and air supply
GAS 210 ECO PRO
7. Connecting the flue gas discharge and air supply
7.1 General
The Remeha Gas 210 PRO is suitable for conventional room ven­tilated or room sealed operation. Specify at the time of ordering if the boiler is to be supplied for room sealed operation. In that case, the boiler will be supplied with a purpose-designed room sealed terminal, air supply connection and some accessories. The air supply connection should rest on the heat exchanger underneath the boiler casing after removing the standard perforated air inlet cover. Horizontal components in the flue gas discharge system should slope towards the boiler. Horizontal components in the air supply system should slope towards the supply opening. Room sealed terminals should comply with the national require­ments for both horizontal and vertical outlet constructions. Care should be taken when siting flue exit positions as a vapour plume will be visible when the boiler is operational (flue gas tem­perature will be less than 80°C resulting in the water vapour con­densing out on contact with the air).
Classification due to discharging flue gases
The boiler is approved according to CE with classification:
Type B23: Conventional room ventilated appliance without draft diverter. Air supply from boiler room; flue gas discharge on roof. Type B23P: Conventional room ventilated boiler without draft diverter. Air supply from boiler room: flue gas discharge on roof, metal flue gas discharge with CE symbol, meets pressure class P1.
Type C13: Room sealed boiler, connected to combined wall outlet. Type C33: Room sealed appliance, connected to combined roof
outlet. Type C43: Room sealed appliance in cascade configuration, con­nected via two ducts to a common duct system serving more than one appliance. Type C53: Room sealed appliance, connected to separate ducts for the air supply and flue gas discharge, terminated in zones of different pressure. Type C63: Room sealed appliance, supplied without the terminal or the air supply and flue gas discharge ducts. Type C83: Room sealed appliance, connected to separate air supply and flue gas discharge duct, with flue gas discharge duct always in underpressure.
7.2 Conventional open flue installation
The open flue version extracts the necessary combustion air from the plant room or compartment. A table showing the maximum dis­charge lengths can be found in Section 7.2.1.
16
114494-03
GAS 210 ECO PRO
7. Connecting the flue gas discharge and air supply
• The air supply opening must stay open.
• The installation area or boiler room must be equipped with the
necessary combustion air supply openings. These openings must not be obstructed or shut off.
• The combustion air supply must be free of dust and chemically-
aggressive agents (such as trichloroethylene or halogenated hydrocarbons), as used in aerosol cans, certain types of adhesive, certain solvents and cleaning agents, and paint, etc.
7.2.1 Possible lengths for the flue gas discharge pipe
Conventional room ventilated, type B23 according to CE.
Maximum permitted flue gas discharge lengths (L) in m
Boiler type D (mm) Free discharge
100 18
210-80
110 35 130 +
fig. 05 Piping for the conventional room ventilated
110 20
210-120
210-160
210-200
130 48 150 +
130 22 150 45 180 +
130 14 150 31 180 +
table 01 Flue gas discharge table for the open version + = Lengths up to 50m possible. For longer lengths, consult our Technical department
When flue gas discharge pipes with diameters other than 150 mm are used, an adapter is required: Ø150/100mm, Ø150/110mm, Ø150/130mm or Ø150/180mm.
For each additional 90° or 45° bend, the pipe length must be reduced by the amount shown in table 02.
114494-03
D in mm length in m
90° bend 45° bend
Ø 100 R=½D 4.9 1.4 Ø 110 R=½D 5.4 5.1 Ø 130 R=D 1.8 1.0 Ø 150 R=D 2.1 1.2 Ø 180 R=D 2.5 1.4
table 02 Metres to be deducted per bend
17
7. Connecting the flue gas discharge and air supply
7.3 Room sealed installation
GAS 210 ECO PRO
The room sealed installation is based on the use of an air supply pipe connected directly to the boiler. This increases the number of installation options within a building, while the discharge location is subject to less stringent requirements because the air supply and flue gas discharge can be incorporated in the same pressure field. Additional ventilation will be required to the room/compartment in accordance with BS 6644-2005 (compartment ventilation). In addition, air from outside is usually cleaner, which has a ben­eficial effect on the boiler service life. An air supply and flue gas discharge table for the enclosed version of the boiler can be found
in table 03. For discharge in two different pressure fields, see Sec­tion 7.3.2.
The boilers can be installed on a flue dilution system, but must have a total flue break to avoid boiler controls being affected by the flue dilution fan pressures. For full details please contact Broag.
7.3.1 Possible lengths for the air supply and flue gas discharge
Room sealed appliance, type C33 according to CE.
Maximum acceptable flue gas discharge/air supply pipe
lengths (L) in m
Boiler Model
210-80
210-120
210-160
210-200
Pipe Ø D
(mm)
100 100 8 130 130 + 130 150 + 150 150 +
100 100 3 130 130 22 130 150 25 150 150 +
130 150 11 150 150 22 180 150
130 130 4 150 150 13 180 150 +
table 03 Air supply and flue gas discharge table for the
enclosed version
Calculated with
concentric roof feed-
through D
nominal
(mm)
[m]
+
0021H7900017
fig. 06 Piping for the room sealed appliance
18
+ = Lengths up to 30m possible. For longer lengths, consult our Technical department
114494-03
GAS 210 ECO PRO
7. Connecting the flue gas discharge and air supply
When air supply and flue gas discharge pipes with diameters other than 150 mm are used, adapters are required: Ø150/100mm, Ø150/110mm, Ø150/130mm or Ø150/180mm and, for connec­tion to our standard combined vertical roof feed-through sets, also Ø180/150mm, Ø130/150mm or Ø110/150mm.
For each additional 90° or 45° bend, the pipe length must be reduced by the amount shown in table 04.
D in mm length in m
90° bend 45° bend
Ø 100 R=½D 4.9 1.4 Ø 110 R=½D 5.4 5.1 Ø 130 R=D 1.8 1.0 Ø 150 R=D 2.1 1.2 Ø 180 R=D 2.5 1.4
table 04 Metres to be deducted per bend
For enclosed versions, combined vertical roof feed-through sets are available, as well as sealing plates for flat roofs, in accordance with the following drawings. Please consult our Technical depart­ment for this option.
Int
Int
Ext
Ext
Ext
Epo y l y rx a e
Ext
fig. 07 Vertical roof feed-through for room sealed operation
Pdf dakdoorvoer
114494-03
19
7. Connecting the flue gas discharge and air supply
GAS 210 ECO PRO
7.3.2 Discharge in different pressure areas
For installations where supply and discharge points are in two dif­ferent pressure zones CLV system please contact Broag Techni­cal Dept. for further details and advice. The maximum acceptable height difference between combustion air supply and flue gas discharge is 36 m and the maximum acceptable length of the air supply and flue gas discharge combined is shown in table 05.
fig. 08 Discharge in different pressure areas
20
Maximum permitted flue gas discharge and
air supply pipe lengths
Boiler model D in mm L in m
210-80 150 36 210-120 150 36 210-160 150 23 210-200 150 11
table 05 Air supply and flue gas discharge table for 'simplified
CLV system'
114494-03
GAS 210 ECO PRO
7. Connecting the flue gas discharge and air supply
7.3.3 Connection of flue gas discharge and choice of material
Connecting the flue gas discharge:
Remove the cap from the flue gas discharge opening Ñ;
• Fit the flue gas discharge pipes seamlessly together.
• Seams and joints must be airtight and watertight or fit seamlessly.
• Horizontal parts must be oriented towards the boiler at a gradient (min.
5 cm per metre).
• Connect the pipes stress-free.
• Flue gas discharge pipes longer than 2 m must be fixed separately and
must not rest on the boiler.
Flue gas discharge:
Material: Rigid single walled: stainless steel (316), aluminium or plastic (to comply with building regulations). Flexible: stainless steel (316). Construction: all joints and seams should be gastight and watertight with the horizontal runs graded towards the boiler (min. discharge 5 cm per meter) to allow condensate free drainage to the boiler. Flue gas discharg­es longer than 2 meters must be supported independently and may not rest on the boiler. The flue outlet should terminate with reduction cone and bird guard only (chinamans hat or GLC type terminals etc. should not be used).
7.3.4 Air supply connection and choice of material
Connecting air supply:
Remove air supply grille from the air supply opening Ð;
• Fit the air supply pipes seamlessly together.
• Seams and joints must be airtight and watertight or fit seamlessly.
• Horizontal parts must be oriented towards the discharge at a
gradient (min. 5 cm per metre).
• Connect the pipes stress-free.
Air supply:
Material: Single walled, rigid or flexible: aluminium, stainless steel and plastic (to comply with building regulations). Air supply ducts longer than 2 meters must be supported independently and may not rest on the boiler air inlet. Care must be taken to ensure that if water is able to enter the duct it will run away from the boiler air inlet connection or supply a suitable train c/w water seal trap.
7.3.5 Additional Directives
Please refer to the manufacturer’s instructions for the material in ques­tion when installing the flue gas discharge and air supply materials. If the flue gas discharge and air supply materials are not installed according to the instructions (e.g. they are not leakproof, not clamped in place etc.), this may cause hazardous situations and/or result in bodily injury. After assembly, check at least all flue gas and air–carrying parts for tightness.
114494-03
21
8. Control and electrical connections
8. Control and electrical connections
8.1 General
The boiler is equipped with electronic control and safety equip­ment with ionisation flame protection. The advanced boiler control (abc®), is a microprocessor that protects and controls the boiler. The boiler is fully prewired; all external connections are made on the terminal strips. Connect the boiler to the mains supply in accordance with the local electricity supplier's instructions and IEE regulations.
8.1.1 Boiler control
The heat output of the Remeha Gas 210 ECO PRO can be con­trolled as follows:
- Modulating, where the output modulates between the minimum
and maximum values on the basis of the flow temperature defined by the modulating controller.
- On/off control, where the heat output modulates between
the minimum and maximum values on the basis of the flow temperature set in the unit. This can be combined with an outside sensor so that the internal heating curve is used.
- Analogue control (0-10 V), where the heat output or
temperature is controlled by a 0-10 V signal, see Section 8.4.4. Only possible with optional 0 - 10 V control PCB (IF-01).
GAS 210 ECO PRO
8.1.2 Modulating controls general
The modulating nature of the boiler is used to maximum effect with a modulating controller based on room and/or outside tempera­tures. If the controller demands heat, the boiler supplies the heat output. If the controller demands a flow temperature, the boiler modulates to this value. This increases the number of operating hours and drastically reduces the number of starts. Combined with the fixed gas/air mixture, this results in greater efficiency. Various types of modulating controls can be connected, including the following:
- Modulating room control, see Section 8.1.3;
- Modulating weather-compensated control see Section 8.1.4;
- Modulating cascade control, see Section 8.1.5.
8.1.3 Modulating room control
The boiler is set up for communication via the OpenTherm pro­tocol. Modulating controllers can be connected according to the OpenTherm protocol, e.g. the Remeha iSense. The controller is mounted in a reference area. Connection is made with a two-core cable to the On/off - OT terminals of terminal strip X6 (not polarity sensitive).
8.1.4 Modulating weather-compensated control rematic
®
22
The following optional controller can be supplied by Broag-Reme­ha. The controller is supplied with a connection adapter and inter­face that are built into the boiler. The connections for this feature are fully pre-wired.
114494-03
Loading...
+ 50 hidden pages