Regency P33S-NG4, P33S-LP4 User Manual

Regency P33 Sunrise
Owners &
Installation Manual
Gas Fireplace
MODEL: P33S-NG4 Natural Gas
P33S-LP4 Propane
WARNING: If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
918-757
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
www.regency-fi re.com
FOR YOUR SAFETY What to do if you smell gas:
Do not try to light any appliance Do not touch any electrical switch:
do not use any phone in your building.
Immediately call your gas supplier
from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
11/05/08
To the New Owner:
Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The P33 Sunrise™ has been designed to provide you with all the warmth and charm of a fi re at the fl ick of a switch. The model P33 Sunrise™ has been approved by Warnock Hersey for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint
yourself with these instructions and the many features of your Regency
MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
This Regency® product has been tested and listed by Warnock Hersey as a Direct Vent Wall Furnace to the following standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88a-2007 / CSA 2.33a-2007 and GAS-FIRED APPLIANCES FOR USE AT HIGH ALTITUDES CAN / CGA 2.17-M91.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada.
®
Fireplace.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.
This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as applicable to local codes.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home, where not prohibited by local codes.
This appliance can only be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used. (Kit # 434-970)
Ensure that structural members are not cut or weakened during installation.
2
Regency P33 SunriseTM Gas Fireplace
TABLE OF CONTENTS
SAFETY LABEL
Copy of Safety Decal .....................................................4
REQUIREMENTS
MA Code - CO Detector.................................................5
DIMENSIONS
Unit Dimensions ............................................................6
INSTALLATION
Important Message ......................................................7
Before You Start ............................................................7
General Safety Information............................................7
Installation Checklist ......................................................8
Locating Your Gas Fireplace .........................................8
Clearances ....................................................................9
Mantel Clearances.......................................................10
Mantel Leg Clearances................................................10
Framing & Finishing..................................................... 11
Framing Dimensions....................................................12
Unit Assembly Prior to Installation ...............................13
Venting Introduction .....................................................13
Exterior Vent Termination Requirements ..................... 14
Regency® Direct Vent fl ex System .............................. 15
Rigid Pipe Venting Systems ........................................16
4" X 6-5/8" Rigid Pipe Cross Reference Chart ............17
Rigid Pipe Venting Arrangements ............................... 19
Vertical Termination with Co-Linear Flex System .......20
Venting Arrangements - Vertical Terminations ............ 21
Unit installation with Horizontal termination .................26
Unit installation with Vertical Termination ....................27
Gas Line Installation .................................................... 27
Pilot Adjustment ........................................................... 28
High Elevation .............................................................28
S.I.T. Valve Description ................................................28
Gas Pipe Pressure Testing ..........................................28
Conversion from NG to LP ..........................................29
DC Spark Box Battery Replacement ..........................31
DC Spark Box Replacement........................................31
Optional Wall Thermostat ........................................... 32
Optional Remote Control ............................................. 32
Wall Switch .................................................................. 32
Aeration Adjustment ....................................................33
Wiring Diagram ...........................................................33
Installing the Optional Fan ...........................................34
Optional Stainless Steel Panel Installation .................. 35
Glass Crystal Installation On Burner ...........................36
Optional Pebble Installation .........................................36
Glass Door installation.................................................37
Flush Door Installation .................................................37
Faceplate Installation...................................................38
OPERATING INSTRUCTIONS
Operating Instructions .................................................40
First Fire ......................................................................40
Lighting Procedure ......................................................40
Shutdown Procedure ................................................... 40
Normal Operating Sounds of Gas Appliances .............40
Copy of Lighting Plate Instructions .............................. 41
MAINTENANCE
Maintenance Instructions.............................................42
General Vent Maintenance ..........................................42
Thermopile / Thermocouple .........................................42
Glass Door...................................................................42
Glass Replacement .....................................................42
Valve Tray Replacement .............................................. 43
Removing Valve ........................................................... 43
Installing Valve ............................................................. 43
PARTS LIST
Main Assembly ............................................................44
WARRANTY
The Warranty: Limited Lifetime ...................................47
Regency P33 SunriseTM Gas Fireplace 3
SAFETY LABEL
This is a copy of the label that accompanies each P33 Sunrise™ Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review.
NOTE: Regency improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
INSTALLATION
®
units are constantly being
343
Serial No./ No de serie
343
0" Clearance to
Ceiling
Minimum Clearances to Combustibles
Degagement Minimum De Materiaux Combustibles
combustibles from:
Top, sides, bottom and rear of unit
Wall
Ceiling Clearances from
Wall
Top of Unit:
(A) 30" (762mm)
Side Wall Clearance from
Side of Unit:
B) 7.5"(190mm)
E
Floor Clearance:
C) 12”(305mm)
Alcove Clearances
C
)
D) Max. Depth 36" (914mm)
E Min. Width 48" (1219mm)
(See Instruction Manual for Detailed Instructions)
the door is properly sealed
DOOR SEAL: Please check that
Delta, BC, Canada
FPI Fireplace Products International Ltd.
918-761
Made in Canada/
Fabrique au Canada
For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, fl exible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appli­ances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.
COPY OF SAFETY DECAL
Duplicate S/N
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE
CANADA and U.S.A.é
CAN/CGA-2.17-M91,
ANSI Z21.88a-2007/CSA 2.33a-2007.
VENTED GAS FIREPLACE HEATER
Listed:
Certified for/Certifi e pour:
Tested to:
WN# 16073
APPAREIL FONCTIONNANT AU NATURAL GAS
NATURAL GAS: Model P33S-NG4
MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE.
Modéle P33S-NG4
ééé
é
CONCU POUR ETRE POELE:
Pression d'allimentation minimum
Pression a la tubulure d' chappement lev e
Pression a la tubulure d' chappement basse
5" WC (1.25 kPa)
3.5" WC (0.87 kPa)
Minimum supply pressure
Manifold pressure high
Model/Modele: P33S-NG4
é
Grandeur de l'injecteur
D bit Califorique minimum selon
1.6" WC (0.39 kPa)
# 47 DMS
12,000 Btu/h (3.51 kW)
Manifold pressure low
Orifice size
é D bit Caliorfique maximum selon
17,000 Btu/h (4.98 kW)
Minimum input
Maximum input
l'altitude
0-4500 ft/pi (0-1372 m)
Altitude
Modéle P33S-LP4
ééé
APPAREIL FONCTIONNANT AU PROPANE
CONCU POUR ETRE POELE:
Pression d'allimentation minimum
Pression a la tubulure d' chappement lev e
11" WC (2.73 kPa)
10" WC (2.49 kPa)
Minimum supply pressure
Manifold pressure high
PROPANE: Model P33S-LP4
Model/Modele: P33S-LP4
é
Pression a la tubulure d' chappement basse
Grandeur de l'injecteur
6.4" WC (1.59 kPa)
# 56 DMS
Manifold pressure low
Orifice size
é
é
D bit Califorique minimum selon
D bit Caliorfique maximum selon
12,000 Btu/h (3.51 kW)
15,500 Btu/h (4.54 kW)
Minimum input
Maximum input
l'altitude
0-4500 ft/pi (0-1372 m)
Altitude
the manufacturer's installation instructions and Manufactured Home Construction and Safety Standard Title 24 CFR, Part 3280, or the current Standard
VENTING: Use listed Direct Vent Pro and others as listed in the manual or Regency Direct Vent System. Only for direct discharge without duct connection. This appliance
must be installed in accordance with the manufacturer's installation instructions and with local codes, if any; if not, follow the current ANSI Z223.1inthe
USA or the current CAN 1-B149 in Canada. For Manufactured Home Installation: This Direct Vent System Appliance must be installed in accordance with
Not for use with solid fuel.
Electrical supply 115VAC, 1.13 A, 60Hz.
for Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240 MH Mobile Home
Standard in Canada Certified for use with Heat Wave (Kit # 946-556).
Fan (Part # 432-917) This vented gas fireplace heater is not for use with air filters.
4
Regency P33 SunriseTM Gas Fireplace
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
INSTALLATION
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
Regency P33 SunriseTM Gas Fireplace 5
DIMENSIONS
INSTALLATION
UNIT DIMENSIONS
6
Regency P33 SunriseTM Gas Fireplace
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The P33 Sunrise™ Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual fi rst. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fi replace is installed in compliance with manufacturers instructions and all applicable codes.
BEFORE YOU START
Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform
with local codes or, in the absence of local codes, with the current Canadian or National Gas Codes, CAN1-B149 or ANSI Z223.1 Installation Codes.
2) The appliance when installed, must be elec-
trically grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/ NFPA 70 or CSA C22.1 Canadian Electrical Code.
3) See general construction and assembly
instructions. The appliance and vent should be enclosed.
4) This appliance must be connected to the
specifi ed vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fi tted as per Venting instructions.
5) Inspect the venting system annually for
blockage and any signs of deterioration.
6) Venting terminals shall not be recessed into
a wall or siding.
7) Any safety glass removed for servicing
must be replaced prior to operating the ap­pliance.
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the replace.
be removed for servicing should be replaced prior to operating this appliance.
12) Installation and any repairs to this appliance
should be done by an authorized service person. A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.
15) The appliance area must be kept clear and
free of combustible materials, (gases and other fl ammable vapours and liquids).
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
INSTALLATION
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPE­CIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
Regency P33 SunriseTM Gas Fireplace 7
9) Wear gloves and safety glasses for protection
while doing required maintenance.
10) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for termination.
11) Under no circumstances should this
appliance be modifi ed. Parts that have to
INSTALLATION
INSTALLATION
CHECKLIST
1) Locate appliance
a) Room location (Refer to "Locating Your
Gas fi replace" section)
b) Clearances to Combustibles (Refer to
"Clearances" section)
c) Mantle Clearances (Refer to "Mantel
Clearances" section)
d) Framing & Finishing Requirements (Refer
INSTALLATION
to "Framing & Finishing" section)
e ) Venting Requirements (Refer to "Venting"
section)
2) Assemble Top and Side Standoffs (Refer to
"Unit Assembly Prior to Installation).
3) Slide unit into place.
4) Install vent (Refer to "Venting Arrangement"
sections).
5) Make gas connections (Refer to "Gas Line
Installation section).
6) Test the pilot (Refer to "Pilot Adjustment"
section).
7) Test Gas Pressure (Refer to "Gas Pipe Pres-
sure Testing" section).
8) Install 1 AA battery in the DC Sparker (see P 31.)
This includes:
1) Clocking the appliance to ensure the correct
ring rate (rate noted on label), after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your replace,
ensure that the clearances are met.
2) The appliance must be installed on a fl at,
solid, continuous surface For example a wood, metal or concrete fl oor or in a raised (on the wall) application. The appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
3) The P33 Sunrise™ Gas Fireplace can be
installed in a recessed position or framed out into the room as in A, B, C and D. See Diagram 1.
4) This appliance is Listed for bedroom
installations when used with a listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
5) The P33 Sunrise™ Gas Fireplace is approved
for alcove installations, see "Clearances" section for details.
6) We recommend that you plan your installation
on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation.
Note: For vent terminations refer to
"Exterior Vent Termination Locations" section.
9) Install standard and optional features. Refer
to the following sections:
a) Optional Stainless Steel Refl ective
Panels b) Glass Crystals or Optional Ceramic Stones c) Optional Firebox Base Pebbles d) Remote Control or Wall Thermostat
e) Optional Fan Assembly f) Faceplate
10) Wall Mounted ON/OFF Switch: Use the toggle wall switch supplied with the
manual package. Use of a “decor” switch
causes higher resistance which is a problem
on gas fi replaces.
11) Final check.
Diagram 1
A) Flat on Wall B) Flat on Wall Corner C) Recessed into Wall/Alcove D) Corner
8
Regency P33 SunriseTM Gas Fireplace
CLEARANCES
INSTALLATION
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fi replace and vent system be installed only in accordance with these instructions.
The top, back and sides of the fi replace are defi ned by
Caution Requirements
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
C
if these clearances (air space) to combustible materials are not
Fire hazard is an extreme risk
adhered to. It is of greatest importance that this fi replace and vent
system be installed only in accordance with these instructions.
C
WARNING
B
INSTALLATION
Close to Ceiling
Clearance: Dimension Measured From:
A: *Front Floor Clearance (min.) 12" (304mm) Underside of Unit
B: *Sidewall (on one side) 7-1/2" (241mm) Side of Unit
C: *Ceiling (room and/or alcove)
D: Alcove Width 48" (1219mm) Sidewall to Sidewall (Minimum)
E: Alcove Depth 36" (914mm) Front to Back Wall (Maximum)
*Note: All measurements are from the top/side of the unit, not optional front.
Regency P33 SunriseTM Gas Fireplace 9
30" (889mm) Top of Unit
Horizontal - Top 2-1/2" Horiztonal - Side 1-1/2"
Horiztonal - Bottom 1-1/2"
Vertical (Flex Vent) 1-1/2"
Vertical (Rigid) 1-1/4"
Flue Clearances
INSTALLATION
MANTEL CLEARANCES
Due to the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel
clearances from top of front facing are shown in the diagram on the right.
Note: A non-combustible mantel may be
installed at a lower height if the framing is made of metal studs covered with a
INSTALLATION
non-combustible board.
Note: Ensure the paint that is used on the mantel
and the facing is "heat resistant" or the paint may discolour.
12
10
8
6
4
2
0
12
11"(279mm)
41"(1041mm)
or 29”(737mm)
to base of unit
Mantel Clearances
6
810
12" (305mm)
9"(229mm)
to floor
4
7-1/2"(191mm)
0” - 3-1/2" (89mm)
7"(178mm)
To p o f Unit
2
0
Drywall
Standoff
3"(76mm)
Side View
MANTEL LEG CLEARANCES
Combustible mantel leg clearances from side of unit as per diagram:
10
Regency P33 SunriseTM Gas Fireplace
FRAMING & FINISHING
INSTALLATION
1) Determine the total thickness of facing material (e.g. drywall, wood
plus ceramic tiles) to allow the fi nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2" (13mm) to 1-1/4" (32mm) thick.
NOTE: Facing material may not protrude beyond unit, otherwise the
optional accesories will not be able to be mounted to the unit.
Install Side Nailing Strips, and Top Facing Support before unit is slipped into position. See "Unit Assembly Prior to Installation" Section
Wood,
2) Frame in the enclosure for the unit with framing material. The top of the glass door frame must not be closer than 35" (889mm)
to the ceiling.
4) Combustible material may be brought up to the top and sides of
INSTALLATION
the unit and be covered with wood, drywall, ceramic tiles, bricks, rock or other suitable combustible fi nishing materials.
Note: The unit does not have to be completely enclosed in a chase.
The clearance on top of the unit is 0" to the standoffs so combustible building materials can be laid directly on top of the standoffs. You must maintain clearance from the vent to combustible materials for fl ex or for Rigid Vent (Refer to "Clearances" Section).
5) Use steel studs for framing where the 1-1/2" (38mm) clearance
from the vent to combustible material cannot be maintained.
The HeatWave Duct Kit has different clearance and framing requirements, check the HeatWave manual for details.
Note: When constructing the framed opening, please ensure there
is access to install the gas lines when the unit is installed.
3) For exterior walls, insulate the enclosure to the same degree as the
rest of the house, apply vapour barrier and drywall, as per local instal­lation codes. (Do not insulate the replace itself.)
WARNING: Failure to insulate and add vapor barriers to the inside
of the exterior wall will result in operational and performance problems including, but not limited to: excessive condensation on glass doors, poor fl ame package, carbon, blue fl ames etc. These are not product related issues.
Regency P33 SunriseTM Gas Fireplace 11
INSTALLATION
FRAMING DIMENSIONS
M
INSTALLATION
H
I
NOTE: If this is an outside corner, the
minimum distance between the vent and the outside corner is 6" (15cm) with AstroCap termination cap or 12" (30cm) with Rigid Vent termination cap.
(For example Dura-Vent)
G
K
I
Wood, drywall
or other facing
J
O
Top Header
.
10" (254mm)
dia. Hole through
wall Vent.
N
J
Floor
I
12
P
L
Framing Dimensions Description P33S
G Framing Width 33-1/4"(845mm)
H Framing Height * 31-3/4" (806mm)
I Framing Rise from Floor 12" (305mm) Min.
J Framing Depth Horizontal
K Corner Wall Length 37-1/2" (953mm)
L Corner Facing Wall Width 53-1/4" (1353mm)
M Framed Chase Ceiling* 36" (914mm) Rigid 32" (812mm) Flex
N
O
P Gas Connection Inset* 4" (102mm)
Q Gas Connection Width* 3" (76mm)
R Minimum Framing Depth 16 1/2 (419mm) Rigid 12-3/4" (324mm) Flex
* Measured from base of unit.
Vertical
Vent Centerline Height* 30" (762mm) Rigid 26" (660mm) Flex
Gas Connection Height* 1 1/2" (38mm)
19-1/2" (495mm) Vertical Rise
16-1/2" (419mm) Rigid / 12-3/4" (324mm) Flex
Opening for gas
Q
connection
Regency P33 SunriseTM Gas Fireplace
INSTALLATION
UNIT ASSEMBLY PRIOR TO INSTALLATION
The Top Facing Support, the Side Nailing Strips and the 2 Top Standoffs must be correctly positioned and attached to the top before the unit is put into position.
Top Standoff Assembly
The top standoffs are shipped in a fl at position and must be pulled up and bent into the correct shape.
1) Remove the standoffs from on top of the
rebox by undoing the screws.
2) Take each standoff and bend into the correct
shape. Bend up at the bend lines until the screw holes in the standoff and the pre­punched screw holes on the fi rebox top line-up.
3) Attach the standoffs securely to the top with
4 screws per standoff.
Note: Secure the standoffs to the holes
closest to the edge of the fi rebox top.
Top Standoff
after bending
Top Standoff (flat shipping
position)
Top Facing Support &
Side Nailing Strips
Determine the total thickness of facing material (e.g. drywall, wood plus ceramic tiles) to allow the fi nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2" (13mm) to 1-1/4" (32mm) thick.
The Top Facing Support & Side Nailing Strips can be mounted in various positions depending on the thickness of the facing material.
1) Mount Top Facing Support using the 3
supplied screws into the three pre-punched screw holes on the top front of the unit. Adjust support to desired facing material depth.
2) Mount Side Nailing Strip using the 3
supplied screws into the three pre-punched screw holes at the front sides of the unit. Adjust support to desired facing material thickness.
Top Facing
Support
For a facing material depth of 1-1/4"(32mm), the top facing support must be reversed.
Side
Nailing
Strip
INSTALLATION
After
Before
Bend
here
VENTING INTRODUCTION
The P33 Sunrise™ uses the "balanced fl ue" technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
There are 5 vent systems approved for use with the P33S: the Regency® Direct Vent Flex System for Horizontal Terminations only and the Simpson Dura-Vent, Selkirk Direct-Temp, Amerivent Direct Vent and Security Secure Vent Systems for Horizontal and Vertical Terminations (see following "Venting" Sections for more details).
Note: These fl ue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited. (See "Rigid Pipe Venting System" for more details and exceptions).
NOTE: Ensure compliance with the outside vent terminal location before cutting hole as both dimensions must be met.
Regency P33 SunriseTM Gas Fireplace 13
INSTALLATION
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm) B= Clearance to window or door that may be opened *(12"/30cm) #(9"/23cm) C= Clearance to permanently closed window *(min. 12"/30cm) D= Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of (24"/60cm) from the centerline of the terminal
(min. 18"/46cm) check with local code.
E= Clearance to unventilated soffi t (min. 15"/38cm) F= Clearance to outside corner: with AstroCap Termination Cap (min. 6"/15cm), with all other approved Caps (12"/30cm) G= Clearance to inside corner: with AstroCap Termination Cap (min. 6"/15cm), with all other approved Caps (12"/30cm) H= Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally from the centerline of the regulator. J= Clearance to service regulator vent outlet *(min. 36"/90cm) K= Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance *(12"/30cm) #(9"/23cm) L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m) #3' (91cm) above if within 10' (3m) horizontally. M= Clearance above paved sidewalk or a paved driveway located on public property *(min. 84"/2.1m) N= Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)
Note:
- A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
- Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
- If the vent termination is accessible, a certifi ed guard shall be installed. * As specifi ed in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances. # In accordance with the current ANSI Z223.1/NFPA 54, Natioinal Fuel Gas Code.
14
Regency P33 SunriseTM Gas Fireplace
INSTALLATION
REGENCY® DIRECT VENT FLEX SYSTEM
Horizontal Terminations Only
This venting system, in combination with the P33S-4 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the "Exterior Vent Terminal Locations" Section .
Regency® Direct Vent Flex Termination Kit (Part # 946-513) includes all the parts needed to install the P33S-4 with a maximum run of 2 feet. If installing the P33S-4 with a continuous vent length of more than 2 ft (.6m) to a maximum of 10 ft. (3.0m) use Kit # 946-515 (4 ft) or 946-
516 (10 ft) or see "Rigid Pipe Venting Systems" Section for alternate venting arrangements.
AstroCap Flex Kits
1
6-7/8" dia. fl exible liner (kit length)
2
4" dia. fl exible liner (kit length)
3
spring spacers (3)
4
thimble (2)
5
AstroCap termination cap (1)
6
screws (12)
7
tube of Mill Pac (1)
8
plated screws (8)
INSTALLATION
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency® may be used for Flex installations.
MINIMUM
RIGID PIPE CENTER-LINE
Horizontal (Feet)
8
6
4
2
Vertical Height (Feet)
0
0
2
Max. 24"(0.6m)
648
Min. 30"
(762mm)
MINIMUM
FLEX KIT CENTER-LINE
Horizontal (Feet)
0
2
8
6
4
2
Vertical Height (Feet)
0
Max. 24"(0.6m)
648
Min. 26”
(660mm)
Alternate
Horizontal
Termination
Caps
Wherever necessary due to external location of cap, the AstroCap can be replaced with the FPI Riser Vent Termina­tion Cap.
Regency P33 SunriseTM Gas Fireplace 15