7. Connecting the flue gas discharge and air supply 16
7.1 General 16
7.2 Conventional open flue installation 16
7.2.1 Possible lengths for the flue gas discharge pipe 17
7.3 Room sealed installation 18
7.3.1 Possible lengths for the air supply and flue gas discharge 18
7.3.2 Discharge in different pressure areas 20
7.3.3 Connection of flue gas discharge and choice of material 21
7.3.4 Air supply connection and choice of material 21
7.3.5 Additional Directives 21
8. Control and electrical connections 22
8.1 General 22
8.1.1 Boiler control 22
8.1.2 Modulating controls general 22
8.1.3 Modulating room control 22
8.1.4 Modulating weather-compensated control rematic® 22
8.1.5 Modulating cascade controller MC4 23
8.2 Electrical specifications 23
8.2.1 Mains voltage 23
8.2.2 Control box 23
8.2.3 Fuse ratings 24
8.3 Electrical connection options 24
8.3.1 Connection options of standard control unit (PCU-01) 24
8.3.2 On/off control (OT) 24
8.3.3 Modulating controls (OT) 24
8.3.4 External interlock (BL) 24
8.3.5 Input release (RL) 25
8.3.6 Circulation pump (Pump) 25
8.3.7Connecting a PC 25
2
114494-03
Page 3
GAS 210 ECO PRO
Table of contents
8.3.8 Connection options for the PCB - SCU - X01 25
8.4 Connection options for the optional 0 - 10 V control PCB (IF-01) 26
8.4.1 Connection status (Nc) 26
8.4.2 OTm connection 26
8.4.3 Analogue input (0 - 10 V) 27
8.4.4 Analogue output (0 - 10 V) 27
8.5 Connection options of the optional expanded control/protection PCB (SCU-S01) 28
8.5.1 Flue gas damper control (FgV) 28
8.5.2 Hydraulic valve control (HdV) 28
8.5.3 External gas valve control (EgV) 28
8.5.4 Operation signal and failure signal (Nc / No) 28
8.5.5 Water pressure sensor (Wps) 28
8.5.6 Outside temperature sensor (Tout) 29
8.5.7 Minimum gas pressure switch (Gps) 29
8.5.8 Gas leakage control (VPS; only for 210- 160 and 210- 200 boilers) 29
8.5.9 Wiring diagram 30
9 Commissioning 31
9.1 Control panel 31
9.1.1 Normal start-up procedure 31
9.1.2 Fault during start-up procedure 32
9.1.3 Reading current values 33
9.1.3.1 Status and sub status 34
9.1.4 Adjusting the boiler to the system 34
9.1.5 Changing parameters at user level (without access code) 35
9.1.6 Changing parameters at service level (with access code) 35
9.1.7 Resetting factory settings 38
9.1.8 Setting manual operation ( symbol) 39
9.2 Commissioning 39
9.3 Taking the boiler out of operation 42
9.3.1 Boiler with frost protection, out of operation for a long time 42
9.3.2 Boiler without frost protection, out of operation for a long time 42
10. Inspection and maintenance 43
10.1 General 43
10.2 Combustion check of the boiler 43
10.2.1 Corrective maintenance 43
10.2.2 Cleaning the fan 44
10.2.3 Cleaning the heat exchanger (flue gas side) 46
10.2.4 Cleaning the burner 47
10.3 Cleaning the trap 48
10.4 Checking the ignition electrode 48
10.5 Checking for leaks 48
10.6 Checking water pressure 48
10.7 Putting boiler back into operation 48
11. Control stops and faults 49
11.1 General 49
11.2 Control stops and faults 49
11.3 Control stop codes 49
11.4 Fault codes 51
11.5 Control stop - and fault memory 54
11.5.1 Reading faults 55
11.5.2 Deleting control stops or faults 55
114494-03
3
Page 4
Table of contents
GAS 210 ECO PRO
12. Service parts 56
12.1 General 56
12.2 Exploded view 57
13. Regulations 58
13.1 General 58
13.2 Standards 58
13.3 Remeha factory test 58
13.4 Supplementary guidelines 59
14. Technical specifications 60
14.1 Technical data 60
15. Efficiency data and gas inspection labels 61
15.1 Unit usable efficiency (HR efficiency) 61
15.2 Water-side efficiency 61
15.3 Zero-load losses 61
15.4 Description of specifications 61
15.5 Accessories 62
15.6 Services 62
15.7 Type of unit 63
15.8 Operating principle 64
15.9 Boiler Control 64
15.9.1 Temperature control 64
15.9.2 Low water level protection 64
15.9.3 Maximum protection 65
15.9.4 Frost protection 65
16. Application data 66
16.1 General 66
16.2 Air and flue gas application options 66
16.3 Hydraulic application options 66
16.4 Cascade application 66
16.5 Control options 69
16.6 Gas application options 69
17. Checklists (records) 70
17.1 Checklist for commissioning (Commissioning record) 70
17.2 Checklist for annual inspection (inspection record) 70
17.3 Checklist for maintenance (maintenance record) 71
4
114494-03
Page 5
GAS 210 ECO PRO
Table of contents
114494-03
5
Page 6
Preface
Preface
GAS 210 ECO PRO
PREFACE
This technical information , which contains a lot of practical information about the Remeha Gas 210 ECO PRO, a High efficiency
central heating unit, is mainly intended for installers. It contains
important instructions for safe and trouble-free operation of the
boiler before commissioning and during operation.
Read these instructions carefully before putting the boiler into
operation, familiarise yourself with its control functions, operation
and strictly observe the instructions given. Failure to do so may
invalidate warranty or prevent the boiler from operating. The boiler
is available in the following types:
- Gas 210 ECO PRO 80 (3 sections; 87 kW)
- Gas 210 ECO PRO 120 (4 sections; 120 kW)
- Gas 210 ECO PRO 160 (5 sections; 166 kW)
- Gas 210 ECO PRO 200 (6 sections; 200 kW)
The installation, commissioning, inspection and servicing of the
boiler must be carried out by a competent Corgi registered engineer who holds valid A.C.S. certification and in accordance with
current gas safety (installation and use) regulations, the building
regulations and all other relevant codes of practice.
All electrical work must be carried out by a competent engineer
and to be installed in accordance with the current IEE regulations.
If you have any questions, require an engineer to call on site, or if
you need more information about specific subjects relating to this
boiler, or it's installation please do not hesitate to contact our technical help line 0118 978 3434.
When contacting Broag with a problem on the boiler, please have
available the boiler type, Serial No (located on the bottom of the
casing), and the symptoms or fault code (the fault code is a series
of flashing digits in the display panel).
The data published in these technical instructions is based on the
latest information (at date of publication) and may be subject to
revisions.
We reserve the right to continuous development in both design
and manufacture, therefore any changes to the materials or technology employed may not be retrospective nor may we be obliged
to adjust earlier supplies accordingly.
6
114494-03
Page 7
GAS 210 ECO PRO
1. EC declaration
EC - DECLARATION OF CONFORMITY
Manufacturer : Remeha B.V.
Address : Kanaal Zuid 110
City, Country : Postbus 32, NL-7300 AA Apeldoorn, Holland
- this is to declare that the following product(s) : Remeha Gas 210 ECO PRO
is/are in conformity with the following EEC-directives:
EEC- Directive: 90/396/EEC tested and examined to the following norms:
EN 656 A1
15240
92/42/EEC
73/23/EEC DIN EN 50165
DIN EN 60335-1
, EN 15417
(2006)
(2006)
(2006)
, EN 50165
(2001)
, EN 60335-1
(2003)
(1997 + A1: 2001)
07
(2002)
1. EC declaration
89/336/EEC EN 55014-1
EN 61000-3-2
(2000+A1:2001)
(2000+A2:2005)
97/23/EEC (article 3, sub 3)
Apeldoorn, aug. 2007
W.F. Tijhuis
Approval manager
, 55014-2
, 61000-3-3
(1997+A1:2001)
(1995+A1:2001)
114494-03
7
Page 8
2. Introduction
2. Introduction
2.1 Pictograms used
2.2 Important instructions
GAS 210 ECO PRO
The following pictograms are used in this document to emphasise
certain instructions. This is in order to increase your personal
safety and to safeguard the technical reliability of the boiler. The
pictograms used are:
Useful advice.
Important instruction forcarryingout an action.
Possible risk of bodily injury or material damage to boiler,
building or environment.
Possible risk of electrical shocks. Serious bodily injury may
occur.
The boiler must be installed in a frost-free area.
Work on the boiler
Installation, commissioning, maintenance and repair work may
only be carried out by suitably qualified specialist installers in
accordance with the applicable national and local standards and
guidelines.Always disconnect the mains supply and close the main
gas cock when working on the boiler. Check the entire system for
leaks after maintenance and servicing work.
Casing panels may only be removed for maintenance and servicing purposes. Refit all panels on completion of maintenance and
servicing work.
Instruction and warning labels on the boiler must never be
removed or covered and must be clearly legible throughout the
entire service life of the boiler. Replace damaged or illegible
instruction and warning labels immediately. Generally applicable
safety instructions related to accident prevention must be consulted in addition to the information supplied in this technical documentation.
Boiler modifications
Modifications to the boilerrequire the written approval of Broag.
Keep this document near to the installation.
8
114494-03
Page 9
GAS 210 ECO PRO
3. Safety
3. Safety
Adhere strictly to the specific safety instructions.
Can you smell gas? Proceed as follows:
• do not smoke and avoid fire and sparks
• do not operate electrical switches.
• close the gas cock.
• open doors and windows.
• trace possible leaks and seal them off.
• if the leak is upstream of the gas meter, notify National Gas
Emergency Service tel: 0800 1110999.
Can you smell flue or combustion gases? Proceed as follows:
• isolate the mains power supply from the boiler.
• open doors and windows.
• trace possible leaks and seal them off.
114494-03
9
Page 10
4. Installation
4. Installation
4.1 Scope of delivery and installation
The boiler is supplied fully assembled and protected. The boiler
is placed on a pallet (70 x 130 cm, 145 cm high), which can be
transported with a pallet truck, hand truck, forklift truck or 4-wheel
transport boards. The packaging passes through all standard
doors (minimum width of 74.5 cm).
The boiler is installed as follows:
- Position the pallet with the boiler in the boiler room;
- Remove the fixing bands and all other packaging (some
components are packaged in the polystyrene cap);
- Lift the boiler from the pallet;
- Slide the boiler into the required position, using the recessed
handles in the boiler base;
- Cover the boiler and do not operate it whilst dust creating
construction processes or insulation to the pipe work etc. are
carried out in the plant room.
GAS 210 ECO PRO
10
114494-03
Page 11
GAS 210 ECO PRO
4.2 Dimensions
4. Installation
1200
1070125
305160140140121
61
A
1272
61
316
152
1190
fig. 01 Elevation drawings
ConnectionGas 210 ECO PRO 80/120/160Gas 210 ECO PRO 200
É Flow
Ê Return
Gas connection
Ò Condensate drain
Ð Combustion air supply
Ñ Flue gas outlet
1¼” male thread1½” male thread (fit supplied adapter 1¼” > 1½”)
1¼” male thread1½” male thread (fit supplied adapter 1¼” > 1½”)
1¼” male thread1¼” male thread
Ø 32 mm externalØ 32 mm external
Ø 150 mmØ 150 mm
Ø 150 mmØ 150 mm
Dimension “A” 1309 mm1324 mm
Ì Second return (option)
1¼” male thread1¼” male thread
114494-03
450
114492LTAL21H001b
11
Page 12
4. Installation
4.3 Installation and service clearances
Clearance of at least 60 cm is required at the front of the boiler.
However, we recommend a clearance of 1 m. We recommend a
clearance of at least 40 cm above the boiler control panel, at least
5 cm on the left side and at least 25 cm on the right side in connection with condensed water discharge. Install a gas cock in the
immediate vicinity of/above the boiler.
GAS 210 ECO PRO
1050
1
1490
250119050
450600
1050
2
450600
34
2100
600450450600
2930
2501190502501190
1890
2501190450
1690
1190
250250
fig. 02 Boiler room installation options
12
4501190
1690
50
114492LTAL21H002a
114494-03
Page 13
GAS 210 ECO PRO
5. Water-side connections
5.1.1 Condensed water discharge
Discharge the condensed water directly into a foul water drain. In
view of the acidity level of condensate (pH between 3 and 5), only
use plastic material for the discharge pipe. After assembly, fill the
trap with clean water. Make an open connection with the drain. The
discharge pipe must slope down by at least 30 mm/m. Condensed
water must not be discharged into gutters or rain water down pipes.
5.1.2 Water treatment
• Use untreated tap water only to fill the CH system.
• The pH value of the system water must be between 7 and 9.
• Where inhibitors are being used, please refer to Broag recom-
mendations in this section and follow the manufactures instructions given.
If used correctly water treatment can improve the boilers efficiency
and increase the anticipated life expectancy of the boiler.
5. Water-side connections
For further information a special document “Remeha water quality
regulations” is available from Broag. The regulations mentioned in
this document must be followed.
As most systems contain a variety of metals, it is considered good
practice to provide some form of water treatment in order to prevent or reduce the following:
• Metallic corrosion
• Formation of scale and sludge
• Microbiological contamination
• Chemical changes in the untreated system water
All scale deposits, however small, will reduce the efficiency of the
boiler and should be prevented.
Suitable chemicals and their use should be discussed with a specialist water treatment company prior to carrying out any work
(environmental aspects, health aspects). The specification of the
system and manufacturers recommendations must be taken into
account, along with the age and condition of the system. New systems should be flushed thoroughly to BS 7593(1992) to remove
all traces of flux, debris, grease and metal swarf generated during installation. Care to be taken with old systems to ensure any
black metallic iron oxide sludge and other corrosive residues are
removed, again by power flushing, ensuring that the system is
drained completely from all low points.
114494-03
Please ensure that the new boiler plant is not in circuit when the
flushing takes place, especially if cleansing chemicals are used to
assist the process.
13
Page 14
5. Water-side connections
GAS 210 ECO PRO
It is important to check the inhibitor concentration after installation, system modifications, filling the system and every service in
accordance with these instructions.
For the correct dosage and the suitability of inhibitors for use with
our boilers and for further information on water treatment or system cleaning we advise direct contact with either of the following
companies:
Sentinal ‘X100®’ manufactured by:
Sentinel Performance Solutions
The Heath Business & Technical
Park
Runcorn
Cheshire,
WA7 4QX
Tel No: 0800 389 4670
Fax No: 0800 389 4677
Email: info.uk@sentinel-solutions.net
Website: www.sentinel-solutions.net
5.1.3 Pressure relief valve
Install an pressure relief valve in the system, in accordance with
NEN 3028, between any valves and the boiler and in the flow pipe
within 0.5 m of the boiler.
5.1.4 Circulation pump
The boiler is equipped with a pump switch to connect an external
circulation pump. This pump is run once every 24 hours to prevent
sticking (24 hour pump operation). Only on/off pumps can be controlled. For connections, see Section 8.3.6.
P (%)
V
D
010203040
35
∆T (°C)
114492LTAL21H031
fig. 03 Output control characteristic
V = full loadP = heat output
D = part load∆T = temperature difference
14
The hydraulic resistance for the various output options of the
boiler is as follows:
The maximum temperature difference between flow and return,
and the maximum rate of rise of the flow temperature and boiler
block temperature are limited by the boiler's modulating controls.
As a result, the boiler is virtually unaffected by low water flow.
However for a continuous supply of heat, the boiler requires a
minimum flow of 30 % of the nominal flow at the relevant design
temperatures.
114494-03
Page 15
GAS 210 ECO PRO
114492LTAL21H003a
6. Gas-side connections
6.1 Gas connection
The boiler is suitable for use with natural gas and propane* category II
department. All gas appliances must, by law, be installed by competent persons (e.g. Corgi). Failure to install appliances correctly
could lead to prosecution. It is in your own interest and that of
safety to ensure that the law is complied with.
The gas connection is at the top of the boiler. We recommend
installing a gas filter in the gas supply pipe to avoid pollution of the
gas multiblock. The gas filter's resistance must not be so high that
the minimum inlet gas pressure can no longer be achieved.
* Refer to Broag for using propane.
6.2 Gas pressure
6. Gas-side connections
. For other types of natural gas, consult our Technical
2H3P
5+6 L3+4 L
fig. 04 Gas multiblocks
6.3 Gas/air ratio control
The boiler has been factory set and tested by Remeha to natural
gas (G20) - with an inlet pressure of 17 mbar.
The boiler is suitable for 17 - 30 mbar inlet gas pressure.
For propane (LPG), an inlet pressure of 37 - 50 mbar is required.
The boiler has a zero governor gas valve. This gas valve maintains the ratio between the gas and air quantities in the burner at
a constant level under variable loads. This ensures clean and reliable combustion and high efficiency across the entire load range.
114494-03
15
Page 16
7. Connecting the flue gas discharge and air supply
GAS 210 ECO PRO
7. Connecting the flue gas discharge and air supply
7.1 General
The Remeha Gas 210 PRO is suitable for conventional room ventilated or room sealed operation. Specify at the time of ordering if
the boiler is to be supplied for room sealed operation. In that case,
the boiler will be supplied with a purpose-designed room sealed
terminal, air supply connection and some accessories. The air
supply connection should rest on the heat exchanger underneath
the boiler casing after removing the standard perforated air inlet
cover. Horizontal components in the flue gas discharge system
should slope towards the boiler. Horizontal components in the air
supply system should slope towards the supply opening.
Room sealed terminals should comply with the national requirements for both horizontal and vertical outlet constructions.
Care should be taken when siting flue exit positions as a vapour
plume will be visible when the boiler is operational (flue gas temperature will be less than 80°C resulting in the water vapour condensing out on contact with the air).
Classification due to discharging flue gases
The boiler is approved according to CE with classification:
Type B23: Conventional room ventilated appliance without draft
diverter. Air supply from boiler room; flue gas discharge on roof.
Type B23P: Conventional room ventilated boiler without draft
diverter. Air supply from boiler room: flue gas discharge on roof,
metal flue gas discharge with CE symbol, meets pressure class P1.
Type C13: Room sealed boiler, connected to combined wall outlet.
Type C33: Room sealed appliance, connected to combined roof
outlet.
Type C43: Room sealed appliance in cascade configuration, connected via two ducts to a common duct system serving more than
one appliance.
Type C53: Room sealed appliance, connected to separate ducts
for the air supply and flue gas discharge, terminated in zones of
different pressure.
Type C63: Room sealed appliance, supplied without the terminal
or the air supply and flue gas discharge ducts.
Type C83: Room sealed appliance, connected to separate air
supply and flue gas discharge duct, with flue gas discharge duct
always in underpressure.
7.2 Conventional open flue installation
The open flue version extracts the necessary combustion air from
the plant room or compartment. A table showing the maximum discharge lengths can be found in Section 7.2.1.
16
114494-03
Page 17
GAS 210 ECO PRO
7. Connecting the flue gas discharge and air supply
• The air supply opening must stay open.
• The installation area or boiler room must be equipped with the
necessary combustion air supply openings. These openings
must not be obstructed or shut off.
• The combustion air supply must be free of dust and chemically-
aggressive agents (such as trichloroethylene or halogenated
hydrocarbons), as used in aerosol cans, certain types of
adhesive, certain solvents and cleaning agents, and paint, etc.
7.2.1 Possible lengths for the flue gas discharge pipe
Conventional room ventilated, type B23 according to CE.
Maximum permitted flue gas discharge lengths (L) in m
Boiler typeD (mm)Free discharge
10018
210-80
11035
130+
fig. 05 Piping for the conventional room ventilated
11020
210-120
210-160
210-200
13048
150+
13022
15045
180+
13014
15031
180+
table 01 Flue gas discharge table for the open version
+ = Lengths up to 50m possible. For longer lengths, consult our
Technical department
When flue gas discharge pipes with diameters other than 150 mm
are used, an adapter is required: Ø150/100mm, Ø150/110mm,
Ø150/130mm or Ø150/180mm.
For each additional 90° or 45° bend, the pipe length must be
reduced by the amount shown in table 02.
7. Connecting the flue gas discharge and air supply
7.3 Room sealed installation
GAS 210 ECO PRO
The room sealed installation is based on the use of an air supply
pipe connected directly to the boiler. This increases the number of
installation options within a building, while the discharge location is
subject to less stringent requirements because the air supply and
flue gas discharge can be incorporated in the same pressure field.
Additional ventilation will be required to the room/compartment in
accordance with BS 6644-2005 (compartment ventilation).
In addition, air from outside is usually cleaner, which has a beneficial effect on the boiler service life. An air supply and flue gas
discharge table for the enclosed version of the boiler can be found
in table 03. For discharge in two different pressure fields, see Section 7.3.2.
The boilers can be installed on a flue dilution system, but must
have a total flue break to avoid boiler controls being affected
by the flue dilution fan pressures. For full details please contact
Broag.
7.3.1 Possible lengths for the air supply and flue
gas discharge
Room sealed appliance, type C33 according to CE.
Maximum acceptable flue gas discharge/air supply pipe
lengths (L) in m
Boiler
Model
210-80
210-120
210-160
210-200
Pipe Ø D
(mm)
1001008
130130+
130150+
150150+
1001003
13013022
13015025
150150+
13015011
15015022
180150
1301304
15015013
180150+
table 03 Air supply and flue gas discharge table for the
enclosed version
Calculated with
concentric roof feed-
through D
nominal
(mm)
[m]
+
0021H7900017
fig. 06 Piping for the room sealed appliance
18
+ = Lengths up to 30m possible. For longer lengths, consult
our Technical department
114494-03
Page 19
GAS 210 ECO PRO
7. Connecting the flue gas discharge and air supply
When air supply and flue gas discharge pipes with diameters other
than 150 mm are used, adapters are required: Ø150/100mm,
Ø150/110mm, Ø150/130mm or Ø150/180mm and, for connection to our standard combined vertical roof feed-through sets, also
Ø180/150mm, Ø130/150mm or Ø110/150mm.
For each additional 90° or 45° bend, the pipe length must be
reduced by the amount shown in table 04.
For enclosed versions, combined vertical roof feed-through sets
are available, as well as sealing plates for flat roofs, in accordance
with the following drawings. Please consult our Technical department for this option.
Int
Int
Ext
Ext
Ext
Epo y l y rx a e
Ext
fig. 07 Vertical roof feed-through for room sealed operation
Pdf dakdoorvoer
114494-03
19
Page 20
7. Connecting the flue gas discharge and air supply
GAS 210 ECO PRO
7.3.2 Discharge in different pressure areas
For installations where supply and discharge points are in two different pressure zones CLV system please contact Broag Technical Dept. for further details and advice. The maximum acceptable
height difference between combustion air supply and flue gas
discharge is 36 m and the maximum acceptable length of the air
supply and flue gas discharge combined is shown in table 05.
table 05 Air supply and flue gas discharge table for 'simplified
CLV system'
114494-03
Page 21
GAS 210 ECO PRO
7. Connecting the flue gas discharge and air supply
7.3.3 Connection of flue gas discharge and choice
of material
Connecting the flue gas discharge:
Remove the cap from the flue gas discharge opening Ñ;
• Fit the flue gas discharge pipes seamlessly together.
• Seams and joints must be airtight and watertight or fit seamlessly.
• Horizontal parts must be oriented towards the boiler at a gradient (min.
5 cm per metre).
• Connect the pipes stress-free.
• Flue gas discharge pipes longer than 2 m must be fixed separately and
must not rest on the boiler.
Flue gas discharge:
Material:
Rigid single walled: stainless steel (316), aluminium or plastic (to comply
with building regulations).
Flexible: stainless steel (316).
Construction: all joints and seams should be gastight and watertight with
the horizontal runs graded towards the boiler (min. discharge 5 cm per
meter) to allow condensate free drainage to the boiler. Flue gas discharges longer than 2 meters must be supported independently and may not
rest on the boiler.
The flue outlet should terminate with reduction cone and bird guard only
(chinamans hat or GLC type terminals etc. should not be used).
7.3.4 Air supply connection and choice of material
Connecting air supply:
Remove air supply grille from the air supply opening Ð;
• Fit the air supply pipes seamlessly together.
• Seams and joints must be airtight and watertight or fit seamlessly.
• Horizontal parts must be oriented towards the discharge at a
gradient (min. 5 cm per metre).
• Connect the pipes stress-free.
Air supply:
Material:
Single walled, rigid or flexible: aluminium, stainless steel and plastic (to
comply with building regulations).
Air supply ducts longer than 2 meters must be supported independently
and may not rest on the boiler air inlet. Care must be taken to ensure that
if water is able to enter the duct it will run away from the boiler air inlet
connection or supply a suitable train c/w water seal trap.
7.3.5 Additional Directives
Please refer to the manufacturer’s instructions for the material in question when installing the flue gas discharge and air supply materials. If the
flue gas discharge and air supply materials are not installed according to
the instructions (e.g. they are not leakproof, not clamped in place etc.),
this may cause hazardous situations and/or result in bodily injury. After
assembly, check at least all flue gas and air–carrying parts for tightness.
114494-03
21
Page 22
8. Control and electrical connections
8. Control and electrical connections
8.1 General
The boiler is equipped with electronic control and safety equipment with ionisation flame protection. The advanced boiler control
(abc®), is a microprocessor that protects and controls the boiler.
The boiler is fully prewired; all external connections are made
on the terminal strips. Connect the boiler to the mains supply in
accordance with the local electricity supplier's instructions and IEE
regulations.
8.1.1 Boiler control
The heat output of the Remeha Gas 210 ECO PRO can be controlled as follows:
- Modulating, where the output modulates between the minimum
and maximum values on the basis of the flow temperature
defined by the modulating controller.
- On/off control, where the heat output modulates between
the minimum and maximum values on the basis of the flow
temperature set in the unit. This can be combined with an
outside sensor so that the internal heating curve is used.
- Analogue control (0-10 V), where the heat output or
temperature is controlled by a 0-10 V signal, see Section 8.4.4.
Only possible with optional 0 - 10 V control PCB (IF-01).
GAS 210 ECO PRO
8.1.2 Modulating controls general
The modulating nature of the boiler is used to maximum effect with
a modulating controller based on room and/or outside temperatures. If the controller demands heat, the boiler supplies the heat
output. If the controller demands a flow temperature, the boiler
modulates to this value. This increases the number of operating
hours and drastically reduces the number of starts. Combined with
the fixed gas/air mixture, this results in greater efficiency.
Various types of modulating controls can be connected, including
the following:
- Modulating room control, see Section 8.1.3;
- Modulating weather-compensated control see Section 8.1.4;
- Modulating cascade control, see Section 8.1.5.
8.1.3 Modulating room control
The boiler is set up for communication via the OpenTherm protocol. Modulating controllers can be connected according to the
OpenTherm protocol, e.g. the Remeha iSense. The controller is
mounted in a reference area. Connection is made with a two-core
cable to the On/off - OT terminals of terminal strip X6 (not polarity
sensitive).
8.1.4 Modulating weather-compensated control
rematic
®
22
The following optional controller can be supplied by Broag-Remeha. The controller is supplied with a connection adapter and interface that are built into the boiler. The connections for this feature
are fully pre-wired.
114494-03
Page 23
GAS 210 ECO PRO
8. Control and electrical connections
rematic® 2945 C3 K
In addition to the weather-compensated boiler pre-control, this
controller provides optimum start, dual zone weather compensation and priority DHW (if required). Fit the controller in the boiler.
Connection takes place using the supplied rematic® adapter and
the supplied interface that can be integrated in the control panel.
Refer to the relevant controller documentation for detailed information.
8.1.5 Modulating cascade controller MC4
The Remeha Celcia MC4 cascade controller is suitable for the
modulated control of 2 to 4 Remeha Gas 210 PRO boilers in cascade. This controller is wall-mounted and communicates according
the OpenTherm protocol. We recommend using our Celcia MC4
modulating cascade controller in conjunction with the iSenseTime/
Weather compensation controller. Refer to the relevant controller
documentation for detailed information.
iSense with MC4 will only control up to 4 boilers
in cascade
8.2 Electrical specifications
230Vac, 50Hz, F6.3AT
L
N
8.2.1 Mains voltage
The boiler is suitable for a 230 V-50 Hz supply with live/neutral/
earth (the control is phase/neutral sensitive). Other connection
values are only acceptable if an isolating transformer is installed.
Connect the mains lead (not supplied) to the 230 V terminal strip.
8.2.2 Control box
Mains voltage : 230 V/50 Hz
Power consumption at: stand-by/low load/full load:
- 210-80 : 4 / 36 / 125 W
- 210-120 : 4 / 37 / 193 W
- 210-160 : 4 / 53 / 206 W
- 210-200 : 4 / 54 / 317 W
Safety time: 3.5 s
Anti-hunting time: Adaptive 1 - 10 minutes.
Pump post-circulation time: adjustable between 0 and 98 minutes
or continuous (= 99 minutes), set by default to 3 minutes
Max. power consumption of external pump: 300 VA.
fig. 09 Connect mains lead
114494-03
114492LTAL21H004a
8.2.3 Fuse ratings
The 230 V terminal strip contains the fuse F - 6.3 AT.
This is a general fuse for all connected components.
The control unit contains the fuse F1 - 1.6 AT.
This is a fuse for the mains voltage of the control unit, gas multiblock and ignition, excluding pump.
23
Page 24
Mainson/of
N
N L
Pump
L
OT BL RL
OT BL RL
X6
X1
X11
X10
X9
X7
X8
X2
X3
X5
X4
F1 1.6 AT
PCU-01
SU
N L
Pump
X9X11 X10
1
4x
2
114492LTAL21H005e
8. Control and electrical connections
8.3 Electrical connection options
GAS 210 ECO PRO
The boiler has several control, protection and regulation connection options. The standard control PCB (PCU-01) can for example
be expanded with:
• an optional 0 - 10 V control PCB (available as an accessory IF-01);
• and/or the optional expanded control/protection PCB (available as
an accessory SCU-SO1).
To install or access these PCBs, the plastic cap must be removed
from the control panel. The required external connections are
made on these (optional) PCBs. The various connection options
are detailed in the following sections.
8.3.1 Connection options of standard control unit
(PCU-01)
Connected on the standard control unit (PCU-01) is the safety unit
(SU) connected, which protects the boiler.
8.3.2 On/off control (OT)
The boiler is suitable for connection to a ‘volt free’ on/off controller.
Connect the controller to the On/off - OT terminals of terminal
strip X6 (not polarity sensitive).
8.3.3 Modulating controls (OT)
The boiler is set up for communication via the OpenTherm protocol. Modulating controllers can be connected.
Connection is made with a two-core cable to the On/off - OT terminals of terminal strip X6 (it does not matter which wire is connected to which cable clamp).
8.3.4 External interlock (BL)
The boiler has an external interlock switch, so that the boiler can
be shutdown in the event that this switch is not made. This input
can be used in combination with a flue gas thermostat (available
as an accessory). This input relates to the BL terminals of terminal
strip X6. Remove the wire bridge before using the input.
The input's behaviour depends on the parameter 33 setting:
1 = Normal shutdown;
2 = Shutdown without frost-protection (= default);
3 = Lock out.
fig. 10 Standard control PCB (PCU-01) with
24
safety unit (SU)
114494-03
Page 25
GAS 210 ECO PRO
8. Control and electrical connections
X3
X2
X11
PCU-01
X9X11X10
X9
X10
X8
Recom
X1
fig. 11 Connecting a PC
F1 1.6 AT
X7
X4
N L
Pump
Mainson/of
X5
X6
www.remeha.com
Pump
L
N
OT BL RL
N L
The boiler is also equipped with an input release so that the burner can be released/shutdown. This input can be used in combination with the limit switches on flue gas throttle valves, hydraulic
control valves, safety interlocks, etc. This input relates to the RL
terminals of terminal strip X6.
8.3.6 Circulation pump (Pump)
8.3.5 Input release (RL)
OT BL RL
A pump with the following specifications can be connected:
- On/off pump with a mains voltage of 230 VAC (50 Hz) and 300
VA (maximum).
Connect the pump to the Pump terminals of terminal strip X4. The
post-circulation time of the circulation pump at the end of a heat
demand can be set according to requirements by means of a program option at user level, see Section 9.1.6.
8.3.7 Connecting a PC
T000058
Using the optional Recom interface package a PC can be connected to the X7 “telephone connector”.
Using the Recom software you can load, change and download
various boiler settings and readings.
See the user instructions supplied with the software.
8.3.8 Connection options for the PCB - SCU - X01
X3
cNoNC
cNoNC
sutatS
SCU-X01
cNoNC
cNoNC
sutatS
X4
X2a
3
2
4
1
5
0
00
6
9
7
8
3
2
4
1
5
0
6
9
7
8
X2
Nr0123456789
Alarm
Descrip-
tion
Alarm
inverted
= fail
BurningBurning
safe
StandbyC-NOC-NCC-NOC-NCC-NOC-NONANANAC-NO
ActiveC-NCC-NOC-NCC-NOC-NCC-NCNANANAC-NC
114494-03
The PCB - SCU - X01 is equipped with two potential-free outputs
that have a capacity of max. 230 VAC/5 A reactive/2 A inductive
(cos 0.6). It also has two rotary switches with ten positions.
See the table below for the rotary switch settings.
inverted
Burning
low
Burning
high
Service
report
CH-
mode
DWH-
mode
CH-
pump
25
Page 26
8. Control and electrical connections
8.4 Connection options for 0 - 10 V control PCB (IF-01)
8.4.1 Connection status (Nc)
If the boiler locks out, a relay is de-energised and the alarm can
be transmitted via a potential-free contact
(maximum 230 V, 1 A) on terminals Nc and C of terminal strip X4.
8.4.2 OTm connection
The interface uses OpenTherm to communicate with the boiler
control. The OTm connection on terminal strip X5 must therefore
be connected to the OpenTherm OT input of the boiler control.
1
%
2
X5
GAS 210 ECO PRO
IF-01
X1
fig. 12 Jumper 2
X4
Status0-10 0-10
114492LTAL21H006a
OTm 0 + 0 +
Nc NoOTm 0 + 0 +C
Nc NoC
26
114494-03
Page 27
GAS 210 ECO PRO
1
%
2
8. Control and electrical connections
8.4.3 Analogue input (0 - 10 V)
This control can be based on temperature or heat output (optional). The two controls are described briefly below. Connect the 0
- 10 V signal to the interface input for analogue control.
Analogue temperature-based control ()
The 0-10 V signal controls the boiler flow temperature between
0°C and 100°C. This control modulates on the basis of flow temperature, where the heat output varies between the minimum and
2
2
maximum values on the basis of the set point flow temperature
calculated by the controller.
Jumper (2) on the interface is used to select either temperature ()
or boiler output (%) control.
fig. 13 Jumper 2
114492LTAL21H023a
Jumper2Input signal
[V]
Temperature
[°C]
Description
0 - 1,50 - 15Boiler off
1,5 - 1,8 15 - 18Hysteresis
1,8 - 10 18 -100 Desired temperature
table 06 Analog input signal for temperature
Analogue output-based control (%)
The 0-10 V signal controls the boiler output between 0% and
100%, where the minimum and maximum values are limited. The
minimum output is linked to the boiler's modulation depth. This
control is output modulated, where the output varies between the
minimum and maximum values on the basis of the value defined
by the controller.
Jumper2Ingput signal
[V]
0 - 2,0*0 - 20Boiler off
%
2,0 - 2,2* 20 - 22Hysteresis
2,0* - 10 20 -100 Desired boiler output
* Dependent on the minimum modulation dept (fan rotation speeds settings, pre set 20%)
Boiler output
[%]
Description
table 07 Analogue input signal for boiler output
1
%
2
fig. 14 Jumper 1
114494-03
11
114492LTAL21H024a
8.4.4 Analogue output (0 - 10 V)
If this feedback message is received, temperature or heat output
can be selected. The two are described briefly below.
Jumper (1) on the interface is used to select either temperature ()
or boiler output (%).
Jumper1 Output signal
[V]
0,5-Alarm
1- 1010 - 100Delivered temperature
table 08 Analogue output signal for temperature
Temperature
[°C]
Description
27
Page 28
8. Control and electrical connections
GAS 210 ECO PRO
Jumper1Output signal
[V]
Boiler output
[%]
Description
00 - 15Boiler off
%
0,5 15 - 18Alarm
2,0* - 10 20 - 100 Delivered boiler output
* Dependent on the minimum modulation dept (fan rotation speeds settings, pre set 20%)
table 09 Analogue output signal for boiler output
8.5 Connection options of the optional expanded control/protection PCB
(SCU-SO1)
8.5.1 Flue gas damper control (FgV)
In a cascade configuration, a flue gas damper (available as an
accessory) prevents flue gases from being discharged through a
non-operating boiler, with flue gas cascade. Therefore, the boiler
is suitable for flue gas overpressure systems. Consult our Technical department. Connect the flue gas damper to the FgV terminals
of terminal strip X3. Also fit this flue gas damper if flue gases flow
back when the boiler is in stand-by mode.
The running time of the flue gas damper must be programmed
with parameter 29.
In a cascade configuration, a hydraulic valve prevents heat loss
when the boiler is not running. Connect the hydraulic valve to the
HdV terminals of terminal strip X3. The running time of the hydrau-
lic valve must be programmed with parameter 28.
8.5.3 External gas valve control (EgV)
If there is a heat demand, an alternating voltage of 230 V 1 A
(maximum) becomes available on the EgV terminals of terminal
strip X3 to control an external gas valve. The voltage is switched
off when the gas multiblock on the boiler closes.
8.5.4 Operation signal and failure signal (Nc / No)
The alarm or operation signal is selected using the relevant
parameter 25, see Section 9.1.6. If the boiler is operational,
the alarm or operation signal can be switched via a potential-free
contact (maximum of 230 V, 1 A) on the No and C terminals of terminal strip X4. If the boiler locks out, the alarm can be transmitted
via a potential-free contact (maximum 230 V, 1 A) on terminals No
and C of terminal strip X4.
8.5.5 Water pressure sensor (Wps)
The water pressure sensor (available as an accessory) shuts
the boiler down when the minimum water pressure (0.8 bar) is
reached. To activate the water pressure sensor, a minimum pressure must be set with parameter 26 (factory setting 0 = off, see
Section9.1.6.) The pump does not run during this shutdown.
28
114494-03
Page 29
GAS 210 ECO PRO
8. Control and electrical connections
Connect the water pressure sensor to the Wps terminals of terminal strip X5.
0 = Earth or neutral of the power supply
S = Signal or output from the sensor
+ = Supply voltage
8.5.6 Outside temperature sensor (Tout)
To take advantage of the boiler's modulating operation during the
entire heating season, a Remeha outside temperature sensor
(available as an accessory) can be used in combination with an
on/off control or connection. Connect the on/off control or connection to the On/off terminals of terminal strip X6 on the standard
control PCB (PCU-01) and the outside temperature sensor to the
Tout terminals of terminal strip X5 on the optional expanded con-
trol/protection PCB (SCU-SO1). The unit modulates with a heat
demand from the controller or because of a connection to a flow
temperature corresponding to the outside temperature (see heat-ing curve graph).
3
fig. 16 Heating curve graph
80
60
40
20
F
01020-15
F = factory setting
2
1
114492LTAL21H025b
Fitting the outside temperature sensor
Fit the external sensor, protected against direct sunlight, to the
north or north-west of the building, at a height of at least 2.5
metres from ground level. Do not fit the outside temperature sensor near windows, doors, ventilation grills and extractors, etc.
Heating curve setting
The maximum flow temperature setting is also the setting for the
‘top’ of the heating curve, i.e. the required flow temperature for an
outside temperature of -15°C. The baseline of the heating curve is
also adjustable and can be changed at service level, see Section
9.1.6. A linear relationship exists between the outside temperatures mentioned and the corresponding flow temperatures.
8.5.7 Minimum gas pressure switch (Gps)
The minimum gas pressure (available as an accessory) switch
shuts the boiler down if the inlet gas pressure becomes too low.
Connect the minimum gas pressure switch to the Gps terminals
of terminal strip X5. The presence of the gas pressure switch
must be activated using parameter 27 in the setting mode (see
Section 9.1.6).
8.5.8 Gas leakage control (VPS; only for 210- 160
and 210- 200 boilers)
The gas leakage control checks and controls the safety valves on
the gas block via a VPS system. The test takes place when the
boiler starts. In the event of a leak in the gas block, the boiler will
lock out. Connect the gas leakage control to the VPS terminals of
terminal strip X5. The presence of a gas leakage control must be
entered using parameter 31, see Section 9.1.6.
114494-03
29
Page 30
9. Commissioning
38
11
X01
X02
123
8.5.9 Wiring diagram
PRIMARY CONTROL UNIT - PCU-01
X03
1234
X04
Pump
12
X05
Mains
3
123
OT
On / Off
1
X06
BL
34RL562
GAS 210 ECO PRO
X07
X08
0
SAFETY UNIT
- SU-01
Ignition
transformer
X05
X01
SU-01
X04
SU-01
PCU-01
X02
X07
X03
X06
X01
PCU-01
X11
X10
X09
X08
CORD COLORS
BL BLUE
BL/WH BLUE/WHITE
BR BROWN
BR/WH BROWN/WHITE
YW YELLOW
GN/YW GREEN/YELLOW
YW/WH YELLOW/WHITE
GN GREEN
GY GREY
OR ORANGE
RD RED
WH WHITE
BK BLACK
BK/WH BLACK/WHITE
GYBKBLBL
BL
11X235981021 3675
GYBLBK
GN/YW
213X21
PE-11
Elektrode
BRBR
PE-6PE-4PE-5
GN/YWGN/YWGN/YW
BL
BR
Safety shut-off
valve1
PE-12
GN/YW
21
BL
GN/YW
BR
21
Safety shut-off
valve 2
SCU-X01
X03
0-10V IF-01
X04
X02a
SCU-X01/
SCU-S01
X02
X50
X01
X04
X03
X04
X05
X05
X02
SCU-S01
PE-2
BL
GN/YW
BK
GN/YW
GN/
LN
PE-2
PE-1
GN/YW
X50
YW
BL
BK
X51
BL
BR
LN
Power supply
230V,50Hz
T
BK
BL
6.3AT
Boiler
switch
on / off
PRIMARY CONTROL UNIT - PCU-01
YW
X10
1.....6
213
CNoNc
Status
X03
12 35 4671089
RDBLOR
WH
Flow
temp.
213
CNoNc
Status
X04
X09
1234
WHBRGN
1X91425
Fan
1.....6
X02
1.....6
X02a
SECONDARY CONTROL UNIT
- SCU-X01
NNNLLL
PC
PE-7
GN/YW
14X23513 12
BR
GN/YW
BL
1X5532
Fan
X11
BK/
BL/
WH
WH
OR
P
Flue gas
pressure
switch
GL/
BR/
WH
WH
PSU
(Parameter
storage unit)
WpsToutGpsVPs
Return
temp.
DISPLAY
BK
Heat exch.
temp.
30
+
0-10V
3
+
0-10V
X05
OTm
-
Nc
Status
X04
-
IF-01
12
No
C
X01
13
X01
2
1.....6
X02
21
Fgv
45
X03
Hdv
78369
Egv
213
CNoNc
Status
X04
214567
OS+
X05
9
SECONDARY CONTROL UNIT - SCU-S01 (OPTION)
T002609-04-C
114494-03
Page 31
GAS 210 ECO PRO
9 Commissioning
9.1 Control panel
9. Commissioning
The boiler's control panel contains four function keys, a menu key,
a service engineers key, an on/off switch and a display.
The display has four positions and several symbols and provides
information about the operating status of the boiler and any faults.
Numbers, dots and/or letters may be shown. The symbols in the
display above the function keys indicate what the function of the
relevant keys is at that moment. If no key is pressed for three min-
utes, the display lighting switches off and only the and sym-
bols are displayed. Press any key; the current boiler status and
the current operating code appear on the display. This is always
displayed in the event of a fault.
67
9.1.1 Normal start-up procedure
114492LTAL21H008a
114494-03
Switch on the mains supply to the boiler; the Gas 210 ECO PRO
will perform the start-up program.
The following will appear in succession in the display:
- a short display test, whereby all of the display's segments are
visible;
fXx software version alternating with 1;
pXx parameter version;
- Afterwards (depending on the operating status), the following
may appear on the display:
N : L (flashes) : live and nutral wires are wrongly connected; chan-
ge wires on the 230V terminal strip!
31
Page 32
9. Commissioning
GAS 210 ECO PRO
With a heat demand:
1 Boiler starts
2 Burner starts
3 Central heating operation; briefly in part load then in full load
When a heat demand ceases:
5 Burner stops
6 Boiler stops
0 Stand-by mode
table 10 Normal operation
9.1.2 Fault during start-up procedure
If nothing appears on the display, check:
- the connection of the mains lead;
- the main fuse in the instrument box (F = 6.3 AT, 230 V);
- the fuse on the control unit (F1 = 1.6 AT, 230 V);
- the mains voltage.
• A fault code in the display is recognised as follows: the fault
symbol appears and
the fault code flashes underneath it;
• The meaning of this fault code can be found in the fault table,
see Section 11.2.
• If possible, solve the fault first.
• Press the RESET key for 3 seconds to restart the Gas 210
ECO PRO.
If the display does not show RESET but SERVICE, the boiler must
be switched off and switched on again after 10 seconds before the
fault can be reset.
32
114494-03
Page 33
GAS 210 ECO PRO
bar
%
114492LTAL21H009c
fig. 18 Reading current values
9. Commissioning
9.1.3 Reading current values
The following current values can be read in the ‘information
menu’
- 5t = Status
- 5u = Sub status
- t1 = flow temperature [°C];
- t2 = return temperature [°C];
- t4 = outside temperature [°C];
(only if outside sensor is connected)
- t6 = boiler block temperature [°C];
- 5p = internal set point [°C];
- fl = ionisation current [uA];
- f = fan rotation speed [rpm];
- pr = water pressure [mbar];
- p = relative output supplied [%];
The current values can be read as follows:
• Press the key, the symbol will then flash, confirm with
the key;
• Press the [+] key again so that 5t appears alternating with
3, the actual status;
• Press the [+] key again so that 5u appears alternating with
, the actual sub status;
• Press the [+] key again so that t1 appears, alternating with,
for example, 60°C, the actual flow temperature;
• Press the [+] key repeatedly so that the remaining temperatures
also appear;
• Press the [+] key again so that 5p appears, alternating with,
for example, 88°C, an internal set point;
• Press the [+] key again so that fl appears alternating with,
for example, u, the actual ionisation current;
• Press the [+] key again so that ñf appears alternating with,
for example, 3000 (rpm), the actual fan rotation speed;
• Press the [+] key again until pr appears alternating and, for
example, 3.0 bar, the actual water pressure
(if no water pressure sensor is connected, --.- bar appears);
• Press the [+] key again until p appears and, for example,
78 %, the actual modulation percentage;
• Press the [+] key again, the read-out cycle starts again with
5t, etc;
• Press the key twice to return to the display with the cur-
rent operating status.
114494-03
33
Page 34
9. Commissioning
9.1.3.1 Status and sub status
In the ‘information menu’ the following status and sub status
numbers are displayed:
Status 5tSub status 5u
NumberStatusNumberSub status
0Stand-by mode0Stand-by mode
1Anti-hunting
1Boiler starts (heat demand)
2Burner starts
3Burning on central heating operation
5Burner stop
6Boiler stop (end of heat demand)
8Control stop
9ShutdownxxShutdown xx
table 11 Settings at service level
2Open hydraulic valve
3Start pump
4Wait for the correct temperatures for burner start
10Open external gas valve
11Fan running
12Open flue gas damper
13Pre-ventilation
14Wait for release signal
15Burner on
16VPS gas leakage control
17For ignition
18Main ignition
19Flame detection
20Intermediate ventilation
30Temperature control
31Limited temperature control (
32Output control
33Increase protection level 1
34Increase protection level 2 (part load)
35Increase protection level 3 (shut down)
36Modulate up for flame control
37Stabilisation time
38Cold start
40Burner off
41Post ventilation
42Fan running
43Close flue gas damper
44Stop fan
45Close the external gas valve
60Pump post circulation
61Pump off
62Close hydraulic valve
63Start anti-hunting
0Wait for burner start
1Anti-hunting
GAS 210 ECO PRO
∆T safety)
(control modulation)
34
9.1.4 Adjusting the boiler to the system
The boiler's control parameters are set to the most common central heating systems. With these settings, practically all central
heating systems will work well. However, the user or the installer
can optimise the parameters as he/she wishes.
114494-03
Page 35
GAS 210 ECO PRO
2x
2x
fig. 19 Changing parameters
114492LTAL21H021b
9. Commissioning
9.1.5 Changing parameters at user level (without
access code)
The following settings can be changed at user level:
p1 = Flow temperature set point [°C], adjustable between 20
and 90°C;
p2 = Pump post-circulation time 0..98 mins, 99 is continuous;
p3 = Boiler control; central heating on/off.
0 = Central heating
1 = Central heating on (= factory setting)
p4 = Display options
0 = Simple display
1 = Comprehensive display
2 = Display automatically goes to simple after three
minutes (factory setting)
* Consult our Technical department for further information and
demands on the system.
The parameters can be changed at user level as follows:
1. Press the -key several times until the symbol flashes in the
menu bar;
2. Select the users menu using the -key, p1 appears (the
1 flashes);
3. Press the [+]-key; p2 appears (the 2 flashes);
3. Press the -key again; 3 (min) appears and flashes: (fac-
tory setting);
4. Change the value by pressing the [-] -key or the [+] -key, in this
case for example to 15 min, with the [+] -key;
5.
Confirm the value with the -key, p2 appears (the 2 flashes);
6. Press the - key twice, the boiler enters the current operating
status.
off
The p1 to p4 settings can be changed in the same way as
p2.
9.1.6 Changing parameters at service level (with
access code)
To prevent undesired settings, some parameter settings can only
be changed after the special access code 12 is entered. This
code may only be used by qualified installers.
The following settings can be changed at user and service levels:
114494-03
35
Page 36
9. Commissioning
GAS 210 ECO PRO
Codes in
display
Flow temperature set point20 - 90°C
1
Pump post-circulation time
2
by users
May also
be changed
Boiler control
3
Display
4
Maximum speed
17
central heating (natural gas)
Minimum speed
central heating and hot water
18
(natural gas)
Starting speed
19
(natural gas)
Maximum flow temperature CH20 - 90°C90
20
Base point heating curve out-
21
side temperature
Baseline of flow temperature
22
heating curve
Outside temperature climate
23
point heating curve
Outside temperature for frost
24
protection
Fault relay function
25
(available as an accessory)
Minimum water pressure
26
(available as an accessory)
Minimum gas pressure check
27
(available as an accessory)
Hydraulic valve running time
28
(available as an accessory)
Can only be changed by the installer
Flue gas damper running time
29
(available as an accessory)
Maximum time for release
30
VPS gas leakage control
31
(available as an accessory)
Mains detection phase
32
External interlock function
33
(available as an accessory)
Display units
34
Automatic detection of optional
Ad
hardware
df
Resetting factory settings
and
dU
DescriptionSetting range and possible explanation
0 – 98 minutes
99 = continuous
0 = Central heating
1 = Central heating
0 = Operation signal
1 = Alarm signal
1 - 60:10 bar (only with water pressure sensor)
0 = off
0 = Off
1 = On (only with a minimum gas pressure sensor)
0 = no waiting time
1 – 255 s (only if connected)
0 = no waiting time
1 – 255 s (only if connected)
0 = no waiting time
1 – 255 s (only if connected)
0 = off
1 = on (only with leakage control)
0 = Off
1 = On
1 = Normal shutdown
2 = Shutdown without frost-protection
3 = Lock out
0 = °C / bar
1 = °F / psi
Do not modify
0 = No
1 = Yes, once
The type plate states the value of
dF (X) and dU (Y); setting these values resets
the factory settings.
Factory setting
210-80210-
120
210-
160
80
3
1
2
51644857
12131012
17
1
0
0
0
0
0
0
0
2
0
0
X
Y
210-
200
table 12 Settings at service level
* Change this parameter when converting to flue gas cascade and LPG gas (please refer to Broag).
36
114494-03
Page 37
GAS 210 ECO PRO
4x
9. Commissioning
• The parameters at service level may only be changed by a
qualified installer.
• Changing the factory settings can result in incorrect operation of
the Gas 210 ECO PRO.
The parameters can be changed at service level as follows:
1. Press the -key several times until the symbol flashes in
the menu bar;
2. Select the installers menu using the -key,
appears in the display;
3. Use the [-] -key or [+] -key to set installers code 0012;
4. Confirm with the -key; appears;
5. Press the -key again; value 80°C appears (factory setting);
6. Lower the value, for example to 60°C, with the [-] key;
7. Confirm the value with the -key; appears;
8. Set other parameters where required by selecting them with the
[-] -key or [+] -key;
9. Press the - key twice, the boiler becomes operational.
fig. 20 Setting service code
Gas 210 ECO PRO also returns to operation if no keys are
pressed for 10 minutes.
114492LTAL21H018b
114494-03
37
Page 38
9. Commissioning
114492LTAL21H010a
4x
GAS 210 ECO PRO
9.1.7 Resetting factory settings
• Press the -key several times until the symbol flashes in
the menu bar;
• Select the installers menu using the -key,
appears in the display;
• Use the [-] -key or [+] -key to set installers code 0012;
• Confirm with the -key; appears;
• Press the [+] -key several times, df X appears;
• By default, the current value X for dF appears on the display; as
a check, compare this with the
value of X on the type plate; enter the value of X on the type
plate with the [-] key or the [+] key.
• Press the key again, dU Y appears;
• By default, the current value Y for dU appears on the display;
as a check, compare this with the value of Y on the type plate;
enter the value of Y on the type plate with the [-] key or the [+]
key.
• Press the key to confirm the values; the factory settings
have been reset.
fig. 21 Resetting factory setting
38
114494-03
Page 39
GAS 210 ECO PRO
114492LTAL21H019a
3x
9. Commissioning
9.1.8 Setting manual operation ( symbol)
In some cases, it may be necessary to set the boiler to manual
operation, for example when the controller has not yet been connected. The boiler can be set to automatic or manual operation
under the symbol. Do this as follows:
• Press the -key several times until the symbol flashes in the
menu bar;
• Press the -key once, either the minimum flow temperature
or AUt) (only if an external sensor
has been connected) will appear in the display; the flow
temperature is determined by the internal heating curve;
• or 20°C (minimum flow temperature) will appear in the display;
• Press the [+] -key to increase this value in manual operation
temporarily;
• Confirm with the -key;
• The boiler is now set to manual operation;
• Press the -key twice to exit manual operation; the boiler
enters operating status.
fig. 22 Setting manual operation
Manual operation keeps active after power breakdown.
9.2 Commissioning
Ensure that the boiler is disconnected from the power supply.
1. Remove front panel.
2. Open the main gas cock.
3. Check the electrical connections including earth.
4. Fill the boiler and the system with water
(minimum pressure 0.8 bar).
5. Vent the system.
6. Fill the trap with clean water.
7. Check the flue gas discharge connection and air supply
connection.
8. Vent the gas pipe (only vent pipework from
gas isolation valve).
9. Open the gas cock in the gas pipe to the boiler.
10. Check the gas connection for leakage.
11. Switch on the mains supply to the boiler.
12. Adjust the boiler and any external controls to heat demand.
13. The boiler now starts to run.
114494-03
39
Page 40
9. Commissioning
GAS 210 ECO PRO
Operation can now be monitored via the code window:
With a heat demand:
1 Boiler starts
2 Burner starts
3 Central heating operation; briefly in part load then in full load
When a heat demand ceases:
5 Burner stops
6 Boiler stops
0 Stand-by mode
15 Check and, if necessary, correct the gas/air ratio control
setting.
Perform the check at full load and minimum load for all boiler
models. Only perform settings for the 210-80 and 210-120 models
1
at minimum load. Perform settings for the 210-160 and 210-200
models at full load and minimum load. An electronic CO
or O2
2
meter is required for checking and adjustment purposes. Check
that the opening around the probe is properly sealed when meas
urements are taken.
CO
2
2
15.a Set full load: press the key, the symbol appears in the
menu bar; if h3 appears in the display, full load has been set.
15.b Now measure the CO2 percentage and compare it with the
3
= full load
T000239-C
values in table 13. If the CO2% level deviates from these
values, set the CO2 percentage using the screw under the
cap of the V2 coil on the gas block (this can only be adjusted
on the 210-160 and 210-200 models). Check the flame
through the inspection glass (at full load): the flame must not
fig. 23 Setting values CO
2
Checking and setting values O2/CO2 for natural gas (H) at full load
blow off and the burner's surface must not be red hot.
2
margin
for natural gas(front housing removed)
2
Control
Control
2
margin
Setting mar-
gin
Setting mar-
gin
O
2
O
2
Control
margin
Control
margin
Setting
margin
Setting mar-
gin
table 14 Checking and setting values O2/CO
40
for natural gas (front housing removed)
2
114494-03
Page 41
GAS 210 ECO PRO
1
3
CO
2
2
= minimum load
T001791-B
9. Commissioning
15.c Set minimum load: press the [-] -key and, when l3
appears in the display, minimum load has been set.
15.d After minimum output has been reached, check the CO2
percentage and compare it with the value in table 14. If the
CO2% level deviates from these values, set the CO2
percentage using the correction screw of the pressure
controller on the gas block (for the 210-80 and 210-120
models, adjustments are only made at minimum load).
The boiler is supplied with a number of basic settings.
burner control - modulating on the basis of flow temperature
maximum flow temperature - 80°C
If other values are required: see Section 9.1.6.
fig. 24 Setting values CO2 for 210-160 and
210-200
1
CO2
CO2
2
114492LTAL21H020a
fig. 25 Setting values CO
120 (only minimum load)
for 210-80 and 210-
2
Gas / Gaz / Gáz
H (G20)
ø 8.4 mm
.
4
8
15.e Remove measuring equipment and seal measuring points.
16. Check gas leakage control (VPS if installed = available as an
accessory):
Then set the gas leakage control pressure switch to a switch pressure equal to 50% of the inlet pressure. Check that the measured
inlet pressure is not the (higher) closing pressure.
17. Press the ‘reset’ key to reset the boiler to 'user level'.
18. Heat the system up to roughly 80°C if possible and switch
the boiler off.
19. Vent the system and check the water pressure.
20. The boiler is now ready for operation.
21. Set the boiler control to the required values and write down
the connected type of gas on the boiler type plate: e.g. G20
– 25 mbar.
22. Switch the boiler on.
If the CO2% with the 210-80 and 210-120 still deviates on full load:
- adjust part load (see point 15.c and 15.d)
- check full load (see point 15.b) ; if the CO2% deviation is still too
large;
- check the size and placing of the restrictor (natural gas; 8.4 mm)
114492LTAL21H027
fig. 26 Check size and positioning of restrictor
114494-03
The following operating modes are now available:
23.aModulating operation: The heat output of the boiler
modulates on the basis of the flow temperature demanded by the modulating controller, see ‘Note’ in point 22
and Section 8.1.2.
23.bOn/off operation: the boiler modulates between mini-
mum and maximum heat output on the basis of the flow
temperature set in the boiler, see Section 8.3.2.
41
Page 42
9. Commissioning
9.3 Taking the boiler out of operation
The boiler must be switched off for maintenance or repair work. If
the central heating system is not going to be used for a long time
(for example, during holidays in frost-free periods), it is advisable
to put the boiler out of operation.
9.3.1 Boiler with frost protection, out of operation
for a long time
• Set the controller low, for example to 10°C;
The Gas 210 ECO PRO will now only come into operation to protect itself against freezing, (= depending on parameter 33, see
table 11).
To prevent radiators and the system from freezing in rooms where
there is a risk of frost (e.g. garage or storage room), a frost thermostat can be connected to the boiler. The boiler will then keep
the radiators in that room warm.
GAS 210 ECO PRO
This frost protection does not work if the boiler is out of operation.
9.3.2 Boiler without frost protection, out of
operation for a long time
• Isolate the mains power supply from the boiler;
• Close the boiler gas cock.
Drain the boiler and central heating system if you are not going
to use your home or the building for a long time and there is a
chance of frost.
42
114494-03
Page 43
GAS 210 ECO PRO
10. Inspection and maintenance
10.1 General
The boiler is virtually maintenance free; it only has to be inspected
once a year and only if necessary be serviced/cleaned.
The annual inspection of the boiler includes:
- combustion check of the boiler (the fan draws in the
combustion air through the venturi. Clean the fan, venturi and
burner if there are irregularities);
- cleaning the trap;
- checking the ignition electrode;
- leakage check (water, flue gas and gas);
- water pressure check.
10.2 Combustion check of the boiler
Combustion is checked by measuring the O2/CO2 percentage in
the flue gas discharge duct. To do this, heat the boiler to a water
temperature of approx. 70°C. The measurements must meet
the values set in table 13. The flue gas temperature can also be
measured at the measuring point in the flue gas discharge duct. If
the flue gas temperature exceeds the return temperature by more
than 30°C, this can indicate that the heat exchanger is dirty.
If these checks show that combustion in the boiler or heat transmission is no longer optimum, corrective maintenance must be
carried out in accordance with the instructions in Sections 10.2.1 to 10.2.4.
10. Inspection and maintenance
10.2.1 Corrective maintenance
This should include cleaning the fan, venturi, the heat exchanger
and the burner. These parts must be cleaned in succession.
A service kit which contains gaskets and most used parts for maintenance is available as an accessory.
Work on the boiler
Disconnect the mains supply, close the main gas cock and allow
the boiler to cool down before working on the boiler.
114494-03
43
Page 44
10. Inspection and maintenance
GAS 210 ECO PRO
3
10.2.2 Cleaning the fan
For the 210-80 and 210-120 versions:
230 V
1
Remove the electrical connections from the fan.
1. Unscrew the union nut under the gas multiblock
(pay attention to the sealing).
2. Remove the bolts from the outlet side of the fan.
2
3. Remove the fan, including venturi and gas multiblock.
4. Remove the bolts on the inlet side of the fan.
5. Detach the venturi from the fan.
6
6. Clean the fan with a plastic brush.
7. Remove loose dust from the fan.
4
8. Re-attach the venturi to the fan.
9. Detach the air silencing tube from the venturi.
5
7
8
10. Clean the venturi with a plastic brush.
11. Refit all removed components; check the correct positioning of
the gasket ring between fan and venturi.
9
12
10
11
13
230 V
15
14
114492LTAL21H028b
fig. 27 Cleaning the fan 210-80 and 210-120
44
114494-03
Page 45
GAS 210 ECO PRO
10. Inspection and maintenance
3
For the 210-160 and 210-200 versions:
1. Remove the electrical connections from the fan.
2. Remove the bolts that fix the venturi on the fan.
3. Remove the bolts and the nuts from the outlet side of the fan.
4. Remove the fan (pay attention to the sealing).
5. Clean the fan with a plastic brush.
1
2
6. Remove loose dust from the fan.
7. Detach the air silencing tube from the venturi.
8. Clean the venturi with a plastic brush.
9. Refit all removed components; check the correct positioning of
4
5
6
7
the gasket ring between fan and venturi.
8
11
10
fig. 28 Cleaning the fan 210-160 and 210-200
9
114492LTAL21H029b
114494-03
45
Page 46
10. Inspection and maintenance
5/6 leden
5/6 leden
5/6 leden
1
4
GAS 210 ECO PRO
10.2.3 Cleaning the heat exchanger (flue gas side)
Caution: The sealing between the inspection hatch and heat
exchanger may stick, as may the sealing between the burner and
heat exchanger Prevent the sealing from tearing.
Damaged or hardened sealing must always be replaced.
2
3
3
1. Remove the nuts from the inspection hatch at the front of the
heat exchanger.
2. Take the inspection hatch off the heat exchanger.
3. Clean the heat exchanger with special cleaning tool (available
as an accessory) or compressed air.
4. Clean the condensate collector by removing the plug (in front of
the flue gas discharge pipe) and rinsing the collector with water.
5. Now refit all removed components.
6
5
fig. 29 Cleaning heat exchanger
114492LTAL21H013a
46
114494-03
Page 47
GAS 210 ECO PRO
10. Inspection and maintenance
10.2.4 Cleaning the burner
1
2
2-5 bar
8
2
1
3
1. Dismantle the burner.
2. Check burner visually and if necessary clean carefully with air
(e.g. compressed air at between 2 and 5 bar,
nozzle - burner distance approx. 1 cm).
3. Now refit all removed components.
Ensure that cables do not come into contact with hot boiler parts!
4
1cm
5
6
8
6
fig. 30 Cleaning burner
7
114492LTAL21H014a
114494-03
47
Page 48
10. Inspection and maintenance
GAS 210 ECO PRO
10.3 Cleaning the trap
Remove the trap from the boiler and clean it.
Fill the trap with fresh water and fit it.
10.4 Checking the ignition electrode
Check the ignition electrode adjustment (between 3 and 4 mm)
and replace electrode if necessary (including sealing). Also check
the electrode's porcelain for hairline fractures because this may
cause spark-over.
3 ... 4 mm
114492LTAL21H030
fig. 31 Check the ignition electrode
10.5 Checking for leaks
Check for water, flue gas and gas leaks.
10.6 Checking water pressure
The water pressure must be a minimum of 0.8 bar. The water
pressure also depends on the height of the central heating system
above the boiler (static pressure, 1 bar = 10 m high). It is recommended to fill the system to approx. 0.8 bar above this static pressure.
10.7 Putting boiler back into operation
1. Open the gas cock in the gas pipe to the boiler.
2. Switch on the mains supply to the boiler.
3. Adjust the boiler and any external controls to heat demand.
4. Perform another flue gas analysis (see Section 9.2 and adjust if
necessary.
48
114494-03
Page 49
GAS 210 ECO PRO
11. Control stops and faults
11.1 General
The boiler is fitted with an advanced control unit. The heart of the
control is a microprocessor, the abc®, which both protects and
controls the boiler.
11.2 Control stops and faults
Control stop:
The control stop is a (temporary) boiler operating mode due to an
abnormal situation. The boiler switches to the neutral position so
that it can return to a normal state. The display then shows the
shutdown status (with code 9) again. The boiler control unit will, at
first, try several times to start the boiler again. The boiler shall operate again when the causes of the control stop have been removed.
Fault:
If the shutdown condition still exists even after various automatic
control unit start attempts have been made or if a non-reproducible phenomenon has arisen, the boiler switches to fault mode
(also known as lock-out). The boiler can only resume operation
if the cause of the fault is rectified and the ‘RESET button’ is
pressed
11. Faults
11.3 Control stop codes
The boiler display will show code 9.
The control stop codes can be read out as follows:
• Push the - key, and then the - key;
• The display shows = 9;
• Push the [+]- key one time; the display shows 5u and the
control stop code.
The boiler shall start automatically when the causes of the control
stop have been removed.
114494-03
49
Page 50
11. Faults
GAS 210 ECO PRO
Code
5u
0
1
3
4
5
6
8
9
10
11
13
14
15
16 *
DescriptionPossible causeCheck/solution
Parameter fault
Maximum flow temperature
exceeded
• No flow or insufficient flow
• Reset dF and dU
• Reset with RECOM PC
Check:
• Flow and/or reason
for heat demand
Check:
• Flow (direction, pump, valves)
Maximum heat exchanger temperature exceeded
• No flow or insufficient flow
during heat demand
• That the system has been correctly bled
• Temperature sensors for deviations
• Water pressure in the system
• Whether the heat exchanger is dirty
Check:
• Flow (direction, pump, valves)
Maximum heat exchanger temperature increase exceeded
• No flow or insufficient flow
• Sensor fault
• That the system has been correctly bled
• Temperature sensors for deviations
• Water pressure in the system
• Whether the heat exchanger is dirty
Check:
Maximum difference between
heat exchanger and return temperature exceeded
• No flow or insufficient flow
during heat demand
• Sensor fault
• Flow (direction, pump, valves)
• That the system has been correctly bled
• Temperature sensors for deviations
• Water pressure in the system
• Whether the heat exchanger is dirty
Check:
Maximum difference between
heat exchanger and flow temperature exceeded
• No flow or insufficient flow
during heat demand
• Sensor fault
• Flow (direction, pump, valves)
• That the system has been correctly bled
• Temperature sensors for deviations
• Water pressure in the system
• Whether the heat exchanger is dirty
Waiting time release signal drift
Phase and neutral of mains supply mixed up
Shutdown interlock active
Shutdown interlock active or frost
protection active
• External cause
• Incorrectly set parameter
• Bad connection
• Mains supply incorrectly wired
• Floating or 2-phase system
• External cause
• Incorrectly set parameter
• Bad connection
• External cause
• Incorrectly set parameter
• Bad connection
• Remove external cause
• Check the parameter
• Check the connection
• Reconnect phase and neutral
• Set parameter 32 to 0
• Remove external cause
• Check the parameter
• Check the connection
• Remove external cause
• Check the parameter
• Check the connection
• BUS connection inadequate or
Communication fault with SCU (=
optional PCB)
non-existent
• SCU PCB not present
• Reconnect
• Carry out automatic detection
(any longer) in boiler
Water pressure too low
• Water pressure non-existent or
too low
• Incorrect water pressure
parameter adjustment
• Water leakage
Check:
• Water pressure in the system
• Minimum water pressure
• That hydraulic pressure sensor is
properly installed /connected
Check:
Gas pressure too low
• No flow or insufficient flow
• Incorrect GPS switch
adjustment
• Wiring defect or switch faulty
• That the gas cock is fully opened
• That there is adequate gas pressure
• That the GPS switch is properly
installed
• Replace the GPS switch if necessary
Configuration fault or SU
not recognised
• Incorrect SU PCB for this boiler • Replace SU PCB
50
114494-03
Page 51
GAS 210 ECO PRO
11. Faults
Code
5u
17 *
18 *
19 *
20 *
21
22
24
25
* These lock-outs are not stored in the failure memory.
DescriptionPossible causeCheck/solution
Configuration fault or default
parameters table incorrect
Configuration fault or parameter
storage unit (PSU) not recognised
Configuration fault or dF-dU
parameters unknown
Configuration procedure active
Communication fault with SU-01• Bad connection
No flame during operation• No ionisation current
VPS test failed
Internal fault SU-01• Replace SU-01
• PCU-01 unit parameters
incorrect
• Incorrect PSU PCB for this
boiler
• Standard briefly activated
following boiler switch-on
• Gas pressure non-existent or
too low
• Faulty gas valve
• Incorrect adjustment of the VPS
switch
• Wiring fault
• Faulty VPS switch
• Replace PCU-01 unit
• Replace PSU PCB
• Add/check dF and dU
• No action
• Check that the PCB is inserted in the
correct connector
Check:
• That the gas cock is fully opened
• That the gas pressure is sufficient
• That the gas block is appropriately
adjusted and working correctly
• Whether the air supply or flue gas
discharge are blocked
• The flue gas circulation; inspect the
flue gas discharge system for
installation faults and the heat
exchanger for leaks
Check:
• That the gas cock is fully opened
• That the gas pressure is sufficient
• That the VPS switch is properly
installed
• Whether the gas valve is leaking or in
the open position
• That the wiring is OK; mix up of the V1
and V2 plugs
• The adjustment of the VPS switch
• Replace the VPS switch if necessary
• Replace the gas valve if necessary
table 15 Control stop codes
11.4 Fault codes
114494-03
The boiler displays the fault codes as follows:
é 12 (the display shows the symbol and the fault code
flashes). The meaning of the fault codes can be found in the fault
table, see table 16.
In the event of faults, proceed as follows:
• Note the fault code.
The fault code is needed to find the cause of the fault quickly and
correctly and for any support from our Customer Care Department.
51
Page 52
11. Faults
GAS 210 ECO PRO
• Press the “RESET- key” for 2 seconds. If the fault code conti-
nues to appear, look for the cause in the
following fault table and rectify the fault.
If the display does not show RESET but SERVICE, the boiler must
be switched off and switched on again after 10 seconds before the
fault can be reset.
Fault
code
E:00
E:01
E:02
E:03
E:04
E:05
E:06
E:07
E:08
E:09
E:10
E:11
DescriptionPossible causeCheck/solution
Storage unit parameter not
found
Safety parameters not in
order
Heat exchanger temperature
sensor short circuited
Heat exchanger temperature
sensor open circuit
Heat exchanger temperature exceeded below normal
range
Heat exchanger temperature
exceeded above normal
range
(high limit thermostat)
Return temperature sensor
short circuited
Return temperature sensor
open circuit
Return temperature exceeded below normal range
Return temperature exceeded above normal range
Too great a difference
between heat exchanger and
return temperature
• Bad connection• Check the cable bundle
• Bad connection• Check the cable bundle
• Bad connection
• Defective sensor
• Sensor not correctly mounted
• Bad connection
• Defective sensor
• Sensor not correctly mounted
• Bad connection
• Defective sensor
• Sensor not correctly mounted
• No or to little flow
• Bad connection
• Defective sensor
• Sensor not correctly mounted
• Bad connection
• Defective sensor
• Sensor not correctly mounted
• Bad connection
• Defective sensor
• Sensor not correctly mounted
• No or to little flow
• Defective sensor
• No or to little flow
• Sensor not correctly mounted
• Check the cable bundle
• Replace the sensor if necessary
• Check if sensor is correctly mounted
• Check the cable bundle
• Replace the sensor if necessary
• Check if sensor is correctly mounted
• Check the cable bundle
• Replace the sensor if necessary
Check:
• flow (direction, pump, valves)
• if system has been correctly bled
• temperature sensors for deviations
• if sensor is correctly mounted
• water pressure in the system
• if heat exchanger is dirty
• Check the cable bundle
• Replace the sensor if necessary
• Check if sensor is correctly mounted
• Check the cable bundle
• Replace the sensor if necessary
• Check if sensor is correctly mounted
• Check the cable bundle
• Replace the sensor if necessary
Check:
• flow (direction, pump, valves)
• if system has been correctly bled
• temperature sensors for deviations
• if sensor is correctly mounted
• water pressure in the system
• if heat exchanger is dirty
•
• Replace the sensor if necessary
Check:
• flow (direction, pump, valves)
• if system has been correctly bled
• temperature sensors for deviations
• water pressure in the system
• if heat exchanger is dirty
• if sensor is correctly mounted
52
114494-03
Page 53
GAS 210 ECO PRO
11. Faults
Fault
code
E:12
E:14
E:15
E:16
E:17
E:32
DescriptionPossible causeCheck/solution
• Check the cable bundle
• Check that the trap is not empty; top up
if necessary
• Blockage in flue gas discharge/RGA
covered
• Cascade valve does not open
• Trap is blocked
Trap protection activated
• Bad connection
• Pressure in flue gas discharge duct
is (was) too high
• air supply obstructed
• Heat exchanger is dirty
• check the air supply
Check:
- connection between ignition cable and
transformer
- electrode distance, this must be 3 to 4 mm
• No ignition spark
- breakdown to earth
- condition of the burner set
(burner set/electrode seal)
- earthing
- bad actuation on SU board
Check:
- is the gas cock opened?
- is the inlet gas pressure sufficient?
5 failed burner starts
• Ignition spark, but no flame
- is the gas pipe vented?
- correct gas block operation and
adjustment?
- is the air supply or flue gas discharge
blocked?
- condition of cable bundle to gas block
- bad actuation on SU board
Check:
- condition of the electrode and earthing
• Flame, but insufficient ionisation
- condition of cable bundle between ignition
cable and transformer
- if gas cock is fully opened
- if the gas pressure is sufficient
• Is the gas cock opened?
• Is the gas pressure sufficient?
• Are the VPS switches correctly fitted?
• Gas valve is leaking or is stuck in the
open position.
• Is the wiring in order, plugs V1, V2 not
mixed up?
• Check the VPS settings
5 failed gas leakage controls
• Defective gas valve
• No or to little gas pressure
• VPS switch wrongly adjusted
• Bad connection
• Defective sensor
• Sensor not correctly mounted
• Replace the sensor if necessary
• Check if sensor is correctly mounted
• Burner glows as a result of a high CO2
percentage (adjust CO
• Check the ignition/ionisation electrode
• Gas valve is leaking or is stuck in the
open position.
False flame signal
•
Ionisation current has been measured, while there may not be a flame
• Defective ignition transformer
• Replace ignition transformer
Gas valve control fault
Flow temperature sensor
short circuited
• Bad connection
• Defective gas valve
• Bad connection
• Defective sensor
• Sensor not correctly mounted
• Check the cable bundle
• Replace the gas valve if necessary
• Check the cable bundle
• Replace the sensor if necessary
• Check if sensor is correctly mounted
).
2
114494-03
53
Page 54
11. Faults
GAS 210 ECO PRO
Fault
code
E:33
E:34
E:35
E:36
E:37
E:38
E:39
DescriptionPossible causeCheck/solution
Flow temperature sensor
open circuit
Fan fault
Flow and return swopped
Flame loss occurs 5 times • Ionisation current drops out
Communication fault with SU
board
Communication fault with
SCU board (optional)
Shutdown input in locked-out
mode
table 16 Fault codes
• Bad connection
• Defective sensor
• Sensor not correctly mounted
• Bad connection
• Defective fan
• Defective sensor
• Wrong flow direction
• Bad sensor connection
• Sensor not correctly mounted
• Bad connection
• Bad connection• Check the cable bundle
• External cause
• Incorrectly set parameter
• Bad connection
• Check the cable bundle
• Replace the sensor if necessary
• Check if sensor is correctly mounted
• Fault in fan cabling
• Defect in fan
• (Too) much draught over boiler, so that
the fan starts to rotate
Check:
- flow direction
- temperature sensors for deviations
• Replace the sensor if necessary
• Inlet gas pressure sufficient? Inlet gas
pressure controller in order?
• Correct gas block operation and
adjustment?
• Blockage in air supply or flue gas
discharge?
• Flue gas circulation, check flue gas
system for installation faults and the
heat exchanger for possible leaks
• Check SU board is correctly inserted in
the connector on the PCU-01
• Remove external cause
• Check the parameter
• Check the cable bundle
11.5 Control stop - and fault memory
The boiler control unit has a control stop and fault memory. This
stores the last 16 control stops and the last 16 faults that have
occurred.
With each fault, the following data is saved:
- B or E = control stop or fault code
- = Number of times that the fault has occurred
in succession
- hr = Burner operating hours since time of fault
- 5t = status
- 5u = sub status
- t1 = flow temperature [°C];
- t2 = return temperature [°C];
- t4 = outside temperature [°C];
- t6 = boiler block temperature [°C];
- 5p = internal set point [°C];
- fl = ionisation current [uA];
- f = fan rotation speed [rpm];
- pr = water pressure [mbar];
- p = relative output supplied [%];
54
114494-03
Page 55
GAS 210 ECO PRO
12. Service parts
5x
t/mt/m
11.5.1 Reading faults
• Press the -key several times until the symbol flashes in
the menu bar;
• Press the key; Bxx will flash in the display, together
with the number of shutdowns that have been memorised;
• Press the [+] or [-]key to select either the control stops B or
faults Er.
• Press the key; Bxx will flash in the display, together
with the number of shutdowns that have been memorised;
• Press the [+] or [-] -key to go forwards or backwards in the list
of faults.
• Press the -key to take a closer look at the fault.
Press the [+] or [-] -key to view the following information:
b12 (shut down code b with fault number e.g. 12);
(number of with the 'number of times that the fault has
occurred’ as number);
hr = 2 (burner operating hours since time of fault) ; (sta-
tus code) ; 5u (sub status);
t180 (temperature t1, the flow temperature 80 when
the fault occurred);
t270 (temperature t2, the return temperature 70
when the fault occurred);
• Press the -key to stop the cycle, B xx will appear
flashing in the display with the number of the last fault;
•
Press the [+] or [-] -key to view any subsequent fault information.
2x2x
fig. 32 Reading faults or control stops
fig. 33 Deleting faults
114492LTAL21H015a
11.5.2 Deleting control stops or faults
The last message in the list in the display is (or
b with shutdowns)
• Press the -key; the display will show: 0
• Press the [+] -key to set the parameter to 1.
• Press the -key ; the fault memory is cleared
• Press the - key twice to exit the fault memory.
With faultfinding, retrieving the operating status when the fault
occurred can contribute to faster rectification of the cause.
114494-03
55
Page 56
12. Service parts
12. Service parts
12.1 General
If it is ascertained during the annual inspection or maintenance
work that a part in the boiler must be replaced, use only original
parts or parts and materials recommended by Broag.
Send the part to be replaced to Broag. Always send a fully completed return form as well, see example. In this way, Broag can
handle its guarantee obligations faster and more efficiently.
Your referenceDate
Customer
Name
Address
Zip code / city
GAS 210 ECO PRO
Telephone
Contact person
Job number
Part. no.Description
t
able 17 Return form sample
* This data can be found on the boiler type plate; the type plate is stuck to the top of the boiler's right side panel.
Boiler
serial nr.*
Model
Installation
date
Problem description
Reference
56
114494-03
Page 57
GAS 210 ECO PRO
12.2 Exploded view
12. Service parts
210-200
210-160
210-80
210-120
210-120
210-80
210-160
210-200
210-200
210-200
210-80
210-120
210-160
210-200
fig. 34 Exploded view
114494-03
114492EVAL21H001b
57
Page 58
13. Regulations
13. Regulations
13.1 General
13.2 Standards
GAS 210 ECO PRO
The Remeha Gas 210 ECO PRO is a high efficiency, floor standing central heating boiler, suitable for use with all types of natural
gas; it recovers both perceptible and latent heat from flue gases.
The units are inspected on the basis of the essential requirements
in the following directives:
The following instructions must be adhered to when the Remeha
Gas 210 ECO PRO is installed:
- Gas Safety (Installation and Use) Regulations 1998 (as amended).
In addition to the above regulations, this boiler must be installed
in compliance with:
- Current I.E.E. Regulations for electrical installations
- Local building regulations
- The Building Standards (Scotland)
- (Consolidation) Regulations
- by-laws of the local water undertaking
- Health and Safety Document No 635 'The Electricity at Work
Regulations 1989'.
It should also be in accordance with the relevant recommendations
in the current edition of the following British Standards and Codes
of Practice, viz. BS 6644, BS 5978 Part 1 & 2, BS 5449, BS 5446,
BS 6798, BS 6891 and BG DM2.
13.3 Remeha factory test
Before leaving the factory, every Remeha boiler is optimally set
and tested for:
- electrical safety;
- CO2 adjustment;
- hot water operation;
- water tightness;
- gas tightness;
- control unit parameters.
58
114494-03
Page 59
GAS 210 ECO PRO
13.4 Supplementary guidelines
13. Regulations
In addition to the regulations and guidelines mentioned in Section
13.2, the supplementary guidelines in this documentation must
also be followed. Supplements or subsequent regulations and
guidelines in existence at the time of installation shall apply to all
regulations and guidelines mentioned in this Installation and Service manual.
The Remeha Gas 210 ECO PRO is a CE certified boiler and must
not be modified or installed in any way contrary to these
"Installation and Maintenance Instructions". Manufacturers
Instructions must NOT be taken as overriding statutory obligations.
114494-03
59
Page 60
14. Technical specifications
GAS 210 ECO PRO
14. Technical specifications
14.1 Technical data
Boiler type Gas 210 ECO PROUnit210-80210-120210-160210-200
General
Number of sections3456
Input control-Modulating, 0-10 V or on/off
Nominal output (80/60°) Pn
Nominal output (50/30°) Pn
Nominal input gross caloric value
(GCV/Hs) Qn
Nominal input net caloric value
(NCV/Hi) Qn
Gas and flue gas side
Category-II
Inlet gas pressure natural gasmbar17 - 30
Gas consumption natural gas
NOX emission per year (BREEAM)
(EN 15420)
Residual fan pressurePa130130130130
Flue gas quantity
Type classification with respect to flue gas
discharge
Central heating side
High limit temperature°C110
Operating temperature range°C20 - 90
Minimum water working pressurebar0.8
Maximum water working pressure PMSbar6
Water contentlitres12162024
Hydraulic resistance at dT = 20°
Electrical
Mains voltageV/Hz230/50
Input power
(without pump)
Insulation classIP20
Other
Weight excluding waterkg115135165188
Noise level at a distance of 1 m from the
boiler (enclosed version)
Environment temperature°C0 - 40
Colour of casingRAL2002 (red)/7037 (grey)
minkW16222939
maxkW87120166200
minkW18243344
maxkW93129179217
minkW19263446
maxkW99137189228
minkW17233141
maxkW89123170205
2H3P
3
minm
maxm
/h1.82.43.34.3
0
3
/h9.413.018.021.7
0
mg/kWh33353837
minkg/h27.236.749.565.5
maxkg/h149.7206.9286.0344.9
-B23, B23
mbar
(kPa)
165
(16.5)
, C13, C33, C43, C53, C63, C83
P
135
(13.5)
170
(17)
180
(18)
minWatt4444
maxWatt125193206317
dB(A)≤ 59
table 18 Technical data
60
114494-03
Page 61
GAS 210 ECO PRO
15. Efficiency data and gas inspection labels
15. Efficiency data and gas inspection labels
15.1 Unit usable efficiency (HR efficiency)
Up to 108.6 with respect to Hi at T
15.2 Water-side efficiency
a. Up to 98.4% with respect to Hi at full load at an average water
temperature of 70°C (80/60°C).
b. Up to 105.7% with respect to Hi at full load an average water
temperature of 40°C (50/30°C).
15.3 Zero-load losses
Approx. 0.21% with respect to Hi at an average water temperature
of 45°C.
15.4 Description of specifications
High efficiency gas boiler
Inspected for compliance with the essential requirements of the
Gas Appliances Directive, Efficiency Directive, Low Voltage Directive and EMC Directive.
- Modulating (18 - 100%) or 0-10V or on/off control is optional.
- Hydraulic efficiency up to 98.4% at full load (with respect to Hi)
- Suitable for use with II
- Annual NOX emissions < 62 mg/kWh, or < 35 ppm at O2 = 0%
- Average boiler housing noise level at 1 m distance around
- Heat exchanger made of cast aluminium sections.
- Cylindrical, stainless steel, premix burner with metal fibre cover.
- Air supply fan.
- Flue gas pressure difference switch.
- Temperature control: adjustable between 20 - 90°.
- Low water level protection using temperature sensors.
- Gas/air mixing system (venture).
- Gas multiblock (210-80 + 210-120 ;230V) (210-160 + 210-200;
- Electronic control and protection equipment: 230 V.
- Fan; 230V
- Pump switch: on/off 230 V max. 300 VA.
- Frost protection.
- Filling and drain cock.
- Trap.
- Suitable for both room ventilated and room sealed versions.
- Sheet steel casing, off the ground.
- Plastic condensate collector.
- Boiler equipped with closed air box.
- Boiler fully pre-wired with built-on control box.
- Installation option for boiler controllers.
- Suitable for OpenTherm controllers.
- Supplied with internal heating curve.
- Well laid-out instrument panel with LCD display.
- Menu-controlled microprocessor boiler control with operating
= 30°C.
Return
at 80/60°C and up to 105.7% (with respect to Hi) at 50/30°C.
2H3P
(NOx - class 5).
boiler ≤ 59 dBA
30 RAC)
and servicing diagnostics.
114494-03
61
Page 62
15. Efficiency data and gas inspection labels
15.5 Accessories
GAS 210 ECO PRO
Available in 4 types:
210 -80: 87 kW nominal output at 80/60°C
210-120: 120 kW nominal output at 80/60°C
210-160: 166 kW nominal output at 80/60°C
210-200: 200 kW nominal output at 80/60°C
- Modulating rematic® weather compensators.
- OpenTherm weather compensators (iSense), also for cascade
configurations (Celcia MC4).
- Air supply filter (only for use with “open flue”).
- Concentric wall and roof feed-through connections.
- Second return connection (for CT circuit).
- Thermostat pocket
- Cleaning tools.
- Service case.
- Recom communication set with CD-ROM, interface and wiring.
- Interfaces for communication with various controllers, see Sec-tion 8.4.3.
- 0 - 10 V control PCB (IF-01).
- Expanded control/protection PCB (SCU-S01).
- Outside temperature sensor* (only possible in combination with
SCU-S01 PCB).
- Flue gas temperature switch* (only possible in combination with
SCU-S01 PCB).
- Minimum gas pressure switch* (only possible in combination
with SCU-S01 PCB).
- Water pressure sensor* (only possible in combination with SCUS01 PCB).
- Motorised flue gas discharge valve* for cascade configurations
and to prevent flue gas from flowing back (only possible in combination with SCU-S01 PCB).
- Gas leakage control* (for the 166 and 200 kW boilers), only
possible in combination with SCU-S01 PCB.
15.6 Services
62
* Only one PCB (SCU-S01) board is needed for one or all of these
options.
The following services can be supplied by Broag:
- Initial commissioning.
- Warranty support.
- Access to list of Broag trained and approved service companies.
Please contact our Technical department for further information on
certified maintenance and inspections.
114494-03
Page 63
GAS 210 ECO PRO
15.7 Type of unit
15. Efficiency data and gas inspection labels
302829
27
26
1
2
3
4
5
6
7
8
9
10
11
25
24
23
22
21
20
19
18
17
16
15
1214
13
114492LTAL21H016b
fig. 35 Cross-section
1. Flue gas discharge11. Return temperature sensor21. Flue gas switch
/CO2 measuring point12. Condensate collector22. Flow temperature sensor
2. O
2
3. Air box13. Condensate trap23. On/off
4. Control panel14. Air silencing tube24. Gas connection
5. Burner15. Filling and drain cock25. Return connection
6. Heat exchanger16. Water pressure switch (option) 26. Flow connection
7. Inspection hatch17. Gas multiblock27. Thermostat pocket
8. Inspectionhatch for condensate collector 18. Venturi28. Display
The inlet side of the fan is fitted with a venturi, where air and gas
are mixed according to a fixed ratio. When there is a heat demand,
the fan will pre-vent. The fan draws in the combustion air, which is
mixed with the gas to optimum effect in the venturi. The fan moves
the homogenous gas/air mixture through to the burner. The mixture
is then ignited by the combined ignition and ionisation electrode,
which also monitors the flame. Combustion then takes place. Following combustion, the hot flue gases pass through the cast aluminium heat exchanger. Here, the flue gases release their heat to the
heating water in the heat exchanger. The heat output of the boiler is
controlled on the basis of the settings and the prevailing water temperatures that are measured by the temperature sensors. With flue
gas temperatures below dew point (approx. 55°, the temperature at
which the water vapour in the flue gases starts to condense), the
water vapour in the flue gases will condense in the lower part of the
heat exchanger. The heat released during this condensation process (called latent heat or heat of condensation) is also transferred
to the heating water. The condensed water is discharged through a
trap. The flue gases flow through the condensate collector and are
discharged via the flue gas discharge pipe.
15.9 Boiler Control
The advanced control system of the boiler, the abc
tees extremely reliable heat supplies. This means that the boiler
responds quickly and efficiently to negative environmental influences (such as hydraulic flow problems, air flow problems, etc.). If
problems of this kind occur, the boiler will not lock out, but initially
modulate down and, depending on the nature of the problem,
switch off temporarily (shutdown or control stop) and try again
after a pre-determined time. Providing the situation is not hazardous, the boiler will always continue to attempt to provide heat. For
a continuous supply of heat, the boiler requires a minimum flow of
30 % of the nominal flow at the relevant design temperatures. The
boiler can be equipped with a second return for CT circuit (available as an accessory). The second return can contribute additional
efficiency if the installation includes different temperature groups.
®
, guaran-
15.9.1 Temperature control
The Remeha Gas 210 ECO PRO is equipped with electronic temperature control based on flow, return and boiler block temperature
sensors. The flow temperature is adjustable between 20 and 90°C
(factory setting 80°C).
64
15.9.2 Low water level protection
The Remeha Gas 210 ECO PRO is equipped with low water protection based on temperature difference measurements and temperature increase measurements.
114494-03
Page 65
GAS 210 ECO PRO
15. Efficiency data and gas inspection labels
15.9.3 Maximum protection
The maximum protection switches the unit off if the water temperature is too high (110°C) and interlocks it on the control box. Once
the fault has been remedied, the unit can be reset using the reset-
key.
15.9.4 Frost protection
The unit must be installed in a frost-free area to prevent freezing
of the condensate drain pipe. If the temperature of the heating
water drops too much, the built-in unit protection activates.
114494-03
65
Page 66
16. Application data
16. Application data
16.1 General
The boiler is suitable for a wide range of applications. The boiler
offers numerous flue gas, hydraulic, gas and control application options, but, at the same time, is not complicated to install.
This and its moderate dimensions, low noise levels and cascade
options mean the boiler can be installed almost anywhere (for
general legal requirements, see Section 13.2).
16.2 Air and flue gas application options
The choice of versions (open or closed combustion air supply)
provides excellent siting flexibility for the boiler. A motorised flue
gas discharge valve is available as an accessory and is used for
overpressure flue gas cascade arrangements.
The boiler is equipped with an enclosed housing that also serves
as an air box. An air filter and connection set are available for situations in which the boiler has to be commissioned during the construction phase or has to operate in a heavily polluted environment
(this only applies to room ventilated versions).
Direct connection to structural ducts is not acceptable because
of condensation, see Chapter 7 for instructions and flue gas discharge tables.
GAS 210 ECO PRO
16.3 Hydraulic application options
The advanced boiler control (abc®) and relatively low hydraulic
resistance ensures that the boiler can be used in virtually any
hydraulic system.
16.4 Cascade application
The boiler is also suited for configuration in a cascade. For overpressure flue gas cascade arrangements, use our motorised flue
gas discharge valve (available as an accessory). This prevents
flue gas from flowing back to boilers that are not in operation. As a
result of the narrow width and depth of the boiler, a heat output of
400 kW (2 x Gas 210- 200) can be provided in a floor area of just
under 1.2 m2. A floor area of less than 3 m2 is sufficient to include
room for service and maintenance. If necessary, consult our Technical department.
66
114494-03
Page 67
GAS 210 ECO PRO
16. Application data
fig. 36 Example of a hydraulic diagram cascade configuration
1. modulating cascade controller8. automatic air vent
2. pump9. pressure-free distributor (not supplied by Remeha, see table 19 for dimensions)
3. safety valve10. drain cock
4. outside temperature sensor11. system pump
5. non return valve12. expansion vessel system
6. expansion vessel13. flow temperature sensor
7. manual seal
114494-03
67
Page 68
16. Application data
BI
GAS 210 ECO PRO
The following table shows the minimum dimensions for the various
pipes and for the low loss header based on a dT design of 20°.
The boiler has a no built-in pump.