Please read through the manual carefully before using the product, and keep it in a safe place for later reference. In order to
ensure continued safe and efficient operation we recommend that the product is serviced regularly. Our service and customer
service organisation can assist with this.
We hope you enjoy years of problem-free operation with the product.
Danger
This appliance can be used by children aged from
8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of
experience and knowledge if they have been
given supervision or instruction concerning use of
the appliance in a safe way and understand the
hazards involved. Children shall not play with the
appliance. Cleaning and user maintenance shall
not be made by children without supervision.
1.1.1
Safety instructions for the installer
Danger
If you smell gas:
1. Do not use a naked flame, do not smoke, do
not operate electrical contacts or switches
(doorbell, light, motor, lift, etc.).
2. Shut off the gas supply.
3. Open the windows.
4. Locate the probable leak and seal it
immediately.
5. If the leak is before the gas meter, contact the
gas supplier.
Danger of electric shock
Before any work, switch off the mains supply to
the boiler.
Danger
If you smell flue gases:
1. Switch off the appliance.
2. Open the windows.
3. Locate the probable source of the flue gas
leak and fix it immediately.
Warning
After any maintenance or repair work, check the
entire heating installation to ensure that there are
no leaks.
Warning
The condensation drain must not be changed or
sealed. If a condensate neutralisation system is
used, the system must be cleaned regularly in
accordance with the instructions provided by the
manufacturer.
Caution
Do not touch the flue gas pipes. Depending on
the boiler settings, the temperature of the flue gas
pipes can rise to over 60°C.
Caution
Do not touch radiators for long periods.
Depending on the boiler settings, the temperature
of the radiators may exceed 60°C.
Caution
Take precautions with the domestic hot water.
Depending on the boiler settings, the domestic
hot water temperature may exceed 65°C.
1.1.2
Safety instructions for the user
Danger
If you smell gas:
1. Do not use a naked flame, do not smoke, do
not operate electrical contacts or switches
(doorbell, light, motor, lift, etc.).
2. Shut off the gas supply.
3. Open the windows.
4. Evacuate the property.
5. Contact a qualified professional.
Danger
If you smell flue gases:
1. Switch off the appliance.
2. Open the windows.
3. Evacuate the property.
4. Contact a qualified professional.
Danger of electric shock
Before any work, switch off the mains supply to
the boiler.
Caution
Do not touch the flue gas pipes. Depending on
the boiler settings, the temperature of the flue gas
pipes can rise to over 60°C.
Caution
Do not touch radiators for long periods.
Depending on the boiler settings, the temperature
of the radiators may exceed 60°C.
Caution
Take precautions with the domestic hot water.
Depending on the boiler settings, the domestic
hot water temperature may exceed 65°C.
1.2
Recommendations
Danger
For safety reasons, we recommend fitting smoke and CO
detectors and alarms at suitable places in your home.
Caution
The boiler must always be connected to the protective earthing.
Earthing must comply with the prevailing installation standards.
Earth the appliance before making any electrical connections.
For the type and calibre of the protective equipment, refer to the
chapter Electrical Connections in the Installation and Service
Manual.
Caution
If a power cord comes with the appliance and it turns out to be
damaged, it must be replaced by the manufacturer, its after sales
service or persons with similar qualifications in order to obviate
any danger.
Caution
A disconnection device must be fitted to the permanent pipes in
accordance with the installation rules.
Caution
Power the appliance via a circuit that includes an omni-polar
switch with contact opening distance of 3 mm or more.
2
Caution
Drain or have the boiler and heating system drained by a qualified
professional if the home is left empty for a long period of time and
there is a chance of frost.
Caution
Remove the boiler casing only to perform maintenance and repair
work. Always put the casing back in place after such work.
Caution
To enjoy warranty cover, no modifications must be made to the
boiler.
Caution
The frost protection function only protects the boiler, not the
heating system.
Caution
The frost protection function does not work if the boiler is powered
off.
Caution
The appliance should be switched to Summer or Frost Protection
mode rather than be switched off in order to guarantee the
following functions:
Avoidance of pumps blocking
Frost Protection
Important
Respect the minimum and maximum water inlet pressure to
ensure correct operation of the boiler: refer to the chapter
Technical Specifications.
Important
Only qualified professionals are permitted to install the boiler, in
accordance with prevailing local and national regulations.
Important
Never remove or cover labels and data plates affixed to the
boiler.
Labels and data plates must be legible throughout the entire
lifetime of the boiler. Immediately replace damaged or illegible
instructions and warning labels.
1.3 Liabilities
Important
Keep this document close to the place where the appliance is
installed.
1.3.1 Manufacturer's liability
Our products are manufactured in compliance with the requirements of the
various Directives applicable. They are therefore delivered with the
marking and any documents necessary. In the interests of the quality of
our products, we strive constantly to improve them. We therefore reserve
the right to modify the specifications given in this document.
Our liability as manufacturer may not be invoked in the following cases:
Failure to abide by the instructions on installing and maintaining the
appliance.
Failure to abide by the instructions on using the appliance.
Faulty or insufficient maintenance of the appliance.
1.3.2 Installer's liability
The installer is responsible for the installation and initial commissioning of
the appliance. The installer must observe the following instructions:
Read and follow the instructions given in the manuals provided with the
appliance.
Install the appliance in compliance with prevailing legislation and
standards.
Carry out initial commissioning and any checks necessary.
Explain the installation to the user.
If maintenance is necessary, warn the user of the obligation to check the
appliance and keep it in good working order.
Give all the instruction manuals to the user.
1.3.3 User's liability
To guarantee optimum operation of the system, you must abide by the
following instructions:
Read and follow the instructions given in the manuals provided with the
appliance.
Call on a qualified professional to carry out installation and initial
commissioning.
Get your installer to explain your installation to you.
Have the required inspections and maintenance carried out by a
qualified installer.
Keep the instruction manuals in good condition close to the appliance.
This manual uses various danger levels to draw attention to special
instructions. We do this to improve user safety, to prevent problems and to
guarantee correct operation of the appliance.
Danger
Risk of dangerous situations that may result in serious personal
injury.
Danger of electric shock
Risk of electric shock.
Warning
Risk of dangerous situations that may result in minor personal
injury.
Caution
Risk of material damage.
Fig.1
Important
Please note: important information.
See
Reference to other manuals or pages in this manual.
2.1.2 Symbols used on the appliance
1 Alternating current.
2 Protective earthing.
3 Before installing and commissioning the appliance, carefully read
the instruction manuals provided.
4 Dispose of used products through an appropriate recovery and
recycling structure.
5 Caution: danger of electric shock, live parts. Disconnect the mains
This product complies with the requirements of the following European
directives and standards:
Standards: EN15502
Efficiency Directive 92/42/EC
Low Voltage Directive 2014/35/EU
Generic standard: EN 60335-1
Relevant standard: EN 60335-2-102
Electromagnetic Compatibility Directive 2014/30/EU
Generic standards: EN 61000-6-3, EN 61000-6-1
Relevant Standard: EN 55014
Ecodesign Directive
This product conforms to the requirements of European Directive
2009/125/EC on the ecodesign of energy-related products.
In addition to the legal requirements and guidelines, the supplementary
guidelines in this manual must also be followed.
Supplements or subsequent regulations and guidelines that are valid at
the time of installation shall apply to all regulations and guidelines
specified in this manual.
Warning
The appliance must be installed by a qualified professional in
accordance with applicable local and national regulations.
3.1.2 Factory test
Before leaving the factory, each appliance is tested for the following:
3.2.1 Electrical diagram for the MID control unit HMI T-control
1 MID control panel HMI T-control
2 Service connector, allows the technician to work on
the equipment
3 230 V mains power supply connection with 10 A fuse
4 On/Off switch
5 230 V connector, connection with the boiler
6 24 V connector, connection with the boiler
7 SCB-02 PCB
8 CB-09 PCB
9 IF-01 PCB
The control box is used to control the operation of a Gas 120 ACE boiler.
The box is equipped with a HMI T-control control panel.
4.2
Main components
Fig.3
4.3 PCBs
Fig.4
SCB-02 expansion board
1 Protective cover
2 On/Off switch
3 HMI T-control control panel
4 Service connector, allows the technician to work on the equipment
5 SCB-02 PCB
6 IF-01 PCB
7 CB-09 PCB
4.3.1 SCB-02 expansion board description
The expansion board SCB-02 has the following features;
control of a (mixing) zone for heating (or cooling)
control of one domestic hot water (DHW) zone
0–10 V output control for a PWM system pump
two potential-free contacts for status notifications
If the boiler is fitted with the SCB-02 board, then this is
automatically recognised by the automatic control unit of the
boiler.
On removing this board, the boiler will show an error code. To
prevent this error, carry out an auto-detect immediately after
removing this board.
4.3.2 Description of the CB-09 PCB
4 Description of the product
Fig.5
Fig.6
The CB-09 PCB allows additional inputs to be connected as per the
following table:
Mar
ker
Con
nector
Description
1R-BusNot used
2BLBoiler frost protection (active if contact open)
3RLRelease open contact
4ToutNot used
5PWMModulating pump control connection
6X4Modulating pump power connection
4.3.3 Description of the IF-01 PCB
The IF-01 PCB is factory fitted and allows additional inputs such as a
sensor or switch to be connected to the system.
This PCB controls the boiler with the 0-10V signal from an external control
system.
ConnectorDescription
0-10 (input)The 0-10V signal corresponds to a temperature or power
set point, depending on the position of the jumpers
0-10 (output)Output signal indicating the boiler's operating mode
A complete control box for a Gas 120 ACE boiler
Two mounting bolts with two serrated washers
An outdoor temperature sensor
A control box installation, user and service manual
A detailed list of accessories and options can be found in our catalogue.
Caution
The appliance must be installed and maintained by a certified
professional in accordance with prevailing statutory texts and
codes of practice.
5.2
Fig.9
Unpack and fit the control box
Caution
Wear gloves when handling the control box.
1. Cut and remove the packaging.
Important
The technical documentation is housed in the protective block.
Fig.10
2. Remove the two screws from the boiler's rear top panel.
Only qualified professionals may carry out electrical connections, always
with the power off.
Earth the appliance before making any electrical connections.
Power the appliance via a circuit that includes an omni-polar switch with
contact opening distance of 3 mm or more.
When making electrical connections to the mains, respect the polarities.
Danger
Position the various electrical cables in such a way that they never
touch the heating pipes.
Keep the various electrical cables far enough from the heating
pipes so that they cannot be damaged by the effect of the heat.
5.3.2 Electrical power supply
Power supply voltage230 V AC/50 Hz
Caution
Please ensure the polarities shown on the terminals are followed,
i.e live (L), neutral (N) and earth ()
5.3.3 Recommended cable cross section
Decide on the cable according to the following information:
Distance of the appliance from the power source.
Upstream protection.
Neutral operating conditions.
Tab.2Specifications of the power cable and the power source
Caution
Provide a separate power supply for the pump and a power
switch, if necessary.
The output available per outlet is 450 W (2 A, with cos ϕ = 0.7)
and the inrush current must be less that 16 A. If the load exceeds
either of these values, the control must be relayed using a
contactor that must in no circumstances be installed in the control
panel. The sum of the currents from all outlets must not exceed
5 A.
5.3.4 Cable routing and access to the connection terminal
blocks
Fig.20
Fig.21
1. Unlock the front door.
2. Tilt and lift the door to remove it.
3. Remove the two screws and dismantle the rear top panel.
5. Ensure that the cables are correctly routed and affix the cable(s) using
the traction arrester devices.
230 V 230 V circuits (left)
Sensor Sensor circuits (right)
Danger
Separate the sensor cables from the 230 V circuit cables.
6. Connect the boiler's main power supply cable.
Fig.24to SCB-02
Fig.25to SCB-02
5.3.5 Connecting a modulating thermostat
The boiler is fitted with an R-Bus connection as standard. This connection
is also compatible with OpenTherm. This enables the user to connect
OpenTherm modulating thermostats (such as iSense Pro) or R-Bus
thermostats (such as eTwist) without any further adjustments being made
to the appliance. The boiler is also suitable for OpenTherm Smart Power.
1. In the case of a room thermostat: install the thermostat in a reference
room.
2. Connect the two-wire cable for the thermostat to the R-Bus terminals
for the connector. It does not matter which wire is connected to which
terminal block.
Important
If the domestic hot water temperature can be set on the
OpenTherm thermostat, the boiler will supply this temperature,
with the value set in the boiler as a maximum.
5.3.6 Connecting an on/off thermostat
The boiler is suitable for connection to a two-wire on/off room thermostat
(Tk).
1. Fit the thermostat in a reference room.
2. Connect the two-wire cable for the thermostat to the R-Bus terminals
of the connector. It does not matter which wire is connected to which
terminal block.
5.3.7 Frost protection combined with on/off thermostat
Fig.26to SCB-02
Fig.27to SCB-02
When an on/off thermostat is used, the pipes and radiators in a frostsensitive room can be protected by a frost thermostat. The radiator valve
in the frost-sensitive room must be open.
1. Place a frost thermostat (Tv) in a frost-sensitive room (e.g. a garage).
2. Connect the frost thermostat (Tv) and the on/off thermostat (Tk) in
parallel to the
R-Bus terminals of the connector.
Warning
If a Remeha eTwist or OpenTherm thermostat is used, a frost
thermostat cannot be connected in parallel to the R-Bus terminals.
In this case, ensure frost protection of the central heating system
in combination with an outside sensor.
5.3.8 Frost protection combined with outdoor temperature
sensor
The central heating system can also be protected against frost in
combination with an outdoor temperature sensor. The radiator valve in the
frost-sensitive room must be open.
1. Connect the outdoor temperature sensor to the Tout terminals of the
connector.
The frost protection works as follows with an outdoor temperature sensor:
If the outdoor temperature is lower than -10 °C: heat demand from the
boiler.
If the outdoor temperature is higher than -10 °C: no heat demand from
the boiler.
Fig.28to SCB-02
Fig.29to CB-09
Important
The outdoor temperature before the start of frost protection can be
changed with the AP080 parameter.
5.3.9 Connecting an outdoor temperature sensor
An outdoor temperature sensor (accessory) can be connected to the Tout
terminals of the connector. If the boiler is equipped with an on/off
thermostat, the temperature is controlled using the setpoint of the internal
heating curve (F). Various parameter settings can be used to change the
internal heating curve.
1. Connect the plug from the outdoor temperature sensor to the Tout
terminal.
5.3.10 Blocking input
The boiler has a blocking input (normally closed contact). This input
relates to the BL terminals of the connector.
If this contact is opened, the boiler will be blocked or locked out.
Change the function of the input by configuring the AP001 parameter.
Important
Remove the bridge if this input is used.
Only suitable for potential-free contacts.
Connecting a three-way valve (230 VAC). The connection can be used for
a boiler group (zone).
Connect the three-way valve as follows:
Earth
N
Neutral
Open
Closed
5.3.18
Connecting a system pump for mix group (zone) The maximum power
consumption is 300 VA.
Connecting a system pump for mix group
Fig.37Pump connector
Fig.38Status notifications
Fig.390–10 V output connector
Connect the pump as follows:
Earth
N
Neutral
L
Phase
5.3.19 Connecting status notifications
The two potential-free contacts, Status, can be configured as required.
Depending on the setting, a particular status can be transmitted by the
boiler.
Connect a relais as follows:
Nc
Normally closed contact. Contact will open when status occurs.
C
Main contact.
No
Normally opened contact. Contact will close when status occurs.
Select the desired status notification (setting) using parameter EP018 and
EP019.
5.3.20 Connecting 0–10 V output
The 0-10 contact can be used to connect a PWM system pump. The
speed of the pump is modulated based on the signal received from the
boiler. Depending on the make and type of pump, the pump can be
controlled by a 0–10 V or a PWM signal.
Connect the system pump controller to connector 0-10.
Select the type of signal that will be sent from the boiler using the
parameter EP029.
Select the type of signal that controls the pump using the parameter
EP028.
If possible, use the pump modulation signal. This provides the
most accurate pump control.
If the automatic burner unit does not support pump modulation,
the pump will behave as an on/off pump.
5.3.21 Connection options for the expansion PCB - IF-01
Fig.40IF-01 PCB
The expansion board IF-01 is pre-installed in the instrument box as
standard.
Caution
Do not connect a frost thermostat or room thermostat to the boiler
if using the 0–10 V control PCB.
Connecting the status relay (Nc)
If the boiler locks out, a relay is de-energised and the alarm can be
transmitted via a potential-free contact (maximum 230 V, 1 A) on terminals
Nc and C of the connector.
Connection (OTm)
The interface uses OpenTherm to communicate with the boiler control
unit. To make this possible, the OTm connection must be connected to the
OpenTherm input of the boiler control unit.OTm
Analogue input (0-10 V)
A choice can be made with this control between control based on
temperature or heat output. The two controls are described briefly below.
1. Connect the input signal to terminals 0–10 of the connector.
Tab.3Temperature-based control (°C)
Jumper 2 Input signal (V)Temperature °CDescription
0–1.50–15Boiler off
1.5–1.815–18Hysteresis
1.8–1018–100Desired temperature
Fig.41Switch jumper (2)
The 0–10 V signal controls the boiler supply temperature. This control
modulates on the basis of flow temperature. The output varies between
the minimum and maximum value on the basis of the flow temperature set
point calculated by the controller.
A jumper (2) on the interface is used to select either temperature-based
control ( ) or output-based control (%).
Tab.4Control based on heat output
Jumper 2 Input signal (V)Heat output (%)Description
(1)
0–2.0
%
2.0–2.2
2.0–10
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
The 0–10 V signal controls the boiler output. This control modulates on the
basis of the heat output. The minimum output is linked to the boiler's
modulation depth. The output varies between the minimum and maximum
value on the basis of the value defined by the controller.
Analogue output (0–10 V)
Fig.42
Switch jumper (1)
Fig.43Connecting an interface connector
This feedback can be based on temperature or heat output. The two
controls are described briefly below.
A jumper (1) on the interface is used to select either temperature ( ) or
output (%).
Tab.5Temperature message
Jumper 1 Output signal (V)Temperature °CDescription
0.5–Alarm
1–1010–100Supplied tempera
ture
Tab.6Output message
Jumper 2 Output signal (V)Heat output (%)Description
00–15Boiler off
0.515–20Alarm
%
(1)
2.0–10
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
20–100Supplied heat output
5.3.22 Connecting a PC/laptop
There is a Service connector next to the control panel. A Recom interface
can be used to connect a PC, laptop or a Smart Service Tool here. Using
the Recom PC/laptop service software, you can enter, change and read
out various boiler settings.
Connecting an interface connector:
1. Move the Service connector slide upwards.
2. Push the interface connector into place. It should snap shut with a
click.
Disconnect the interface connector again:
3. Maintain slight tension on the interface connector
4. Push the slide downwards. The interface connector will now be
released.
5. Pull the interface connector from the connector.
In the factory, the different circuits are configured as indicated in the table.
You can modify this configuration and adapt it to the needs of your
installation using the installation type described here as a guide.
Tab.7
CircuitCircuit typeSpecifications
CIRCADirect heating circuitGradient: 1.5
Maximum temperature: 90 °C
DHWDomestic hot water circuitSet point temperature: 55 °C
6.2
Fig.44
Connection example - SCB-02
1 boiler + 1 mixing zone + domestic hot water (DHW) zone
Commissioning the boiler is done for first time use, after a prolonged shutdown (more than 28 days) or after any event that would require complete
re-installation of the boiler. Commissioning of the boiler allows the user to
review the various settings and checks to be made to start up the boiler in
complete safety.
1. Check that the gas type supplied matches the data shown on the
boiler's data plate.
Do not commission the boiler if the gas supplied does not match the
gas types approved for the boiler.
2. Check connection of the earth wires.
3. Check the tightness of the gas circuit from the non-return valve to the
burner.
4. Check the hydraulic circuit from the boiler's isolation valves to the
connection to the heating body.
5. Check the hydraulic pressure in the heating system.
6. Check the electricity supply connections to the various boiler
components.
7. Check the electrical connections on the thermostat and the other
external components.
8. Check the ventilation in the room in which the system is installed.
9. Check the flue gas connections.
7.3 Checking the gas inlet
Danger
Ensure that the boiler is switched off.
1. Open the main gas valve.
2. Open the front panel.
3. Check the gas supply pressure at the pressure outlet on the gas valve
unit.
4. Check the tightness of the gas connections made after the gas valve
unit in the boiler.
5. Check the tightness of the gas pipe, including any valves, from the
non-return valve to the burner. The test pressure must not exceed 60
bar (0.006 MPa).
6. Vent the gas supply pipe by unscrewing the pressure outlet on the gas
valve unit. Close the outlet again when the pipe has been sufficiently
vented.
7. Check the tightness of the gas connections in the boiler.
Initial commissioning must be done by a qualified professional.
If adapting to another type of gas, e.g. propane, the boiler must
be adjusted before it is switched on.
1. Open the main gas valve.
2. Switch the power on with the boiler's on/off switch.
The boiler starts before the control panel display is active.
3. Set the following parameters when the appliance is first switched on:
Select Country and Language
Configure the date and time used by the appliance
Enable Daylight Saving Time
CN1 and CN2 (codes present on the boiler data plate).
4. Set the components (thermostats, control system) so that they request
heat.
5. Check the hydraulic pressure in the installation shown on the control
panel display.
Recommended hydraulic pressure between 0.15 and 0.2 MPa (1.5
and 2.0 bar).
7.7 Gas settings
Fig.46
Important
In the event of an error during start-up, a message with the
corresponding code is displayed. The meaning of the error codes
can be found in the error table.
7.6.2 Shutting down the boiler
The boiler must be shut down in order for certain operations to be carried
out on the equipment or its environment.
In other situations, such as an extended absence period we recommend
that Holiday Mode mode is used in order to benefit from the heating pump
anti-blocking function and to protect the installation from frost.
To shut down the boiler:
1. Press the on/off switch.
7.7.1 Adapting/adjusting the boiler to different types of gas
1 Gas valve unit on the
Gas 120 ACE - 65
Gas 120 ACE - 90
2 Gas valve unit on the
Gas 120 ACE - 115
Warning
Only a qualified engineer may carry out the following operations.
The boiler is pre-set in the factory to run on G20 type natural gas (H gas).
Before operating with a different type of gas, carry out the following steps:
4. If the measured value differs from that given in the table, correct the
gas/air ratio.
5. Using the setting screw A, set the percentage of O2 for the gas type
being used to the nominal value. This should always be within the
highest and lowest setting limits.
Allow the pressure to stabilise for approximately 60 seconds between
each setting modification.
Important
The boilers are supplied with a variety of gas valve units.
Compare the gas valve unit in the boiler with those in the drawings
and see the drawing for the position of adjusting screw A for full
load.
Fig.50Part load test
Tab.16
Values at part load for G20 (H gas)
(1) nominal value
(2) Values given as a guide
Performing the part load test
1. If the full load test is still running, press the button to change the
load test mode.
2. If the full load test was finished, select the tile [] to restart the
chimney sweep menu.
A
Change load test mode
B MinimumPower
3. Select the MinimumPower test in the menu Change load test mode.
The part load test starts. The selected load test mode is shown in
the menu and the icon
appears in the top right of the screen.
4. Check the load test settings and adjust if necessary.
Only the parameters shown in bold can be changed.
5. End the part load test by pressing the button.
The message Running load test(s) stopped! is displayed.
Control and setting values for O2 at part load
1. Set the boiler to part load.
2. Measure the percentage of O2 in the flue gases.
3. Compare the measured value with the set point values in the tables.
The O2 values at low load must be higher than the values at full
load.
4. If the measured value is outside of the values given in the table,
correct the gas/air ratio.
5. Using the adjusting screw B, set the percentage of O2 for the gas type
being used to the nominal value. This should always be within the
highest and lowest setting limits.
Allow the pressure to stabilise for approximately 60 seconds between
each setting modification.
7.8
7.9
Important
The boilers are supplied with a variety of gas valve units.
Compare the gas valve unit in the boiler with those in the drawings
and see the drawing for the position of adjusting screw A for full
load.
6. Repeat the high speed test and the low speed test as often as
necessary until the correct values are obtained without having to
make additional adjustments.
7. Set the boiler back to the normal operating status.
Displaying the water pressure on the control panel
1. Highlight the Water Pressure icon.
The pressure is displayed on the main screen of the control panel.
Modifying the ΔT value
In systems with several operating temperatures, the boiler's ΔT value must
be increased.
Increase the ΔT value using the GP021 parameter. When increasing the
ΔT, the control unit limits the linear flow temperature to 80 °C maximum.
This does not modify the value set for the maximum flow temperature. This
value can be adjusted using the CP000 parameter.
Important
If the heat demand is greater than 80 °C with the increased ΔT
value, Recom (or the service tool) will use a sub-status to
indicate that the limited flow temperature is active.
Always ensure that circulation is minimal (using a bypass or
low-loss header if necessary) to prevent the boiler from locking
out.
If a PWM-controlled central heating pump is controlled by the
boiler control panel, set the PP014 parameter to 2.
7 Commissioning
7.10
Points to check after commissioning
1. Remove the measuring equipment.
2. Put the flue gas sampling plug back in place.
3. Put the front casing back.
4. Bring the heating system temperature up to approximately 50°C.
5. Shut down the boiler.
6. After about 10 minutes, vent the air in the heating system.
7. Check that there are no leaks (hydraulic circuit, gas circuit, etc.).
8. Check that the boiler equipment is operating correctly.
9. Check that the thermostats are operating correctly and have the
correct settings.
10. Check the water pressure. Recommended pressure: between 0.15
and 0.2 MPa (1.5 and 2.0 bar).
11. Tidy away or scrap the various packaging items.
12. If necessary, affix the second type plate provided with the
documentation to a visible part of the boiler.
13. Affix the data plate supplied with the control box beside the boiler type
plate.
14. Instruct the user in the operation of the system, boiler and controller.
15. Inform the user of the periodicity of maintenance work to be carried
out.
Term given to the different hydraulic circuits CIRCA, CIRCB, .... It
indicates several rooms served by the same circuit.
Tab.20Example
MarkerZoneFactory-set name
Zone 1CIRCA
Zone 2CIRCB
8.1.2 Activity
This term is used when programming time ranges. It refers to the client's
desired comfort level for different activities during the course of the day.
One set point temperature is associated to each activity. The last activity
of the day remains valid until the first activity of the following day.
Tab.21Example:
Start
of the activity
6:30
9:00
17:00
20:00
23:00
ActivitySet point temperature
Morning
Away
Home
Evening
Sleep
20 °C
19 °C
20 °C
22 °C
16 °C
8.2 Switching the summer mode on or off
You can switch off the central heating function of the boiler to save energy,
for example during the summer period.
1. Select the tile [].
2. Press the button to confirm the selection.
3. Use the rotary knob to select Force summer mode.
4. Press the button to confirm the selection.
5. Use the rotary knob to select the following setting:
5.1. On to switch off the central heating function.
5.2. Off to switch the central heating function on again.
6. Press the button to confirm the selection.
8.3
Activating the holiday program
If you will be absent for several weeks, you can reduce the room
temperature and domestic hot water temperature in order to save energy.
To activate holiday mode for all zones including the domestic hot water:
4. Modify the name of the zone (20 characters max.).
5. Select Icon display zone.
6. Modify the linked symbol.
Factory-set name and symbolCustomer-set name and symbol
8.7
Room temperature for a zone
8.7.1 Selecting the operating mode
To set the room temperature for the different living zones, you can choose
between five operating modes:
Tab.26
ModeDescription
Scheduling
Manual
Short temperature change
Holiday
Antifrost
Selection of a timer programme
The room temperature is constant
The room temperature is forced for a defined period
The room temperature is reduced during an absence period to save energy
The installation and equipment are protected during the winter period
8.7.2 Changing the temperature settings of a zone
You can change the temperature settings of activities for the zone
selected.
1. Select the icon for the affected zone, , for example.
2. Select the desired operating mode:
1. Select the icon for the zone to be modified; , for example.
2. Select Set Heating Activity Temperatures.
3. Select the activity to change its temperature setting.
8.7.3 Changing the room temperature temporarily
Regardless of the operating mode selected for a zone, it is possible to
modify the room temperature for a defined period. Once this time has
elapsed, the selected operating mode will restart.
1. Select the icon for the zone to be modified; , for example.
2. Select Short temperature change.
3. Define the duration in Hour and in Minute.
4. Set the Temporary room setpoint per zone parameter.
8.7.4 Timer programming for heating
Activating timer programming mode
In order to use the timer programme, the timer programming (Scheduling)
mode must be activated. This is activated for each zone individually.
1. Select the icon for the zone to be configured, , for example.
2. Select Zone configuration > ZoneCurrentMode > Scheduling.
A timer programme can be used to vary the room temperature in a living
zone depending on activities during the day. This can be programmed for
each day of the week.
1. Select the icon for the zone to be programmed, , for example.
Fig.54
8.8 Domestic hot water temperature
2. Select Zone configuration > Heating Schedule.
3. Select the programme to be modified.
The programmed activities for Sunday are displayed.
The last activity of the day remains active until the first activity of the
following day.
4. Select the day to be modified.
5. Carry out the following actions according to your needs:
Modify the timings for programmed activities.
Add a new activity.
Delete a programmed activity (choose the activity "Delete").
Copy programmed daily activities to other days.
Modify temperatures linked to an activity.
Selecting a timer programme
In the Timer programming operating mode, three programs are available
per zone. Each program is independent.
To select a timer programme for a zone:
1. Select the icon for the affected zone, , for example.
2. Select Scheduling.
3. Select the desired timer programme.
8.8.1 Selecting the operating mode
Tab.27
ModeDescription
Scheduling
Manual
Hot water boost
Holiday
Antifrost
For the production of domestic hot water, you can choose between five
operating modes.
1. Select the icon for the DHW zone.
2. Select the desired operating mode:
Selection of a timer programme
The domestic hot water temperature remains at the comfort temperature
permanently
The production of domestic hot water is forced at the comfort temperature
for a defined duration
The domestic hot water temperature is reduced during an absence period
to save energy
The installation and equipment are protected during the winter period
8.8.2 Forcing domestic hot water production (override)
Regardless of the selected operating mode, you can force domestic hot
water protection to the comfort temperature for a defined duration.
8.8.3 Modifying the domestic hot water set point temperatures
You can modify the "Comfort domestic hot water" and "Reduced domestic
hot water" set point temperatures.
1. Select the icon for the DHW zone.
2. Select one of the following menus:
MenuDescription
ComfortZoneDHWtempOnly modify the "Comfort domestic hot water" set point tem
perature
Zone configuration > Domestic Hot Water SetpointsModify the "Comfort domestic hot water" and "Reduced do
mestic hot water" set point temperatures.
8.8.4 Timer programming for domestic hot water
Activating timer programming mode
In order to use the timer programme, the timer programming (Scheduling)
mode must be activated. This is activated for each zone individually.
1. Select the icon for the DHW zone.
2. Select Zone configuration > OperatingZoneMode > Scheduling.
Fig.55
Creating a timer programme for domestic hot water
A timer programme can be used to vary the domestic hot water
temperature depending on activities during the day. This can be
programmed for each day of the week.
1. Select the icon for the DHW zone.
2. Select Zone configuration > DHW Schedule.
3. Select the programme to be modified.
The programmed activities for Sunday are displayed.
The last activity of the day remains active until the first activity of the
following day.
4. Select the day to be modified.
5. Carry out the following actions according to your needs:
Modify the timings for programmed activities.
Add a new activity.
Delete a programmed activity (choose the activity "Delete").
Copy programmed daily activities to other days.
Modify temperatures linked to an activity.
Selecting a timer programme
In the Timer programming operating mode, three programs are available.
To select a timer programme:
Certain parameters, which may affect the operation of the appliance, are
protected by an access code. Only the installer is authorised to modify
these parameters.
To access the installer level:
9.2 Setting the heating curve
Fig.56
1. Select the
icon.
2. Enter the code 0012.
The Installer level is activated On. After modifying the desired
settings, exit the Installer level.
3. To exit the Installer level, select the On icon, then Confirm.
If no actions are taken for 30 minutes, the system will automatically exit
the Installer level.
The relationship between the outdoor temperature and the central heating
flow temperature is controlled by a heating curve. This can be adjusted
according the requirements of the installation.
To set the heating curve for a zone:
1. Select the icon for the zone to be modified; , for example.
2. Select Heating Curve.
3. Set the following parameters:
Tab.28
ParameterDescription
Slope: Value of the heating curve gradient.
underfloor heating circuit: gradient between 0.4 and 0.7
radiator circuit: gradient of approx. 1.5
Max: Maximum temperature of the circuit
Base: Curve base point temperature (default value: Off = auto
matic mode).
If Base: Off, the curve base point temperature becomes
equal to the room set point temperature
50 °C; 0 °CWater temperature in the circuit for an outdoor tempera
ture. This data is visible all along the curve.
9.3
Drying screed
The screed drying function reduces the drying time of the screed for
underfloor heating. This function can be activated for individual zones.
Every day at midnight, the set point temperature is recalculated and the
number of days is decreased.
To activate this function:
1. Select the icon for the zone to be activated, , for example.
1 to 7+25 °C+55 °CTemperature increased every day by 5 °C
8 to 14+55 °C+55 °CTemperature maintained at +55 °C without dropping at night
15 to 21+55 °C+25 °CTemperature decreased every day by 5 °C
9.4
Configuring the maintenance message
The boiler control panel is used to display a message whenever a service
is necessary.
To configure the maintenance message:
1. Select the Maintenance icon.
2. Select Service notification.
3. Select the desired type of notification:
Type of notification:Description
NoneNo maintenance message
Custom notificationThe maintenance message will be displayed once the burner operating hours defined
by the Service Burning hrs parameter have elapsed
ABC notificationRecommended setting
The maintenance message will be displayed according to the power input (energy val
ue):
Gas 120 ACE - 65 : 90,000 kWh
Gas 120 ACE - 90 : 135,000 kWh
Gas 120 ACE - 115 : 180,000 kWh
9.5
Saving the installer details
The name and phone number of the installer can be saved so that the
user can find it easily.
1. Press the key.
2. Select System Settings > Installer Details.
3. Enter the name and phone number.
9.6
Saving the commissioning settings
You can save all installation-specific settings. These settings can be
restored if necessary, for example after replacement of the main electronic
control system board.
1. Press the key.
2. Select Advanced Service Menu > Save as commissioning settings.
3. Select Confirm to save the settings.
When you have saved the commissioning settings, the option Revert
SCB-02Information about the PCB controlling the zones for heating and domestic hot water
CB-09Information on the input/output control PCB
9.9 Menu tree
Level 1 menus accessible with the button:
Level 1 menu
Installation Setup
Commissioning Menu
Advanced Service Menu
Error History
System Settings
Version Information
9.10
List of parameters
Fig.58Code on a OEtroCom-3
Fig.59First letter
Fig.60Second letter
9.10.1 Introduction to parameter codes
The controls platform makes use of an advanced system to categorise
parameters, measurements and counters. Knowing the logic behind these
codes, makes it easier to identify them. The code consists of two letters
and three numbers.
The first letter is the category the code relates to.
AAppliance: Appliance
CCircuit: Zone
DDomestic hot water: Domestic hot water
GGas fired: Gas-fired heat engine
PProducer: Central heating
Category D codes are appliance controlled only. When the domestic hot
water is controlled by an SCB, it is handled like a circuit, with C-category
codes.
The number is always three digits. In certain cases, the last of the three
digits relates to a zone.
9.10.2 Changing the parameters
The boiler’s control unit is set for the most common central heating
systems. These settings will ensure that virtually every central heating
system operates effectively. The user or the installer can optimise the
parameters as required.
Changing the factory settings may adversely affect the operation
of the boiler.
9.10.3 Control unit settings
Important
All tables show the factory setting for the parameters.
The tables also list parameters that are only applicable if the
boiler is combined with other equipment such as an outdoor
sensor.
All possible options are indicated in the adjustment range. The
display of the boiler only shows the relevant settings for the
appliance.
Tab.30Navigation for BASIC INSTALLER level
LevelMenu cascade
Basic installer
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
> Installation Setup > CU-GH08 > Submenu
(1)
> Parameters, counters, signals > Parameters
9 Settings
Tab.31Factory settings at BASIC INSTALLER level
CodeDisplay textDescriptionRangeGas 120
ACE - 65
AP016CH function onEnable central heating heat
demand processing
AP017DHW function onEnable domestic hot water
heat demand processing
AP073Summer WinterOutdoor temperature: upper
0 = Off
111
1 = On
0 = Off
111
1 = On
10 °C - 30 °C222222
Gas 120
ACE - 90
Gas 120
ACE - 115
limit for heating
AP074Force summer
mode
The heating is stopped. Hot
water is maintained. Force
0 = Off
1 = On
000
Summer Mode
AP083Enable master
func
Enable the master functionality
of this device on the S-Bus for
0 = No
1 = Yes
000
system control
AP089Installer nameName of the installer-NoneNoneNone
AP090Installer phoneTelephone number of the
-000
installer
CP510Temporary Room
Setp
Temporary room setpoint per
zone
5 °C - 30 °C202020
Tab.32Navigation for INSTALLER level
LevelMenu cascade
Installer
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
We recommend having the boiler inspected and serviced at regular
intervals.
Caution
Do not neglect to service the boiler. Contact a qualified
professional or take out a maintenance contract for the obligatory
annual servicing of the boiler.
Failure to service the appliance voids the warranty.
Danger of electric shock
Before service work is started, the boiler has to be de-energised
and secured from accidentally being switched back on.
Caution
Have an inspection carried out and the flues swept at least once a
year or more, depending on the regulations in force in your
country.
Caution
Only qualified professionals are authorised to carry out
maintenance work on the boiler and the heating system.
10.2 Maintenance message
Caution
After maintenance or repair work, check the entire heating system
to ensure that there are no leaks.
Caution
Only genuine spare parts may be used.
The boiler display will clearly indicate that a service is required at the
appropriate time. Use the automatic maintenance message for preventive
maintenance, to keep faults to a minimum. The maintenance messages
show which service kit must be used. These service kits contain all parts
and gaskets that are required for the relevant service. These service kits
(A, B or C) are available from your spare parts supplier.
Important
A maintenance message must be followed up within 2 months.
Call your installer as soon as possible.
Caution
Reset the maintenance message following every service.
10.2.1 Viewing the service notifications
When a service notification appears on the display, you can view the
details of the notification.
1. Select the Maintenance icon.
Information about maintenance is displayed (cannot be modified).
10.3 Standard inspection and maintenance operations
Combustion is checked by measuring the O2 percentage in the flue gas
discharge pipe.
For more information, see
Checking/adjusting the combustion, page 36
Performing the full load test, page 36
Control and setting values for O2 at full load, page 36
Performing the part load test, page 37
Control and setting values for O2 at part load, page 37
10.3.2 Venting the heating system
10 Maintenance
Fig.62
Any air in the boiler, pipes or valves must be vented in order to prevent
annoying noises that may be generated during heating or when drawing
water.
1. Open the valves of all the radiators and/or underfloor heating circuits
connected to the system.
2. Set the room thermostat to the highest possible temperature.
3. Wait until the radiators are warm.
4. Shut down the boiler.
5. Wait approximately 10 minutes, until the radiators feel cold.
6. Bleed the radiators. Work from the lowest to the highest.
7. Open the venting valve with the bleed key, keeping a cloth pressed
against the vent.
Warning
The water may still be hot.
8. Wait until water comes out of the venting valve and then close the
venting valve.
9. Start the boiler.
Important
After the power is switched on, the boiler always runs through an
automatic venting program lasting approx. 3 minutes.
10. After venting, check that the water pressure in the system is still
adequate. If necessary, top up the water level in the heating system
11. Adjust the room thermostat or temperature control.
It may be necessary to drain the central heating system if radiators need
to be replaced, if there is a major water leak or if there is a risk of freezing.
1. Open the valves on all the radiators connected to the system.
2. Shut down the boiler.
3. Wait approximately 10 minutes, until the radiators feel cold.
4. Connect a drain hose to the lowest draining point. Place the end of the
hose in a drain or at a place where drained pipe water will not cause
any damage.
5. Open the central heating system filling/draining valve. Drain the
installation.
Warning
The water may still be hot.
6. Close the drain valve when no more water comes from the draining
point.
10.3.4 Check the hydraulic pressure
1. Check the hydraulic pressure in the installation.
Caution
The hydraulic pressure must reach a minimum of 0.08 MPa (0.8
bar).
Important
If the hydraulic pressure is lower than 0.08 MPa (0.8 bar), the bar
symbol flashes.
2. Top up the heating system with water to increase the hydraulic
pressure.
Important
The recommended hydraulic pressure when cold is between 0.15
MPa (1.5 bar) and 0.2 MPa (2 bar).
For more information, see
Displaying the water pressure on the control panel, page 38
10.3.5 Topping up the installation with water
1. Open the valves on all radiators connected to the heating system.
2. Set the room thermostat to as low a temperature as possible.
3. Put the boiler in shut-down/frost protection mode.
4. Open the fill valve.
5. Close the filling valve when the pressure gauge shows a pressure of
7. When the pump has stopped, vent again and top up the water
pressure.
Important
Filling and venting the installation twice a year should be sufficient
to obtain an adequate hydraulic pressure. If it is often necessary
to top up the installation with water, contact your installer.
10.3.6 Cleaning the casing
1. Clean the outside of the boiler using a damp cloth and a gentle
detergent.
10.4
Specific maintenance operations
10.4.1
Carry out an auto-detect after removing or replacing a control PCB.
Proceed as follows:
1. Press the key.
2. Select Advanced Service Menu / This will send a command to
3. Select Confirm
4. The auto-detect is carried out and after a while the main display
Carrying out an auto-detect
autodetect all devices connected to the Local Bus
The selection options appear on the screen:
Cancel
Confirm
appears.
10.4.2 Other specific maintenance operations
In addition to the maintenance operations described in this manual, please
also ensure that the maintenance operations listed in the boiler manual
are carried out.
The error memory stores the 32 most recent errors. You can check the
details of each error and then clear it from the error memory.
To display and clear the error memory:
1. Press the key.
2. Select Error History.
3. Carry out the following actions according to your needs:
The list of the 32 most recent errors is displayed with the error code,
a short description and the date.
Show the details of an error: select the desired error.
To clear the error memory, press and hold the rotary knob.
11.2
Type of codeDescription
Axx.xx codesWarningGrey
Hxx.xx codesBlockageRed
Exx.xx codesLock outRed + red flashing screen
Error codes
If an error occurs, the control panel displays a message and a
corresponding code.
The control panel status LED flashes and/or is displayed in red.
The control panel can display three types of error codes:
Colour of the error icon
1. Make a note of the code displayed. The code is important for the
correct and rapid diagnosis of the type of malfunction and for any
technical assistance that may be needed.
2. Switch the boiler off and switch it back on.
3. The boiler starts up again automatically when the cause of the error
has been removed.
If the code is displayed again, correct the problem by following the
instructions in the tables below.
11.2.1 Warning
If it is anticipated that a situation may develop into a fault, a warning will
first be given for some malfunctions. The error code is displayed in the
main display and the LED for status indication flashes green.
Press the key to remove the warning from the main display.
CU-GH-08 alarm codes
Tab.69
CodeDisplay textDescription/Solution
A00.34TOutside MissingOutside temperature sensor was expected but not detected
A00.42WaterPressureMissingWater pressure sensor was expected but not detected:
Water pressure sensor is not connected: connect the sensor
Water pressure sensor is not connected correctly: connect the sensor correctly
A02.36Funct device lostFunctional device has been disconnected:
Run a PCB auto-detect.
Bad connection: check the wiring and connectors.
Faulty SCB PCB: replace SCB PCB
A02.37Uncritic device lostUncritical device has been disconnected:
Run a PCB auto-detect.
Bad connection: check the wiring and connectors.
Faulty SCB PCB: replace SCB PCB
A02.45Full Can Conn MatrixFull Can Connection Matrix :
Carry out an auto-detect
A02.46Full Can Device AdmFull Can Device Administration:
Carry out an auto-detect
A02.48Funct Gr Conf FaultFunction Group Configuration Fault:
Carry out an auto-detect
A02.49Failed Init NodeFailed Initialising Node:
Carry out an auto-detect
A02.69Fair mode activeFair mode active
A08.02Shower Time ElapsedThe time reserved for the shower has elapsed
11 Troubleshooting
11.2.2 Blockage
A (temporary) blockage is a status resulting from an abnormal state. The
error code is displayed in the main display and the LED for status
indication flashes red. The control unit makes a number of attempts to
restart. If the cause of blocking persists, the blockage will turn into a fault.
Press the key to remove the warning from the main display.
Important
If the cause of blocking is resolved, the system will restart
automatically.
Blocking codes CU-GH-08
CodeDisplay textDescription/Solution
H01.00Comm ErrorCommunication Error occured:
Restart the boiler
H01.05Max Delta TF-TRMaximum difference between flow temperature and return temperature:
No flow or insufficient flow:
Check the circulation (direction, pump, valves)
Check the hydraulic pressure
Check the cleanliness of the heat exchanger
Sensor error:
Check that the sensors are operating correctly
Check that the sensor has been correctly fitted
H01.08CH Temp Grad. Level3 Maximum CH temperature gradient level3 exceeded:
No flow or insufficient flow:
Check the circulation (direction, pump, valves).
Check the hydraulic pressure.
Check the cleanliness of the heating body.
Check that the installation has been correctly vented to remove air.
Sensor error:
Check that the sensors are operating correctly.
Check that the sensor has been fitted properly.
Check that the gas valve is fully opened
Check the gas supply pressure
Wrong setting on the Gps gas pressure switch:
Check whether the Gps pressure switch is installed correctly
Replace the gas pressure switch (Gps) if necessary
H01.14Max TflowFlow temperature has exceeded the maximum operating value:
Bad connection: check the wiring and connectors.
No flow or insufficient flow:
Check the circulation (direction, pump, valves).
Check the hydraulic pressure.
Check the cleanliness of the heating body.
H01.21Dhw Temp GradLevel3 Maximum Dhw Temperature Gradient Level3 Exceeded:
Check the circulation (direction, pump, valves)
Check that the heating pump is operating correctly
H02.00Reset In ProgressReset In Progress:
No action
H02.02Wait Config NumberWaiting For Configuration Number:
Reset and (see boiler data plate).
H02.03Conf ErrorConfiguration Error
H02.04Parameter ErrorParameter Error:
Parameters are not correct:
Restart the boiler
Reset and
Replace the control system
H02.05CSU CU mismatchCSU does not match CU type:
Reset and .
H02.09Partial blockPartial blocking of the device recognized:
External cause: remove external cause.
Wrong parameter set: check the parameters.
Bad connection: check the connection.
H02.10Full BlockFull blocking of the device recognized:
External cause: remove external cause.
Wrong parameter set: check the parameters.
Bad connection: check the connection.
H02.12Release SignalRelease Signal input of the Control Unit from device external environment:
External cause: remove external cause.
Wrong parameter set: check the parameters.
Bad connection: check the connection.
H02.38No water hardnessNo hardness of water
H02.70HRU test errorExternal heat recovery unit test failed
H03.00Parameter ErrorSafety parameters level 2, 3, 4 are not correct or missing :
Restart the boiler
Replace the CU-GH-08 control panel
H03.01CU to GVC data errorNo valid data from CU to GVC received:
Restart the boiler
H03.02Flame loss detectedMeasured ionisation current is below limit:
No ionization current:
Vent the gas supply to remove air.
Check whether the gas valve is properly open.
Checking the gas supply pressure.
Check the operation and setting of the gas valve unit.
Check that the air supply and flue gas discharge flues are not blocked.
Check that there is no recirculation of flue gases.
If the blocking conditions continue, the boiler goes into lockout (also called
an error). The boiler will also lock out if an error is signalled anywhere in
the boiler. The error code appears in the main display and alternates with
a flashing red screen.
The meaning of the error codes can be found in the error table. Note the
error code.
Important
The error code is important for correct and fast tracing of the
nature of the error and for obtaining support from your supplier.
Tab.70
CodeDisplay textDescription/Solution
E00.04TReturn OpenReturn temperature sensor is either removed or measures a temperature below range:
Bad connection: check the wiring and connectors.
Incorrectly fitted sensor: check that the sensor has been correctly fitted.
Faulty sensor: replace the sensor.
E00.05TReturn ClosedReturn temperature sensor is either shorted or measures a temperature above range:
Bad connection: check the wiring and connectors.
Faulty sensor: replace the sensor.
E00.06TReturn MissingReturn temperature sensor was expected but not detected:
Bad connection: check the wiring and connectors.
Faulty sensor: replace the sensor
E00.07dTReturn Too HighReturn temperature difference is too large:
No circulation:
Vent the air from the heating system
Check the hydraulic pressure
If present: check the boiler type parameter setting
Check the circulation (direction, pump, valves)
Check that the heating pump is operating correctly
Check the cleanliness of the heat exchanger
Sensor not connected or incorrectly connected:
Check that the sensors are operating correctly
Check that the sensor has been correctly fitted
Faulty sensor: replace the sensor if necessary
E01.045x Flame Loss Error5x Error of unintended Flame Loss occurance:
Vent the gas supply to remove air.
Check whether the gas valve is properly open.
Check the gas supply pressure.
Check the operation and setting of the gas valve unit.
Check that the air supply and flue gas discharge flues are not blocked.
Check that there is no recirculation of flue gases.
E01.11Fan Out Of RangeFan speed has exceeded normal operating range:
Bad connection: check the wiring and connectors.
Faulty fan: replace the fan
Fan operates when it should not be operating: check for excessive chimney draught
E01.12Return Higher FlowReturn tempearture has a higher temperature value than the flow temperature:
Bad connection: check the wiring and connectors.
Water circulation in wrong direction: check the circulation (direction, pump, valves).
Incorrectly fitted sensor: check that the sensor has been correctly fitted.
Malfunctioning sensor: check the Ohmic value of the sensor.
Faulty sensor: replace the sensor.
E02.13Blocking InputBlocking Input of the Control Unit from device external environment:
Bad connection: check the wiring and connectors.
CSU faulty: replace the CSU.
E02.17GVC CommTimeoutGas Valve Control unit communication has exceeded feedback time:
Restart the boiler
Replace the CU-GH-08 control panel
E02.35Safety device lostSafety critical device has been disconnected
E02.47Failed Conn Funct GrFailed Connecting Function Groups
E04.00Parameter errorSafety parameters Level 5 are not correct or missing
E04.01TFlow ClosedFlow temperature sensor is either shorted or measuring a temperature above range :
Bad connection: check the wiring and connectors.
Incorrectly fitted sensor: check that the sensor has been correctly fitted.
Faulty sensor: replace the sensor.
E04.02TFlow OpenFlow temperature sensor is either removed or measuring a temperature below range:
Bad connection: check the wiring and connectors.
Faulty sensor: replace the sensor.
E04.03Max Flow tempMeasured flow temperature above savety limit
E04.04TFlue ClosedFlue temperature sensor is either shorted or measuring a temperature above range
E04.05TFlue OpenFlue temperature sensor is either removed or measuring a temperature below range
E04.06Max Flue tempMeasured flue temperature above limit
E04.07TFlow SensorDeviation in flow sensor 1 and flow sensor 2 detected:
Bad connection: check the connection.
Faulty sensor: replace the sensor.
E04.08Safety inputSafety input is open:
Non-return valve does not open.
Siphon blocked or empty.
Check that the air supply and flue gas discharge flues are not blocked.
Check the cleanliness of the heating body.
E04.09TFlue SensorDeviation in flue sensor 1 and flue sensor 2 detected
Check the wiring between the CU-GH-08 unit and the igniter.
Check the ionization/ignition electrode.
Check the earthing.
Check the surface condition of the burner.
Check the earthing.
SU PCB faulty: replace the PCB.
Ignition spark but no flame:
Vent the gas pipes to remove air.
Check that the air supply and flue gas discharge flues are not blocked.
Check whether the gas valve is properly open.
Check the gas supply pressure.
Check the operation and setting of the gas valve unit.
Check the wiring on the gas valve unit.
Replace the CU-GH-08 control panel
Presence of the flame but insufficient ionization (<3 µA):
Check whether the gas valve is properly open.
Check the gas supply pressure.
Check the ionization/ignition electrode.
Check the earthing.
Check the wiring on the ionization/ignition electrode.
E04.11VPSVPS Gas Valve proving failed
E04.12False flameFalse flame detected before burner start :
The burner remains very hot: adjust the O
2
Ionization current measured but no flame should be present: check the ionization/igni
tion electrode.
Faulty gas valve: replace the gas valve.
Faulty igniter: replace the igniter.
E04.13FanFan speed has exceeded normal operating range:
Bad connection: check the wiring and connectors.
Fan operates when it should not be operating: check for excessive chimney draught.
Faulty fan: replace the fan.
E04.14Combustion ErrorThe burner temperature and setpoint differ more than 60s regarding GVC configuration
E04.17GasValve Driver Err.The driver for the gas valve is broken
E04.18Min Temp Flow ErrorThe flow temperature is less than the minimum defined by the GVC parameter
E04.21Burner temperatureDeviation in burner sensor 1 and burner sensor 2 detected
E04.23Internal ErrorGas Valve Control internal locking
Do not block ventilation outlets.
Do not cover the radiators. Do not hang curtains in front of the radiators.
Install reflective panels behind the radiators to prevent heat losses.
Insulate the pipes in rooms that are not heated (cellars and lofts).
Close the radiators in rooms not in use.
Do not run hot (or cold) water pointlessly.
Install an energy-saving shower head, which can save up to 40 %
energy.
Take showers rather than baths. A bath consumes twice as much water
and energy.
14.2
Room thermostat and settings
Various models of room thermostat are available. The type of thermostat
used and the parameter selected impact total energy consumption.
A modulating regulator, which may be combined with thermostatic
valves, is eco-friendly in terms of energy and offers an excellent level of
comfort. This combination allows you to set the temperature separately
for each room. However, do not install thermostatic radiator valves in the
room in which the room thermostat is located.
Complete opening and closing of the thermostatic radiator valves
causes undesirable variations in temperature. Therefore, these must be
opened/closed progressively.
Set the room thermostat to a temperature of approximately 20°C to
reduce heating costs and energy consumption.
Lower the thermostat setting to approximately 16°C at night or when you
are not at home. This reduces heating costs and energy consumption.
Lower the thermostat setting well before airing the rooms.
Set the water temperature to a lower level in summer than in winter (e.g.
60°C and 80°C respectively) when an ON/OFF thermostat
is used.
When clock thermostats and programmable thermostats are to be set,
do not forget to take any holidays and days when no one is at home into
account.
We would like to thank you for buying one of our appliances and for your
trust in our product.
In order to ensure continued safe and efficient operation, we recommend
that the product is regularly inspected and maintained.
Your installer and our service department can assist with this.
15.2
Terms of warranty
The following provisions do not affect the application, in favour of the
buyer, of the legal provisions with regard to hidden defects that are
applicable in the buyer's country.
This appliance comes with a warranty that covers all manufacturing faults;
the warranty period will commence on the date of purchase stated on the
installer's invoice.
The warranty period is stated in our price list.
As a manufacturer, we can by no means be held liable if the appliance is
used incorrectly, is poorly maintained or not maintained at all, or is not
installed correctly (it is your responsibility to ensure that installation is
carried out by a qualified installer).
In particular, we cannot be held liable for material damage, intangible
losses or physical injury resulting from an installation that does not comply
with:
Legal or regulatory requirements or provisions laid down by the local
authorities.
National or local regulations and special provisions relating to the
installation.
Our manuals and installation instructions, in particular in terms of regular
maintenance of the appliances.
Our warranty is limited to the replacement or repair of the parts found to
be defective by our technical services team, excluding labour, transfer and
transport costs.
Our warranty does not cover replacement or repair costs for parts that may
become defective due to normal wear, incorrect usage, the intervention of
unqualified third parties, inadequate or insufficient supervision or
maintenance, a mains supply that is not appropriate or the use of
unsuitable or poor quality fuel.
Smaller parts, such as motors, pumps, electrical valves etc., are
guaranteed only if these parts have never been dismantled.
The rights established in European Directive 99/44/EEC, implemented by
legal decree No. 24 of 2 February 2002 and published in Official Journal
No. 57 of 8 March 2002, remain in force.
A* = 0.95, A = 0.91,
B = 0.86, C = 0.83,
D - G = 0.81
5
%( - ‘I’ ) x ‘II’ = +
6
%0.5 x 0.5 x = -
54
<30%
GFEDCBAA
+
A
++
A
+++
%+ (50 x ‘II’) =
7
7
%
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building, as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics.
Boiler and supplementary heat pump installed with low temperature heat emitters at 35°C ?
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in %)
Supplementary heat pump
Tank rating
Collector effi ciency (in
%)
Tank volume (in m³) Collector size (in m²)
Seasonal space heating energy effi ciency (in %)
Supplementary boiler
Class I = 1%, Class II = 2%, Class III = 1.5%,
Class IV = 2%, Class V = 3%, Class VI = 4%,
Class VII = 3.5%, Class VIII = 5%
Temperature control
Seasonal space heating energy effi ciency of boiler
IIThe factor for weighting the heat output of preferential and
supplementary heaters of a package as set out in the following
table.
IIIThe value of the mathematical expression: 294/(11 · Prated),
whereby "Prated" is related to the preferential space heater.
IVThe value of the mathematical expression 115/(11 · Prated),
whereby "Prated" is related to the preferential space heater.
Tab.72Weighting of boilers
Psup / (Prated + Psup)
(1)(2)
II, package without hot water storage tankII, package with hot water storage tank
000
0.10.30.37
0.20.550.70
0.30.750.85
0.40.850.94
0.50.950.98
0.60.981.00
≥ 0.71.001.00
(1) The intermediate values are calculated by linear interpolation between the two adjacent values.
(2) Prated is related to the preferential space heater or combination heater.
All technical and technological information contained in these technical instructions, as well as any drawings and technical
descriptions supplied, remain our property and shall not be multiplied without our prior consent in writing. Subject to alterations.
Remeha B.V.
Marchantsts tr aa t 55
7332 AZ Ape ld oo rn
P.O. Box 32
7300 AA Ape ld oo rn
NLT +31 (0)55 549 6969
F +31 (0)55 549 6496
E remeha@remeha.nl
Uw leverancier / Votre fournisseur / Ihr Lieferant:BE
Walter Bösch K.G.
Industrie N or d
6890 Lusten au
ATT +43 5577 81310
F +43 5577 8131250
E info@boesch.at
Cipag S.A.
Zone Indust ri el le
1070 Puidou x- Ga re
CHT +41 21 9266666
F +41 21 9266633
E contact@cipag.ch
Bergen s.r.o.
Karlická 9/ 37
153 00 Prah a 5 - Radotín
CZT +420 257 912 060
F +420 257 912 061
E info@bergen.cz
Remeha GmbH
Rheiner Str as se 1 51
48282 Emsd et te n
DET +49 25572 9161 - 0
F +49 25572 9161 - 102
E info@remeha.de
Scanboiler Varmeteknik A/S
Vangvedvæng et 1
8600 Silkeb or g
DKT +45 86 82 63 55
E info@scanboiler.dk
Ecotherm Energy S.L.
Berreteaga Bi de a 19
48180 Loiu
EST +34 94 471 03 33
F +34 94 471 11 52
E info@remeha.es
EST Systems Oy
Kujamatinti e 16
48720 Kotka
FIT +358 50 554 3068
E toimisto@estsystems.fi
Marketbau - Remeha Kft.
Gyár u. 2.
2040 Budaor s
HUT +36 23 503 980
F +36 23 503 981
E remeha@remeha.hu
Euro Gas Ltd.
Unit 38, So ut he rn Cross Business P ar k
Wicklow
IET +353 12868244
F +353 12861729
E sales@eurogas.ie
Revis S.r.l.
Via Trieste 4 a
31025 Santa L uc ia di Piave (TV)
ITT +39 0438 7019 07
F +39 02 360 285 83
E info@re-vis.it
Remeha S.R.L.
Str. Padin, N r. 9-13
Scara 5, Ap 5 3, Judejul Cluj
Cluj-Napoca
ROT +40 74 6170 515
F +40 26 4421 175
E remeha@remehacazan.ro
Green Building
Temerinska 57
21000 Novi Sa d
RST +381 21 47 70 888
F +381 21 47 70 888
E info@greenbuilding.rs
RES Enerji Sistemleri A.S.
Barbaros Bu lv ar i No: 52/2
Besiktas - IS TA NBUL
TRT +90 212 356 06 33
F +90 212 275 00 62
E info@resenerji.com
Remeha Commercial UK
Innovations H ou se
3 Oaklands Bu si ne ss Centre
Oaklands Pa rk
RG41 2FD Wo ki ng ha m
UKT +44 (0)118 978 3434
F +44 (0)118 978 6977
E boilers@remeha.co.uk
7717201 - v03 - 25062019
7717201-001-03
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.