Maximum Input45,000 BTU/h (13.19 kW) 43,000 BTU/h (12.60 kW)
Vent Sizing5” Inner / 8” Outer5” Inner / 8” Outer
Approved Venting Systems
Flex Vent Systems:FPI AstroCap™ Flex Vent
Rigid Pipe Vent Systems:Simpson Dura-Vent® Direct Vent GS
Selkirk Direct-Temp
B
A
Gas Fireplaces
Unit requires
120V to operate. See
“Wiring Diagram,” on page 17,
for more details. Receptacle is
included with manual.
D
C
A
Unit DimensionsDescriptionP40
AFront Face Width40” (1016mm)
BRear Firebox Width33-7/16” (889mm)
CFront Face Height34” (864mm)
DHeight w/ Standoff42-1/2” (1080mm)
EUnit Depth20-1/16” (508mm)
FHeight to Vent35-1/4” (826mm)
Framing Dimensions DescriptionP40
GFraming Width40-1/2” (1029mm)
***Framing Height***42-1/2” (1080mm)*** + Hearth
H
IFraming Depth20-1/16” (508mm)
JCorner Wall Length50-5/8” (1286mm)
KCorner Facing Wall Width71-5/8” (1524mm)
LMinimum Height to Combustibles51-7/8” (1318mm)
MVent Centerline Height45-3/8” (1153mm)
NNon-Combustible Facing Height10-1/4” (260mm)
OGas Connection Height1-1/2” (38mm)
PGas Connection Inset4-3/4” (121mm)
QGas Connection Width3-1/4” (102mm)
E
L
Drywall
(or other
F
Top Header
(non-combustible)
facing)
Top Header
(non-combustible)
N
Non-Combustible Facing
H
11" (279mm)
dia. Hole through
wall Vent.
G
I
M
J
O
P
K
Q
Opening for gas
connection
Please refer to Page 11 (Exterior Vent Terminations)
for additional guidelines on vent locations.
Important: Framing height requires consideration of the hearth
***
depth. Dimension H = H + the thickness of installed hearth.
45June 2007 Regency Product Specifi cations Book
P40 Gas Fireplace
Framing and Finishing
1) Frame the enclosure for the unit with framing material. Use the
determined total thickness of facing material (e.g. drywall plus
ceramic tiles) to adjust the framing depth to allow the fi nished
surface to be fl ush with the front of the unit. Total facing thickness
Gas Fireplaces
can vary from 1/2” (13mm) to 1-1/4” (32mm) thick.
Note: Header for the P40 must be non combustible.
2) For exterior walls, insulate the enclosure to the same degree as
the rest of the house, apply vapor barrier and drywall, as per local
installation codes. (Do not insulate the fi replace itself.)
3) Ensure that all of the clearances listed below are met. Combustible
material may be brought up to the sides of the unit and be covered
with ceramic tiles, bricks, rock or other suitable combustible
fi nishing materials. Non-combustible facing is required above
the unit. (See Dimension “N” on page 41)
Note: You must maintain proper clearances from the vent to
combustible materials (See Below).
4) Use metal studs for framing where the minimum clearance from
the vent to combustible material cannot be maintained.
Clearance Requirements
Required hearth must be non-combustible. (Page 43)
Required non-combustible facing above unit. (See Dimension
“N” on page 41)
Gas Fireplaces
Vent ClearancesClearance Dimension
Horizontal - Top2-1/2” (64mm)
Horizontal - Side1-1/2” (38mm)
Horizontal - Bottom1-1/2” (38mm)
Vertical (Flex or Rigid)1-1/4” (32mm)
WARNING
Failure to maintain required clearances is a major cause of
chimney related fi res. Installation of this fi replace must comply
with these clearances.
Hearth Requirements
A 40" (1016mm) wide x 16" (406mm) deep x 1-1/2" (38mm) thick hearth
is required, unless the unit is raised 4" (102mm).
All measurements are from the bottom of the unit. Therefor the
bottom of the unit would be fl ush with the top of a non-combustible
hearth or 4” above the surface of a combustible fl oor.
Floor Mounted Fireplace
D
C
A
F
B
B
H
I
G
E
Clearance:DimensionMeasured From:
A: Mantel Height12” (305mm)Minimum (Additional on this page)
B: Sidewall8” (203mm)Side of installed front
C: Ceiling39” (991mm)Top of installed unit
D: Mantel Depth13” (330mm)Maximum (Additional on this page)
E: Alcove Width56” (1422mm)Sidewall to Sidewall (Minimum)
F: Alcove Depth36” (914mm)Front to back wall (Maximum)
G: Hearth Height1-1/2” (39mm)Floor to top of Hearth.
H: Hearth Width40” (1016mm)Edge to Edge of Hearth
I: Hearth Depth16” (406mm)Front of Hearth to Wall
not be higher than base of fi rebox.)
(Hearth must
Raised Fireplace
Full Screen Door Facing Requirements
WARNING: When installing the
10-1/4” Above Fireplace
6”
6”
Full Screen Doors
The Full Screen Front requires
additional non combustible facing
and non-combustible framing.
Ensure the 10-1/4" above the
fi replace, 6" on both sides and
both the header and side studs
are non-combustible materials.
All other clearances, including
mantel, remain the same.
46June 2007 Regency Product Specifi cations Book
Gas Fireplaces
Combustible Mantels
Because of the extreme heat this fi replace emits, the mantel
clearances are critical. Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed
anywhere in the shaded area or higher.
Note: If desired a non-combustible mantel may be installed at a
lower height.
Note: Ensure the paint that is used on the mantel and the facing
is “heat resistant” or the paint may discolour.
Mantel Leg Clearances
Combustible mantel leg clearances as per diagram below:
Clearances are from the fi nished edge of the unit or installed front.
8” Side Wall
P40
Mantel leg
6”
Maximum
1-1/2” projection at 2”
minimum clearance.
Mantel leg
1-1/2"
2"
7¼”
Allowable mantel leg
projection.
Wall Thimble
(required in Canada only)
5” dia. flue pipe
8" dia.
Flue pipe
spring spacer
Vinyl Siding
Standoff
Snorkel Terminations
Snorkel Terminations:
For installations requiring a vertical rise on the exterior of the building, 14inch and 36-inch tall Snorkel Terminations are available. Follow the same
installation procedures as used for standard Horizontal Termination.
NEVER install the snorkel upside down.
Regency Direct Vent System (Flex)
Horizontal Terminations Only
These venting systems, in combination with the P40 Direct Vent Gas
Fireplace, have been tested and listed as a direct vent heater system
by Warnock Hersey. The location of the termination cap must conform
to the requirements in the Vent Terminal Locations diagram.
FPI Direct Vent (Flex) System Termination Kits include all the parts
needed to install the P40 using a fl exible vent.
Below Grade Snorkel Installation (Dura-Vent Only)
If the Snorkel Termination must be installed below grade, i.e. basement
application, proper drainage must be provided to prevent water from
entering the Snorkel Termination. Refer to Rigid Pipe Installation
instructions for details. Do not attempt to enclose the Snorkel within the
wall, or any other type of enclosure.
47June 2007 Regency Product Specifi cations Book
101216
18
14
2026
28
2224
30
101216
18
14
2026
28
2224
30
1216
18
2026
28
2224
30
P40 Gas Fireplace
Alternate Snorkel
Termination Cap
Part #1282 (14”)
Part #1281 (36”)
Rigid Pipe Venting
Horizontal or Vertical Terminations
Vertical
Terminal
Gas Fireplaces
Storm Collar
Flashing
Vinyl Siding
Standoff
Gas Fireplaces
2
0
40
4
8
6
1012
14
Ceiling Firestop
Pipe Length
If required by the external termination location the listed
alternate termination caps may be used. (Refer to Page 11)
Venting Arrangements - Vertical
Terminations
Rigid Pipe System
(Propane & Natural Gas)
Two 45° elbows = One 90° elbow
The P40 is approved for a maximum 40 ft. straight vertical, with Rigid
Pipe vent systems for Propane and Natural Gas.
The diagram to the right shows allowable combinations of straight vertical
and offset to vertical terminations with Rigid Pipe vent systems for
Propane and Natural Gas. Maximum two 90° elbows allowed.
The unshaded area in the diagram shows allowable venting
confi gurations with the Vent Restrictor Factory Set.
The lightly shaded area,
confi gurations with the Vent Restrictor on Set 1.
The darker shaded area,
confi gurations with the Vent Restrictor on Set 2.
• Vent must be supported at offsets.
• Horizontal sections must be supported every 3 feet
• Firestops are required at each floor level and whenever
passing through a wall.
• Maintain clearances to combustible materials.
• Minimum of 1’ pipe section between any elbows.
Note: Must use optional rigid pipe adapter when using Rigid Pipe
(Part # 770-994).
48June 2007 Regency Product Specifi cations Book
Termination Cap
Wall Thimble
(required in Canada only)
Adj.Pipe Length
o
90 Elbow
24" Pipe
Length
Rigid Pipe Adapter
11" - 14-5/8"
Alternate Horizontal
Termination Caps
(770-994)
, in the diagram shows all allowable venting
, in the diagram shows allowable venting
AstroCap XL
(946-623/P)
38
36
34
32
30
28
26
24
22
20
18
Vertical Height (Feet)
16
14
12
10
8
6
4
2
0
Minimum 12” (305mm)
Maximum: 40 ft. (12.2m)
Vent Restrictor on Set 2
Vent Restrictor on Set 1
Vent Restrictor
Factory Set
Minimum 8’9” (2.6m)
Max. 10’ (3m)(centerline to centerline)
Maximum: 28 ft. (8.5m)
Gas Fireplaces
Vertical Venting
with Two (2) 90° Elbows
Two 45° elbows = One 90° elbow
P40 Gas Fireplace
Gas Fireplaces
OptionVHV+ V1Maximum total pipe: length, of
A)0’ Min.2’ Max.1’ Min.
B)1’ Min.4’ Max.2’ Min.
C)2’ Min.5’ Max.3’ Min.
D)3’ Min.6’ Max.4’ Min.
E)4’ Min.7’ Max.5’ Min.
F)5’ Min.8’ Max.6’ Min.
all sections, must not exceed
30 feet.
Total horizontal sections must
not exceed 8 feet.
Minimum of 1’ pipe section
between any elbows.
When the total vertical
exceeds total horizontal by
2x then the vent restrictor
must be set to 1.
Vertical Venting
with Three (3) 90° Elbows
Two 45° elbows = One 90° elbow
OptionVH + H1V+ V1Maximum total pipe: length, of
A)0’ Min.2’ Max.3’ Min.
B)1’ Min.2’ Max.3’ Min.
C)2’ Min.3’ Max.4’ Min.
D)3’ Min.4’ Max.6’ Min.
E)4’ Min.5’ Max.7’ Min.
F)5’ Min.6’ Max.8’ Min.
G)6’ Min.7’ Max.9’ Min.
H)7’ Min.8’ Max.10’ Min.
all sections, must not exceed
30 feet.
Total horizontal sections must
not exceed 8 feet.
Minimum of 1’ pipe section
between any elbows.
When the total vertical
exceeds total horizontal by
3x then the vent restrictor
must be set to 1.
49June 2007 Regency Product Specifi cations Book
101216
18
14
2026
28
2224
30
101216
18
14
2026
28
2224
30
P40 Gas Fireplace
Venting Arrangements - Horizontal
Terminations
Two 45° elbows = One 90° elbow
This diagram shows all allowable combinations of vertical runs with
horizontal terminations, using one 90° elbow
The unshaded area in the diagram shows allowable venting
Gas Fireplaces
confi gurations with the Vent Restrictor Factory Set.
The lightly shaded area,
confi gurations with the Vent Restrictor on Set 1.
The darker shaded area,
confi gurations with the Vent Restrictor on Set 2.
14
, in the diagram shows allowable venting
, in the diagram shows allowable venting
0
2
4
Gas Fireplaces
Note: Must use optional rigid pipe adapter (Part # 770-994) when
using Rigid Pipe.
• Maintain clearances to combustibles.
• Horizontal vent must be supported every 3 feet.
• Minimum of 1’ pipe section between any elbows.
• Firestops are required at each fl oor level and whenever passing
through a wall.
A vent guard may be required as per local codes, refer to page 11 for
“Exterior Vent Termination Locations”.
Note: FPI Direct Vent System (Flex) is only approved for horizontal
terminations.
Horizontal (Feet)
614
816
1018
1220
Vertical Height (Feet)
12
10
8
Vent Restrictor
on Set 2
6
Vent Restrictor
4
2
0
on Set 1
45-3/8”
Vent Restrictor
Factory Set
(1143mm)
Minimum
Height
Requirement
Please refer to Page 11 (Exterior Vent Terminations)
for additional guidelines on vent locations.
50June 2007 Regency Product Specifi cations Book
Gas Fireplaces
Horizontal Venting
with Two (2) 90° Elbows
Two 45° elbows = One 90° elbow
P40 Gas Fireplace
Gas Fireplaces
OptionVH+ H1Maximum total pipe: length, of
A)2’ Min. 2’ Max.
B)3’ Min. 5’ Max.
C)4’ Min.6’ Max.
D)5’ Min.7’ Max.
E)6’ Min.8’ Max.
all sections, must not exceed
30 feet.
Total horizontal sections must
not exceed 8 feet.
Minimum of 1’ pipe section
between any elbows.
When the total vertical
exceeds total horizontal by
2x then the vent restrictor
must be set to 1.
Horizontal Venting
with Three (3) 90° Elbows
Two 45° elbows = One 90° elbow
OptionVHV+ V1H + H1 Maximum total pipe:
A)0’ Min.1’ Max.1’ Min.1’ Max.
B)1’ Min.2’ Max.3’ Min.3’ Max.
C)2’ Min.2’ Max.5’ Min.4’ Max.
D)3’ Min.2’ Max.7’ Min.5’ Max.
E)4’ Min.3’ Max.9’ Min.6’ Max.
F)5’ Min.4’ Max. 10’ Min. 7’ Max.
G)6’ Min.5’ Max. 11’ Min. 8’ Max.
H)7’ Min.6’ Max. 12’ Min. 9’ Max.
length, of all sections,
must not exceed 30 feet.
Total horizontal sections
must not exceed 9 feet.
Minimum of 1’ pipe
section between any
elbows.
When the total vertical
exceeds total horizontal
by 3x then the vent
restrictor must be set
to 1.
51June 2007 Regency Product Specifi cations Book