Regency P40-LP, P40-NG User Manual

www.regency-fi re.com
P40 Gas Fireplace
Owners &
Installation Manual
MODELS: P40-NG Natural Gas P40-LP Propane
WARNING: If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
918-566b
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
FOR YOUR SAFETY What to do if you smell gas:
Do not try to light any applianceDo not touch any electrical switch:
do not use any phone in your building.
Immediately call your gas supplier
from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
07/05/06
To the New Owner:
Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The P40 has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch. The model P40 has been approved by Warnock Hersey for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint
yourself with these instructions and the many features of your Regency
MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
This Regency® product has been tested and listed by Warnock Hersey as a Vented Gas Fireplace Heater to the following standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88-2005/CSA 2.33-2005 and GAS-FIRED APPLIANCES FOR USE AT HIGH ALTITUDES CAN/CGA 2.17-M91.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada.
®
Fireplace.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.
This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as applicable to local codes.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home, where not prohibited by local codes.
This appliance can only be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used. (Kit# 502-969)
Ensure that structural members are not cut or weakened during installation.
2
Regency® P40 Direct Vent Gas Fireplace
TABLE OF CONTENTS
SAFETY LABEL
Copy of Safety Label .....................................................4
REQUIREMENTS
MA Code - CO Detector
(for state of Massachusetts only) ..................................5
UNIT DIMENSIONS
Dimensions ....................................................................6
INSTALLATION
Important Message ......................................................7
Before You Start ............................................................7
General Safety Information ...........................................7
Installation Checklist ......................................................7
Manufactured Mobile Home Additional Requirements ..8
Locating Your Gas Fireplace .........................................8
Heatwave Duct Kit ........................................................8
Heat Release Kit ..........................................................8
Hearth Requirements ....................................................8
Clearances ....................................................................9
Mantel Clearances ......................................................10
Mantel Leg Clearances ...............................................10
Framing & Finishing .................................................... 11
Unit Assembly Prior To Installation ..............................12
Top Standoff Assembly ........................................ 12
Top Facing Support and Side Nailing Strips ........12
Venting Introduction .....................................................12
Vent Restrictor Position ...............................................12
Exterior Vent Termination Requirements .....................13
Venting Arrangements ................................................14
Horizontal Termination (Flex) ...............................14
Rigid Pipe Venting Systems ........................................15
Basic Horizontal & Vertical Terminations ............. 15
Rigid Pipe Venting Components List ...........................16
Venting Arrangements ................................................17
Allowable Horizontal Terminations .......................17
Venting Arrangements ................................................20
Allowable Vertical Terminations ........................... 20
Unit Installation with Horizontal Termination ................21
Unit Installation with Vertical Termination .................... 22
Horizontal Termination with Flex Vent System ............23
P40-NG System Data .................................................24
P40-LP System Data ..................................................24
High Elevation .............................................................24
Gas Line Installation ....................................................24
Pilot Adjustment ...........................................................24
Gas Pipe Pressure Testing ..........................................25
SIT Valve Description ..................................................25
Back-Up Battery Installation ........................................25
Conversion Kit #502-969 from NG to LP .....................26
Brick Panel Installation ................................................28
Log Set Installation ......................................................29
Aeration Adjustment ....................................................32
Standard Flush Door ...................................................32
Flush Louvers ..............................................................32
Finishing Trim .............................................................. 33
Wiring Diagram ...........................................................33
OPERATING INSTRUCTIONS
Operating Instructions .................................................34
Shutdown Procedure ...................................................34
First Fire ......................................................................34
Lighting Procedure ......................................................34
Operation During Power Outage .................................35
Summary Of Controls .................................................35
FireWizardTM Remote Control Functions ....................35
Normal Operating Sounds of Gas Appliances .............36
Copy of Lighting Plate Instructions ..............................36
MAINTENANCE
Maintenance Instructions ............................................37
General Vent Maintenance ..........................................37
Log Replacement ........................................................37
Thermopile / Thermocouple .........................................37
Glass Gasket ...............................................................37
Louvers ........................................................................37
Door Glass ..................................................................38
Glass Replacement .............................................38
Fan Replacement ........................................................38
Valve Replacement ......................................................39
DC Sparker Replacement ...........................................40
Power Module Replacement .......................................41
Control Module Replacement ......................................41
Backup Battery Replacement ......................................41
PARTS LIST
Main Assembly ............................................................42
Valve Tray Assembly ...................................................43
Flush Door & Louvers ..................................................44
WARRANTY
The Warranty: Limited Lifetime ...................................47
Regency® P40 Direct Vent Gas Fireplace 3
SAFETY LABEL
This is a copy of the label that accompanies each P40-NG and P40-LP Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review.
®
NOTE: Regency improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
units are constantly being
INSTALLATION
Copy of Safety Label
For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, fl exible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appli­ances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.
4
Regency® P40 Direct Vent Gas Fireplace
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
INSTALLATION
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
Regency® P40 Direct Vent Gas Fireplace 5
INSTALLATION
UNIT DIMENSIONS
Dimensions
6
Regency® P40 Direct Vent Gas Fireplace
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The P40 Direct Vent Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual fi rst. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fi replace is installed in compliance with manufacturers instructions and all applicable codes.
BEFORE YOU START
Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPE­CIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform
with local codes or, in the absence of local codes, with the current Canadian or National Gas Codes, CAN1-B149 or ANSI Z223.1 Installation Codes.
2) The appliance when installed, must be
electrically grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Canadian Electrical Code.
3) See general construction and assembly
instructions. The appliance and vent should be enclosed.
4) This appliance must be connected to the
specifi ed vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fi tted as per Venting instructions.
5) Inspect the venting system annually for
blockage and any signs of deterioration.
6) Venting terminals shall not be recessed into
a wall or siding.
7) Any safety glass removed for servicing
must be replaced prior to operating the appliance.
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the fi replace.
9) Wear gloves and safety glasses for protection
while doing required maintenance.
10) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for termination.
11) Under no circumstances should this
appliance be modifi ed. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
12) Installation and any repairs to this appliance
should be done by an authorized service person. A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.
15) The appliance area must be kept clear and
free of combustible materials, (gases and other fl ammable vapours and liquids).
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
INSTALLATION
CHECKLIST
1) Locate appliance
a) Room location (Refer to "Locating Your
Gas fi replace" section)
b) Clearances to Combustibles (Refer to
"Clearances" section)
c) Mantle Clearances (Refer to "Mantel
Clearances" section)
d) Framing & Finishing Requirements
(Refer to "Framing & Finishing" section)
e) Venting Requirements (Refer to
"Venting" section)
2) Assemble Top Standoffs and Top Facing
Support and Side Nailing Strips (Refer to "Unit Assembly Prior to Installation). NOTE: Must be done before installing unit into place.
3) Install vent (Refer to "Venting Arrangement"
sections).
4) Back-up battery installation. Refer to "Back-
up Battery Installation" section.
5) Make gas and electrical connections. Test
the pilot. Must be as per diagram (Refer to "Pilot Adjustment " section).
Convert to propane if desired (Refer to
"Conversion from NG to LP" section).
6) Test Gas Pressure. (Refer to "Gas Pipe
Pressure Testing" section).
INSTALLATION
Regency® P40 Direct Vent Gas Fireplace 7
INSTALLATION
7) Install standard and optional features. Refer
to the following sections:
a) Brick Panels b) Log Set c) Standard Flush Door d) Flush Louvers e) Finishing trim f) Remote Control
8) Final check.
INSTALLATION
Before leaving this unit with the customer, the installer must ensure that the appliance is fi ring correctly and operation fully explained to
customer.
This includes:
1) Clocking the appliance to ensure the correct
fi ring rate (rate noted on label 45,000 (NG) Btu/h, 43,000 (LP) Btu/h) after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
Diagram 1
A) Flat on Wall B) Flat on Wall Corner C) Recessed into
Wall/Alcove
D) Corner
4) This appliance is Listed for bedroom
installations when used with the FireWizard (millivolt thermostat system). Some areas may have further requirements, check local codes before installation.
5) The P40 Direct Vent Gas Fireplace is
approved for alcove installations, see "Clearances" section for details.
6) We recommend that you plan your installation
on paper using exact measurements for clearances and fl oor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation.
Note: For vent terminations see "Exterior
Vent Termination Locations" section.
HEAT RELEASE KIT
The Heat Release Kit expels warm air from the fi replace to the outside of the building, allowing the fi replace to be operated with less heat entering the room. The kit may be used on either the left or right side.
See Heat Release installation manual for complete details and clearances from side only.
HEARTH
REQUIREMENTS
A 40" (1016mm) wide x 16" (406mm) deep x 1-1/2" (38mm) thick hearth is required, unless the unit is raised 4" (102mm).
Floor Mounted Fireplace
2) Ensure proper grounding using the #8
ground lug provided. See "Wiring Diagram" section.
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your fi replace,
ensure that the clearances are met.
2) The appliance must be installed on a fl at,
solid, continuous surface (e.g. wood, metal, concrete). This may be the fl oor, or raised up on a platform to enhance its visual impact. The appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
3) The P40 Direct Vent Gas Fireplace can be
installed in a recessed position or framed out into the room as in A, B, C, D. See Diagram 1.
8
HEATWAVE
DUCT KIT
The HeatWave Air Duct Kit increases the effectiveness of your fi replace by dispersing warm air from the fi replace to remote locations in the same room or other rooms in your home.
Up to two kits may be installed on the fi replace. Please Note: Only 1 HeatWave kit may be operated at one time. This includes the internal blower option as well.
See HeatWave installation manual for complete details and clearances from side only.
The HeatWave Duct Kit has different clearance and framing requirements, check the HeatWave manual for details.
Raised Fireplace
Regency® P40 Direct Vent Gas Fireplace
CLEARANCES
INSTALLATION
The clearances listed below are minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fi replace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fi replace are defi ned by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
Clearance to Combustibles from:
Back 0" (0mm) Side 0" (0mm) Floor 0"* (0mm)
* Note: A hearth is required, unless the unit is raised
4" (102mm), see "Hearth Requirements" section for details.
Minimum Clearance from Top of Louver Opening:
Mantel Height min. 12" (305mm) (at 1" mantel depth) Ceiling 39" (990mm)
Side Wall to Unit:
8" (203mm)
Horizontal Vent Clearances to Combustibles:
Top 2-1/2" (64mm) Side 1-1/2" (38mm) Bottom 1-1/2" (38mm)
INSTALLATION
Vertical Vent Clearances to Combustibles:
All Sides 1-1/4" (32mm)
Alcove Clearances:
Max. Depth 36" (914mm) Min. Width 56" (1422mm) Min. Height 72" (1829mm)
if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this
fi replace and vent system be installed only in
Fire hazard is an extreme risk
WARNING
accordance with these instructions.
Regency® P40 Direct Vent Gas Fireplace 9
INSTALLATION
MANTEL CLEARANCES
Because of the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from top of louver opening
are shown in the diagram below.
Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible
board.
INSTALLATION
This drawing is to scale at 1:6 (one inch = 6 inches)
Mantel can be installed anywhere in shaded area using the above scale.
Note: Ensure the paint that is used
on the mantel and the facing is "heat resistant" or the paint may discolour.
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram:
10
Maximum 1-1/2" projection at 2" minimum clearance.
Regency® P40 Direct Vent Gas Fireplace
FRAMING & FINISHING
1) Frame in the enclosure for the unit with framing material. The framed
opening for the assembled kit is 42-1/2" high x 40-1/2" wide x 20-1/16" deep (1080mm H x 1029mm W x 508mm D), see Diagram 1. Also see Diagram 2 for corner installations.
Note: Height is from the base of the unit. Take into consideration
the hearth height and material.
Height = 42-1/2" plus height of hearth.
INSTALLATION
INSTALLATION
Diagram 1
Diagram 2
Diagram 3
Note: When constructing the framed opening, please ensure there
is access to install the gas lines when the unit is installed. See diagram 3 for details.
2) For exterior walls, insulate the enclosure to the same degree as
the rest of the house, apply vapour barrier and drywall, as per local
installation codes. (Do not insulate the fi replace itself.)
3) The unit does not have to be completely enclosed in a chase. A non-
combustible header must be used. You must maintain clearances
from the vent to combustible materials: See "Clearances" section.
Combustible materials can be laid against the side and back standoffs
and the stove base.
The HeatWave Duct Kit has different clearance and framing requirements, check the HeatWave manual for details.
Regency® P40 Direct Vent Gas Fireplace 11
INSTALLATION
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
NOTE: The Top Facing Support, the Side Nailing
Strips and the 2 Top Standoffs must be correctly positioned and attached before unit is slipped into position.
INSTALLATION
TOP STANDOFF ASSEMBLY
The top standoffs are shipped in a fl at position and must be folded into shape and attached.
1) Remove the standoffs from top of the fi replace.
2) Take each standoff and bend into the correct shape. Bend up at the bend lines until the screw holes in the standoff and the pre­punched screw holes on the fi replace top line up.
3) Attach the standoff securely to the top with 2 screws per standoff (on opposite corners).
Note: For screw position C with a facing material depth of 1-1/4" (32mm), the top facing support must be reversed.
Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.
VENT RESTRICTOR
POSITION
Vent restriction is required for certain venting installations, see the diagrams in the "Venting Arrangements" section to determine if they are required for your installation.
To set the Vent restriction as indicated in the diagrams in the "Venting Arrangements" section, refer to the instructions below;
1) Remove the top louver if installed.
2) Loosen the screw on the vent restrictor
indicating plate.
3) Rotate the vent restrictor adjustment rod
counter clockwise to line up the slot on the indicating plate with the point on the air box to the required setting.
4) Tighten screw to lock position.
Screw
TOP FACING SUPPORT AND
SIDE NAILING STRIPS
Determine the total thickness of facing material to allow the fi nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2" (13mm) to 1-1/4" (32mm) thick.
The Top Facing Support & Side Nailing Strips can be mounted in 3 different positions depending on the thickness of the facing material.
Screw
Facing Material Depth
Position
A 1/2" / 13mm
B 7/8" / 22mm
C* 1-1/4" / 32mm
* For "C" screw position the top facing support is reversed.
1) Mount Top Facing Support using the 3
supplied screws into the three pre-punched screw holes on the top front of the unit. Use hole positions A, B, or C depending on your facing depth.
12
2) Use the same screw hole position for the
Side Nailing Strips as was used for the Top Facing Support. Attach each side nailing strip using 3 screws.
Note: When installing side strips into position C, the side strips are not reserved.
VENTING
INTRODUCTION
The P40 uses the "balanced fl ue" technology Co Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These flue pipes must not be
connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance.
Point on AirBox
Factory Set Vent Restrictor Setting
(no adjustment required)
Point on AirBox
Vent Restrictor setting at Set 1
Point on AirBox
Vent Restrictor setting at Set 2
Regency® P40 Direct Vent Gas Fireplace
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
INSTALLATION
from the centerline of the regulator.
any other appliance *(12"/30cm) #(9"/23cm)
H= Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally
J= Clearance to service regulator vent outlet *(min. 36"/90cm)
K= Clearance to non-mechanical air supply inlet to building or the combustion air inlet to
*(min. 84"/2.1m)
L= Clearance to a mechanical air supply inlet *(6'/1.83m)
#3' (91cm) above if within 10' (3m) horizontally.
M= Clearance above paved sidewalk or a paved driveway located on public property
N= Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)
distance of (24"/60cm) from the centerline of the terminal (min. 23") check with local
code.
A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm)
B= Clearance to window or door that may be opened *(12"/30cm) #(9"/23cm)
C= Clearance to permanently closed window *#(min. 12"/30cm)
D= Vertical clearance to ventilated soffi t located above the terminal within a horizontal
E= Clearance to unventilated soffi t (min. 15"/38cm)
F= Clearance to outside corner: 13"
G= Clearance to inside corner: 13"
Regency® P40 Direct Vent Gas Fireplace 13
Note:
- Excluding direct vent or non-condensing appliances, a vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family
dwellings and serves both dwellings.
- Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
- If the vent termination is accessible, a certifi ed guard shall be installed.
* (Canada) As specifi ed in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.
# (US) In accordance with the current ANSI Z223.1/NFPA 54, Natioinal Fuel Gas Code.
INSTALLATION
VENTING ARRANGEMENTS
HORIZONTAL TERMINATION (FLEX)
Regency® Direct Vent System
These venting systems, in combination with the P40 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination Requirements" section.
INSTALLATION
Regency® Direct Vent (Flex) System Termination Kit (Part# 946-615) includes all the parts needed to install the P40 with a maximum run of 4 feet.
1) 8" dia. fl exible liner (4 ft. length)
2) 5" dia. fl exible liner (4 ft. length)
3) spring spacers (4)
4) thimble
5) AstroCap XL termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point,
Stainless Steel (4)
10) vinyl siding standoff
If longer runs are needed, the Regency® Direct Vent system (Flex) Part# 946-616 includes all the parts needed to install the P40 with a maximum 10' run.
1) 8" dia. fl exible liner (10 ft. length)
2) 5" dia. fl exible liner (10 ft. length)
3) spring spacers (7)
4) thimble (2)
5) AstroCap XL termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point,
Stainless Steel (4)
10) vinyl siding standoff
Wall Thimble
(required in Canada only)
5” dia. flue pipe
8" dia.
Flue pipe
AstroCap XL
(Part# 946-623/P)
Vinyl Siding
Standoff
spring spacer
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from FPI may be used for Flex installations.
3) Horizontal vent must be supported every 3 feet. (For 10' fl ex kit 946-616 only.)
14
Regency® P40 Direct Vent Gas Fireplace
RIGID PIPE VENTING SYSTEMS
INSTALLATION
BASIC HORIZONTAL & VERTICAL TERMINATIONS
Rigid Pipe Vent Systems offer a complete line of component parts for installation of both horizontal and vertical installations. Many items are offered in decorative black, as well as galvanized fi nish.
The minimum components required for a basic horizontal termination are:
1 Horizontal Termination Cap 1 90 1 Rigid Pipe Adaptor 1 Wall Thimble (Canada only) 1 Length of pipe to suit wall thickness
The minimum components required for a basic vertical termination are:
1 Vertical Termination Cap 1 Rigid Pipe Adaptor 1 Lengths of pipe to adequately penetrate roof 1 Ceiling Firestop 1 Flashing 1 Storm Collar
Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap. For siding other than vinyl furring strips may be used, instead of the vinyl siding standoff, to create a level surface to mount the vent terminal. The Terminal must not be recessed into siding. Measure the wall thickness including furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add 2 inches.
o
Elbow
Ceiling Firestop
Vertical
Terminal
Storm Collar
Flashing
Pipe Length
Adj.Pipe Length
11" - 14-5/8"
o
90 Elbow
24" Pipe
Length
Rigid Pipe Adapter
(770-994)
Vinyl Siding
Standoff
AstroCap XL
Termination Cap
(946-623/P)
Wall Thimble
(required in Canada only)
Alternate
Horizontal Termination
Caps
INSTALLATION
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
The FPI AstroCap XL AstroCap XLTM is a proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
Regency® P40 Direct Vent Gas Fireplace 15
TM
is certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent GS and Selkirk Direct-Temp.
WARNING:
Do not combine venting components from different venting systems.
TM
Use of the the AstroCap XL acceptable with all systems.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with Duravent Direct-Vent GS and Selkirk Direct­Temp systems. Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Intertek WHI listing of components.
and FPI Riser is