Regency P33 Sunrise Gas Fireplace
Model P33S-NG4 P33S-LP4
Fuel Type Natural Gas Propane
Minimum Supply Pressure 5” W.C. (1.25 kPa) 11” W.C. (2.73 kPa)
Manifold Pressure - High 3.5” W.C. (0.87 kPa) 10” W.C. (2.49 kPa)
Manifold Pressure - Low 1.6” W.C. (0.39 kPa) 6.4” W.C. (1.59 kPa)
Maximum Input
Altitude 0-4500 ft. (0-1372m)
Vent Sizing 4” Inner / 6 5/8” Outer 4” Inner / 6 5/8” Outer
Approved Venting Systems
Flex Vent Systems: FPI AstroCap™ Flex Vent
Rigid Pipe Vent Systems: Simpson Direct Vent Pro®
17,000 BTU/h
(4.98 kW)
American Metal Products® Amerivent Direct
Security Secure Vent®
Selkirk Direct-Temp™
Metal-Fab® Sure Seal
15,500 BTU/h
(4.54 kW)
Regency P33 Sunrise Gas Fireplace
P33 Sunrise Gas Fireplace
Unit Dimensions Description P33S
A Front Face Width 33-5/8” (846mm)
B Rear Firebox Width 23” (584mm)
C Front Face Height 29” (737mm)
D Height w/ Standoff 31 1/2” (800mm)
E Unit Depth 12-3/4” (324mm)
F Firebox Height 29” (737mm)
Framing Dimensions Description P33S
G Framing Width 33-1/4” (845mm)
H** Framing Height** 31-3/4” (806mm)**
I*
J
K Corner Wall Length 37 -1/2” (953mm)
L Corner Facing Wall Width 53-1/4” (1353mm)
M*** Framed Chase Ceiling*** 36” (914mm) Rigid*** 32” (813mm) Flex***
N Vent Centerline Height 30” (762mm) Rigid 26” (660mm) Flex
Framing Rise from Floor
Framing
Depth
Vertical
Horizontal
1” (25mm) minimum*
19 -1/2” (495mm) Vertical Rise
16 1/2” (419mm) Rigid 12-3/4” (324mm) Flex
* The unit must be raised a minimum of 1” above the fi nished fl oor.
** Dimension H = H + I (minimum)
*** Dimension M = M + I (minimum)
This manual is intended to be a Sales Reference Guide only.
Do NOT use for actual framing and installation of any unit.
Some specifi cations may change without notice.
You must use the actual manual for exact installation specifi cations.
Dimension Description P33S
O Gas Connection Height 1-1/2” (38mm)
P Gas Connection Inset 4” (102mm)
Q Gas Connection Width 3” (76mm)
R Minimum Framing Depth 16 1/2” (419mm) Rigid / 12-3/4” (324mm) Flex
S
Maximum Framing Depth
(including wall thickness)
40 1/2” (1028mm) Rigid / 36-3/4” (933mm) Flex
Clearance Requirements
C
B
Close to Ceiling
Clearance: Dimension Measured From:
A: Rise 1” minimum Finished Floor
B: Sidewall 7-1/2” Side of Unit
C: Ceiling 30” Top of Unit
D: Alcove Width 48” Sidewall to Sidewall (Minimum)
E: Alcove Depth 36” Front to back wall (Maximum)
WARNING
Failure to maintain required clearances is a major cause of chimney related fi res.
Installation of this fi replace must comply with these clearances
Please note: Due to ongoing product development, product appearance and specifi cations
are subject to change without notice.
Regency P33 Sunrise Gas Fireplace
Venting Arrangements - Horizontal
Terminations
This lightly shaded area of the diagram shows allowable combinations of
vertical runs with horizontal terminations, using one 45° and one 90° elbow
(two 45º elbows equal one 90° elbow).
Note: Must use optional rigid pipe adapter (Part # 510-994) when using
Rigid Pipe.
• Maintain clearances to combustibles.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through
a wall.
A vent guard may be required as per local codes, refer to Exterior Vent
Termination Locations.
Note: FPI Direct Vent System (Flex) is only approved for horizontal
terminations.
Horizontal (Feet)
4
2
0
8
6
10
12
14
18
16
P33 Sunrise Gas Fireplace
Venting Arrangements - Vertical
Terminations
Rigid Pipe System
(Propane & Natural Gas)
The P33 is approved for a maximum 40 ft. straight vertical, with Rigid
Pipe vent systems for Propane and Natural Gas.
The lightly shaded area,
confi gurations with a maximum two 45° elbows.
The darker shaded area,
confi gurations using one 45° and one 90° elbow.
• Vent must be supported at offsets.
• Horizontal sections must be supported every 3 feet.
• Firestops are required at each floor level and whenever
passing through a wall.
• Maintain clearances to combustible materials.
• Minimum of 1’ pipe section between elbows.
Note: Must use optional rigid pipe adapter when using Rigid Pipe
(Part # 510-994).
20
, in the diagram shows allowable venting
, in the diagram shows allowable venting
204
8
6
10 12 1
14
16
14
12
10
8
Vertical Height (Feet)
6
4
- Rigid
2
0
8"(0.2m)
2’ (0.6m)
30” (762mm)
Minimum
Height
Note: Height measured from the base of the unit.
Requirement
26” (660mm) - Flex
40
38
36
34
32
30
28
26
24
22
20
18
Vertical Height (Feet)
16
14
12
Maximum: 40 ft. (12.2m)
Maximum: 27 ft. (8.2m)
10
8
6
4
Minimum 9’6” (2.9m)
2
0
Minimum 12” (305mm)
Max. 10’ (3m)(centerline to centerline)
Minimum 8’6” (2.6m)
Note: Height measured from the base of the unit.