Regency Panorama P48 Installation Manual

P48-2 Gas Fireplace
Owners &
Installation Manual
MODELS: P48-NG2 Natural Gas P48-LP2 Propane
WARNING: If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
Tested by:
918-524b
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
www.regency-fi re.com
Do not try to light any applianceDo not touch any electrical switch:
do not use any phone in your building.
Immediately call your gas supplier
from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
07/15/09
WARNING
HOT GLASS
CAUSE BURNS
DO NOT TOUCH
UNTIL COOLED
NEVER
TO TOUCH GLASS
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND SHOULD ST AY AWA Y TO AVOID BURNS OR CLOTHING IGNITION.
ALLOW CHILDREN
WILL
GLASS
To the New Owner:
Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The P48-2 has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch. The model P48-2 has been approved by Warnock Hersey for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow . Please take a moment now to acquaint
yourself with these instructions and the many features of your Regency
MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
This Regency® product has been tested and listed by Warnock Hersey as a Direct Vent Wall Furnace to the following standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88a-2007/CSA 2.33a-2007 and GAS-FIRED APPLIANCES FOR USE AT HIGH ALTITUDES CAN/CGA 2.17-M91.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada.
®
Fireplace.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.
This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as applicable to local codes.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home, where not prohibited by local codes.
This appliance can only be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
Ensure that structural members are not cut or weakened during installation.
2
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace
TABLE OF CONTENTS
SAFETY LABEL
Copy of Safety Decal .....................................................4
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only) ............................5
INSTALLATION
Important Message ......................................................6
Before You Start ............................................................6
General Safety Information............................................6
Installation Checklist ......................................................6
Manufactured Mobile Home Additional Requirements ..7
Locating Your Gas Fireplace .........................................7
Unit Specifi cations .........................................................7
Heatwave Optional Duct System Kit..............................7
Optional Heat Release Kit ............................................7
Hearth ............................................................................7
Clearances ....................................................................8
Mantels ..........................................................................9
Mantel Leg Clearances..................................................9
Framing & Finishing.....................................................10
Unit Assembly Prior To Installation ..............................11
Top Standoff Assembly ........................................11
Top Facing Support and Side Nailing Strips ........11
Venting Introduction .....................................................11
Exterior Vent Termination Requirements .....................12
Venting Arrangements ................................................13
Horizontal Termination .........................................13
Simpson Dura-vent Venting .................................14
Simpson Dura-vent Venting Components List .....14
5” x 8” Rigid Pipe Cross Reference Chart ...................15
Vertical Terminations ...........................................21
Unit Installation with Horizontal Termination ................23
Unit Installation with Vertical Termination ....................24
System Data ...............................................................26
High Elevation .............................................................26
Gas Line Installation ....................................................26
Pilot Adjustment ...........................................................26
Gas Pipe Pressure Testing ..........................................26
S.I.T. Valve Description ................................................26
Conversion Kit from NG to LPG Part #372-969 ..........27
Brick Panels Installation ..............................................30
Log Set Installation ......................................................31
Standard Flush Door ...................................................34
Flush Louvers ..............................................................34
Optional Flush Trim .....................................................34
Optional Bay Door .......................................................35
Optional Bay Trim ........................................................35
Bay Louvers.................................................................35
Optional Finishing Trim ................................................36
Double Screen Door ...................................................36
Optional Remote Control .............................................37
Optional Wall Switch ....................................................37
Optional Wall Thermostat ...........................................37
Wiring Diagrams .........................................................38
Installing The Optional Fan ..........................................40
To Remove the Fan .............................................40
OPERATING INSTRUCTIONS
Operating Instructions .................................................41
Shutdown Procedure ...................................................41
First Fire ......................................................................41
Lighting Procedure ......................................................41
Aeration Adjustment ....................................................41
Normal Operating Sounds of Gas Appliances .............42
MAINTENANCE
Maintenance Instructions.............................................43
General Vent Maintenance ..........................................43
Log Replacement ........................................................43
Thermopile / Thermocouple .........................................43
Glass Gasket ...............................................................43
Gold-Plated Louvers & Trim ........................................43
Door Glass...................................................................44
Glass Replacement .............................................44
Bay Glass Replacement ......................................44
Installing Valve .............................................................44
Removing Valve ...........................................................45
PARTS LIST
Main Assembly ............................................................46
Burner & Log Assembly ...............................................48
Flush Door & Louvers ..................................................49
Bay Front & Louvers ....................................................50
WARRANTY
Warranty ......................................................................51
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace 3
SAFETY LABEL
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE
308
308
PROPANE:
Minimum supply pressure
Manifold pressure high
Manifold pressure low
Orifice size
Minimum input
Maximum input
Altitude
Model P48-LP2
L
FPI Fireplace Products International Ltd.
Delta, BC, Canada
Minimum Clearances to Combustibles
/Degagement Minimum
De Materiaux Combustibles
DUPLICATE SERIAL NO.
Serial No./ No de serie
918-502a
NATURAL GAS:
Minimum supply pressure
Manifold pressure high
Manifold pressure low
Orifice size
Minimum input
Maximum input
Altitude
Model P48-NG2
L
5" (1.25 kPa)
3.8" (0.94 kPa)
1.1" (0.27 kPa)
# 27 DMS
29,000 (8.49 Kwh)
51,000 (14.94Kwh)
0-4500 (0-1372 m)
WC
WC
WC
B
B
ft/pi
tu/h
tu/h
MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE.
Model/Modele: P48-NG2
Model/Modele: P48-LP2
Listed:
Certified for/Certifi e pour:
Tested to:
WN# 16454
CANADA and U.S.A.
CGA-2-17-M91, ANSI Z21.88a-2007 / CSA 2.33a-2007
VENTED GAS FIREPLACE HEATER / FOYER AUGAZÀÉVACUATION
é
This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation Code, CSA B149.1.
This appliancemust be installed inaccordance with theStandard CAN/CSAZ240 MH, MobileHousing, inCanada, orwith the Manufactured HomeConstruction and SafetyStandard, Title24 CFR, Part 3280,in the UnitedStates, or
when sucha standardis not applicable,ANSI/NCSBCSA225.1/NFPA 501A, ManufacturedHome InstallationsStandard orANSIA119.2 ouNFPA501C Standardfor RecreationalVehicles
This applianceis only for use withthe type of gas indicatedon therating plate andmay beinstalled in anaftermarket, permanentlylocated, manufactured (mobile) home wherenot prohibited by local codes.See owner'smanual for
details.
Installer l'appareilselon lescodes ou règlementslocaux, ou,en l'absence detels règlements,selon les codesd'installation ANSIZ223.1, NationalFuel Gas Codeou CSA-B149.1en vigueur.
Installer l'appareilselon la norme CAN/CSA-Z240, SérieMM, Maisonmobiles ou CAN/CSA-Z240VC, Véhiculesde camping, oula norme24 CFR Part 3280, ManufacturedHome Construction and Safety Standard.Si cesnormes
ne sontpas pertinentes,utilisez la normeANSI/NCSBCSA225.1/NFPA 501A, ManufacturedHome InstallationsStandard, ouANSIA119.2 ouNFPA501C Standardfor RecreationalVehicles.
For usewith glassdoors certified withthe applianceonly
Made in Canada/ Fabrique au Canada
This ventedgas fireplaceheater is notfor usewith air filters. Ne pasutiliser defiltre à airavec cefoyer au gazà évacuation.
Cet appareildoit être utilizeuniquement avec letype de gazindiqué sur laplaque signalétique. Cetappareil peut êtreinstallé dans unemaison préfabriquée oumobile (É.-U. seulement) installéeà demeure siles règlements locaux
le permettent.Voir lanotice del'utilisateur pour plusde renseignements.Cet appareil nepeut pasêtre utilisé avecd'autres gazsauf si unetrousse deconversion certifiéeest fournie.
Pour utilisationuniquement avecles portes enverre certifiéesavec l'appareil
Electrical supply / Électrique 115VAC, 1.13 A, 60Hz.
(See Instruction Manual for
Detailed Instructions)
DOOR SEAL: Please check that the door is properly sealed
12" WC(3.00 kPa)
11" WC(2.74 kPa)
2.9" WC(0.72 kPa)
# 47 DMS
26,000 Btu/h (7.61 kW)
48,000 Btu/h (14.06 kW)
0-4500 ft/pi (0-1372 m)
0" Clearance to
combustibles from:
Mantel Clearances from Top:
Side Wall Clearance
from Side Facing
Alcove Clearances:
Minimum Vent Clearances:
Top, sides, bottom and rear of unit
(A) Min. 8" (203mm)
B) 6"
Max. Depth 36" (914mm)
Min. Width 60" (1524mm),
Min. Height 80" (2032mm)
Horizontal Top 2-1/2" (64mm)
Horizontal Side
Horizontal Bottom 1-1/2" (38mm)
1-1/2" (38mm)
B
B
39”
Ceiling
Wall
Wall
A
APPAREIL FONCTIONNANT AU NATURAL GAZ
CONCU POUR ETRE POELE:
Pression d'allimentation minimum
Pression à la tubulure d' chappement lev e
Pression à la tubulure d' chappement basse
Grandeur de l'injecteur
D bit minimum selon
D bit maximum selon
l'altitude
Calorifique
Calorifique
Modéle P48-NG2
ééé
é
é
é
APPAREIL FONCTIONNANT AU GAZ PROPANE
CONCU POUR ETRE POELE:
Pression d'allimentation minimum
Pression à la tubulure d' chappement lev e
Pression à la tubulure d' chappement basse
Grandeur de l'injecteur
D bit minimum selon
D bit maximum selon
Calorifique
Calorifique
l'altitude
Modéle P48-LP2
ééé
é
é
é
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUELS. / NE PAS UTILISER AVEC DU
COMBUSTIBLE SOLIDE.
FOYER AU GAZ À ÉVACUATION -
This is a copy of the label that accompanies each P48-NG2 and P48-LP2 Zero Clearance Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review. The safety label is located on the front inside base of the unit, visible when the bottom louver is open.
NOTE: Regency improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
®
units are constantly being
For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, fl exible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appli­ances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.
4
COPY OF SAFETY DECAL
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace 5
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The P48-NG2/P48-LP2 Direct Vent Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual fi rst. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fi replace is installed in compliance with manufacturers instructions and all applicable codes.
BEFORE YOU ST ART
Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
INST ALLA TION AND REP AIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: F AILURE TO INST ALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
CHILDREN AND ADUL TS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPE­CIALL Y THE FIREPLACE GLASS, AND SHOULD ST AY AWA Y TO A VOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform
with local codes or, in the absence of local codes, with the current Canadian or National Gas Codes, CAN1-B149 or ANSI Z223.1 Installation Codes.
2) The appliance when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Canadian Electrical Code.
3) See general construction and assembly instructions. The appliance and vent should be enclosed.
4) This appliance must be connected to the specifi ed vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fi tted as per Venting instructions.
5) Inspect the venting system annually for blockage and any signs of deterioration.
6) Venting terminals shall not be recessed into a wall or siding.
7) Any safety glass removed for servicing must be replaced prior to operating the appliance.
8) To prevent injury, do not allow anyone who is unfamiliar with the operation to use the replace.
9) Wear gloves and safety glasses for protection while doing required maintenance.
10) Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.
11) Under no circumstances should this appliance be modifi ed. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
12) Installation and any repairs to this appliance should be done by an authorized service person. A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.
15) The appliance area must be kept clear and free of combustible materials, (gases and other fl ammable vapours and liquids).
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
INSTALLATION
CHECKLIST
1) Locate appliance
a) Room location (Refer to "Locating Y our
Gas fi replace" section)
b) Clearances to Combustibles (Refer to
"Clearances" section)
c) Mantle Clearances (Refer to "Combustible
Mantel Clearances" section)
d) Framing & Finishing Requirements (Refer
to "Framing & Finishing" section)
e) Venting Requirements (Refer to
"Venting" section)
2) Assemble Top Standoffs and Top Facing Support and Side Nailing Strips (Refer to "Unit Assembly Prior to Installation). NOTE: Must be done before installing unit into place.
3) Install vent (Refer to "V enting Arrangement" sections).
4) Make gas and electrical connections. Test the pilot. Must be as per diagram (Refer to "Pilot Adjustment " section).
Convert to propane if desired (Refer to
"Conversion from NG to LPG" section).
5) Test Gas Pressure. (Refer to "Gas Pipe Pressure Testing" section)
6
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
6) Install standard and optional features. Refer
to the following sections:
a) Brick Panels Installation b) Log Set Installation c) Standard Flush Door d) Flush Louvers e) Flush Trim f) Bay Door g) Bay Trim h) Bay Louvers i) Finishing trim j) Double Screen Door k) Remote Control l) Wall Switch m) Wall Thermostat n) Installing the Fan
11) Final check. Before leaving this unit with the customer, the
installer must ensure that the appliance is fi ring correctly and operation fully explained to
customer.
This includes:
1) Clocking the appliance to ensure the correct
ring rate (rate noted on label 51,000 (NG) Btu/h, 48,000 (LP) Btu/h) after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure that the fl ame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8 ground lug provided. See "Wiring Diagram" section.
UNIT SPECIFICATIONS
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your replace,
ensure that the clearances outlined on this page are met.
2) Provide adequate clearances for servicing.
3) The appliance must be installed on a fl at, solid, continuous surface (e.g. wood, metal, concrete). This may be the fl oor, or raised up on a platform to enhance its visual impact. If the appliance is going to be installed on carpeting, combustible linoleum tile or other combustible material other than wood ooring, the appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
4) The P48-2 Direct Vent Gas Fireplace can be installed in a recessed position or framed out into the room as in A, B, C, D. See Diagram 1.
5) This appliance is Listed for bedroom installations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
6) The P48-2 Direct Vent Gas Fireplace is approved for alcove installations, which meet the clearances listed on this page.
7) We recommend that you plan your installation on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation.
Note: For vent terminations see "Exterior
Vent Termination Locations" section.
HEATWAVE
OPTIONAL
DUCT SYSTEM KIT
#946-556
The HeatWave Air Duct Kit increases the effectiveness of your fi replace by dispersing warm air from the fi replace to remote locations in the same room or other rooms in your home.
Up to two kits may be installed on the fi replace. Please Note: Only 1 HeatWave kit may be operated at one time. This includes the internal blower option as well.
OPTIONAL
HEAT RELEASE KIT
#946-570
The Heat Release Kit expels warm air from the fi replace to the outside of the building, allowing the fi replace to be operated with less heat entering the room. The kit may be used on either the left or right side.
Diagram 1
A) Flat on Wall B) Flat on Wall Corner C) Recessed into
Wall/Alcove D) Corner
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace 7
A hearth is not mandatory , but is recommended for aesthetics and for added safety.
HEARTH
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fi replace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back 0" (0mm) Side 0" (0mm) Floor 0" (0mm)
Minimum Clearance from Top of Front Facing:
Mantel min. 8" (203mm) Ceiling 39" (990mm) from top of front facing
above louvers.
Side Wall:
6" (152mm)
Horizontal Vent Clearances:
Top 2-1/2" (64mm) Side 1-1/2" (38mm) Bottom 1-1/2" (38mm)
Vertical Vent Clearances:
1-1/4" (32mm)
Alcove Clearances:
Max. Depth 36" (914mm) Min. Width 60" (1524mm) Min. Height 80" (2032mm)
The top, back and sides of the fi replace are defi ned by
Caution Requirements
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
if these clearances (air space) to combustible materials
Fire hazard is an extreme risk
are not adhered to. It is of greatest importance that this
replace and vent system be installed only in
accordance with these instructions.
Heat Release Kit
8
WARNING
The HeatWave Duct Kit and the Heat Release Kit have different clearance and framin requirements, check the HeatWave and Heat Release manual for details.
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
MANTELS
Because of the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from louver are shown
in the diagram below.
Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible
board.
This drawing is to scale at 1:6 (one inch = 6 inches)
Mantel can be installed anywhere in shaded area using the above scale for units with the Flush Front and with the optional Bay Front.
Note: Ensure the paint that is used
on the mantel and the facing is "heat resistant" or the paint may discolour.
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram:
Maximum 1-1/2" projection at 3" minimum clearance.
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace 9
INSTALLATION
FRAMING & FINISHING
1) Determine the total thickness of facing material (eg. drywall plus
ceramic tiles) to allow the fi nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2" (13mm) to
1-1/4" (32mm) thick.
2) Frame in the enclosure for the unit with framing material. The framed opening for the assembled kit is 47-1/2" high x 48-1/2" wide x 26-1/4" deep (1207mm H x 1232mm W x 667mm D). See Diagram 1. See important note below when installing with any veritical venting off of the top.
Diagram 1
Note: 43" (1092mm) is the minimum height for fl ex termination and
Simpson Dura-Vent terminations.
3) For exterior walls, insulate the enclosure to the same degree as
the rest of the house, apply vapour barrier and drywall, as per local installation codes. (Do not insulate the replace itself.)
4) The unit does not have to be completely enclosed in a chase. The clearance on top of the unit from the top standoffs is 0" so combustible building materials can be laid directly on top of the standoffs. You must maintain clearances from the vent to combustible materials: See "Clearances" section. Combustible materials can be laid against the side and back standoffs and the stove base.
The HeatWave Duct Kit has different clearance and framing requirements, check the HeatWave manual for details.
IMPORTANT
When installing the unit with any vertical venting off the top of the unit as shown, the minimum framing depth changes accordingly.
10
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The T op Facing Support, the Side Nailing Strips and the 2 Top Standoffs must be correctly positioned and attached to the top before unit is slipped into position.
TOP STANDOFF ASSEMBLY
The top standoffs are shipped in a fl at position and must be folded into shape and attached.
1) Remove the standoffs from the fi replace top.
2) T ake each standoff and bend into the correct shape. Bend up at the bend lines until the screw holes in the standoff and the pre­punched screw holes on the fi replace top line up.
3) Attach the standoff securely to the top with 2 screws per standoff (on opposite corners).
TOP FACING SUPPORT AND
SIDE NAILING STRIPS
Determine the total thickness of facing material (e.g. drywall plus ceramic tiles) to allow the nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2" (13mm) to 1-1/4" (32mm) thick.
The T op Facing Support & Side Nailing Strips can be mounted in 3 different positions depending on the thickness of the facing material.
Screw
Facing Material Depth
Position
A 1/2" / 13mm B 7/8" / 22mm
C* 1-1/4" / 32mm
* For "C" screw position the top facing support is reversed.
1) Mount Top Facing Support using the 3 supplied screws into the three pre-punched screw holes on the top front of the unit. Use hole positions A, B, or C depending on your facing depth.
"C" Screw Position:
For a facing material depth of 1-1/4" (32mm), the top facing support must be reversed.
2) Use the same screw hole position for the Side Nailing Strips as was used for the Top Facing Support. Attach each side nailing strip using 3 screws.
VENTING
INTRODUCTION
The P48-2 uses the "balanced fl ue" technology Co Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These flue pipes must not be
connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace 11
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
1
Minimum Clearance Requirements
A Clearance above grade, veranda, porch, deck, or balcony 12"(30cm) 12"(30cm)
B Clearance to window or door that may be opened 12"(30cm) 12" (30cm)
C Clearance to permanently closed window **
D Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm) 23"(58cm) 23"(58cm)
E Clearance to unventilated soffi t **(32"/81cm with vinyl siding) 23"(58cm) 23"(58cm)
F Clearance to outside corner: with AstroCap Termination Cap. 13"(33cm) 13"(33cm)
Clearance to outside corner: with all other approved Termination Caps. 13"(33cm) 13"(33cm)
G Clearance to inside corner: with AstroCap Termination Cap 13"(33cm)) 13"(33cm)
Clearance to inside corner: with all other approved Termination Caps. 13"(33cm)) 13"(33cm)
H Clearance to each side of center line extended above meter/regulator assembly 36"(90cm)
J Clearance to service regulator vent outlet 36"(90cm) *
K Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance 12"(30cm) 12" (30cm)
L Clearance to a mechanical air supply inlet 72"(1.8m) 36"(90cm)
M Clearance above paved sidewalk or a paved driveway located on public property 84"(2.1m)
N Clearance under veranda, porch, deck, or balcony 12"(30cm)
1
In accordance with current CSA B149.1, Natural Gas and Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor
Clearance in accordance with local installation codes and the requirements of the gas supplier
*
a
3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly
b
3 feet (91cm) above - if within 10 feet (3m) horizontally
Canada
a
USA
*
*
*
2
b
12
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
VENTING ARRANGEMENTS
HORIZONTAL TERMINATION
Regency® Direct Vent System (Flex)
These venting systems, in combination with the P48-2 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination Locations" section.
Regency® Direct Vent (Flex) System Termination Kit (Part# 946-618) includes all the parts needed to install the P48-2 with a maximum run of 4 feet.
1) 8" dia. exible liner (6 ft. length)
2) 5" dia. exible liner (6 ft. length)
3) spring spacers (4)
4) thimble (2)
5) AstroCap XL termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point,
Stainless Steel (4)
10) vinyl siding standoff
If longer runs are needed, the Regency® Direct Vent system (Flex) Part# 946-616 includes all the parts needed to install the P48-2 with a maximum 10' run.
1) 8" dia. exible liner (10 ft. length)
2) 5" dia. exible liner (10 ft. length)
3) spring spacers (7)
4) thimble (2)
5) AstroCap XL termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point,
Stainless Steel (4)
10) vinyl siding standoff
Notes:
1) Liner sections should be continuous without any joints or seams.
®
2) Only Flex pipe purchased from Regency
3) If you are installing the P48-2 into a Regency® Mantel Kit, use the minimum horizontal vent height (centre-line of 43"). Remember to include the mantel base in your calculations and to maintain the 2-1/2" clearance to the underside of the mantel top.
may be used for Flex installations.
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace 13
INSTALLATION
SIMPSON DURA-VENT VENTING
Horizontal or Vertical Terminations
The Simpson Dura-Vent Direct V ent System offers a complete line of component parts for installation of both horizontal and vertical installations. Many items are offered in decorative black, as well as galvanized fi nish. We recommend using the galvanized fi nish for installation with the P48-2.
The minimum components required for a basic horizontal termination are:
1 Horizontal Termination Cap 1 45 1 Flue Adaptor 1 Wall Thimble 1 Length of pipe to suit wall thickness (see chart)
Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap. For siding other than vinyl furring strips may be used, instead of the vinyl siding standoff, to create a level surface to mount the vent terminal. The Terminal must not be recessed into siding. Measure the wall thickness including furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add 2 inches.
o
Elbow
Alternate
Horizontal Termination
Caps
Flat Wall Installation
Wall Thickness
(inches)
Vent Length
Required (in.)
4" - 5-1/2" none
7" - 8-1/2" 6" 10" - 1-1/2" 9" 9" - 14-1/2" 12"
15" - 23-1/2" 11" - 14-5/8" Adj.
Pipe
14
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace
Components from different Manufacturers may not be mixed
Not all rigid pipe components are available directly from Regency
INSTALLATION
5” X 8” RIGID PIPE CROSS REFERENCE CHART
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
.
Description
6” Pipe Length-Galvanized 58DVA-06 5DT-6 5D6 TC-5DL6
6” Pipe Length-Black 58DVA-06B 5DT-6B 5D6B TC-5DL6B
9” Pipe Length-Galvanized 58DVA-09 5DT-9 N/A N/A
9” Pipe Length-Black 58DVA-09B 5DT-9B N/A N/A
12” Pipe Length-Galvanized 58DVA-12 5DT-12 5D12 TC-5DL1
12” Pipe Length-Black 58DVA-12B 5DT-12B 5D12B TC-5DL1B
18” Pipe Length-Galvanized 58DVA-18 5DT-18 5D18 TC-5DL18
18” Pipe Length-Black 58DVA-18B - N/A from FPI 5DT-18B 5D18B TC-5DL18B
24” Pipe Length-Galvanized 58DVA-24 5DT-24 5D24 TC-5DL2
24” Pipe Length-Black 58DVA-24B 5DT-24B 5D24B TC-4DL2B
36” Pipe Length-Galvanized 58DVA-36 5DT-36 5D36 TC-5DL3
36” Pipe Length-Black 58DVA-36B 5DT-36B 5D36B TC-5DL3B
48” Pipe Length-Galvanized 58DVA-48 5DT-48 5D48 TC-5DL4
48” Pipe Length-Black 58DVA-48B 5DT-48B 5D48B TC-5DL4B
60” Pipe Length-Galvanized 58DVA-60 N/A N/A N/A
60” Pipe Length-Black 58DVA-60B - N/A from FPI N/A N/A N/A
Adjustable Length 3”-10”-Galvanized N/A N/A 5DAL TC-5DLT
Adjustable Length 3”-10”-Black N/A N/A 5DALB TC-5DLTB
Adjustable Length 11”-14” -Galvanized Disc. - See 58DV-08A 5DT-AJ N/A N/A
Adjustable Length 11”-14” -Black Disc. - See 58DV-08B 5DT-AJB N/A N/A
Extension Pipe 17”-24” -Galvanized Disc. - See 58DV-16A N/A N/A N/A
Extension Pipe 17”-24” -Black Disc. - See 58DV-16AB N/A N/A N/A
Adjustable Length 8-1/2”-Galvanized 58DVA-08A - N/A from FPI N/A N/A N/A
Adjustable Length 8-1/2”-Black 58DVA-08AB N/A N/A N/A
Extension Pipe 16”-Galvanized 58DVA-16A - N/A from FPI N/A N/A N/A
Extension Pipe 16”-Black 46DVA-16AB N/A N/A N/A
Simpson
Direct Vent Pro
®
Selkirk
Direct Temp™
Metal-Fab™
Sure Seal
.
ICC Excel
Direct
45º Elbow-Galvanized 58DVA-E45 5DT-EL45 5DT-EL45 TE-5DE45
45º Elbow-Black 58DVA-E45B 5DT-EL45B 5DT-EL45B TE-5DE45B
45º Elbow Swivel-Galvanized
45º Elbow Swivel-Black
90º Elbow-Galvanized 58DVA-E90 5DT-EL90S 5DT-EL90S TE-5DE90
90º Elbow-Black 58DVA-E90B 5DT-EL90SB 5DT-EL90SB TE-5DE90B
90º Elbow, Swivel-Galvanized
90º Elbow, Swivel-Black
90º Starter Elbow, Swivel-Galvanized N/A N/A N/A N/A
Adaptor* N/A N/A N/A N/A
Ceiling Support 58DVA-DC 5DT-CS 5DSP TE-5DE45
Cathedral Support Box 58DVA-CS 5DT-CSS 5DRS TE-5DE45B
Wall Support/Band 58DVA-WS 5DT-WS/B 5DWS N/A
Offset Support
Wall Thimble-Black 58DVA-WT 5DT-WT 5DWT TE-5DE90
Wall Thimble Support/Ceiling Support 58DVA-DC
Firestop Spacer 58DVA-FS 5DT-FS 5DFS N/A
Trim Plate-Black 58DAV-WFS 5DT-TP 5DCP N/A
Disc. - See 58DVA-E45
Disc.-See 58DVA-E45B
Disc. - See 46DVA-E45
Disc. - See 46DVA-E45
58DVA-ES - N/A from FPI
- N/A from FPI N/A N/A TE-5DE90B
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
5DT-OS N/A N/A
Regency® P48-2 Zero Clearance Direct Vent Gas Fireplace 15