Regency E33S User Manual

E33 Sunrise
MODELS: E33S-NG1 Natural Gas E33S-LP1 Propane
Gas Insert
Owners &
Installation Manual
www.regency-fi re.com
WARNING: If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
918-747
Tested by:
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
FOR YOUR SAFETY What to do if you smell gas:
Do not try to light any appliance Do not touch any electrical switch:
do not use any phone in your building.
Immediately call your gas supplier
from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
02/16/09
FPI GAS FIREPLACE INSERT
TO THE NEW OWNER
Congratulations! You are the owner of a state-of-the-art Gas Insert by FPI.
The E33 SunriseTM Gas Insert has been designed to provide you with all the warmth and charm of a fi replace, at the fl ick of a switch. The E33S-NG1 and E33S-LP1 have been approved by Warnock Hersey for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your FPI Fireplace.
2
Regency® E33S-1 Sunrise Gas Insert
TABLE OF CONTENTS
SAFETY LABEL
Copy of the Safety Label ...............................................4
REQUIREMENTS
MA Code - CO Detector.................................................5
UNIT DIMENSIONS
Unit Dimensions ............................................................6
INSTALLATION
Important Message .......................................................7
For Your Safety ..............................................................7
Gas Pressure Testing ....................................................7
Specifi cations ................................................................7
Installation Into A Solid Fuel Burning Fireplace Or
Factory Built Fireplace ...................................................7
Before You Start ............................................................7
Installation Checklist .....................................................8
Materials Required ........................................................8
Minimum Fireplace Opening..........................................8
Minimum Clearances To Combustibles .........................9
Combustible Mantel Clearances..................................9
Gas Connection ..........................................................10
Venting.........................................................................10
Flue Liner Installation ..................................................10
Gas Pipe Pressure Testing .......................................... 11
SIT Valve Description .................................................. 11
Gas Insert Aeration System ......................................... 11
Conversion from NG to LP ..........................................12
Wiring Diagrams ..........................................................15
Optional Remote Control ............................................ 16
Optional Wall Thermostat ...........................................16
Glass Crystal or Ceramic Stone Installation ................ 17
Glass Door Installation ................................................17
Faceplate & Door Frame Installation ........................... 18
Optional Hearth Trim Installation ................................. 20
OPERATING INSTRUCTIONS
Final Check..................................................................21
First Fire ......................................................................21
Operating Instructions .................................................21
Lighting Procedure ......................................................21
Shutdown Procedure ................................................... 21
Copy Of Lighting Instruction Plate .............................. 22
Automatic Convection Fan Operation..........................22
Normal Operating Sounds Of Gas Appliances ............ 22
MAINTENANCE
Maintenance Instructions.............................................23
General Vent Maintenance ..........................................23
Door Glass ..................................................................23
Valve Tray Replacement ..............................................24
Fan Replacement ........................................................ 26
PARTS LIST
Main Assembly ............................................................28
Contemporary Faceplate & Door Frame .....................29
WARRANTY
Warranty ......................................................................31
Regency® E33S-1 Sunrise Gas Insert 3
SAFETY LABEL
This is a copy of the safety label that accompanies the E33 SunriseTM Gas Insert. We have printed a copy of the contents here for your review. The safety label is located on a plate inside the base of the unit visible when the bottom louver is opened.
NOTE: FPI units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
INSTALLATION
For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, fl exible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appli­ances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.
4
Regency® E33S-1 Sunrise Gas Insert
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
INSTALLATION
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
Regency® E33S-1 Sunrise Gas Insert 5
UNIT DIMENSIONS
INSTALLATION
6
Regency® E33S-1 Sunrise Gas Insert
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The FPI Gas Insert must be installed in accord­ance with these instructions. Carefully read all the instructions in this manual fi rst. Consult the building authority having jurisdiction to determine the need for a permit prior to starting the installation.
NOTE: Failure to follow the instructions could cause a malfunction of the heater which could result in death, serious bodily injury, and/or property damage. Failure to follow these instructions may also void your fi re insurance and/or warranty.
FOR YOUR SAFETY
This appliance requires air for proper combustion. Always provide adequate combustion and ventilation air. Follow instructions and information in CSA B149.1 (in Canada) or the National Fuel Gas Code ANS Z223.1/NFPA (in the USA), regarding requirements for combustion and ventilation air.
GAS PRESSURE
TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa).
SPECIFICATIONS
At pressures over 1/2 psig, the pipe to the unit must be disconnected. Gas Input Capacity: Natural Gas 26,000 Btu/h Propane 23,000 Btu/h
Min. Input:
Natural Gas 13,500 Btu/h Propane 12,000 Btu/h
INSTALLATION INTO A
SOLID FUEL BURNING
FIREPLACE OR
FACTORY BUILT
FIREPLACE
The E33S Gas Insert have been tested and approved to be vented into any masonry fireplace or approved solid fuel burning factory built fi replace that will allow the insert to physically fi t into the fi rebox. Refer to the "Minimum Fireplace Dimensions" section.
If the factory built fi replace* height is too low for your Insert, you may remove the smoke baffl e plate and damper from the factory built fi replace as long as these items are saved and are reinstalled in the event that the Insert is removed. NOTE: Any alterations made to the listed solid fuel burning factory built fi replace may void the listing of the replace. Cutting any sheet-metal parts of the fi replace, in which the gas fi replace insert is to be installed, is prohibited.
If the factory-built fi replace has no gas access hole(s) provided, an access hole of
1.5" (37.5mm) or less may be drilled through the lower sides or bottom of the fi rebox in a proper workmanship like manner. This access hole must be plugged with non­combustible insulation after the gas supply line has been installed.
The fi replace and fi replace chimney must be clean and in good working order and constructed of non-combustible materials and chimney cleanouts must fi t properly. Refractory, glass doors, screen rails, screen mesh, and log grates can be removed from the fi replace before installing the gas replace insert. Smoke shelves, shields and baffl es may be removed if attached by mechanical fasteners. A tight connection between the gas fi replace insert fl ue collar and the fi replace chimney must be made.
*Check with your local inspector before commencing with this installation.
Installer must mechanically attach the supplied label to the inside of the fi rebox of the fi replace into which the gas fi replace insert is installed.
BEFORE YOU START
Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
General Safety Information
1) The appliance installation must conform
with local codes or in the absence of local codes, with CAN/CSA B149.1 (in Canada) or the National Fuel Gas Code ANSI Z223.1 NFPA 54 in the U.S.A. This appliance should be installed by a qualifi ed gas fi tter technician only.
2) Installation and repair should be done by a qualifi ed service person.
3) The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, animal hair, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
4) See general construction and assembly
instructions. This appliance may only be installed in a vented, noncombustible replace.
5) This appliance is Listed for bedroom installations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
6) Always connect this appliance to a vent system vent that is run (or routed) to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is properly sized and is of adequate height to provide the proper draft.
7) Inspect the venting system annually for blockage and any signs of deterioration.
8) Any glass removed for servicing must be replaced prior to operating the appliance.
INSTALLATION
Fuels: Approved for use with both natural gas, and propane. Approved as is for use at 0' to 4,500' (0-1370m).
Electrical: 120V A.C. system. Circulation Fan: Variable speed, 127 CFM. Vent System: 3" co-linear aluminum ex. Cobalt Blue Glass Crystals
Regency® E33S-1 Sunrise Gas Insert 7
"WARNING: This fi replace has been converted for use with a gas fi replace insert only and cannot be used for burning wood or solid fuels unless all original parts have been replaced, and the fi replace re-approved by the authority having jurisdiction."
9) WARNING: Failure to position the parts in accordance with the diagrams in this manual or failure to use only parts specifi cally approved with this appliance may result in property damage or personal injury.
10) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the replace.
INSTALLATION
11) Due to high temperatures, the appliance
should be located out of high traffi c areas and away from furniture and draperies. Children and adults should be alerted to the hazards of high surface temperatures, especially the fi replace glass, and should stay away to avoid burns or clothing ignition. Young children should be carefully supervised when they are in the same room as the appliance. Clothing or other ammable material should not be placed on or near the appliance.
INSTALLATION
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
INSTALLATION
CHECKLIST
Before installing vent system ensure that the damper plate is open and secure to prevent the damper plate from falling down and crushing the liner.
The FPI Gas Insert is installed as listed below.
1) Check all clearances to combustibles.
Refer to the following sections where applicable:
a. Minimum Clearances to Combustibles b. Combustible Mantel Clearances
a. Glass Crystals b. Contemporary Faceplate c. Remote Control d. Wall Thermostat
9) Final check. Refer to the "Final Check" section. Before leaving this unit with the
customer, the installer must ensure that the appliance is fi ring correctly. This includes:
a) Clocking the appliance to ensure the
correct fi ring rate.
b) Adjusting the primary air, if required,
to ensure that the fl ame does not carbon. Refer to the "Gas Insert Aeration System" section.
c) Ensuring that the appliance is venting
correctly.
MATERIALS
REQUIRED
No electrical power supply is required for the gas control to operate. A 120 Volt AC power cord is hooked up to the fan. Plug the 3 wire cord into a suitable receptacle. Do not cut the ground terminal off under any circumstances. When connected with 120 volts, the appliance must be electrically grounded in accordance with local codes, current version of the Canadian Electrical Code CSA C22.1 (in Canada) or in the absence of local codes, with the National Electrical Code ANSI/NFPA 70.
MINIMUM FIREPLACE
OPENING
The minimum fi replace opening is shown in the following diagrams:
Width (at front) 32-1/4" (819mm)
Width (at rear) 25" (635m)
Depth 16-3/4" (425mm)
Height 24-3/16" (614mm)
2) Make the gas connection. Refer to the "Gas
Connection" section.
3) Install the 3" fl ue liner to the sliding connector
plate. Refer to the "Flue Liner Installation" section.
4) Slide the unit half way into the replace.
5) Pull the vent connector plate through the
tapered brackets and fasten to the front plate. Refer to the "Flue Liner Installation" section.
6) Slide the unit fully into the replace.
7) Test gas pressure, refer to the "Gas Pipe
Pressure Testing" section. Check aeration system, refer to "Gas Insert Aeration Systems" section.
8) Install standard and optional features.
Refer to the following sections where applicable:
WARNING: Electrical Grounding Instructions This appliance is equipped with a three pronged (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
8
Regency® E33S-1 Sunrise Gas Insert
MINIMUM CLEARANCES TO COMBUSTIBLES
From Unit Side Walls A* 8" (203 mm)
Ceiling B 47" (1194 mm)
Min. Mantel Height C 15" (381 mm) Max. Mantel Depth D 3-1/2" (89 mm)
Alcove Width E 76" (1930 mm) Alcove Depth F 36" (914 mm)
* Alcove side wall must have a min. of 8" clearance on one side.
INSTALLATION
INSTALLATION
COMBUSTIBLE MANTEL CLEARANCES
Due to the extreme heat this fi replace emits, the mantel clearances are critical.
Note: A non-combustible mantel may be installed at a lower height
if the framing is made of metal studs covered with a non­combustible board.
Mantel can be installed anywhere in shaded area or higher using the above scale.
Note: Ensure the paint that is used on the mantel and the facing
is "heat resistant" or the paint may discolour.
Regency® E33S-1 Sunrise Gas Insert 9
INSTALLATION
GAS CONNECTION
GAS CONNECTION WARNING: Only persons licensed to work
with gas piping may make the
necessary gas connections to
this appliance.
1) If the appliance is to be installed into an
existing chimney system, thoroughly clean
INSTALLATION
the masonry or factory built fi replace.
2) The appliance is provided with an opening on
the left hand side of the control compartment. A 3/8" NPT gas supply pipe must be brought near this inlet hole.
3) Locate the center point where the vent
will pass through the chimney above the appliance. Move the appliance into the exact location where it is to be installed. Ensure that the Insert is level.
NOTE: This unit is equipped with a heat sensor thermodisc which will prevent the blower from operating until the unit reaches the correct temperature.
VENTING
THE APPLIANCE MUST NOT BE
CONNECTED TO A CHIMNEY FLUE
SERVING A SEPARATE SOLID FUEL
BURNING APPLIANCE.
This appliance is designed to be attached to two 3" (76mm) co-linear aluminium fl ex running the full length of the chimney. The fl ue length must be a minimum length of 8 ' (2.44m) and a maximum of 35' (10.7m). See chart above for minimum distances from roof. Periodically check that the vent is unrestricted.
Masonry chimneys may take various contours which the fl exible liner will accommodate. However, keep the exible liner as straight
as possible, avoid unnecessary bending.
Part # Description
948-305 3" Flex - 35 ft. 946-529 FPI Co-linear DV Vertical Termination Cap
Alternate Approved Caps
46DVA-VC Vertical Termination Cap 46DVA-VCH High Wind Cap 46DVA-GK 3" Co-linear Adaptor with fl ashing
In areas of consistently high winds, we recommend using the Simpson Dura-Vent System (46DVA-GK adapter and 46DVA-VCH high-wind cap).
The Air Intake pipe must be attached to the inlet air collar of the termination cap.
FLUE LINER
INSTALLATION
1) Cut the ex liner as required.
2) Mark the end of one liner with an "E" to indicate Exhaust.
3) Connect the other end of the above liner to
the exhaust side of the termination adaptor, seal connection with high temperature silicone. Secure with gear clamp.
4) Connect the 2nd liner to the inlet side of the adaptor, seal connection with high temperature silicone. Secure with gear clamp.
5) Install ashing.
6) Insert both liners into chimney, passing
through the damper opening.
7) Install termination cap.
8) Connect the marked end of the liner to the
exhaust collar of the vent connector plate marked with an "E", seal connection with high temperature silicone. Secure with gear clamp.
9) Connect the 2nd liner to the intake collar, seal connection with high temperature silicone. Secure with gear clamp.
10) Align vent connector plate with guides on unit.
11) Slide unit into masonry opening, while ensuring that the slot at the rear of the connector plate mates up with the hold down plate on the unit.
12) Secure with Screw.
NOTE:
1) Final gas connection should be made after
unit is in place to avoid damage to line when pushing the unit into position.
10
2) Mill-pac may be used instead of high
tempture silicone and screws may be used instead of gear clamps at connections of liner to inlet and vent collars.
Regency® E33S-1 Sunrise Gas Insert