Red Lion XCRS User Manual

Bulletin No. XCRS- A Drawing No. LP0669 Released 01/10
Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net
MODEL XCRS - RS232/485 OPTION CARD FOR DATA STATION PLUS AND MODULAR CONTROLLER
CONFIGURED USING CRIMSON SOFTWARE
(VERSION 2.0 OR LATER)
ISOLATED RS232 AND RS485 MULTIPLEXED PORTS CAPABLE
OF COMMUNICATING WITH RS232, RS422, RS485 AND DH485 DEVICES AT UP TO 115,200 BAUD
EASY INSTALLATION
GENERAL DESCRIPTION
The XCRS option card adds an additional RS232 and RS422/485 port to the series. This isolated card protects user equipment from potentially harmful ground loops while providing high-speed RS232, RS422, RS485, and DH485 communication options to the end user.
The XCRS communication card is easily installed by removing the blank expansion port cover of your Modular Controller or Data Station Plus, and plugging the XCRS card into the expansion port. Configuration is simple using Red Lion's free Crimson 2.0 software.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the controller.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CONTENTS OF PACKAGE
- XCRS option card
- This hardware bulletin
ORDERING INFORMATION
MODEL NO. DESCRIPTION PART NUMBER
XCRS
CBL
DR SFCRM2 Crimson 2.0 with G3/Data Station Manual SFCRM2 Crimson 2.0 with Modular Controller Manual 3SFCRM2MC
1
Contact your Red Lion distributor or visit www.redlion.net for complete
selection.
2
Red Lion offers RJ modular jack adapters. Refer to DR literature for
complete details.
3
Use these part numbers to purchase Crimson 2.0 on CD with a printed
RS232/485 option card for Modular Controller or Data Station Plus
Communication Cables DIN Rail Mountable Adapter Products
1
2
3
XCRS0000
CBLxxxxx DRxxxxxx
SFCRM200
manual, USB cable and RS-232 cable. Otherwise, download free of charge from www.redlion.net.
SPECIFICATIONS
1. POWER REQUIREMENTS: 24 V @ 50 mA max. Power is supplied to the
option card from the main board of the Modular Controller Master or Data Station Plus.
2. COMMUNICATIONS: Serial Ports: Format and Baud Rates for each port are individually software programmable up to 115,200 baud and are isolated to help prevent ground loops. The RS422/485 and DH485 port via RJ45 and the RS232 port via RJ12 share the same hardware. The XCRS option card multiplexes the ports to communicate via two protocols. These ports may be used to configure different master protocols, but only one port may be used if configuring a slave protocol or AB DH485.
DH485 TXEN: Transmit enable; open collector , VOH = 15 VDC, VOL = 0.5 VDC Isolation from XCRS Communication ports to the Modular Controller Master or Data Station Plus: 1000 VDC for 1 minute.
3. CERTIFICA TIONS AND COMPLIANCES: Refer to main unit manual or “Agency Approvals” section of Red Lion’s
website for agency certifications.
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
Control and Laboratory use.
Reference Modular Controller Master or Data Station Plus unit for EMC
specifications
1
4. ENVIRONMENTAL CONDITIONS:
+
-
ISOLATING
DC : DC
A
RS422
PORT
PORT
RS232
B
B
RS485/
Refer to the specifications of the Modular Controller Master or Data Station
Plus you are installing this card in.
5. CONSTRUCTION: For indoor use only. Installation Category II, Pollution
Degree 2.
6. INSTALLATION REQUIREMENTS: See “Installing the XCRS Option
card” for more details.
7. WEIGHT: 1.9 oz (53.9 g)
BLOCK DIAGRAM
INSTALLING THE XCRS OPTION CARD
1. Remove power from the unit
2. Insert a flat-bladed screwdriver into the slot at the top of the expansion port cover. Gently apply pressure on the screwdriver in an upward direction until the expansion port cover disengages from the unit as shown in Figure 1.
3. Verify that the option card knobs are in the “unlocked” position as shown in Figure 2.
4. Carefully insert the option card into the expansion port opening while aligning the card-edge connector on the option card with the main board's header, as shown in Figure 3. Once aligned, gently press on the front of the card until it is flush with the front of the case.
5. Turn the option card knobs to the locked position as shown in Figure 4.
Figure 1
Caution: The expansion and main circuit boards contain static
sensitive components. Before handling the cards, discharge static charges from your body by touching a grounded bare metal object. Ideally, handle the cards at a static controlled clean workstation. Also, handle the cards by the edges only. Dirt, oil, or other contaminants that may contact the cards can adversely affect circuit operation.
Warning: Risk of Danger: Be sure to remove all power before
removing the expansion port cover.
XCRS
RX
TX
RS485
RS232
Figure 2
XCRS
RX
TX
RS485
RS232
XCRS
Figure 3
RX
TX
RS485
RS232
Figure 4
2
POWER SUPPLY REQUIREMENTS
NEW AND EXISTING INSTALLATIONS
The XCRS option card draws all of its power from the main board of the Modular Controller Master or Data Station Plus. The specifications of the Modular Controller Master or Data Station Plus account for the power needs of an option card.
COMMUNICATING WITH THE XCRS OPTION CARD
CONFIGURING A XCRS OPTION CARD
The XCRS is configured using Crimson software. Crimson is available as a free download from www.redlion.net, or it can be ordered on CD. Updates to Crimson for new features and drivers are posted on the website as they become available. By configuring the XCRS using the latest version of Crimson, you are assured that your unit has the most up-to-date feature set. Crimson software can configure the XCRS through the RS232 PGM port, USB port, Ethernet port, or CompactFlash socket on your Modular Controller Master or Data Station Plus. Additional information can be found in your Modular Controller Master or Data Station Plus hardware bulletin and the Crimson user manual.
CABLES AND DRIVERS
Red Lion has a wide range of cables and drivers for use with many different communication types. A list of these drivers and cables along with pin outs is available from www.redlion.net. New cables and drivers are added on a regular basis. If making your own cable, refer to the “XCRS Port Pin Outs” for wiring information.
RS232 PORTS
The XCRS option card has one RS232 port. The port can be used for either master or slave protocols with any Modular Controller Master or Data Station Plus configuration. The RS232 port and RS422/485 port on the XCRS option card are multiplexed because they share the same hardware. Both ports can be used with master protocols. However, when the RS232 port is used with a slave protocol, the RS422/485 port is not available. For examples of RS232 communications refer to your Modular Controller Master or Data Station Plus literature.
DH485 COMMUNICATIONS
The XCRS option card’s RS422/485 port can also be used for Allen Bradley DH485 communications. When this port is configured to communicate DH485, the RS232 port can not be used because the ports share the same hardware and the XCRS option card multiplexes the ports to communicate via two protocols.
WARNING: DO NOT use a standard DH485 cable to connect this port to Allen
Bradley equipment doing so may cause irreparable damage to the equipment
connected. A cable and wiring diagram are available from Red Lion.
Modular Controller Master or Data Station Plus to AB SLC 500 (CBLAB003)
Connections
RJ45: RLC Name RJ45: A-B Name
1 TxB 1 A
2 TxA 2 B 3, 8 RxA - 24V 4, 7 RxB - COMM
5 TxEN 5 TxEN
6 COMM 4 SHIELD 4, 7 TxB - COMM 3, 8 TxA - 24V
SOFTWARE/UNIT OPERATIONS
XCRS PORT PIN OUTS
RxA
RxB
TxEN
COMM
TxB
TxA (PIN 8)
CTS (PIN 1)
COMM
Rx
COMM
Tx
RS232RS485
RTS (PIN 6)
RX TX
TxB (PIN 1)
TxA
RS422/485 COMMS PORT
The XCRS option card has one RS422/485 port. This port can be configured
to act as either RS422 or RS485.
The RS422/485 port and RS232 port are multiplexed because they share the same hardware. Both ports can be used with master protocols. However, when the RS422/485 port is used with a slave protocol, the RS232 port is not available.
RS422/485 4-WIRE
CONNECTIONS
5V
130K
TX
130K
5V
130K
RX
130K
7
1
8
2
5
4
3
6
TxB
TxA
TxEN (OC)
RxB
RxA
GND
RS485 2-WIRE
CONNECTIONS
5V
130K
TX/RX
130K
7
TxB
1
8
TxA
2
TxEN (OC)
5
6 GND
LEDS
The transmit LED(TX) will flash when information is transmitted from the
XCRS card. The receive LED(RX) will flash when information is received.
CRIMSON SOFTWARE
Crimson 2.0 software is available as a free download from www.redlion.net or it can be purchased on a CD, see “Ordering Information” for part number. The latest version of the software is always available from the web site, and updating your copy is free.
TROUBLESHOOTING YOUR XCRS OPTION CARD
If for any reason you have trouble operating, connecting, or simply have questions concerning your new XCRS option card, contact Red Lion's technical support. For contact information, refer to the back page of this bulletin for phone and fax numbers.
EMAIL: techsupport@redlion.net
Web Site: http://www.redlion.net
Note: All Red Lion devices connect A to A and B to B, except for Paradigm
devices. Refer to www.redlion.net for additional information.
For examples of RS422/485 communications refer to your Modular Controller
Master or Data Station Plus literature.
3
The Company warrants the products it manufactures against defects in materials and workmanship
LIMITED WARRANTY
for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.
Red Lion Controls Headquarters 20 Willow Springs Circle York PA 17406 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839
Red Lion Controls
Europe
Printerweg 10
NL - 3821 AD Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
54, Vishvas Tenement
GST Road, New Ranip,
Ahmedabad-382480 Gujarat, India
Tel +91 987 954 0503
Fax +91 79 275 31 350
Red Lion Controls
China
Unit 101, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113-3688
Fax +86 21 6113-3683
Loading...