WARNING:
If the information in these instructions are not followed exactly,
a fi re or explosion may result causing property damage,
personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed
installer, service agency or the gas supplier.
Tested by:
918-510
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any applianceDo not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
02/01/07
CONGRATULATIONS!
You are the owner of a state-of-the-art Gas Insert by:
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.
The Regency® Gas Fireplace Series has been designed to provide you with all the warmth and charm
of a fi replace, at the fl ick of a switch. The models E21-NG2 and E21-LP2 of this series have been
approved by Warnock Hersey for safety. As it also bears our own mark, it promises to provide you with
economy, comfort and security for many trouble free years to follow. Please take a moment now to
acquaint yourself with these instructions and the many features of your Regency® Fireplace.
2 Regency® E21-2 Gas Fireplace Insert
E21 GAS INSERT
TABLE OF CONTENTS
SAFETY LABEL
Serial No. Decal ...........................................................4
REQUIREMENTS
MA Code - CO Detector
(for state of Massachusetts only) ..................................5
INSTALLATION
Important Message ......................................................6
Before You Start ............................................................6
General Safety Information ...........................................6
Policy for Solid Fuel Burning &
Factory Built Fireplaces ................................................. 7
This is a copy of the label that accompanies
each Regency® Gas Insert. We have printed
a copy of the contents here for your review.
The safety label is located on the front inside
base of the unit visible when the bottom louver
is open.
Note: Regency® units are constantly being
improved. Check the label on the unit
and if there is a difference, the label
on the unit is the correct one.
Please note that with the addition
of thermostat control and outside
combustion air supply, this unit is
approved for bedroom installations.
296
296
Minimum Clearances to Combustibles/
Degagement Minimum Des Materiaux
Serial No./
No de Serie
Duplicate Serial No.
DO NOT REMOVE THIS LABEL/ NE PAS ENLEVER CETTE ÉTIQUETTE
For installation into a vented non-combustible
fi replace, listed factory built fi replace. This vented
gas fi replace heater is not for use with air fi lters.
918-488
Combustibles:
Side of unit to wall /
Cote:
A 9"/229mm
Top of unit to
mantle / Au dessus:
B 14"/355mm
Ne peut etre installe que dans un foyer non
combustible muni d'un event. Ne pas utiliser de
fi ltre à air avec ce foyer au gaz à évacuation.
WARNING: This fi replace has been converted for use
with a gas fi replace insert only and cannot be used for
burning wood or solid fuels unless all original parts
have been replaced, and the fi replace re-approved by
the authority having jurisdiction.
ELECTRICAL SUPPLY/ALIMENTATION
ELECTRIQUE:115V60HZ less than/Moins de 2 AMP.
For the State of Massachusetts, installation
and repair must be done by a plumber or
gasfi tter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, fl exible
connectors shall not exceed 36 inches in
length.
For the State of Massachusetts, the appliances individual manual shut-off must be a
t-handle type valve.
Listed: VENTED GAS FIREPLACE HEATER
Tested to: ANSI Z21.88b-2003/CSA-2.33b-2003, CGA 2.17-M91
Gas fi red appliance for use at high altitude.
Certifi ed for/Certifee pour: CANADA and U.S.A. Report No. 476-1428-00 (DEC. 2000)
MADE IN CANADA / FABRIQUE AU CANADA
FPI Fireplace Products International Ltd., Delta, B.C., Canada
The State of Massachusetts requires the
installation of a carbon monoxide alarm in
accordance with NFPA 720 and a CO alarm
with battery back up in the same room where
the gas appliance is installed.
FIREPLACE INSERT: E21-NG2 E21-LP2 APPAREIL FONCTIONNANT CONCU POUR
Natural Gas (Naturel Gaz) Propane ETRE INSERE DANS UN FOYER
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
5Regency® E21-2 Gas Fireplace Insert
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The Regency® Gas Fireplace must be installed
in accordance with these instructions. Carefully
read all the instructions in this manual fi rst.
Consult the "authority having jurisdiction" to
determine the need for a permit prior to starting the installation. It is the responsibility of the
installer to ensure this fi replace is installed in
compliance with the manufacturer's instructions
and all applicable codes.
BEFORE YOU START
Safe installation and operation of this appliance requires common sense, however, we
are required by the Canadian Safety Standards
and ANSI Standards to make you aware of the
following:
INSTALLATION AND REPAIR
SHOULD BE DONE BY A
QUALIFIED SERVICE PERSON.
THE APPLIANCE SHOULD
BE INSPECTED BEFORE USE
AND AT LEAST ANNUALLY BY
A PROFESSIONAL SERVICE
PERSON. MORE FREQUENT
CLEANING MAY BE REQUIRED
DUE TO EXCESSIVE LINT FROM
CARPETING, BEDDING MATERIAL,
ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS,
BURNERS AND CIRCULATING
AIR PASSAGEWAYS OF THE
APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES,
THE APPLIANCE SHOULD BE
LOCATED OUT OF TRAFFIC AND
AWAY FROM FURNITURE AND
DRAPERIES.
WARNING: FAILURE TO INSTALL
THIS APPLIANCE CORRECTLY
WILL VOID YOUR WARRANTY AND
MAY CAUSE A SERIOUS HOUSE
FIRE.
CHILDREN AND ADULTS SHOULD
BE ALERTED TO THE HAZARDS OF
HIGH SURFACE TEMPERATURES,
ESPECIALLY THE FIREPLACE
GLASS, AND SHOULD STAY AWAY
TO AVOID BURNS OR CLOTHING
IGNITION.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN
THEY ARE IN THE SAME ROOM
AS THE APPLIANCE.
CLOTHING OR OTHER
FLAMMABLE MATERIAL SHOULD
NOT BE PLACED ON OR NEAR
THE APPLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform
with local codes or, in the absence of local
codes, with the current Canadian or National
Gas Codes, CAN1-B149 or ANSI Z223.1
Installation Codes.
2) The appliance when installed, must be
electrically grounded in accordance with
local codes, or in the absence of local codes
with the current National Electrical Code,
ANSI/NFPA 70 or CSA C22.1 Canadian
Electrical Code.
3) See general construction and assembly
instructions. The appliance and vent should
be enclosed.
4) This appliance must be connected to the
specifi ed vent and termination cap to the
outside of the building envelope. Never
vent to another room or inside a building.
Make sure that the vent is installed as per
Venting instructions.
5) This appliance may only be installed in a
vented, solid fuel burning masonry, listed
factory built fi replace, or zero clearance kit
part # 530-936.
6) This appliance is Listed for bedroom
installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
7) This appliance is Listed for Alcove
installations, maintain minimum Alcove
clearances as follows, minimum ceiling
height of 53-1/2", minimum width of 48"
and a maximum depth of 36".
8) This unit is not approved for installation into
a mobile home.
9) Inspect the venting system annually for
blockage and any signs of deterioration.
10) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
11) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fi replace insert.
12) Wear gloves and safety glasses for protection
while doing required maintenance.
13) Ensure adequate combustion and ventilation
air.
14) Under no circumstances should this
appliance be modifi ed. Parts that have to
be removed for servicing should be replaced
prior to operating this appliance.
15) Installation and any repairs to this appliance
should be done by a qualifi ed service person.
A professional service person should be
called to inspect this appliance annually.
Make it a practice to have all of your gas
appliances checked annually.
16) Do not slam shut or strike the glass door.
17) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
18) The appliance area must be kept clear and
free of combustible materials, (gases and
other fl ammable vapours and liquids).
19) Do not use this appliance if any part has been
under water. Immediately call a qualifi ed
service technician to inspect the appliance
and to replace any part of the electrical
control system and any gas control which
has been under water.
20) WARNING: Failure to position
the parts in accordance with the
diagrams in this manual or failure to
use only parts specifi cally approved
with this appliance may result
in property damage or personal
injury.
21) WARNING: Operation of this
appliance when not connected to
a properly installed and maintained
venting system or tampering with
the blocked vent shut-off system
can result in carbon monoxide (CO)
poisoning and possible death.
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
6 Regency® E21-2 Gas Fireplace Insert
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
a
a
a
a
a
a
a
a
a
a
aaaaaaaaaa
INSTALLATION
POLICY FOR SOLID
FUEL BURNING &
FACTORY BUILT
The Regency® E21 may be installed and vented
into any solid fuel fi replace that has been installed
in accordance with the National, Provincial and
local building codes and is constructed of noncombustible materials.
1) Installer must mechanically attach the sup-
plied label to the inside of the fi rebox of the
fi replace into which the gas fi replace insert
is installed.
"WARNING: This fi replace has been converted
for use with a gas fi replace insert only and
cannot be used for burning wood or solid fuels
unless all original parts have been replaced,
and the fi replace re-approved by the authority
having jurisdiction."
2) Do not cut any sheet-metal parts of the
fi replace, in which the gas fi replace insert
is to be installed.
3) If the factory-built fi replace has no gas access
hole(s) provided, an access hole of 1-1/2"
(37.5mm) or less may be drilled though the
lower sides or bottom of the fi rebox in a proper
workmanship like manner. This access hole
must be plugged with a non-combustible
insulation after the gas supply line has been
installed.
4) The fi replace fl ue damper can be fully blocked
open or removed for installation of the gas
fi replace insert.
5) The fi replace and fi replace chimney must
be clean and in good working order and
constructed of non-combustible materials.
6) The chimney cleanouts must fi t properly.
7) Refractory (fi rebricks), glass doors, screen
rails, screen mesh and log grates can be
removed from the fi replace before installing
the gas fi replace insert.
8) Smoke shelves, shields and baffl es may be
removed if attached by mechanical fasteners.
If any part is removed it must not weaken
the structural integrity of the factory built.
9) Trim panels or surrounds shall not seal
ventilation openings in the fi replace.
FIREPLACES
INSTALLATION
CHECKLIST
1) Locate your appliance. Refer to the "Clear-
ances to Combustibles" and "Minimum
Fireplace Clearances" sections.
2) Make gas and electrical connections. Refer
to the "Gas Connection" section.
Test the pilot. Must be as per diagram in the
"Valve Description" section.
3) Install Flue Connector. Refer to the "Flue
Connector Installation" section.
4) Install vent. Refer to the "Venting" section.
5) Test Gas pressure. Refer to the "Gas Pipe
Pressure Testing" section.
Check aeration. Refer to the "Gas Insert
Aeration System" section.
6) Test for fl ue spillage. Refer to the "Test for
Flue Spillage" section.
7) Install standard and optional features. Refer
to the following sections where applicable:
a. Brick Panel
b. Faceplate & Trim
c. Flush Glass
d. Flush Louver
e. Bay Front
f. Full Screen Doors
g. Remote Control
h. Wall Switch
i. Wall Thermostat
8) Final check. Refer to the "Final Check"
section.
Before leaving this unit with the customer,
the installer must ensure that the appliance is
fi ring correctly and operation fully explained to
customer.
This includes:
1) Clocking the appliance to ensure the correct
fi ring rate (rate noted on label) after burning
appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
3) Ensure that the appliance is venting
correctly.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
MINIMUM FIREPLACE
CLEARANCES
Diagram shows the minimum fi replace opening
required to be able to install the Regency® gas
fi replace insert.
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Note: If you are installing the Molded Faceplate,
the minimum fireplace dimensions are as
follows:
The minimum clearance from the side of the appliance to a combustible
side wall is 9 inches (229mm). The minimum clearance from the top of
the louver to a combustible mantel is 14 inches (356mm). The minimum
height from the top of the louver to the ceiling is 36 inches (914mm).
Note: A non-combustible mantel may be installed at a lower height
if the framing is made of metal studs covered with a noncombustible board.
8 Regency® E21-2 Gas Fireplace Insert
INSTALLATION
GAS CONNECTION
Only persons licensed to work with gas piping
may make the necessary gas connections to
this appliance.
The gas connection is a 3/8" NPT accessible on
the left side of the unit. The gas line connection
may be made of rigid pipe, copper pipe or an
approved fl ex connector. (If you are using rigid
pipe, ensure that the valve can be removed
for servicing.) Since some municipalities have
additional local codes it is always best to consult
with your local authorities and the CAN/CGA
B149 installation code.
For USA installations follow local codes and/or
the current National Fuel Gas Code, ANSI
Z223.1.
When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so that
gas lines can be easily disconnected for burner
or fan servicing. Flare nuts for copper lines and
fl ex connectors are usually considered to meet
this requirement.
Important: Always check for gas leaks
with a soap and water solution or gas
leak detector. Do not use open fl ame
for leak testing.
For minimum and maximum supply pressure
see the System Data table.
1) If the appliance is to be installed into an
existing chimney system, thoroughly clean
the masonry fi replace that has been chosen
for the Regency
2) The appliance is provided with an opening on
the left hand side of the control compartment
for the gas line.
®
Gas Fireplace.
System Data
For altitude: Natural Gas 0-2000 ft.
Propane: 0-4500 ft.
Note: During any pressure testing of the gas
supply piping system that exceeds test pressures
of 1/2 psig, this appliance and its individual
shut-off valve must be disconnected from the
piping system. If test pressures equal to or less
than 1/2 psig are used then this appliance must
be isolated from the piping system by closing
its individual manual shut-off valve during the
testing.
CAUTION: If the glass is removed for
servicing, it must be replaced prior to
operating the appliance. The glass must
be fixed in the closed position when
operating.
Burner Inlet Orifi ce Size: 44 DMS
Max. Input Rating 22,000 Btu/h
Min. Input Rating +/-5% 11,000 Btu/h
HIGH ELEVATION
This unit is approved in Canada for altitude
0 to 4500 ft. (CAN/CGA 2.17-M91) with the
orifi ce supplied.
9Regency® E21-2 Gas Fireplace Insert
INSTALLATION
WIRING DIAGRAMS
This heater does not require a 120V A.C. supply
for operation. In case of a power failure, the
burner switch and the optional remote control/
thermostat will continue to operate. However,
a 120V A.C. power supply is needed for the
fan/blower operation.
For NATURAL GAS Units and Units NOT Equipped with DC Spark Boxes
#8 Ground Lug
Nut
Lockwasher
Star washer
Nut
Star washer
Grounding
Lug Detail
Fan ground
Power cord
ground wire
Pilot
Assembly
Caution: Ensure that the wires do
not touch any hot surfaces and are
away from sharp edges.
When connected with 120 volts, the appliance
must be electrically grounded in accordance
with local codes or, in the absence of local
Neutral
Live
60 Hz
Thermodisc
Gas Pilot
Thermopile
Electrode
120V AC
codes the current CSA C22.1 (in Canada) or
with the National Electrical Code ANSI/NFPA
70-1987 (in USA).
NOTE: This unit is equipped with a heat
sensor thermodisc which will
prevent the blower from operating
until the unit reaches the correct
temperature.
Ground
Ground
Green
Fan
ONOFF
Fan
Red
Black
Rotary Speed
Control
Black
Black
Thermocouple In
O
N
Gas
In
T
O
I
L
H
I
P
F
F
O
L
O
White
Brown
"S.I.T" Valve
CAUTION: Label all wires prior
to disconnection when servicing
controls. Wiring errors can
cause improper and dangerous
operation.
Piezo
Ignitor
Red
ONOFF
Vent Spill
Switch
(Auto Reset)
Remote
Receiver
(Optional)
(Millivolt)
WARNING: Electrical Grounding
Instructions
This appliance is equipped with a
three pronged (grounding) plug for
your protection against shock hazard
and should be plugged directly into
a properly grounded three-prong
receptacle. Do not cut or remove the
grounding prong from this plug.
Thermostat
(Millivolt)
(Optional)
Black
Red
Remote Transmitter
ON
Burner
OFF
(Optional)
Regency
10 Regency® E21-2 Gas Fireplace Insert
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.