Regency P40-LP1, P40-NG1 User Manual

Gas Fireplaces
P40 Gas Fireplace
P40 Direct Vent Gas Fireplace
Model P40-NG1 P40-LP1
Fuel Type Natural Gas Propane
Minimum Supply Pressure 5” W.C. (1.25 kPa) 12” W.C. (3.00 kPa)
Manifold Pressure - High 3.5” W.C. (0.87 kPa) 10” W.C. (2.49 kPa)
Manifold Pressure - Low 1.6” W.C. (0.39 kPa) 3.6” W.C. (0.89 kPa)
Orifi ce Size - Front Burner #44 DMS #55 DMS
Orifi ce Size - Rear Burner #35 DMS #53 DMS
Minimum Input 13,000 BTU/h (3.81 kW) 12,000 BTU/h (3.51 kW)
Vent Sizing 5” Inner / 8” Outer 5” Inner / 8” Outer
Approved Venting Systems
Flex Vent Systems: FPI AstroCap™ Flex Vent
Rigid Pipe Vent Systems: Simpson Dura-Vent® Direct Vent GS
Selkirk Direct-Temp
B
A
Gas Fireplaces
Unit requires
120V to operate. See
“Wiring Diagram,” on page 17,
for more details. Receptacle is
included with manual.
D
C
A
Unit Dimensions Description P40
A Front Face Width 40” (1016mm)
B Rear Firebox Width 33-7/16” (889mm)
C Front Face Height 34” (864mm)
D Height w/ Standoff 42-1/2” (1080mm)
E Unit Depth 20-1/16” (508mm)
F Height to Vent 35-1/4” (826mm)
Framing Dimensions Description P40
G Framing Width 40-1/2” (1029mm)
*** Framing Height*** 42-1/2” (1080mm)*** + Hearth
H
I Framing Depth 20-1/16” (508mm)
J Corner Wall Length 50-5/8” (1286mm)
K Corner Facing Wall Width 71-5/8” (1524mm)
L Minimum Height to Combustibles 51-7/8” (1318mm)
M Vent Centerline Height 45-3/8” (1153mm)
N Non-Combustible Facing Height 10-1/4” (260mm)
O Gas Connection Height 1-1/2” (38mm)
P Gas Connection Inset 4-3/4” (121mm)
Q Gas Connection Width 3-1/4” (102mm)
E
L
Drywall
(or other
F
Top Header
(non-combustible)
facing)
Top Header (non-combustible)
N
Non-Combustible Facing
H
11" (279mm)
dia. Hole through
wall Vent.
G
I
M
J
O
P
K
Q
Opening for gas
connection
Please refer to Page 11 (Exterior Vent Terminations)
for additional guidelines on vent locations.
Important: Framing height requires consideration of the hearth
***
depth. Dimension H = H + the thickness of installed hearth.
45June 2007 Regency Product Specifi cations Book
P40 Gas Fireplace
Framing and Finishing
1) Frame the enclosure for the unit with framing material. Use the determined total thickness of facing material (e.g. drywall plus ceramic tiles) to adjust the framing depth to allow the fi nished surface to be fl ush with the front of the unit. Total facing thickness
Gas Fireplaces
can vary from 1/2” (13mm) to 1-1/4” (32mm) thick.
Note: Header for the P40 must be non combustible.
2) For exterior walls, insulate the enclosure to the same degree as
the rest of the house, apply vapor barrier and drywall, as per local installation codes. (Do not insulate the fi replace itself.)
3) Ensure that all of the clearances listed below are met. Combustible material may be brought up to the sides of the unit and be covered with ceramic tiles, bricks, rock or other suitable combustible fi nishing materials. Non-combustible facing is required above
the unit. (See Dimension “N” on page 41)
Note: You must maintain proper clearances from the vent to
combustible materials (See Below).
4) Use metal studs for framing where the minimum clearance from
the vent to combustible material cannot be maintained.
Clearance Requirements
Required hearth must be non-combustible. (Page 43)
Required non-combustible facing above unit. (See Dimension “N” on page 41)
Gas Fireplaces
Vent Clearances Clearance Dimension
Horizontal - Top 2-1/2” (64mm)
Horizontal - Side 1-1/2” (38mm)
Horizontal - Bottom 1-1/2” (38mm)
Vertical (Flex or Rigid) 1-1/4” (32mm)
WARNING
Failure to maintain required clearances is a major cause of chimney related fi res. Installation of this fi replace must comply with these clearances.
Hearth Requirements
A 40" (1016mm) wide x 16" (406mm) deep x 1-1/2" (38mm) thick hearth is required, unless the unit is raised 4" (102mm). All measurements are from the bottom of the unit. Therefor the bottom of the unit would be fl ush with the top of a non-combustible hearth or 4” above the surface of a combustible fl oor.
Floor Mounted Fireplace
D
C
A
F
B
B
H
I
G
E
Clearance: Dimension Measured From:
A: Mantel Height 12” (305mm) Minimum (Additional on this page)
B: Sidewall 8” (203mm) Side of installed front
C: Ceiling 39” (991mm) Top of installed unit
D: Mantel Depth 13” (330mm) Maximum (Additional on this page)
E: Alcove Width 56” (1422mm) Sidewall to Sidewall (Minimum)
F: Alcove Depth 36” (914mm) Front to back wall (Maximum)
G: Hearth Height 1-1/2” (39mm) Floor to top of Hearth.
H: Hearth Width 40” (1016mm) Edge to Edge of Hearth
I: Hearth Depth 16” (406mm) Front of Hearth to Wall
not be higher than base of fi rebox.)
(Hearth must
Raised Fireplace
Full Screen Door Facing Requirements
WARNING: When installing the
10-1/4” Above Fireplace
6”
6”
Full Screen Doors
The Full Screen Front requires additional non combustible facing and non-combustible framing. Ensure the 10-1/4" above the fi replace, 6" on both sides and both the header and side studs are non-combustible materials. All other clearances, including mantel, remain the same.
46 June 2007 Regency Product Specifi cations Book
Gas Fireplaces
Combustible Mantels
Because of the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed anywhere in the shaded area or higher.
Mantel Clearances
12
14
64810
13" (330mm)
8”(203mm)
1" (25mm)
B
C
2
D
0
Drywall
Non-Combustible
Header
Non-Combustible
Standoff
Facing
P40 Gas Fireplace
FPI Kit # Length Contains:
#946-618 6 Feet 1) 8” fl exible outer liner (Kit length)
2) 5” fl exible inner liner (Kit length)
3) spring spacers (3)
4) thimble (2)
5) AstroCap termination cap (1)
#946-616 10 Feet
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) S.S. screws #8 x 1-1/2” drill point, (4)
10) vinyl siding standoff
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency may be used for Flex installations.
3) Horizontal sections must be supported every 3 feet.
AstroCap XL
(Part# 946-623/P)
Gas Fireplaces
0
Mantel Clearances
Front 33” (838mm) 21” (356mm) 17” (254mm) 12” (178mm)
To p o f
A
Louvers
To Floor
ABCD
Side View
Note: If desired a non-combustible mantel may be installed at a
lower height.
Note: Ensure the paint that is used on the mantel and the facing
is “heat resistant” or the paint may discolour.
Mantel Leg Clearances
Combustible mantel leg clearances as per diagram below: Clearances are from the fi nished edge of the unit or installed front.
8” Side Wall
P40
Mantel leg
6”
Maximum 1-1/2” projection at 2” minimum clearance.
Mantel leg
1-1/2"
2"
7¼”
Allowable mantel leg
projection.
Wall Thimble
(required in Canada only)
5” dia. flue pipe
8" dia.
Flue pipe
spring spacer
Vinyl Siding
Standoff
Snorkel Terminations
Snorkel Terminations:
For installations requiring a vertical rise on the exterior of the building, 14­inch and 36-inch tall Snorkel Terminations are available. Follow the same installation procedures as used for standard Horizontal Termination. NEVER install the snorkel upside down.
Regency Direct Vent System (Flex)
Horizontal Terminations Only
These venting systems, in combination with the P40 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram.
FPI Direct Vent (Flex) System Termination Kits include all the parts needed to install the P40 using a fl exible vent.
Below Grade Snorkel Installation (Dura-Vent Only)
If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent water from entering the Snorkel Termination. Refer to Rigid Pipe Installation instructions for details. Do not attempt to enclose the Snorkel within the wall, or any other type of enclosure.
47June 2007 Regency Product Specifi cations Book
10 12 16
18
14
20 26
28
22 24
30
10 12 16
18
14
20 26
28
22 24
30
12 16
18
20 26
28
22 24
30
P40 Gas Fireplace
Alternate Snorkel
Termination Cap
Part #1282 (14”) Part #1281 (36”)
Rigid Pipe Venting
Horizontal or Vertical Terminations
Vertical
Terminal
Gas Fireplaces
Storm Collar
Flashing
Vinyl Siding
Standoff
Gas Fireplaces
2
0
40
4
8
6
10 12
14
Ceiling Firestop
Pipe Length
If required by the external termination location the listed alternate termination caps may be used. (Refer to Page 11)
Venting Arrangements - Vertical Terminations
Rigid Pipe System
(Propane & Natural Gas)
Two 45° elbows = One 90° elbow
The P40 is approved for a maximum 40 ft. straight vertical, with Rigid Pipe vent systems for Propane and Natural Gas.
The diagram to the right shows allowable combinations of straight vertical and offset to vertical terminations with Rigid Pipe vent systems for Propane and Natural Gas. Maximum two 90° elbows allowed.
The unshaded area in the diagram shows allowable venting confi gurations with the Vent Restrictor Factory Set.
The lightly shaded area, confi gurations with the Vent Restrictor on Set 1.
The darker shaded area, confi gurations with the Vent Restrictor on Set 2.
Vent must be supported at offsets.
Horizontal sections must be supported every 3 feet
• Firestops are required at each floor level and whenever passing through a wall.
Maintain clearances to combustible materials.
Minimum of 1’ pipe section between any elbows.
Note: Must use optional rigid pipe adapter when using Rigid Pipe
(Part # 770-994).
48 June 2007 Regency Product Specifi cations Book
Termination Cap
Wall Thimble
(required in Canada only)
Adj.Pipe Length
o
90 Elbow
24" Pipe
Length
Rigid Pipe Adapter
11" - 14-5/8"
Alternate Horizontal
Termination Caps
(770-994)
, in the diagram shows all allowable venting
, in the diagram shows allowable venting
AstroCap XL
(946-623/P)
38
36
34
32
30
28
26
24
22
20
18
Vertical Height (Feet)
16
14
12
10
8
6
4
2
0
Minimum 12” (305mm)
Maximum: 40 ft. (12.2m)
Vent Restrictor on Set 2
Vent Restrictor on Set 1
Vent Restrictor
Factory Set
Minimum 8’9” (2.6m)
Max. 10’ (3m)(centerline to centerline)
Maximum: 28 ft. (8.5m)
Gas Fireplaces
Vertical Venting with Two (2) 90° Elbows
Two 45° elbows = One 90° elbow
P40 Gas Fireplace
Gas Fireplaces
Option V H V+ V1 Maximum total pipe: length, of
A) 0’ Min. 2’ Max. 1’ Min.
B) 1’ Min. 4’ Max. 2’ Min.
C) 2’ Min. 5’ Max. 3’ Min.
D) 3’ Min. 6’ Max. 4’ Min.
E) 4’ Min. 7’ Max. 5’ Min.
F) 5’ Min. 8’ Max. 6’ Min.
all sections, must not exceed 30 feet. Total horizontal sections must not exceed 8 feet.
Minimum of 1’ pipe section between any elbows.
When the total vertical exceeds total horizontal by 2x then the vent restrictor must be set to 1.
Vertical Venting with Three (3) 90° Elbows
Two 45° elbows = One 90° elbow
Option V H + H1 V+ V1 Maximum total pipe: length, of
A) 0’ Min. 2’ Max. 3’ Min.
B) 1’ Min. 2’ Max. 3’ Min.
C) 2’ Min. 3’ Max. 4’ Min.
D) 3’ Min. 4’ Max. 6’ Min.
E) 4’ Min. 5’ Max. 7’ Min.
F) 5’ Min. 6’ Max. 8’ Min.
G) 6’ Min. 7’ Max. 9’ Min.
H) 7’ Min. 8’ Max. 10’ Min.
all sections, must not exceed 30 feet. Total horizontal sections must not exceed 8 feet.
Minimum of 1’ pipe section between any elbows. When the total vertical exceeds total horizontal by 3x then the vent restrictor must be set to 1.
49June 2007 Regency Product Specifi cations Book
10 12 16
18
14
20 26
28
22 24
30
10 12 16
18
14
20 26
28
22 24
30
P40 Gas Fireplace
Venting Arrangements - Horizontal
Terminations
Two 45° elbows = One 90° elbow
This diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90° elbow
The unshaded area in the diagram shows allowable venting
Gas Fireplaces
confi gurations with the Vent Restrictor Factory Set.
The lightly shaded area, confi gurations with the Vent Restrictor on Set 1.
The darker shaded area, confi gurations with the Vent Restrictor on Set 2.
14
, in the diagram shows allowable venting
, in the diagram shows allowable venting
0
2
4
Gas Fireplaces
Note: Must use optional rigid pipe adapter (Part # 770-994) when
using Rigid Pipe.
Maintain clearances to combustibles.
Horizontal vent must be supported every 3 feet.
Minimum of 1’ pipe section between any elbows.
• Firestops are required at each fl oor level and whenever passing through a wall.
A vent guard may be required as per local codes, refer to page 11 for
“Exterior Vent Termination Locations”.
Note: FPI Direct Vent System (Flex) is only approved for horizontal
terminations.
Horizontal (Feet)
6 14
8 16
10 18
12 20
Vertical Height (Feet)
12
10
8
Vent Restrictor
on Set 2
6
Vent Restrictor
4
2
0
on Set 1
45-3/8”
Vent Restrictor
Factory Set
(1143mm) Minimum Height Requirement
Please refer to Page 11 (Exterior Vent Terminations)
for additional guidelines on vent locations.
50 June 2007 Regency Product Specifi cations Book
Gas Fireplaces
Horizontal Venting with Two (2) 90° Elbows
Two 45° elbows = One 90° elbow
P40 Gas Fireplace
Gas Fireplaces
Option V H+ H1 Maximum total pipe: length, of
A) 2’ Min. 2’ Max.
B) 3’ Min. 5’ Max.
C) 4’ Min. 6’ Max.
D) 5’ Min. 7’ Max.
E) 6’ Min. 8’ Max.
all sections, must not exceed 30 feet. Total horizontal sections must not exceed 8 feet.
Minimum of 1’ pipe section between any elbows. When the total vertical exceeds total horizontal by 2x then the vent restrictor must be set to 1.
Horizontal Venting with Three (3) 90° Elbows
Two 45° elbows = One 90° elbow
Option V H V+ V1 H + H1 Maximum total pipe:
A) 0’ Min. 1’ Max. 1’ Min. 1’ Max.
B) 1’ Min. 2’ Max. 3’ Min. 3’ Max.
C) 2’ Min. 2’ Max. 5’ Min. 4’ Max.
D) 3’ Min. 2’ Max. 7’ Min. 5’ Max.
E) 4’ Min. 3’ Max. 9’ Min. 6’ Max.
F) 5’ Min. 4’ Max. 10’ Min. 7’ Max.
G) 6’ Min. 5’ Max. 11’ Min. 8’ Max.
H) 7’ Min. 6’ Max. 12’ Min. 9’ Max.
length, of all sections, must not exceed 30 feet. Total horizontal sections must not exceed 9 feet.
Minimum of 1’ pipe section between any elbows. When the total vertical exceeds total horizontal by 3x then the vent restrictor must be set to 1.
51June 2007 Regency Product Specifi cations Book