Regency GEM54-NG, GEM54-LPG, GEM54-ULPG Owners & Installation Manual

Page 1
Regency Gem54
Gas Fireplace
Owners &
Installation Manual
MODELS: GEM54-NG
GEM54-LPG
GEM54-ULPG
LISTINGS AND CODE APPROVALS These gas appliances have been tested in
accordance with AS4558 / NZS 5262 and have been certifi ed by the Australian Gas Association for installation and operation as described in these Installation and Operating Instructions.
www.regency-fi re.com.au
WARNING: If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
918-784
Your unit should be serviced annually by an authorised service person.
FOR YOUR SAFETY What to do if you smell gas:
Do not try to light any applianceDo not touch any electrical switch:
do not use any phone in your building.
Immediately call your gas supplier
from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
07/08/09
Page 2
To the New Owner:
Congratulations! Y ou are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The Gem54 has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch. The model Gem54 has been approved by AGA for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow . Please take a moment now to acquaint yourself with
these instructions and the many features of your Regency
®
Fireplace.
2
Regency Gemfi reTM Gas Fireplace
Page 3
TABLE OF CONTENTS
DATA BADGE
Copy of data badge .......................................................4
DIMENSIONS
Unit Dimensions ............................................................5
Faceplate & Door Frame Dimensions ...........................5
INSTALLATION
Important Message ......................................................6
Before You Start ............................................................6
General Safety...............................................................6
Installation Checklist ......................................................7
Locating Your Gas Fireplace .........................................7
Clearances ....................................................................8
Non-Combustible Requirements ...................................8
Mantel Clearances.........................................................9
Mantel Leg Clearances..................................................9
Framing & Finishing.....................................................10
Unit Assembly Prior To Installation ..............................12
Top Standoff Assembly ........................................12
Side Nailing Strips ...............................................12
Venting Introduction .....................................................12
Vent Restrictor Position ...............................................13
Exterior Vent Termination Requirements .....................14
Venting Arrangements ................................................15
Horizontal Termination (Flex) ...............................15
Rigid Pipe Venting Systems ........................................16
Basic Horizontal & Vertical Terminations .............16
5” x 8” Rigid Pipe Cross Reference Chart ...................17
Venting Arrangements ................................................19
Allowable Horizontal Terminations .......................19
Venting Arrangements ................................................20
Venting Arrangements ................................................23
Allowable Vertical Terminations for Gem54-ng ....23
Venting Arrangements ................................................24
Allowable Vertical Terminations ...........................24
Unit Installation with Horizontal Termination ................25
Unit Installation with Vertical Termination ....................26
Unit Installation ............................................................27
Horizontal Termination .........................................27
with Flex Vent System .........................................27
High Elevation .............................................................28
Gas Line Installation ....................................................28
Pilot Adjustment ...............................................................
Pilot Adjustment ...........................................................28
Gas Pipe Pressure Testing ..........................................28
S.I.T. Valve Description ................................................28
Conversion from NG to LPg .......................................29
Conversion from NG to ULPG .....................................29
Aeration Adjustment ....................................................32
Wiring Diagram ...........................................................32
Optional Stainless Steel ..............................................33
Refl ective Panel Installation ........................................33
Glass Crystals or optional ceramic stones ..................34
Installation On Burner ..................................................34
Optional Pebble Installation .........................................34
Screen & Door frame Installation................................35
Faceplate Installation...................................................36
OPERATING INSTRUCTIONS
Operating Instructions .................................................38
First Fire ......................................................................38
Lighting Procedure ......................................................38
Normal Operating .......................................................38
Shutdown Procedure ...................................................38
Sounds of Gas Appliances ..........................................38
Copy of Lighting Plate Instructions ..............................39
MAINTENANCE
Maintenance Instructions.............................................40
General Vent Maintenance ..........................................40
Thermopile / Thermocouple .........................................40
Glass Gasket ...............................................................40
Glass Door...................................................................40
Glass Replacement .............................................40
Glass Door Removal ...................................................41
DC Spark Box Battery Replacement ...........................42
DC Spark Box Replacement........................................42
V alve Tray Replacement ..............................................43
PARTS LIST
Main Assembly ............................................................45
Accessories .................................................................46
WARRANTY
Warranty ......................................................................47
Regency Gemfi reTM Gas Fireplace 3
Page 4
DATA BADGE
This is a copy of the badge that accompanies each Gem54™-NG Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review . NOTE: Regency® units are constantly being improved. Check the badge on the unit and if there is a difference, the badge on the unit is the correct
one.
COPY OF DATA BADGE
INSTALLATION
Regency Gas Fireplace
Model
Gas Type NG LPG ULPG
Model Gem54-NG Gem54-LP Gem54-ULPG
Gas Consumption 35.9 mj. 32.2mj. 28.7mj.
Manifold Pressure 0.88 kPa 2.49kPa 2.49 kPa
Injector Size 1 x #32 1 x#51 1 x #52
2.95mm 1.70mm 1.61mm
AGA Approval number to: # 7493
Code AS4558 / NZ5262
Electrical: Millivolt Only
918-785
N2134
Distributed by:
Western Australia:
Eastern Australia:
accordance with installation instructions provided
Serial Number
Air Group Australia
28 Division St
Welshpool WA 6106
Fireplace Products
Australia Pty. Ltd.
21-23 South Link Blvd.
Dandenong, VIC 3175
To be installed by an authorised person in
with the appliance.
345
WARNING: “PRIMARILY A DECORATIVE APPLIANCE NOT CERTIFIED AS A SPACE HEATER”
4
909-133
(Australia Only)
Regency Gemfi reTM Gas Fireplace
Page 5
52-5/8” (1337mm)
59” (1499mm)
DIMENSIONS
UNIT DIMENSIONS
INSTALLATION
19-3/4” (502mm)
17-1/8” (435mm)
8”(203mm)
Outer Dia.
5” (127mm)
Inner Dia.
46-3/8” (1178mm)
31-5/8” (803mm)
48-1/2” (1232mm)
21-5/8” (549mm)
5-11/16”
(144mm)
1-1/2”
(38mm)
FACEPLATE & DOOR FRAME OVERLAY DIMENSIONS
10-5/8”
(270mm)
20-1/2” (521mm)
35-1/4” (895mm)
Regency Gem reTM Gas Fireplace 5
Page 6
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The Gem54™ Direct Vent Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual rst. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of
INSTALLATION
the installer to ensure this fi replace is installed in compliance with manufacturers instructions and all applicable codes and complies with a S5601 / AG601 clause 5.12, 13.2 and 5.12, 13.5.
BEFORE YOU ST ART
INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: F AILURE TO INST ALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPE­CIALL Y THE FIREPLACE GLASS, AND SHOULD ST AY AWA Y TO A VOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform with
local codes or, in the absence of local codes, with the current Installation and Building Codes.
2) The appliance when installed, must be electrically grounded in accordance with local codes.
3) See general construction and assembly instructions. The appliance and vent should be enclosed.
4) This appliance must be connected to the specifi ed vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fi tted as per Venting instructions.
5) Inspect the venting system annually for blockage and any signs of deterioration.
6) V enting terminals shall not be recessed into a wall or siding.
7) Any safety glass removed for servicing must be replaced prior to operating the appliance.
8) To prevent injury, do not allow anyone who is unfamiliar with the operation to use the replace.
9) Wear gloves and safety glasses for protection while doing required maintenance.
10) Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.
11) Under no circumstances should this appliance be modifi ed. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
12) Installation and any repairs to this appliance should be done by an authorized service person. A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.
15) The appliance area must be kept clear and free of combustible materials, (gases and other fl ammable vapours and liquids).
"THIS UNIT MUST ALWAYS TERMINATE / VENT DIRECTLY TO THE OUTDOORS."
6
Regency Gemfi reTM Gas Fireplace
Page 7
INSTALLATION
INSTALLATION
CHECKLIST
1) Locate appliance
a) Room location (Refer to "Locating Your
Gas fi replace" section)
b) Clearances to Combustibles (Refer to
"Clearances" section)
c) Mantle Clearances (Refer to "Mantel
Clearances" section)
d) Framing & Finishing Requirements (Refer
to "Framing & Finishing" section)
e) Venting Requirements (Refer to "Venting"
section)
2) Assemble the standoffs and nailing strips (Refer to "Unit Assembly Prior to Installation).
3) Slide unit into place.
4) Install vent (Refer to "Venting Arrangement"
sections).
5) Make gas connections (Refer to "Gas Line Installation section).
6) Test the pilot (Refer to "Pilot Adjustment" section).
7) T est Gas Pressure (Refer to "Gas Pipe Pres­sure Testing" section).
8) Install standard and optional features. Refer to the following sections:
This includes:
1) Clocking the appliance to ensure the correct
ring rate (rate noted on label 41,500 Btu/h, after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure that the fl ame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your replace,
ensure that the clearances are met.
2) The appliance must be installed on a fl at, solid, continuous surface For example a wood, metal or concrete fl oor or in a raised (on the wall) application. The appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
3) The Gem54 Direct Vent Gas Fireplace can be installed in a recessed position or framed out into the room as in A, B, C and D. See Diagram 1.
4) This appliance is Listed for bedroom installations using the standard Remote (millivolt thermostat system). Some areas may have further requirements, check local codes before installation.
5) The Gem54 Direct Vent Gas Fireplace is approved for alcove installations, see "Clearances" section for details.
6) We recommend that you plan your installation on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation.
Note: For vent terminations refer to
"Exterior Vent T ermination Locations" section.
INSTALLATION
a) Glass Crystals b) Optional Firebox Base Pebbles c) Optional Stainless Steel Refl ective
Panels d) Faceplate / Door Frame Overlay e) Remote Control or Wall Thermostat
9) Wall Mounted ON/OFF Switch: Use the toggle wall switch supplied with the
manual package. Use of a “decor” switch
causes higher resistance which is a problem
on gas fi replaces.
10) Final check. Before leaving this unit with the customer, the
installer must ensure that the appliance is fi ring correctly and operation fully explained to customer.
Diagram 1
A) Flat on Wall B) Flat on Wall Corner C) Recessed into Wall/Alcove D) Corner
Regency Gem reTM Gas Fireplace 7
Page 8
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fi replace and vent system be installed only in accordance with these instructions.
INSTALLATION
The top, back and sides of the fi replace are defi ned by
Caution Requirements
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fi replace and vent
system be installed only in accordance with these instructions.
Clearance: Dimension Measured From:
A: Mantel Height (min.) 20" (508mm) Top of Fireplace Opening B: Sidewall 4" (102mm) Side of Fireplace Opening
C: Ceiling (room and/or alcove)
D: Mantel Depth (max.) 13" (330mm) 30" Above Fireplace Opening E: Alcove Width 83" (2108mm) Sidewall to Sidewall (Minimum) F: Alcove Depth 36" (914mm) Front to Back Wall (Maximum)
Note 0" No hearth required
D
A
40-7/8" (1038mm) Top of Fireplace Opening
C
F
B
Fire hazard is an extreme risk
WARNING
Flue Clearances
Horizontal - Top 3" (76mm) Horiztonal - Side 2" (51mm) Horiztonal - Bottom 2" (51mm) Vertical 2" (51mm)
F
B
G
E
Installed Close
to Floor
Installed Close
to Ceiling
NON-COMBUSTIBLE REQUIREMENTS
Metal Stud (header)
Wood Stud
Non-combustible Material
5-11/16”
(144mm)
48" (1219mm)
Wood Stud
20"
(508mm)
28”
(711mm)
Non-combustible Material
4"
(102mm)
60-1/2" (1537mm)
Non-combustible
Material
52-5/8”
21-3/4”
Non-combustible Material
8
Regency Gemfi reTM Gas Fireplace
Page 9
MANTEL CLEARANCES
4"
INSTALLATION
Due to the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel
clearances from top of front facing are shown in the diagram on the right.
Note: A non-combustible mantel may be
installed at a lower height if the framing is made of metal studs covered with a non-combustible board.
Note: Ensure the paint that is used on the mantel
and the facing is "heat resistant" or the paint may discolour.
14
0
(356mm)
(305mm)
(254mm)
12
30” (762mm)
28-1/8”
(724mm)
To Floor
(203mm)
(152mm)
(102mm)
6
810
4
13" (330mm)
3 ½" (89mm)
1" (25mm)
21”
To p o f Fireplace Opening
(51mm)
2
20”
INSTALLATION
0
Drywall
Metal Stud (On Edge)
Non-combustible
Facing
Standoff
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram:
MANTEL LEG
Allowable mantel leg projection
Regency Gemfi reTM Gas Fireplace 9
(102mm) Non-Combustible
4”
1.5" (38mm)
11-1/2” (292mm)
14” (356mm)
15-3/4” (400mm)
Page 10
INSTALLATION
FRAMING & FINISHING
1) Frame in the enclosure for the unit with framing material. IMPORTANT : Header must be metal stud. All other framing may be
of combustible type such as 2x4 (0.6m x 1.2m) / 2x6 (0.6m x 1.8m) framing materials.
Note: When constructing the framed opening, please ensure there
is access to install the gas lines when the unit is installed.
INSTALLATION
2) For exterior walls, insulate the enclosure to the same degree as the rest of the house, apply vapour barrier and drywall, as per local instal­lation codes. (Do not insulate the replace itself.)
WARNING: Failure to insulate and add vapor barriers to the inside
of the exterior wall will result in operational and performance problems including, but not limited to: excessive condensation on glass doors, poor fl ame package, carbon, blue fl ames etc. These are not product related issues.
3) The unit does not have to be completely enclosed in a chase. You
must maintain clearances from the vent to combustible materials: See "Clearances" section. Combustible materials can be laid against the side and back standoffs and the stove base.
4) If material such as brick, stone, etc extends past the faceplate depth, when fi nishing around the faceplate, the minimum opening dimen- sions noted below must be adhered to ensuring for the removal of the faceplate.
5) When fi nishing around the faceplate, if material such as brick, stone, etc. extend past the faceplate depth - the minimum opening
dimensions noted below must be adhered to, this is to assure
removal of the faceplate.
Nailing Strips
Finished
Material
Nailing Strip
Position
13mm 25mm
Factory
Setting
Nailing Strip 1” Forward
26-5/8” (676mm)
58-3/16” (1478mm)
Unit
25mm 13mm
Nailing Strip ½” Forward
Unit
38mm 0mm (fl ush)
Nailing Strip Flush w/unit Factory Set
Unit
10
Regency Gemfi reTM Gas Fireplace
Page 11
INSTALLATION
Framing Dimensions
A Framing Height 46-5/8” (1184mm) B Framing Width 60” (1524mm)
C
* Framing Depth*
D Minimum Height to Combustibles 51” (1295mm) E Corner Wall Length 72" (1829mm) F Corner Facing Wall Width 101-7/8 (2586mm) G Vent Centerline Height 44” (1118mm) H Non-combustible facing height 20” (508mm) I Gas Connection Opening Height 1-1/2” (38mm) J Gas Connection Height 4” (102mm) K Gas Connection Inset 7-1/4” (184mm) L Gas Connection Opening Width 3-1/4” (83mm)
Description Gem54
22” (559mm)
* Framing depth measurement is noted with the side nailing strips set as far forward on the fi rebox as possible.
The nailing strips can be adjusted back - up to 1” (25mm) to allow for varying thicknesses in non-combustible material & wall fi nishes.
D
INSTALLATION
A
Metal Stud
(Header)
on edge
B
E
Metal Stud (Header) on edge
H
Non-Combustible
Facing
G
C
I
J
L
K
F
Regency Gemfi reTM Gas Fireplace 11
(Located on the right side of the fireplace)
Page 12
INSTALLATION
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The top and side nailing strips and the top, rear and side standoffs must be correctly positioned and attached to the top before unit is slipped into position.
ST ANDOFF ASSEMBLY
INSTALLATION
The top, rear and side standoffs are shipped in a fl at position and must be folded into shape and attached.
1) Remove the standoffs from the replace top.
2) T ake each standof f and bend into the correct shape. Bend up at the
bend lines until the screw holes in the standoff and the pre-punched screw holes on the fi replace top line up.
3) Attach the standoff securely with 2 screws per standoff (on opposite corners).
NAILING STRIPS
The nailing strips come attached to the unit. There is 1 plate on each side, 1 on the top, and one on the bottom that can be folded out as required. The top and side nailing strips are secured to the framing. The bottom nailing strip is secured to the unfi nished fl oor - if installing the unit directly on the fl oor
Nailing Strips
Nailing Strips shown folded out.
IMPORTANT NOTE
Framing depth measurement is noted with the nailing strips set as far forward on the fi rebox (top and sides) as possible. The nailing strips can be adjusted back - up to 1”(25mm) to allow for varying thicknesses in non-combustible material & wall fi nishes.
VENTING INTRODUCTION
The Gem54™ uses the "balanced fl ue" technology Co Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These fl ue pipes must not be connected to any other
appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.
12
Regency Gemfi reTM Gas Fireplace
Page 13
VENT RESTRICTOR POSITION
INSTALLATION
Vent restriction is required for certain venting installations, see the diagrams in the "Venting Arrangements" section to determine if they are required for your installation.
The Vent Restrictor plate is located on the inside top of the fi rebox. To set the vent restriction as indicated in the venting arrangements diagrams, refer to the following instructions;
1) Remove the glass door.
2) Remove the screws that hold the vent restrictor plate in place.
3) Adjust the vent restrictor plate to the required vent restrictor position as per the diagrams shown.
4) Once the vent restrictor plate is in the required position, secure with screws.
Vent Restrictor Settings for Gem54-NG
Vent Restrictor Settings for Gem54-LP
Gem54-ULPG
SET 1
THIS HOLE SETS THE
VENT RESTRICTOR
(factory setting)
AT 108mm
108mm
SET 1
THIS HOLE SETS THE
VENT RESTRICTOR
(factory setting)
AT 108mm
INSTALLATION
SET 2
THIS HOLE SETS THE
VENT RESTRICTOR
AT 76mm
SET 3
THIS HOLE SETS THE
VENT RESTRICTOR
AT 51mm
Vent Restrictor Set 1
Factory Set Vent Restrictor
(No adjustment required)
76mm
SET 3
THIS HOLE SETS THE
VENT RESTRICTOR
AT 51mm
Vent Restrictor Set 2
51mm
SET 4
THIS HOLE SETS THE
VENT RESTRICTOR
AT 25mm
Vent Restrictor Set 3
Regency Gem reTM Gas Fireplace 13
Page 14
INSTALLATION
INSTALLATION
EXTERIOR FLUE TERMINATION LOCATIONS
Minimum clearances required for balanced fl ue terminals or
the fl ue terminals of outdoor appliances
according to AS5601-2004 (AGA gas installation code) or NZS 5262 (New Zealand)
and local authorities having jurisdiction.
Minimum Clearance (mm) a Below eaves, balconies or other projections:
- Appliances up to 50 MJ/h input 300
- Appliances over 50 MJ/h input 500 b From the ground or above a balcony 300 c From a return wall or external corner 500 d From a gas meter (M) 1000 e From an electricity meter or fuse box (P) 500 f From a drain or soil pipe 150 g Horizontal from any building structure (unless appliance is approved for closer installation) or obstruction facing a terminal 500 h From any other fl ue terminal, cowl or combustion air intake 500 j Horizontally from an openable window, door, or non-mechanical air inlet, or any other opening into a building, with the exception of sub-fl oor ventilation (see also Note (I)):
- Appliances up to 150 MJ/h input 500
- Appliances over 150 MJ/h input 1500 k Vertically below an openable window, door, or non-mechanical air inlet, or any other opening into a building, with the exception of sub-fl oor ventilation
(see also Note (I)): see table below
Clearance 'k' in mm
Space Heaters All Other Appliances Up to 50 MJ/h
input
Up to 50 MJ/h Over 50 MJ/h input
to 150 MJ/h input
Over 150 MJ/h
input
150 500 1000 1500
(I) For mechanical air inlets, including spa blowers, the clearance 'j' and 'k' shall be 1500 mm in all cases. (II) All distances shall be measured vertically or horizontally along the wall to a point in line with the nearest par to of the terminal. (III) Prohibited area below electricity meter or fuse box extends to ground level. (IV) A fl ue terminal of this type shall not be located under a roofed area unless the roofed area is fully open on at least two sides and a free fl ow of
air at the appliance is achieved.
14
Regency Gemfi reTM Gas Fireplace
Page 15
VENTING ARRANGEMENTS
INSTALLATION
HORIZONTAL TERMINATION (FLEX)
Regency® Direct Vent System
These venting systems, in combination with the Gem54, have been tested and listed as a direct vent system by AGA. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.
FPI Direct Vent (Flex) System Termination Kits include all the parts needed to install the Gem54 using a fl exible vent.
FPI Kit # Length Contains:
#946-615 4 Feet
(1.2 m)
#946-618 6 Feet
(1.8 m)
#946-616 10 Feet
(3 m )
1) 8” (203mm) exible liner (Kit length)
2) 5”(127mm) exible liner (Kit length)
3) spring spacers
4) thimble
5) AstroCap termination cap
6) screws
7) tube of Mill Pac
8) plated screws
9) S.S. screws #8 x 1-1/2” (38mm) drill
point
10) vinyl siding standoff
Vinyl Siding
Wall Thimble
(Mandatory in all
Horizontal Terminations)
Standoff
AstroCap XL
Vent Guard - if required*
(Part #946-506/P)
TM
Termination Cap
5” (127mm) dia. flue pipe
(Part #946-623/P)
INSTALLATION
8” (203mm) dia.
Flue pipe
Regency Gemfi reTM Gas Fireplace 15
spring spacer
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from FPI may be used for Flex installations.
3) Horizontal vent must be supported every 3 feet (0.9m).
4) A wall thimble is mandatory for all horizontal terminations due to high temperatures.
Page 16
INSTALLATION
RIGID PIPE VENTING SYSTEMS
BASIC HORIZONTAL & VERTICAL TERMINATIONS
Rigid Pipe Vent Systems offer a complete line of component parts for installation of both horizontal and vertical installations. Many items are offered in decorative black, as well as galvanized fi nish.
Vertical Terminal
The minimum components required for a basic
INSTALLATION
Horizontal Termination are:
1 AstroCap XL Termination Cap 1 90o Elbow 1 Rigid Pipe Adaptor 1 Wall Thimble 1 Length of rigid pipe to suit wall thickness
The minimum components required for a basic Vertical Termination are:
1 Vertical Termination Cap 1 Rigid Pipe Adaptor 1 Lengths of pipe to adequately penetrate roof 1 Ceiling Firestop 1 Flashing 1 Storm Collar
Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap. For siding other than vinyl furring strips may be used, instead of the vinyl siding standoff, to create a level surface to mount the vent terminal. The T erminal must not be recessed into siding. Measure the wall thickness including furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add 2" (51mm).
Flashing
Pipe Length
Length
Pipe
Pipe Length
o
90 Elbow
Rigid Pipe
Adaptor (770-994)
AstroCap XL
Termination Cap
(Part #946-623/P)
Wall Thimble
(Mandatory in all
Horizontal Terminations)
Vent Guard - if required*
(Part #946-506/P)
WARNING:
Do not combine venting components from different venting systems.
Exception: However, use of the the AstroCap XLTM is acceptable with all systems.
16
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
Regency Gemfi reTM Gas Fireplace
Page 17
INSTALLATION
5” X 8” RIGID PIPE CROSS REFERENCE CHART
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Description
6” Pipe Length-Galvanized 58DVA-06 5DT-6
6” Pipe Length-Black 58DVA-06B 5DT-6B
9” Pipe Length-Galvanized 58DVA-09 5DT-9
9” Pipe Length-Black 58DVA-09B 5DT-9B
12” Pipe Length-Galvanized 58DVA-12 5DT-12
12” Pipe Length-Black 58DVA-12B 5DT-12B
18” Pipe Length-Galvanized 58DVA-18 5DT-18
18” Pipe Length-Black 58DVA-18B - N/A from FPI 5DT-18B
24” Pipe Length-Galvanized 58DVA-24 5DT-24
24” Pipe Length-Black 58DVA-24B 5DT-24B
36” Pipe Length-Galvanized 58DVA-36 5DT-36
36” Pipe Length-Black 58DVA-36B 5DT-36B
48” Pipe Length-Galvanized 58DVA-48 5DT-48
48” Pipe Length-Black 58DVA-48B 5DT-48B
60” Pipe Length-Galvanized 58DVA-60 N/A
60” Pipe Length-Black 58DVA-60B - N/A from FPI N/A
Simpson
Direct Vent Pro
®
Selkirk
Direct Temp™
INSTALLATION
Adjustable Length 3”-10”-Galvanized N/A N/A
Adjustable Length 3”-10”-Black N/A N/A
Adjustable Length 11”-14” -Galvanized Disc. - See 58DV-08A 5DT-AJ
Adjustable Length 11”-14” -Black Disc. - See 58DV-08B 5DT-AJB
Extension Pipe 17”-24” -Galvanized Disc. - See 58DV-16A N/A
Extension Pipe 17”-24” -Black Disc. - See 58DV-16AB N/A
Adjustable Length 8-1/2”-Galvanized 58DVA-08A - N/A from FPI N/A
Adjustable Length 8-1/2”-Black 58DVA-08AB N/A
Extension Pipe 16”-Galvanized 58DVA-16A - N/A from FPI N/A
Extension Pipe 16”-Black 46DVA-16AB N/A
45º Elbow-Galvanized 58DVA-E45 5DT-EL45
45º Elbow-Black 58DVA-E45B 5DT-EL45B
45º Elbow Swivel-Galvanized
45º Elbow Swivel-Black
90º Elbow-Galvanized 58DVA-E90 5DT-EL90S
90º Elbow-Black 58DVA-E90B 5DT-EL90SB
90º Elbow, Swivel-Galvanized
90º Elbow, Swivel-Black
90º Starter Elbow, Swivel-Galvanized N/A N/A
Adaptor* N/A N/A
Ceiling Support 58DVA-DC 5DT-CS
Cathedral Support Box 58DVA-CS 5DT-CSS
Wall Support/Band 58DVA-WS 5DT-WS/B
Offset Support
Wall Thimble-Black 58DVA-WT 5DT-WT
Wall Thimble Support/Ceiling Support 58DVA-DC
Firestop Spacer 58DVA-FS 5DT-FS
Trim Plate-Black 58DAV-WFS 5DT-TP
Disc. - See 58DVA-E45
Disc.-See 58DVA-E45B
Disc. - See 46DVA-E45
Disc. - See 46DVA-E45
58DVA-ES - N/A from FPI
- N/A from FPI N/A
N/A
N/A
N/A
N/A
5DT-OS
Regency Gem reTM Gas Fireplace 17
Page 18
INSTALLATION
INSTALLATION
Description
Attic Insulation Shield 12” 58DVA-IS N/A from FPI N/A N/A N/A
Basic Horizontal Termination Kit (A) N/A 5DT-HKA N/A N/A
Horizontal Termination Kit (B) 58DVA-KHA 5DT-HKB N/A N/A
Vertical Termination Kit 58DVA-VHA 5DT-VKC N/A N/A
High Wind Vertical Cap 58DVA-VCH N/A N/A TM-5VT
High Wind Horizontal Cap N/A N/A N/A TM-5DHT
Horizontal Square Termination Cap N/A 5DT-HHC 5DHT TM-5HT
Vertical Termination Cap N/A 5DT-HVC 5DVT TM-5VT
Storm Collar 58DVA-SC 5DT-SC 5DSC TM-SC
Adjustable Flashing 0/12-6/12 58DVA-F6 5DT-AF6 5DF TF-5FA
Adjustable Flashing 6/12-12/12 58DVA-F12 5DT-AF12 5DF1-2 TF-5FB
Vinyl Siding Standoff 58DVA-VSS 5DT-VS 5DVS TM-VSS
Vinyl Siding Shield Plate N/A 5DT-VSP N/A N/A
Snorkel Termination 14” 58DVA-SNK14 N/A N/A TM-5ST14
Snorkel Termination 36” 58DVA-SNK36 (N/A - FPI) N/A N/A TM-5ST36
Restrictor Disk 58DVA-RD N/A N/A TM-5DS
Colinear Flex Connectors N/A N/A N/A N/A
Simpson
Direct Vent Pro
®
Selkirk
Direct Temp™
Metal-Fab™
Sure Seal
ICC Excel
Direct
FPI
946-604/P Simpson Direct Vent -Vent Guard (Optional) 946-623/P AstroCap XL Horizontal Cap
770-994 Rigid Pipe Adaptor (Must use with all rigid piping) 946-506/P Vent Guard (Optional)
946-606 Starter collar reducer 5” x 8” to 4” x 6-5/8” 946-625 Vinyl Siding Standoff - AstroCap XL
Note: When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).
Offset Pipe Selection: Use this table to determine offset pipe lengths.
Pipe Length
(L)
0” (0mm) 5-11/16” (144mm) 15-5/16” (389mm) Simpson Direct Vent Pro: www.duravent.com
6” (152mm) 8-13/16” (224mm) 18-7/16” (468mm) Selkirk Direct-Temp: www.selkirkcorp.com
9” (229mm) 10-15/16” (278mm) 20-9/16” (522mm) Metal-Fab Sure Seal: www.mtlfab.com
12” (305mm) 13” (330mm) 22-11/16” (576mm) Industrial Chimney Company: www.icc-rsf.com
24” (610mm) 21-7/16” (697mm) 31-1/16” (789mm) Note: Horizontal runs of vent must be level, or have a 1/4”
36” (914mm) 29-13/16” (757mm) 39-7/16” (1002mm)
48” (1219mm) 38-1/4” (972mm) 47-7/8” (1216mm)
5” x 8” Venting For specifi c instructions on venting components - visit the
Run (X) Rise (Y)
manufacturers website listed below.
rise for every 1 foot of run towards the termination. Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard.
L676 & L900 DIRECT VENT FIREPLACE
IMPORTANT NOTE
• A Vent Guard is required when the AstroCap is installed above grade at 7 feet or lower.
• The Simpson Dura-Vent and Selkirk Direct Temp horizontal termination caps cannot be used in any applications.
• Only the AstroCap XL and Snorkels are certifi ed for horizontal terminations.
18
Regency Gemfi reTM Gas Fireplace
Page 19
VENTING ARRANGEMENTS
2
2
0
0
12
12 20
6
6 14
4
4
14
8
8 16
10
10
18
16
18
INSTALLATION
ALLOWABLE HORIZONTAL TERMINATIONS
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o (two 45o elbows equal one 90o elbow).
Note: Must use optional rigid pipe adapter (Part# 770-994) when using Simpson Duravent Venting Systems.
Horizontal (Feet)
18
18
Vent Restrictor
on Set 3
Vent Restrictor
on Set 2
INSTALLATION
Vent Restrictor
Vertical Height (Feet)
44” (1118mm)
Minimum Height
Requirement
VENT RESTRICTOR SETTING: Vent restrictor factory set, no adjustment required unless otherwise indicated.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 1 to Set 2 or Set 3 if required.
• Maintain clearances to combustibles as listed in "Clearances" section
• Horizontal vent must be supported every 3 ft / 91 cm.
• Firestops are required at each fl oor level and whenever passing through a wall.
• A wall thimble is mandatory for all horizontal terminations due to high temperatures.
on Set 1
(factory setting)
"THIS UNIT MUST ALWAYS TERMINATE / VENT DIRECTLY TO THE OUTDOORS."
Regency Gem reTM Gas Fireplace 19
Page 20
INSTALLATION
2
2
0
0
12
12 20
6
6 14
4
4
14
8
8 16
10
10
18
16
18
VENTING ARRANGEMENTS
ALLOWABLE HORIZONTAL TERMINATIONS FOR GEM54-LPG/ULPG
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o (two 45o elbows equal one 90o elbow).
Note: Must use optional rigid pipe adapter (Part# 770-994) when using Rigid Pipe Venting Systems.
INSTALLATION
18
Vertical Height (Feet)
Horizontal (Feet)
18
Vent Restrictor
on Set 3
Vent Restrictor
on Set 1
(factory setting)
44” (1118mm)
Minimum Height
Requirement
"THIS UNIT MUST ALWAYS TERMINATE / VENT DIRECTLY TO THE OUTDOORS."
VENT RESTRICTOR SETTING: Vent restrictor factory set, no adjustment required unless otherwise indicated.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 1 to Set 3 if required.
Note: Regency® Direct Vent System (Flex) is only approved for horizontal terminations.
• Maintain clearances to combustibles as listed in "Clearances" section
• Horizontal vent must be supported every 3 feet (0.9m).
• Firestops are required at each fl oor level and whenever passing through a wall.
• A wall thimble is mandatory for all horizontal terminations due to high temperatures.
20
Regency Gemfi reTM Gas Fireplace
Page 21
Horizontal Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V H + H1
A) .6m Min. 1.2m Max. B) .9m Max. 1.8m Max. C) 1.2m Max. 2.4m Max. D) 1.5m Max. 2.7m Max. E) 1.8m Max. 3m Max.
Please note minimum .3m between 90 required.
VENT RESTRICTOR SETTING: Vent restrictor factory set at Set 1, no adjustment required.
With these options, maximum total pipe length is 9m with minimum of 1.8m total vertical and maximum 3m total horizontal.
o
elbows is
INSTALLATION
INSTALLATION
Horizontal Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V H V+ V1 H+ H1
A) .6m Min. .3m Max. .9m Min. .6m Max. B) .6m Min. .6m Max. 1.5m Min 1.2m Max. C) .9m Min. .6m Max. 2.1m Min. 1.5m Max. D) 1.2m Min. .9m Max. 2.7m Min. 1.8m Max. E) 1.5m Min. 1.2m Max. 3m Min. 2.1m Max. F) 1.8m Min. 1.8m Max. 3.3m Min 2.7m Max.
Please note minimum .3m between 90
VENT RESTRICTOR SETTING: Vent restrictor factory set at Set 1, no adjustment required.
o
elbows is required.
With these options, max. total pipe length is 9m with min. of 3.4m total vertical and max.
2.7m total horizontal.
Regency Gemfi reTM Gas Fireplace 21
Page 22
INSTALLATION
INSTALLATION
Vertical Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V H V+ V1
A) .6m Min. .6m Max. 1.2m Min. B) .9m Min. 1.2m Max. 1.8m Min C) 1.2m Min. 1.5m Max. 2.1m Min. D) 1.5m Min. 1.8m Max. 2.4m Min. E) 1.8m Min. 2.4m Max. 2.7m Min.
Please note minimum .3m between 90
VENT RESTRICTOR SETTING: Vent restrictor factory set at Set 1, no adjustment required.
o
elbows is required.
With these options, max. total pipe length is 9m with min. of
2.7m total vertical and max. 2.4m total horizontal.
22
Regency Gemfi reTM Gas Fireplace
Page 23
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
6
8
2
0
4
10
12 16
18
14
20
VENTING ARRANGEMENTS
ALLOWABLE VERTICAL TERMINATIONS FOR GEM54-NG
INSTALLATION
INSTALLATION
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90 Systems for Natural Gas. Two 45
o
elbows, with Rigid Pipe Venting
o
elbows equal to one 90o
elbow. Maximum of four 45o elbows allowed.
"THIS UNIT MUST ALWAYS TERMINATE / VENT DIRECTLY TO THE OUTDOORS."
Horizontal (Feet)
12
Maximum: 40 ft. (12.2m)
Vent Restrictor on Set 3
Vent Restrictor on Set 2
Please note min. 0.3m between 90 is required.
o
elbows
• Vent must be supported at offsets.
• Firestops are required at each fl oor level and whenever passing through a wall.
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 1 to Set 2 or Set 3 if required.
Note: Must use optional fl ue adaptor when using
Rigid Pipe (Part # 770-994).
Vertical Height (Feet)
Minimum length of pipe
between elbows 12” (305mm)
Vent Restrictor on Set 1
(factory setting)
Min. 44”
(1118mm)
Max. 10’ (3m)(centerline to centerline)
Minimum
8’6” (2.6m)
Maximum: 27 ft. (8.2m)
Regency Gem reTM Gas Fireplace 23
Page 24
INSTALLATION
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
6
8
2
0
4
10
12 16
18
14
20
ALLOWABLE VERTICAL TERMINATIONS FOR GEM54-LPG/ULPG
VENTING ARRANGEMENTS
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90o elbows, with Rigid Pipe Venting Systems for Natural Gas. Two 45
o
elbows equal to one 90o
elbow. Maximum of four 45o elbows allowed.
INSTALLATION
"THIS UNIT MUST ALWAYS TERMINATE / VENT DIRECTLY TO THE OUTDOORS."
Horizontal (Feet)
12
Maximum: 40 ft. (12.2m)
Vent Restrictor on Set 4
Please note min. 1 ft/305mm between 90 elbows is required.
o
Vertical Height (Feet)
Vent Restrictor on Set 3
Vent Restrictor on Set 1
(factory setting)
Maximum: 27 ft. (8.2m)
• Vent must be supported at offsets.
• Firestops are required at each fl oor level and whenever passing through a wall.
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 1 to Set 3 or Set 4 if required.
Note: Must use optional fl ue adaptor when using
Rigid Pipe (Part # 770-994).
Minimum length of pipe
between elbows 12” (305mm)
Min. 44”
(1118mm)
Max. 10’ (3m)(centerline to centerline)
Minimum
8’6” (2.6m)
24
Regency Gemfi reTM Gas Fireplace
Page 25
INSTALLATION
UNIT INSTALLATION
WITH HORIZONTAL
TERMINATION
(Rigid Vent Systems)
A top clearance of 3"(76mm) and side & bottom clearance of 2"(51mm) must be maintained; except when passing through a wall, ceil­ing, or at the termination where the use of a restop or wall thimble reduces the required clearance to 1-1/2" (38mm). We recommend framing a 11"(279mm) x 11"(279mm) (inside dimensions) hole to give structural rigidity for mounting the termination.
Install the vent system according to the manufacturer's instructions included with the components.
1) Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit.
2) Direct Vent pipe and fi ttings are designed with special twist-lock connections to connect the venting system to the appliance fl ue outlet. A twist-lock appliance adaptor is required.
3) In conjunction with the Simpson Direct Vent Pro system, install the adaptor after the unit is set in its desired location. Put a bead of high temperature silicone inside the outer section of the adapter and a bead of Mill Pack on the inner collar. Slip the adapter over the existing inner and outer fl ue collar. Fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier).
4) Level the fi replace and fasten it to the framing using nails or screws through the top and side nailing strips.
5) Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.
Note: For best results and optimum
performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty. Silicone (red RTV) is optional.
"THIS UNIT MUST ALWAYS TERMINATE / VENT DIRECTLY TO THE OUTDOORS."
Diagram 1
Horizontal runs of vent must be supported every 3 feet (0.9meter). Wall straps are available for this purpose.
6) Mark the wall for a 11" x 11" (279mm x
279mm) square hole. The center of the square hole should line up with the center­line of the horizontal pipe. Cut and frame the 11 inch (279mm) square hole in the exterior wall where the vent will be terminated. See diagram 2 for center line requirements.
If the wall being penetrated is constructed of
non-combustible material, i.e. masonry block or concrete, an 8" (203mm) diameter hole is acceptable.
Diagram 2
Note: a) The horizontal run of vent must be level,
or have a 1/4"/6mm rise for every 1 ft/305mm of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fi re.
b) The location of the horizontal vent
termination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. See "Exterior Vent Termination Locations" section for more details.
7) Ensure that the pipe clearances to combustible materials are maintained (Diagram 3). Install the termination cap.
Note: If installing termination on a vinyl
siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.
Diagram 3
The four wood screws provided should be re-
placed with appropriate fasteners for stucco, brick, concrete, or other types of sidings.
8) Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble over the vent pipe. The wall thimble is required for all horizontal terminations.
9) Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly. It is important that the vent pipe extends into the vent cap suffi cient distance so as to result in a minimum pipe overlap of 1-1/4 inches (32mm). Secure the connection between the vent pipe and the vent cap.
10) Install wall thimble in the center of the 11" (279mm) square and attach with wood screws (Diagram 4).
Diagram 4
INSTALLATION
Regency Gem reTM Gas Fireplace 25
Page 26
INSTALLATION
UNIT INSTALLATION
WITH VERTICAL
TERMINATION
(Rigid Vent Systems)
Note: A clearance of 2"(51mm) must be
maintained; except when passing through a wall, ceiling, or at the termination where the use of a fi restop
INSTALLATION
or wall thimble reduces the required clearance to 1-1/2" (38mm). We recommend framing a 11"(279mm) x 11"(279mm) (inside dimensions) hole to give structural rigidity for mounting the termination.
1) Maintain the 1-1/2" (38mm)
clearances (air spaces) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible surfaces, ensuring that the use of a firestop or wall thimble is used as noted above. Do not pack air spaces with insulation. Check "Venting Arrangemnt
- Vertical Termination" section for the maximum vertical rise of the venting system and the maximum horizontal offset limitations.
2) Set the gas appliance in its desired location. Drop a plumb bob down from the ceiling to the position of the appliance fl ue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at his point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters or other framing will obstruct the venting system. You may wish to relocate the appliance or to offset, as shown in Diagram 2 to avoid cutting load bearing members.
3) A Firestop spacer must be installed in the fl oor or ceiling of every level.
Diagram 2
Diagram 1
4) Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed.
Note: For best results and optimum performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every inner pipe connec­tion. Failure to do so may result in drafting or performance issues not covered under warranty. Silicone (red RTV) is optional.
5) Cut a hole in the roof centered on the small
drilled hole placed in the roof in Step 2. The hole should be of suffi cient size to meet the minimum requirements for clearance to combustibles of 1-1/2"(38mm). Slip the fl ashing under the shingles (shingles should overlap half the fl ashing) as per Diagram 4.
Diagram 4: The upper half of the fl ashing is
installed under the roofi ng material and not
nailed down until the chimney is installed.
This allows for small adjustments.
6) Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic
to avoid obstructions, it is important to support the vent pipe every 3 feet (0.9 meter), to avoid excessive stress on the elbows, and possible separation. Wall straps are available for this purpose
(Diagram 2).
Galvanized pipe is desirable above the roofl ine
due to its higher corrosion resistance. Continue to add pipe sections through the fl ashing until the height of the vent cap meets the minimum height requirements specifi ed in Diagram 5 or local codes. Note that for steep roof pitches, the vertical height must be increased.
Diagram 5
Minimum Vent
Roof Pitch
at to 7/12 2 0.61 over 7/12 to 8/12 2 0.61 over 8/12 to 9/12 2 0.61
over 9/12 to 10/12 2.5 0.76 over 10/12 to 11/12 3.25 0.99 over 11/12 to 12/12 4 1.22 over 12/12 to 14/12 5 1.52 over 14/12 to 16/12 6 1.83 over 16/12 to 18/12 7 2.13 over 18/12 to 20/12 7.5 2.29
A poor draft, or down drafting can result from
high wind conditions near big trees or adjoining roof lines, in these cases, increasing the vent height may solve the problem.
7) Ensure vent is vertical and secure the base of the fl ashing to the roof with roofi ng rails, slide storm collar over the pipe section and seal with a mastic.
8) Install the vertical termination cap by twist­locking it.
Note: Any closets or storage spaces, which
the vent passes through must be enclosed.
Height
Feet Meters
Offset Chart
26
Diagram 3
"THIS UNIT MUST ALWAYS TERMINATE / VENT DIRECTLY TO THE OUTDOORS."
Regency Gemfi reTM Gas Fireplace
Page 27
INSTALLATION
UNIT INSTALLATION
(With Horizontal Termination Flex
System)
Note: A top clearance of 3"(76mm) and
side & bottom clearance of 2"(51mm) must be maintained; except when passing through a wall, ceiling, or at the termination where the use of a restop or wall thimble reduces the required clearance to 1-1/2" (38mm). We recommend framing a 11"(279mm) x 11"(279mm) (inside dimensions) hole to give structural rigidity for mounting the termination.
1) Locate the unit in the framing, rough in the
gas (preferably on the right side of the unit). Locate the centerline of the termination and mark wall accordingly. Cut an 11"(279mm) hole in the wall (inside dimension).
4) Separate the 2 halves of the wall thimble and securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall. The thimble halves slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls.
5) Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap that show which way is up). This will position the termination cap with proper down slope for draining water. Fasten the cap to the outer wall with the 4 supplied screws.
6) Pull the centre 5"(127mm) liner and outer
8"(203mm) liner out enough to slip over
the fl ue collars of the fi replace. (You may wish to cut the liner shorter to make it more workable.) Do not bend liner more than 90
The liners must slip over the collars a minimum of 1-3/8".
7) Apply Mill Pac over the fi replace inner collar and slip the 5"(127mm) liner down over it and attach with 3 supplied screws.
8) Do the same with the 8"(203mm) liner.
o
IMPORTANT: Do not locate termination hood where excessive snow or ice buildup may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.
ASTROCAP XL
DIMENSIONS (946-623/P)
.
INSTALLATION
Note: If installing termination on a siding
covered wall, a vinyl siding standoff or vinyl furring strips must be used to ensure that the termination is not recessed into the siding.
2) Level the replace and fasten it to the fram-
ing using nails or screws through the nailing strips.
3) Assemble the vent assembly by applying Mill Pac to the 5"(127mm) inner collar of the termination and slipping the 5"(127mm) liner over it at least 1-3/8" (35mm). Fasten with the 3 screws (drilling pilot holes will make this easier). Apply Mill Pac or high temperature silicone to the 8"(203mm) fl ex pipe and slip it over the 8" outer collar of the vent terminal at least 1-3/8"(35mm) and fasten with the 3 screws.
NOTE: Horizontal sections must be sup-
ported at intervals not exceeding 3 feet (0.9 meter). (Flame picture and performance will be affected by sags in the liner).
9) Apply a bead of silicone between the thimble
and termination and around the outer edge of the terminal at the wall in order to keep the water out.
5”(127mm) dia. flue pipe with spring spacer
8" (203) dia. air intake
Screws
Wall Thimble*
*Mandatory on all
horizontal terminations.
"THIS UNIT MUST ALWAYS TERMINATE / VENT DIRECTLY TO THE OUTDOORS."
2”x4”or2”x6”
51mm X 102mm x 51mm x 152mm
AstroCap XL
Termination Cap
Screws
Vinyl Siding
Regency Gemfi reTM Gas Fireplace 27
Page 28
38mm
184mm
83mm
Located on the right
side of the firebox.
102mm
INSTALLATION
Gem54-NG SYSTEM DATA
Min. Supply Pressure 1.13 kpa Low Setting Man.
Pressure Max. Manifold
Pressure Injector Size #32 DMS Minimum Input 26.2 mj
Maxiumm Input 35.9 mj
INSTALLATION
Gem54-LPG SYSTEM DATA
Min. Supply Pressure 2.74 kpa Low Setting Man.
Pressure Max. Manifold
Pressure Injector Size #51 DMS Minimum Input 26.4 mj
Maxiumm Input
Gem54-ULPG SYSTEM DATA
Min. Supply Pressure 2.74 kpa Low Setting Man.
Pressure Max. Manifold
Pressure Injector Size #52 DMS Minimum Input
Maxiumm Input
0.87 kpa
1.6 kpa
2.49 kpa
32.2 mj
1.6 kpa
2.49 kpa
22.6 mj
28.7 mj
0.4kpa
IMPORTANT : Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open fl ame for leak testing.
PILOT ADJUSTMENT
Periodically check the pilot fl ames. Correct ame pattern has three strong blue fl ames: 1 fl owing around the thermopile, 1 around the thermocouple and 1 fl owing across the burner (it does not have to be touching the burner).
Note: If you have an incorrect fl ame pattern,
contact your Regency further instructions.
Incorrect fl ame pattern will have small, probably yellow fl ames, not coming into proper contact with the rear burner or thermopile or thermocouple.
®
dealer for
Note: To properly check gas pressure, both
inlet and manifold pressures should be checked using the valve pressure ports on the valve.
1) Make sure the valve is in the "OFF"
position.
2) Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a
1/8" (3.175 mm) wide fl at screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" (7.9 mm) ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with the unit burning and the setting should be within the limits specifi ed on the safety label.
6) When fi nished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" (3.175 mm) fl at screwdriver. Note: Screw should be snug,
but do not over tighten.
S.I.T. VALVE DESCRIPTION
1) Gas on/off knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection Point
HIGH ELEVATION
This unit is approved for altitude 0 to 1372m.
GAS LINE
INSTALLATION
Since some municipalities have additional local codes it is always best to consult with your local authorities.
When using copper or fl ex connectors use only approved fi ttings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and fl ex connectors are usually considered to meet this requirement.
NOTE: A shutoff / dante valve should be sup­plied in or near the unit (or as per local codes) for ease of servicing this appliance.
28
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.
Regency Gemfi reTM Gas Fireplace
Page 29
INSTALLATION
CONVERSION KIT # 476-967 FROM NG TO LPG
CONVERSION KIT #476-968 FROM NG TO ULPG
FOR GEM54™ USING SIT 820 NOVA GAS VALVE
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER
IF IN DOUBT DO NOT DO THIS CONVERSION !!
INSTALLATION
Each Kit contains one LPG Conversion Kit # 476-968
LPG Conversion Kit Contains: Qty. Part # Description
1 904-645 Burner Orifi ce #51 1 918-590 Decal "Converted to
LPG" 1 908-528 Red "LPG" label 1 904-529 5/32" Allen Key 1 910-037 LPG Injector
(Pilot Orifi ce) 1 918-798 Instruction Sheet
1
)
Warning:
Turn off the unit by way of the wall switch or remote. Allow unit to cool at least 10 min. - prior to removing the faceplate.
2) Shut off the gas supply to the unit.
3) Remove the faceplate by lifting it up off the hinges on the sides of
the fi rebox.
Each Kit contains one ULPG Conversion Kit # 476-967
ULPG Conversion Kit Contains: Qty. Part # Description
1 904-390 Burner Orifi ce #52 1 918-272 Decal "Converted to
ULPG" 1 918-273 Red "ULPG" label 1 904-529 5/32" Allen Key 1 910-037 LPG Injector
(Pilot Orifi ce) 1 918-798 Instruction Sheet
4) Remove the door frame overlay by swinging out 45 bottom and lift up and out.
5) Remove the glass door by removing 3 screws and then swinging the door out 45
6) Remove the following, if installed:
a) Colbalt Glass Crystals b) Optional Ceramic Stones c) Pebbles d) Stainless Steel Panels (see instructions in manual)
Regency Gemfi reTM Gas Fireplace 29
o
from the bottom and lift up and out.
Glass door screws
o
from the
Page 30
INSTALLATION
7) Loosen 6 screws that secure the burner extenders. on burner tray, located behind the burner on either side of the pilot assembly.
8)
Lift out the 2 burner tray extenders.
INSTALLATION
Burner tray extenders
Burner tray
11) With burner removed - lift out burner tray.
12) Pull off the pilot cap to expose the pilot orifi ce. (see below)
Burner tray extenders
9) After extenders have been removed. Remove the 2 screws that secure the burner tray, at the base of the fi rebox.
10) Slide the burner to the left and lift it out.
Location of screws securing burner
Burner Bracket
Pilot Orifi ce
13) Unscrew the pilot orifi ce with the Allen key and replace with the LPG pilot orifi cein the kit and replace pilot cap (see below).
14)
Remove burner orifi ce with a 1/2" wrench and discard. Use another wrench to hold on to the elbow below the orifi ce (see below).
Pilot Cap
30
15) Reinstall new burner orifi ce LPG stamped #51 or ULPG burner
orifi ce stamped # 52 and tighten.
Regency Gemfi reTM Gas Fireplace
Page 31
INSTALLATION
15) Turn control knob to the “OFF” position.
16) Remove the black protection cap by
hand from the high-low knob (Fig.1).
Fig. 1
17) Insert a 5/32” or 4mm Allen wrench into
the hexagonal key-way of the screw (Fig. 2), rotate it counter-clockwise until it is free and extract it.
20) Using the Allen wrench as shown in
Fig.4, rotate the screw clockwise until snug, do not overtighten.
Fig.4
WARNING!
Do not overtighten the screw.
Recommended to grip
the wrench by the short side.
21) Verify that if the conversion is from
NG to LPG, the screw must be re­assembled with the red o-ring visible (Fig. 5).
23) Attach the label "This unit has been
converted to LPG (or ULPG)" near or on top of the serial # decal.
24) Replace yellow "NG" label with red
"LPG" or ULPG label.
25) Adjust aeration settings according to the
fuel type.
NG 13mm LP Full open 22 mm ULPG Full open 22mm
26) Reverse steps 11-1
27) Check for gas leaks.
28) Check inlet and outlet pressures.
29) Check operation of fl ame control.
30) Check for proper fl ame appearance.
INSTALLATION
Fig.2
18) Check that the screw is clean and if
necessary remove dirt.
19) Flip the screw (Fig. 3).
Red o-ring visible
LPG Configuration
Fig.5
22) Re-assemble the black protection cap
(Fig. 6).
Fig. 6
WARNING!
Also check that the pilot and
main burner injectors
Fig.3
Regency Gemfi reTM Gas Fireplace 31
are appropriate for the gas type.
Page 32
INSTALLATION
The burner aeration is factory set but may need adjusting due to either the local gas supply or altitude. Open the air shutter for a blue fl ame or close for a more yellow fl ame.
INSTALLATION
Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges.
AERA TION ADJUSTMENT
Minimum Air Shutter Opening:
NG 13mm LP Full open 22 mm ULPG Full open 22mm
WIRING DIAGRAM
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
CAUTION: Carbon will be produced if air shutter
is not fully open.
Note: Any damage due to carboning
resulting from improperly setting the aeration controls is NOT covered under warranty.
32
Regency Gemfi reTM Gas Fireplace
Page 33
OPTIONAL STAINLESS STEEL
py
pyp y
REFLECTIVE PANEL INSTALLATION
INSTALLATION
Before you start:
Stainless panels must be inspected for scratches and dimples prior to installation. All claims to be recorded at this time. Claims for damage after installa­tion will not receive consideration.
To protect the fi nish during installation and handling - cotton gloves MUST be worn at all times while handling the panels (even when removing protective coating).
Stainless panels will discolor a little during normal operation. This is normal and should not be considered a defect.
All hand and fi nger marks MUST be cleaned off with a soft cloth and a stainless steel cleaner. Most stainless steel cleaners leave a fi lm/residue on the surface of the panels. Use an ammonia based cleaner (ie. glass cleaner) to remove this fi lm before applying heat to the unit. Failure to do this will result in burn stain on panels which you will be unable to remove. This is not a warranty item.
Warning: Turn off the unit by way of the wall switch or remote. Allow unit to cool at least 10 min. - prior to removing faceplate.
will be unable to remove. Not protected by product warranty.
1) Position the left side panel in place - top of panel in fi rst, then fi t the
bottom tab into the slot at the bottom of the fi rebox as shown below. Repeat for right side panel.
Left Side
Panel
2) Fit the back panel into position by clearing the pilot shield - bottom of panel goes in fi rst.
Then fi t the tabs on the bottom left and right side of the back panel
into the slots at the base of the fi rebox.
Right side panel in position
INSTALLATION
Fit side panel tab into slot
Left side panel in position
Secure the back panel in place by placing the brackets over the
screws on the top of the inside left and right side of the fi rebox and tighten the screw to hold the bracket against the back panel.
Back Panel
Right side back panel tab fi tted into slot
Bracket shown in place on right side of the fi rebox
Regency Gem reTM Gas Fireplace 33
Page 34
INSTALLATION
GLASS CRYSTALS OR OPTIONAL CERAMIC STONES
Gem54 Glass Crystal/Optional Ceramic Spa Stone Quantity
Glass Crystals only 2 bags
*Ceramic Spa Stones 1 bag glass crystals + 70
* 1 bag of glass crystals must be used on burner when using ceramic spa stones.
Evenly spread an appropriate amount of glass crystals
INSTALLATION
(approx. 12mm) or optional ceramic stones over the burner. Ensure the crystals or stones do not excessively overlap as this will effect the fl ame pattern.
NOTE: When installing, use either the supplied crystals or optional ceramic stones with one bag of glass crystals. Only the supplied and approved Cobalt Blue Glass Crystals or Optional Ceramic Stones are to be used with this fi replace. Use of any other type of glass crystals or stones can alter the unit's performance and is not covered under warranty.
Warning: T urn off the unit by way of the wall switch or remote.
Allow unit to cool at least 10 min. - prior to removing
faceplate.
ceramic spa stones
INSTALLATION ON BURNER
Glass Crystals shown on Burner
Optional Ceramic Stones + Glass Crystals shown on burner.
OPTIONAL PEBBLE INSTALLATION
FOR FIREBOX BASE
There is an optional pebble package to choose from:
1) Natural River Pebbles Spread the pebbles evenly on the exposed base of the fi rebox. Pebbles are NOT to be placed anywhere on the burner or over top of the Cobalt Blue
Glass Crystals or optional Ceramic Spa Stones.
Warning: Turn off the unit by way of the wall switch or remote. Allow unit to cool at least 10 min. - prior to removing faceplate.
NOTE: Only the supplied and approved pebbles are to be used.
Use of any other type of pebbles or material can create a danger and will void warranty.
34
Natural River Pebbles shown surrounding the Burner
Regency Gemfi reTM Gas Fireplace
Page 35
INSTALLATION
SCREEN & DOOR FRAME OVERLAY INSTALLATION
Before you start:
Stainless must be inspected for scratches and dimples prior to installation. All claims to be recorded at this time. Claims for damage after installation will not receive consideration.
To protect the  nish during installation and handling - cotton gloves MUST be worn at all times while handling the panels (even when removing protective coating).
Stainless will discolor a little during normal operation. This is normal and should not be considered a defect.
All hand and fi nger marks MUST be cleaned off with a soft cloth and a stainless steel cleaner. Most stainless steel cleaners leave a fi lm/residue on the surface of the panels. Use an ammonia based cleaner (ie. glass cleaner) to remove this fi lm before applying heat to the unit. Failure to do this may result in burn stains which you will be unable to remove. This is not a warranty item.
Warning: Turn off the unit by way of the wall switch or remote. Allow unit to cool at least 10 min. - prior to removing faceplate.
1) Orient the safety screen so the raised part of the screen faces up.
2) Place the screen into the back side of the door frame as shown
below.
4) Install the door frame overlay by hooking the top fl ange over top of
the glass door, push in the bottom of the door frame overlay to secure in place.
INSTALLATION
3) Hold the screen in place in door frame as shown below - install door frame with screen onto unit.
Glass Door
5) Door frame and screen installed on the Gemfi re 54.
6) Place 2 of the supplied magnets on the lower corners of the Door
Frame Overlay, this will keep the Faceplate in postion after it has been installed.
Door Frame
Overlay
Screen
Magnet Position
Regency Gem reTM Gas Fireplace 35
Page 36
INSTALLATION
FACEPLATE INSTALLATION
Warning: Turn off the unit by way of the wall switch or remote. Allow unit to cool at least 10 min. - prior to removing the faceplate.
) Secure the left side mounting bracket to the backside of the faceplate
as shown below. Use 3 screws supplied to secure the mounting bracket in place. Repeat for right side.
INSTALLATION
2) Install the faceplate to the unit by hooking the left and right side
mounting brackets into the mounting slots at the side of the fi rebox as shown below. It is recommended that you use the fi rst mounting slot (the one closest to the door frame overlay) out of the 5 so that the faceplate and door frame overlay are fl ush with one another. See diagram below.
NOTE: There are 5 mounting slots available, this is to accomodate
any fi nishing that protrudes slightly beyond the faceplate.
Left Side
Mounting Bracket
NOTE: Ensure that the faceplate is positioned correctly when installing the mounting brackets to the faceplate. There is a top and bottom, the top of the faceplate is insulated - the bottom is uninsulated.
See diagram below.
Top
Bottom
36
Mounting Bracket
shown in place
First Mounting Slot
(recommended)
Regency Gemfi reTM Gas Fireplace
Page 37
IMPORTANT NOTE
To ensure the gap between the door frame and the faceplate are equal from side to side you may need to slide the faceplate slightly to the left or right accordingly.
Also if necessary, the faceplate may be adjusted up and down by loosening the top screw as shown in the diagram below and sliding the plate up or down as required.
INSTALLATION
INSTALLATION
Faceplate Mounting Slots
Completed Faceplate & Door Frame Overlay Installation
Faceplate Screen Door Frame
Regency Gem reTM Gas Fireplace 37
Page 38
OPERATING INSTRUCTIONS
OPERATING
INSTRUCTIONS
1) Read and understand these instructions
before operating this appliance.
2) Check to see that all wiring is correct and enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass in the glass door frame
is properly positioned. Never operate the appliance with the glass removed.
5) Verify that the venting and cap are unobstructed.
6) The unit should never be turned off, and on again without a minimum of a 60 second wait.
FIRST FIRE
OPERATION
The FIRST FIRE in your heater is part of the paint curing process. To ensure the paint is properly cured, it is recommended you burn your fi replace for at least four (4) hours the fi rst time.
When fi rst operated, the unit will release an odour caused by the curing of the paint and the burning off of any oils remaining from manufac­turing. Smoke detectors in the house may go off at this time. Open a few windows to ventilate the room for a couple of hours. The glass may require cleaning.
NOTE: When the glass is cold and the appliance
is lit, it may cause condensation and fog the glass. This condensation is normal and will disappear in a few minutes as the glass heats up.
DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS STILL HOT!
DO NOT BURN THE UNIT WITHOUT THE GLASS DOOR IN PLACE.
LIGHTING
PROCEDURE
NOTE: The Gas ON/OFF knob cannot be turned from "ON", "PILOT" or "OFF" unless it is partially depressed.
Warning: Turn off the unit by way of the wall
switch or remote. Allow unit to cool at least 10 min. - prior to removing faceplate.
1) Ensure the wall mounted switch or remote is in the "OFF" position.
2) Ensure unit has cooled at least 10 min. -
prior to removing faceplate.
3) Turn the gas control knob so the indicator
points to the "OFF" position and wait 5 minutes for any gas in the combustion chamber to escape.
4) Turn the gas control knob counterclockwise so the indicator points to the "PILOT" position. Depress the gas control knob fully. Depress the igniter button until the pilot lights. After approximately one minute, release the gas control knob. The pilot fl ame should continue to burn.
Only when the pilot holds, without pressure
being applied to the gas control knob, re-install the glass door to the unit. The unit must not be operated without the glass door in place.
If the pilot does not remain lit, repeat opera-
tion allowing a longer period before releasing gas control knob.
5) When the pilot stays lit, turn the gas control knob to the "ON" position.
6) Use the wall switch or remote control to turn the unit ON.
7) Re-install faceplate.
NOTE: When using the remote control refer to
the remote manual.
NOTE: If there is no spark present at the pilot
when depressed, the AA battery may be weak. Refer to "DC Spark Battery Replacement" section.
NORMAL OPERATING
SHUTDOWN
PROCEDURE
Warning: Turn off the unit by way of the wall
switch or remote. Allow unit to cool at least 10 min. - prior to removing faceplate.
1) Turn the wall mounted switch or remote to the "OFF" position.
2) Press "OFF" on the remote control.
3) Turn the gas control knob to the "OFF"
position to turn off the pilot.
SOUNDS OF
GAS APPLIANCES
It is possible that you will hear some sounds from your gas appliance. This is perfectly normal due to the fact that there are various gauges and types of steel used within your appliance. Listed below are some examples. All are normal operating sounds and should not be considered as defects in your appliance.
Burner Tray:
The burner tray is positioned directly under the burner and is made of a different gauge material from the rest of the fi rebox and body. Therefore, the varying thicknesses of steel will expand and contract at slightly different rates which can cause "ticking" and "cracking" sounds. Y ou should also be aware that as there are temperature changes within the unit these sounds will likely re-occur. Again, this is normal for steel fi reboxes.
Pilot Flame:
While the pilot fl ame is on it can make a very slight "whisper" sound.
Gas Control Valve: As the gas control valve turns ON and OFF, a dull clicking sound may be audible, this is normal operation of a gas regulator or valve.
During the fi rst few fi res, a white fi lm may develop on the glass front as part of the curing process. The glass should be cleaned after the unit has cooled down or the fi lm will bake on and become very diffi cult to remove. Use a non-abrasive cleaner and DO NOT A TTEMPT TO CLEAN THE GLASS WHILE IT IS HOT.
38
Unit Body/Firebox:
Different types and thicknesses of steel will expand and contract at different rates resulting in some "cracking" and "ticking" sounds will be heard throughout the cycling process.
Regency Gemfi reTM Gas Fireplace
Page 39
OPERATING INSTRUCTIONS
COPY OF LIGHTING PLATE INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
This appliance must be installed in accordance with local codes, if any; if none, follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Natural Gas and Propane Installation Codes,
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner’s information manual provided with this appliance. For assistance or additional information consult a qualified installer, service agency or gas supplier.
A) This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these
instructions exactly.
B) BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the fl oor
because some gas is heavier than air and will settle on the fl oor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance.
- Do not touch any electric switch, do not use any phone in your building.
- Immediately call your gas supplier from a neighbours phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fi re department.
C) Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not
push in or turn by hand, don’t try to repair it, call a qualifi ed service technician. Forced or attempted repair may result in a fi re or explosion.
D) Do not use this appliance if any part has been under water. Immediately call a qualifi ed service
technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
E) This appliance needs fresh air for safe operation and must be installed so there are provisions for
adequate combustion and ventilation air.
CAUTION: Hot while in operation. Do not touch. Severe Burns may result. Due to high surface temperatures keep children, clothing and furniture, gasoline and other liquids having fl ammable vapors away. Keep burner and control compartment clean. See installation and operating instructions accompanying appliance.
CSA B149.1. (Australia: AS5601-2004, New Zealand: NZS 5261)
OPERATION
LIGHTING INSTRUCTIONS
STOP! Read the safety information above on this label.
1) Push in gas control knob slightly and turn clockwise to “OFF”. Knob cannot be turned from “PILOT” to “OFF” unless knob is pushed in slightly. Do not force.
PILOT BURNER
VEILLEUSE
THERMOPILE
ELEMENT THERMO­ELECTRIQUE
2) Wait fi ve (5) minutes to clear out any gas. If you then smell gas STOP! Follow step “B” in the Safety Information above on this label. If you don’t smell gas, go to the next step.
3) Turn knob on gas control counterclockwise to“PILOT”.
4) Push in control knob all the way and hold in until the pilot lights up. Continue to hold the control knob in for about 20 seconds after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 1) to 4). If knob does not pop up when released, stop and immediately call your service technician or gas supplier. If the pilot will not stay lit after several tries, turn the gas control knob to “OFF” and call your service technician or gas supplier.
5) Turn gas control knob counterclock-wise to “ON”.
6) Turn the unit on.
OFF
TO TURN OFF GAS APPLIANCE
1) Turn off the unit.
2) Push in the gas control knob slightly and turn clockwise to “OFF”. Do not force.
3) Turn off all electric power to the appliance if service is to be performed. You may shut off the pilot during prolonged non use periods to conserve fuel.
DO NOT REMOVE THIS INSTRUCTION PLATE
918-583
Regency Gem reTM Gas Fireplace 39
Page 40
MAINTENANCE
MAINTENANCE
INSTRUCTIONS
1) Always turn off the gas valve before cleaning.
For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year.
2) Clean appliance and door with a damp cloth (never when unit is hot). Never use an abrasive cleaner. The glass should be cleaned with a gas fi replace glass cleaner.
The glass should be cleaned when it starts looking cloudy.
3) The faceplate is fi nished in a heat resistant paint and should only be refi nished with heat resistant paint. Regency® uses StoveBright Paint - Metallic Black #6309.
Note: Faceplates and inner panels made
from stainless steel will naturally change color over time.
4) Make a periodic check of burner for proper
position and condition. Visually check the ame of the burner periodically, making sure the fl ames are steady; not lifting or fl oating. If there is a problem, call a qualifi ed service person.
5) The appliance and venting system must be inspected before use, and at least annually, by a qualifi ed fi eld service person, to ensure that the fl ow of combustion and ventilation air is not obstructed.
Note: Never operate the appliance without
the glass properly secured in place.
6) Do not use this appliance if any part has been
under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under
MAINTENANCE
water.
7) In the event this appliance has been serviced check that the vent-air system has been properly resealed & reinstalled in accordance with the manufacturer's instructions.
8) Verify operation after servicing.
GENERAL VENT
MAINTENANCE
Conduct an inspection of the venting system semi-annually. Recommended areas to inspect as follows:
1) Check the Venting System for corrosion in areas that are exposed to the elements. These will appear as rust spots or streaks, and in extreme cases, holes. These components should be replaced immediately.
2) Remove the Cap, and shine a fl ashlight down the Vent. Remove any bird nests, or other foreign material.
3) Check for evidences of excessive condensation, such as water droplets forming in the inner liner, and subsequently dripping out the joints, Continuous condensation can cause corrosion of caps, pipe, and fi ttings. It may be caused by having excessive lateral runs, too many elbows, and exterior portions of the system being exposed to cold weather.
4) Inspect joints, to verify that no pipe sections or fi ttings have been disturbed, and consequently loosened. Also check mechanical supports such as Wall Straps, or plumbers' tape for rigidity.
THERMOPILE /
THERMOCOUPLE
1) Remove the valve tray by following the
procedures from "Valve Tray Replacement" section.
2) Disconnect thermocouple by loosening nut from the valve with a 9mm wrench. Disconnect thermopile by loosening 2 screws marked TP on the valve.
3) Remove 2 screws from the pilot assembly and pull up far enough to be able to loosen the thermocouple or thermopile with a 7/16" wrench. NOTE: the pilot line is very fragile, use caution when pulling it up.
4) Drop the thermocouple or thermopile down through the extrusion and pull it out of the unit.
GLASS GASKET
If the glass gasket requires replacement use a tadpole glass gasket (Part # 936-159).
GLASS DOOR
Your Regency® fi replace is supplied with high temperature 5mm-Ceramic glass. If your glass requires cleaning, we recommend using an approved glass cleaner available at all authorized dealers. Do not use abrasive materials.
CAUTION & WARNINGS:
* Do not clean when the glass is hot. * The use of substitute glass will void all product
warranties.
* Care must be taken to avoid breakage of the
glass. * Do not strike or abuse the glass. * Do not operate this fi replace without the
glass front or with a cracked or broken glass
front. * Wear gloves when removing damaged or
broken glass. * Replacement of the glass panel(s) should be
done by a licensed or qualifi ed service per
son.
GLASS REPLACEMENT
In the event that you break your glass by impact, purchase your replacement from an authorized Regency® dealer only.
Replacement glass is shipped already installed into the door frame.
CAUTION: Wear gloves when removing damaged or broken glass.
WARNING: Do not operate the appliance with the glass panels removed, cracked or broken. Replacement of the glass panels should be done by a licensed or qualifi ed service person.
40
5) Reinstall the new ones in reverse order.
Regency Gemfi reTM Gas Fireplace
Page 41
GLASS DOOR REMOVAL
Warning: Turn off the unit by way of the wall switch or remote.
Allow unit to cool at least 10 min. - prior to removing faceplate.
1) Turn the unit off and allow it to cool down to room temperature
- prior to handling.
2) Turn off the gas supply to the unit.
3) Remove the faceplate by lifting it up off the hinges on the sides of the
rebox.
MAINTENANCE
5) Remove the glass door.
a) Remove the 3 screws shown below at the bottom of the glass
door.
b) Swing the door out 45o from the bottom and lift up and out.
4) Remove the door frame overlay by swinging out 45
and lift up and out.
o
from the bottom
MAINTENANCE
Regency Gem reTM Gas Fireplace 41
Page 42
MAINTENANCE
DC SPARK
BOX BATTERY
REPLACEMENT
1) Remove the faceplate by lifting it up off the
hinges on the sides of the fi rebox.
2) Remove the door frame overlay by swinging out 45o from the bottom and lift up and out.
3) Remove the DC spark box braket assembly by lifting the bracket tab out from the fi rebox.
DC SPARK BOX REPLACEMENT
1) Remove the faceplate by lifting it up off the
hinges on the sides of the fi rebox.
2) Remove the door frame overlay by swinging
3) Disconnect the spark electrode wire from the
4) Remove the DC spark box braket assembly by
o
from the bottom and lift up and out.
out 45
DC spark box shown in the image below.
Spark Electrode Wire
lifting the bracket tab out from the fi rebox.
5) Disconnect the 2 DC spark generator wires from the DC Spark box located just behind the bracket tab as shown.
Generator Wires
6) Remove the 2 screws that secure the DC spark box to the bracket.
DC Spark Box Bracket Assembly
partially removed.
4) Remove the battery cover from the DC Spark Box.
MAINTENANCE
5) Remove the AA battery and replace with a new one.
6) Reverse steps 4 to 1.
DC Spark Box Bracket Assembly
partially removed.
DC Spark Box Bracket Assembly
removed from fi rebox.
DC Spark Box
7) Replace DC spark box and reverse steps.
42
Regency Gemfi reTM Gas Fireplace
Page 43
VALVE TRAY REPLACEMENT
MAINTENANCE
Warning: Turn off the unit by way of the wall switch or remote.
Allow unit to cool at least 10 min. - prior to removing faceplate.
1) Turn the unit off and allow it to cool down to room temperature prior to handling.
2) Turn off the gas supply to the unit.
3) Remove the faceplate by lifting it up off the hinges on the sides of the
rebox.
5) Remove the glass door. a) Remove the 3 screws shown below at the bottom of the glass
.
door
b) Swing the door out 45o from the bottom and lift up and out.
6) Remove the burner tray by undoing the 2 screws in between the bot-
tom cover and burner on the fi rebox. Carefully lift the burner up and out ensuring not to spill the glass crystals.
4) Remove the door frame overlay by swinging out 45o from the bottom and lift up and out.
MAINTENANCE
Aerial View of the inside of the unit shown.
Regency Gem reTM Gas Fireplace 43
Page 44
MAINTENANCE
7) Remove bottom cover by undoing 3 screws securing it to the rebox
base, lift up and out.
Aerial View of the inside of the unit shown.
8) Disconnect the ON/OFF connector wires from the valve.
10) Unplug the Ignitor wire from the DC Sparker.
Ignitor Wire
11) Remove the valve tray by undoing 12 screws.
ON/OFF Connector Wires
9) Disconnect the DC Sparker leads at the valve.
MAINTENANCE
12) Slightly lift out valve tray.
13) Disconnect the inlet gas line.
DC Sparker Lead
44
14) Replace valve and reverse steps.
Regency Gemfi reTM Gas Fireplace
Page 45
MAIN ASSEMBLY
PARTS LIST
Part # Description
1) 910-074 Spark Generator Switch c/w Wire
2) 476-032 DC Spark Mounting Bracket 910-073 Spark Generator Battery Holder 910-078 Battery AA 910-363 White Wall Switch 910-366 White Switch Plate Wire
3) 476-100 Bottom Cover NG/LP
4) 476-530 Burner Assembly NG/LP
5) 476-578/P Valve Assembly NG 476-580/P Valve Assembly LP
6) 910-568 Valve 820
7) 910-008 Pilot Assembly - NG
8) 904-688 Orifi ce # 32 904-645 Orifi ce # 51
9) 476-101 Burner Extenders
904-658 Inlet Gas Flex Line SS 370-055 Flue Collar Gasket
476-023 Plate Relief Gasket 476-055 Valve Tray Gasket 521-035 Inner Flue Collar Gasket
940-359/P Flush Glass 476-011 Flush Glass
910-882 Wire (Valve to Burner ON/OFF) 948-409 Flue Collar 948-415 Lifting Handle
918-784 Manual
9
7
8
3
2
1
4
5
6
Regency Gemfi reTM Gas Fireplace 45
PARTS LIST
Page 46
PARTS LIST
ACCESSORIES
Part # Description
30) 476-907 Refl ective Stainless Steel Panels
31) 476-944 Faceplate & Door Frame Overlay - Black 476-947 Faceplate & Door Frame Overlay - Stainless Steel
946-671 Cobalt Blue Glass Crystals 946-672 Natural River Pebbles
476-540 Door frame w/ Glass
32) 476-532 Screen Assembly
PARTS LIST
30
32
31
46
Regency Gemfi reTM Gas Fireplace
Loading...