STYLE MODEL
See Thru P121-NG2 Natural Gas P121-LP2 Propane
Left Corner P121LC-NG2 Natural Gas P121LC-LP2 Propane
Right Corner P121RC-NG2 Natural Gas P121RC-LP2 Propane
Pier P131-NG2 Natural Gas P131-LP2 Propane
WARNING:
If the information in these instructions are not followed exactly, a
fi re or explosion may result causing property damage, personal
injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable vapours and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed
installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
918-519b
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
www.regency-fi re.com
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical switch: do not use any
phone in your building.
Immediately call your gas supplier from a neighbour's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fi re
department.
08/13/09
WARNING
HOT GLASS
CAUSE BURNS
DO NOT TOUCH
UNTIL COOLED
NEVER
TO TOUCH GLASS
CHILDREN AND ADULTS SHOULD BE ALERTED TO
THE HAZARDS OF HIGH SURFACE TEMPERATURES,
ESPECIALLY THE FIREPLACE GLASS, AND SHOULD
ST AY AWA Y TO AVOID BURNS OR CLOTHING IGNITION.
ALLOW CHILDREN
WILL
GLASS
To the New Owner:
Congratulations!
Y ou are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The P121 / P121LC / P121RC / P131
is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood
fi replace at the fl ick of a switch. The model P121 / P121LC / P121RC / P131 has been approved by Intertek
for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy,
comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself
with these instructions and the many features of your Regency® Fireplace.
IMPORTANT : If the unit is to be installed into a bathroom, optional Neo ceramic glass Part# 360-946 Front
or Part# 360-948 Side must be purchased and installed in place of the tempered glass supplied with the
unit.
MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
This Regency® product has been tested and listed by Intertek as a Direct Vent Wall Furnace to the following standards: VENTED
GAS FIREPLACE HEA TERS ANSI Z21.88a-2007/CSA 2.33a-2007 and GAS-FIRED APPLIANCES FOR USE AT HIGH AL TITUDES
CAN/CGA 2.17-M91.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for
Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard
in Canada.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of
local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the
U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.
This Regency® mobile/manufactured home listed appliance comes factory equipped with four 1/4" diameter holes located near each
corner of the base. Fasten the fi replace in place using screw, inserted through the holes.
This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as applicable
to local codes. See the "Wiring Diagram" section.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with
the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home, where not
prohibited by local codes.
This appliance can only be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with
other cases, unless a certifi ed kit is used.
Ensure that structural members are not cut or weakened during installation.
2
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
TABLE OF CONTENTS
SAFETY LABEL
Copy of Safety Label .....................................................4
REQUIREMENTS
MA Code - CO Detector.................................................5
INSTALLATION
General Safety Information............................................6
For usewith glassdoors certified withthe applianceonly.
This ventedgas fireplaceheater is notfor usewith air filters.
Ne pasutiliser defiltre à airavec cefoyer au gazà évacuation.
Cet appareil doit être utilize uniquement avec le type de gaz indiqué sur la
plaque signalétique. Cet appareil peut être installé dans une maison
préfabriquée ou mobile (É.-U. seulement) installée à demeure si les
règlements locaux le permettent. Voir la notice de l'utilisateur pour plus de
renseignements. Cetappareilne peut pas êtreutilisé avec d'autres gazsauf
si unetrousse deconversion certifiée estfournie.
Pour utilisation uniquement avec les portes en verre certifiées avec
l'appareil.
Electrical supply/ Électrique115VAC,1.13A, 60Hz.
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUELS. /
NE PAS UTILISER AVEC DU COMBUSTIBLE SOLIDE.
FOYER
AU GAZ À ÉVACUATION -
This is a copy of the label that accompanies
each P121-2/P121LC-2/P121RC-2/P131-2
Zero Clearance Direct Vent Gas Fireplace.
We have printed a copy of the contents here
for your review. The safety label is located
on the front inside base of the unit, visible
when the bottom louver is open.
®
NOTE: Regency
improved. Check the label on the unit and
if there is a difference, the label on the unit
is the correct one.
units are constantly being
For the State of Massachusetts, installation
and repair must be done by a plumber or
gasfi tter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, fl exible
connectors shall not exceed 36 inches in
length.
Copy of Safety Decal for P121/P121LC/P121RC/P131
For the State of Massachusetts, the appliances individual manual shut-off must be a
t-handle type valve.
The State of Massachusetts requires the
installation of a carbon monoxide alarm in
accordance with NFPA 720 and a CO alarm
with battery back up in the same room where
the gas appliance is installed.
4
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace5
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The Panorama P121/P121LC/P121RC/P131NG1 or P121/P121LC/P121RC/P131-LP1 Direct
Vent Fireplace must be installed in accordance
with these instructions. Carefully read all the
instructions in this manual fi rst. Consult the
"authority having jurisdiction" to determine the
need for a permit prior to starting the installation.
It is the responsibility of the installer to ensure
this fi replace is installed in compliance with
manufacturer's instructions and all applicable
codes.
BEFORE YOU ST ART
Safe installation and operation of this appliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of
the following:
INSTALLATION AND REPAIR SHOULD
BE DONE BY A QUALIFIED SERVICE
PERSON. THE APPLIANCE SHOULD
BE INSPECTED BEFORE USE
AND AT LEAST ANNUALLY BY A
PROFESSIONAL SERVICE PERSON.
MORE FREQUENT CLEANING MAY
BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, BEDDING
MATERIAL, ETC. IT IS IMPERATIVE
THAT CONTROL COMPARTMENTS,
BURNERS AND CIRCULATING AIR
P ASSAGEWA YS OF THE APPLIANCE
BE KEPT CLEAN.
DUE TO HIGH TEMPERA TURES, THE
APPLIANCE SHOULD BE LOCATED
OUT OF TRAFFIC AND AWAY FROM
FURNITURE AND DRAPERIES.
WARNING: F AILURE TO INSTALL THIS
APPLIANCE CORRECTLY WILL VOID
YOUR WARRANTY AND MAY CAUSE
A SERIOUS HOUSE FIRE.
CLOTHING OR OTHER FLAMMABLE
MA TERIAL SHOULD NOT BE PLACED
ON OR NEAR THE APPLIANCE.
CHILDREN AND ADULTS SHOULD
BE ALERTED TO THE HAZARDS OF
HIGH SURFACE TEMPERATURES,
ESPECIALLY THE FIREPLACE GLASS,
AND SHOULD ST AY AWAY TO AVOID
BURNS OR CLOTHING IGNITION.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform
with local codes or, in the absence of
local codes, with the current Canadian or
National Gas Codes, CAN1-B149 or ANSI
Z223.1 Installation Codes.
2) See general construction and assembly
instructions. The appliance and vent should
be enclosed.
3) This appliance must be connected to the
specifi ed vent and termination cap to the
outside of the building envelope. Never vent
to another room or inside a building. Make
sure that the vent is fi tted as per Venting
instructions.
4) Inspect the venting system annually for
blockage and any signs of deterioration.
5) Venting terminals shall not be recessed into
a wall or siding.
6) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
7) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fi replace.
8) Wear gloves and safety glasses for protection
while doing required maintenance.
9) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for
termination.
10) Under no circumstances should this
appliance be modifi ed. Parts that have to be
removed for servicing should be replaced
prior to operating this appliance.
11) Installation and any repairs to this appliance
should be done by a qualifi ed service person.
A professional service person should be
called to inspect this appliance annually.
Make it a practice to have all of your gas
appliances checked annually.
12) Do not slam shut or strike the glass door.
13) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
14) The appliance area must be kept clear and
free of combustible materials, (gases and
other fl ammable vapours and liquids).
INSTALLATION
CHECKLIST
Note: These units are
non-load bearing.
1) Locate appliance. Refer to the following
sections:
a) Locating Your Fireplace
b) Clearances
c) Combustible Mantel Clearances
d) Framing & Finishing
e) Venting. See the "Venting Introduction"
to "Venting Arrangements" sections.
2) Assemble Top Standoffs. Refer to the "Unit
Assembly Prior to Installation" section.
(NOTE: must be done before installing
unit into fi replace.)
3) Install vent. See the "Horizontal
Installations" to "Installation Procedures"
sections
4) Make gas connections. Test the pilot. Must
be as per diagram. Refer to the "Gas Line
Installation" & "Pilot Adjustment" sections.
5) Install standard and optional features. Refer
to the following sections where applicable:
a. Log Set
b. Glass Door
c. Finishing Trim
d. Louvers & Grills
e. Remote Control
f. Wall Switch
g. Wall Thermostat
6) Final check.
Before leaving this unit with the customer,
the installer must ensure that the appliance is
fi ring correctly and operation fully explained to
customer.
This includes:
1) Clocking the appliance to ensure the correct
fi ring rate (rate noted on label 40,000 Btu/h
NG, and 39,000 Btu/h LP) after burning
appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN
THEY ARE IN THE SAME ROOM AS
THE APPLIANCE.
6
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
SPECIFICATIONS
P121-2 See Thru
INSTALLATION
Note: These units are
non-load bearing.
P131-2 Pier
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace7
INSTALLATION
P121LC-2 Left Corner Unit
Note: These units are
non-load bearing.
P121RC-2 Right Corner Unit
8
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your fi replace,
ensure that the clearances are met as
outlined in the "Clearances" section.
2) Provide adequate clearances for servicing.
3) The appliance must be installed on a fl at,
solid, continuous surface (e.g. wood, metal,
concrete). This may be the fl oor, or raised up
on a platform to enhance its visual impact.
If the appliance is going to be installed
on carpeting, combustible linoleum tile or
other combustible material other than wood
fl ooring, the appliance must be installed on a
metal or wood panel extending the full width
and depth of the appliance.
4) The Direct Vent Gas Fireplace can be
installed as follows:
Model # Position
A) P121-2: See Thru
B) P131-2: Pier
C) P121LC-2: Left Corner
D) P121RC-2: Right Corner
5) This appliance is Listed for bedroom
installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
A) P121-2 See Thru
B) P131-2 Pier
6) The P121-2/P121LC-2/P121RC-2/P1312 Direct Vent Gas Fireplace is approved
for alcove installations, which meet the
clearances listed on this page.
7) We recommend that you plan your installation
on paper using exact measurements for
clearances and floor protection before
actually installing this appliance. Have a
qualifi ed inspector, dealer , or installer review
your plans before installation.
Note: For Exterior Vent Termination
Locations see section "Exterior Vent
Termination Locations."
C) P121LC-2 Left Corner
D) P121RC-2 Right Corner
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace9
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated (refer to diagrams in the "Locating Your Fireplace" section):
Clearance to Combustibles from:
Back 0" (0mm)
Side 0" (0mm)
Floor 0" (0mm)
CAUTION REQUIREMENTS: The top, back and sides of the fi replace are defi ned by standoffs.
The metal ends of the standoffs may NOT be recessed into combustible construction.
Determine the total thickness of the fi nished fl oor (eg. tile, carpet, slate) to allow the fi nished
surface to be fl ush with the base of the unit.
Ceiling Height from Floor 72" (1828mm)
Mantel Height from Base of Unit:
39" min. (991mm)
Horizontal Vent Clearances:
Top 2-1/2" (64mm)
Side 1-1/2" (38mm)
Bottom 1-1/2" (38mm)
Vertical Vent Clearances 1-1/4" (32mm)
COMBUSTIBLE MANTELS
Mantel Clearances
Because of the extreme heat this fi replace emits,
the mantel clearances are critical. Combustible
mantel clearances from top of unit are shown in
Diagram to the right.
Note: A non-combustible mantel may be
installed at a lower height if the framing
is made of metal studs covered with a
non-combustible board.
WARNING:
Fire hazard is an extreme risk
if these clearances (air space)
to combustible materials are
not adhered to. It is of greatest
importance that this fi replace
and vent system be installed
only in accordance with these
This drawing is to scale at 1:6 (one inch = 6
inches)
Mantel can be installed anywhere in shaded area
or higher using this scale.
Caution: Ensure the paint that is used on the
mantel and the facing
is "heat resistant" or the paint may
discolour.
* If the 3" (76mm) metal extension trim is removed
it must be replaced with a 8" (203mm) noncombustible material.
10
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
FRAMING AND FINISHING
INSTALLATION
1) For ease of installation, frame your fi replace after it is positioned and
the vent system is installed. Remember to install the top standoffs.
See the "Unit Assembly Prior to Installation" section. Use 2x4's and
frame to local building codes.
CAUTION: Verify your fi replace dimensions, framing methods and
fi nished wall facing details before framing. Determine the total
thickness of facing material - drywall plus ceramic tiles, slate, etc.
Allow the fi nish surface to be fl ush with the front or side of the
unit. Total facing thickness can vary from 1/2" (13mm) to 1-1/4"
(32mm) thick.
2) When locating your appliance on an exterior wall or in a chase, apply
a vapour barrier and drywall, as per local building codes. DO NOT
INSULATE THE FIREPLACE ITSELF.
CAUTION: The unit does not have to be completely enclosed in
a chase. The clearance on top of the unit is 0" to the standoffs
so combustible building materials can be laid directly on top
of the standoffs. You must maintain clearance from the vent to
combustible materials for both rigid and fl ex, see Vent Clearances
in the "Clearances" section.
P121-2 - See Thru
Framing Dimensions
P121-2 (See Thru) P131-2 (Pier) P121LC-2 / P121RC-2
(Corner Unit)
A 25"(635mm) 25"(635mm) 26-13/16"
minus two times minus two times minus one time
the fi nishing the fi nishing the fi nishing material thickness* material thickness* material thickness*
B 42-1/2"(1080mm) 42-1/2"(1080mm) 42-1/2"(1080mm)
C 46-3/4"(1187mm) 45" (1143mm) 45"(1143mm)
minus one time minus one time
the fi nishing the fi nishing
* Finish material thickness includes: drywall, ceramic tile, slate, etc.
P121LC-2 - Corner Unit
P131-2 - Pier
P121RC-2 - Corner Unit
C
A
B
Note: These units are
non-load bearing.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace11
INSTALLATION
Facing & Finishing Requirements
This fi replace is supplied with a 3" metal extension trim above the fi replace. The extension trim may be replaced if the framing is faced with a non-
combustible material placed fl ush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.)
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The 4 Top Standoffs must be correctly positioned and attached to the top before unit is slipped
into position.
Top Standoff Assembly
The top standoffs are shipped in a fl at position and must be folded into shape and attached.
1) Remove the standoffs from the fi replace
top.
2) Take each standoff and bend into the correct
shape. Bend up at the bend lines until the
screw holes in the standoff and the prepunched screw holes on the fi replace top
line up.
3) Attach the standoff securely to the top with 4
screws per standoff (on opposite corners).
VENTING
INTRODUCTION
The P121-2/P121LC-2/P121RC-2/P131-2 uses
the "balanced fl ue" technology Co -Axial system.
The inner liner vents products of combustion to
the outside while the outer liner draws outside
combustion air into the combustion chamber
thereby eliminating the need to use heated
room air for combustion and losing warm room
air up the chimney.
Note: These flue pipes must not be
connected to any other appliance.
The gas appliance and vent system must be
vented directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each direct vent gas appliance must use it's
own separate vent system. Common vent
systems are prohibited. (See "Rigid Pipe Venting
Systems" for more details and exceptions).
12
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
EXTERIOR VENT TERMINATION LOCATIONS
1
Minimum Clearance Requirements
AClearance above grade, veranda, porch, deck, or balcony12"(30cm)12"(30cm)
BClearance to window or door that may be opened 12"(30cm)9" (23cm)
CClearance to permanently closed window**
DVer tical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm)18"(46cm)18"(46cm)
EClearance to unventilated soffi t20"(51cm)20"(51cm)
FClearance to outside corner: with AstroCap Termination Cap. 6"(15cm)6"(15cm)
Clearance to outside corner: with all other approved Termination Caps.14"(36cm)14"(36cm)
GClearance to inside corner: with AstroCap Termination Cap 6"(15cm)6"(12cm)
Clearance to inside corner: with all other approved Termination Caps.12"(30cm) 12"(30cm)
HClearance to each side of center line extended above meter/regulator assembly 36"(90cm)
JClearance to service regulator vent outlet36"(90cm)*
KClearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance12"(30cm)9" (23cm)
LClearance to a mechanical air supply inlet 72"(1.8m)36"(90cm)
MClearance above paved sidewalk or a paved driveway located on public property 84"(2.1m)
NClearance under veranda, porch, deck, or balcony 12"(30cm)
1
In accordance with current CSA B149.1, Natural Gas and Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
┼
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor
Clearance in accordance with local installation codes and the requirements of the gas supplier
*
a
3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly
b
3 feet (91cm) above - if within 10 feet (3m) horizontally
Canada
a
┼
‡
USA
*
*
*
2
b
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace13
INSTALLATION
4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.