The Temperature Control Unit (TCU) is a multi-purpose series of
industrial control products that are field-programmable for solving various
applications. This series of products is built around the concept that the end
user has the capability to program different personalities and functions into
the unit in order to adapt to different indication and control requirements.
The TCU unit, which you have purchased, has the same high quality
workmanship and advanced technological capabilities that have made Red
Lion Controls the leader in today’s industrial market.
Red Lion Controls has a complete line of industrial indication and control
equipment, and we look forward to servicing you now and in the future.
ConfigurationOfParameters ··················································15
ParameterEntry ···························································· 16
NormalDisplayMode ························································ 16
Modifying A Secondary Display Parameter From The Front Panel ·······················16
Models With User Input ······················································ 20
Models With Program Disable ················································· 20
HIDDEN FUNCTION MODE ·····················································21
Hidden Function Mode Reference Table ·········································· 21
PrintOptions(PoPt) ······················································36
Second Analog Input Module (7-2n) (Optional) ·····································36
CommunicationFormat ······················································ 48
Sending Commands And Data ················································· 48
OutputStatus ························································ 49
ReceivingData ···························································· 51
Terminal Emulation Program For IBM
®
PC ········································53
Serial Connections ·························································· 54
TerminalDescriptions ····················································· 54
Connecting To A Host Terminal ·············································56
Troubleshooting Serial Communications ··········································56
HEATER CURRENT MONITOR OPTION ··········································· 57
VALVEPOSITIONOPTION ·····················································58
The TCU Controller accepts signals from a variety of temperature sensors
(thermocouple or RTD elements), precisely displays the process temperature,
and provides an accurate output control signal (time proportional, linear, or
valve positioning) to maintain a process at the desired control point. A
comprehensive set of easy to use steps allows the controller to solve various
application requirements.
The controller can operate in the PID control mode for both heating and
cooling. On-demand auto-tune establishes the tuning constants. The PID
tuning constants may be fine-tuned by the operator at any time and locked out
from further modification. The controller employs a unique overshoot
suppression feature that allows the quickest response without excessive
overshoot. The unit can be transferred to operate in the manual mode,
providing the operator with direct control of the output. The controller can
also be programmed to operate in the ON/OFF control mode with adjustable
hysteresis.
Dual 4-digit displays allow viewing of the process temperature and
setpoint simultaneously. Front panel indicators inform the operator of the
controller and output status. Replaceable and interchangeable output
modules (Relay, SSR Drive, or Triac) can be installed for the main control
output, alarm output(s), cooling output, and Valve Positioner outputs.
Optional dual alarms can be configured to activate according to a variety o f
actions (Absolute HI or LO, Deviation HI or LO, Band IN or OUT, Heater
Break, and Valve Fail Detect) with adjustable hysteresis. A standby feature
suppresses the output during power-up until the temperature stabilizes
outside the alarm region. An optional secondary output is available (for
processes requiring cooling) that provides increased control accuracy and
response.
A linear 4 to 20 mA or 0 to 10 VDC output signal is available to interface
with actuators, chart recorders, indicators, or other controllers. The type o f
Linear DC output is determined by the model ordered. (See Ordering
Information, page 90, for available models.) The output signal can be
digitally scaled and selected to transmit one of the following: % output
power, process temperature value, process temperature value deviation o r
setpoint value. For Linear DC control applications, the adjustable output
demand dampening, output deadband, and output update time parameters
expand the versatility of the TCU to final control devices.
The optional Heater Current Monitor serves as a digital ammeter for heater
current monitoring. Used with current transformer accessory (CT005001),
this display is integrated within the controller. An alarm event output can be
programmed to signal when the heater or heater control devices have failed,
before damage to process material occurs. The Heater Break Alarm triggers
under two conditions:
1. The main output (OP1) is “on” and the heater current is below the heater
current alarm value, indicating an aged or failed heater.
2. Output (OP1) is “off” and the heater current is more than 10% of the alarm
value, indicating a shorted heater control device or other problem.
The optional Motorized Valve Positioner directly controls the position of a
valve by the use of twin outputs (open and close) to control the direction of
motor rotation. The motor position defines the opening position at the valve.
Two control modes are possible: position control, which makes use of the
slidewire feedback signal supplied with the positioner and velocity control,
in which no slidewire feedback signal is used. Parameters are p rovided to
adjust the operation of the valve. These include:
- Valve activity hysteresis
- Valve update time
- Variable control d ampening
- Slidewire signal fail action
- Adjustable valve position limits
The Valve Positioner TCU achieves tight process control; yet minimizes
unnecessary valve activity. An alarm event output or display alarm can be
programmed under loss of slidewire feedback or under valve fail detection.
The optional Second Analog Input (0 to 20 mA DC) can be configured as a
Remote Setpoint signal or as a Secondary Process signal. Configuration of
the Second Analog Input as a Remote Setpoint signal allows ratio control,
master setpoint/multiple slave operation, and the ability to cascade the TCU
with another controller (External Cascade). Configuration of the Second
Input as a Secondary Process signal allows operation as a two-process
cascade controller within a single unit (Internal Cascade). In either control
mode, parameters are provided to scale, configure, communicate and monitor
the activity of both analog inputs. A square law linearizer function can be
used to linearize signals derived f rom flow transmitters.
1
The optional RS485 multi-drop serial communication interface provides
two-way communication between a TCU unit and other compatible
equipment such as a printer, a programmable controller, or a host computer.
In multi-point applications the address number of each unit on the line can be
programmed from zero to ninety nine. Up to thirty-two units can be installed
on a single pair of wires. The Setpoint value, % Output Power, Setpoint Ramp
Rate, etc. can be interrogated or changed, by sending the proper command
code via serial communications. Alarm output(s) may also be reset via the
serial communications interface option. A programmable User Input is
available with RS485, Valve Position, Heater Current Monitor, and Second
Analog Input models. The User Input can be programmed to perform a variety
of controller functions.
An optional NEMA 4X/IP65 rated bezel is available for wash down
applications and similar environments, when properly installed. Modern
surface-mount technology, in-house assembly and testing, and high
immunity to noise interference makes the controller extremely reliable in
industrial environments.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in
the manual or onequipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Do not use the TCU to directly command motors, valves, or other actuators
not equipped with safeguards. To do so, can be potentially harmful to persons
or equipment in the event of a fault to the unit. An independent and redundant
temperature limit indicator with alarm outputs is strongly recommended. The
indicators should have input sensors and AC power feeds independent from
other equipment.
2
INSTALLATION & CONNECTIONS
Installation Environment
The unit should be installed in a location that does not exceed the maximum
operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.
Continuous exposure to direct sunlight may accelerate the aging process of
the bezel.
The bezel should be cleaned only with a soft cloth and neutral soap
product. Do NOT use solvents.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate
the keypad of the unit.
Standard Unit Installation
Prepare the panel cutout to the dimensions shown in Figure 1, Panel
Installation & Removal. Remove the panel latch and cardboard sleeve from
the unit and discard the cardboard sleeve. The unit should be installed with
the bezel assembly in place. Insert the unit into the panel cutout. While
holding the front of the unit in place, push the panel latch over the rear of the
unit so that the tabs of the panel latch engage in the slots on the case. The panel
latch should be engaged in the farthest forward slots possible. Tighten the
screws evenly until the unit is snug in the panel.
NEMA 4X/IP65 Unit Installation
The optional NEMA 4X/IP65 TCU Controller is designed to provide a
watertight seal in panels with a minimum thickness of 1/8 inch. The unit
meets NEMA 4X/IP65 requirements for indoor use, when properly installed.
The units are intended to be mounted into an enclosed panel. Prepare the
panel cutout to the dimensions shown in Figure 1, Panel Installation &
Removal. Carefully apply the adhesive side of the panel gasket to the panel
cutout. Remove the panel latch and cardboard sleeve from the unit. Discard
the cardboard sleeve. The unit should be installed with the bezel assembly in
place and the bezel screws tightened slightly. Insert the unit into the panel
cutout. While holding the front of the unit in place, push the panel latch over
the rear of the unit so that the tabs of the panel latch engage in the slots on the
case. The panel latch should be engaged in the farthest forward slot possible.
To achieve a proper seal, tighten the latch screws evenly until the unit is snug
in the panel (Torque to approximately 7 in-lbs [79N-cm]). Do NOT
over-tighten the screws.
Note: The installation location of the controller is important. Be sure to keep it
away from heat sources (ovens, furnaces, etc.), away from direct contact with
caustic vapors, oils, steam, or any other process by-products in which
exposure may affect proper operation.
Caution: Prior to applying power to the controller, the internal AC power
selector switch must b e set. Damage to the controller mayoccur if the switch is
set incorrectly.
3
Figure 1, Panel Installation & Removal
4
Unit Removal Procedure
To remove a NEMA 4X/IP65 or standard unit from the panel, first unscrew
and remove the panel latch screws. Insert f lat blade screwdrivers between the
latch and the case on the top and bottom of the unit, so that the latches
disengage from the grooves in the case. Push the unit through the panel from
the rear.
Removing Bezel Assembly
The bezel assembly, shown in Figure 2, must be removed from the case to
install o r replace output modules, to select the input sensor type, or to set the
115/230 VAC selector switch. Disconnect power to the unit and to the output
control circuits to eliminate the potential shock hazard when removing the
bezel assembly. To remove a standard bezel assembly (without bezel securing
screws), press the latch under the lower bezel lip and withdraw the bezel
assembly. To remove the sealed NEMA 4X/IP65 bezel assembly, loosen the
two bezel securing screws until a slight “click” is felt (the screws are retained
in the bezel) and withdraw the assembly.
Caution: The bezel assembly contains electronic circuits that are damaged by
static electricity. Before removing the assembly, discharge stray static
electricity on your body by touching an earth ground point. It is also
important that the bezel assembly be handled only by the bezel itself.
Additionally, if it is necessary to handle a circuit board, be certain that hands
are free from dirt, oil, etc., to avoid circuit contamination that may lead to
malfunction. If it becomes necessary to ship the unit for repairs, place the unit
in its case before shipping it.
Installing Bezel Assembly
To install the standard bezel assembly, insert the assembly into the case
until the bezel latch snaps into position.
To install the NEMA 4X/IP65 bezel assembly, insert the assembly into the
case and tighten the bezel screws uniformly until the bezel contacts the case
and then turn each screw another half turn to insure a watertight seal (do not
over-tighten screws).
Caution: When substituting or replacing a bezel assembly, be certain that it is
done with the same model using the same Output Modules. Damage to the
controller may result if the unit’s output modules are not the same. A NEMA
4X/IP65 and a standard b ezel assembly are NOT interchangeable.
Figure 2, Bezel Assembly
5
Output Modules
The main control, optional Alarm, optional Cooling output and optional
Valve Position control output sockets must be fitted with the appropriate
output module. Output modules are shipped separately and must be installed
by the user.
Typical Connections
Output Module Restrictions
With some models, the Alarm outputs and Valve Position outputs share the
same common terminal. When using these models, the same type of output
modules are usually installed in these positions.
Installing Output Modules
To install an output module into the controller, remove the bezel assembly
from the case (See Removing Bezel Assembly, page 5). Locate the correct
output module socket (OP1, AL1, or AL2/OP2, see Figure 6, Hardware, or
label outside of case) and plug the output module into the socket. No
re-programming is required. If changing an output module type, be sure the
appropriate output interface wiring changes are made. Re-install the bezel
assembly when complete.
Note: For Valve Positioner models, the circuit board markings have the
following meaning:
AL1 - Open Output
AL2/OP2 - Close Output
OP1 - Alarm #1 Output
OUTPUT MODULE “OUTPUT ON” STATE
RelayNormally open contact is closed.
Logic/SSR DriveSource is active.
TriacSolid state switch is closed.
Figure 3, Relay Module
Relay:
Type: Form-C
Rating: 5 Amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 HP @
120 VAC (inductive load).
Life Expectancy: 100,000 cycles at maximum load rating. (Decreasing
load and/or increasing cycle time, increases life expectancy).
Figure 4, Logic/SSR Drive Module
Logic/SSR Drive:
Type: Non-isolated switched DC, 12 VDC typical
Drive: 45 mA Max. Can drive multiple SSR Power Units.
Min. Load Current: 10 mA
Off State Leakage Current: 7mAmaximum@60Hz
Operating Frequency: 20 to 400 Hz
Protection: Internal Transient Snubber, Fused.
0.75 amp @ 50°C
Select Input Sensor Type
The input sensor type (Thermocouple or RTD) must be selected by an
internal hardware jumper to match the programmed input sensor type. The
jumper is located inside the case on a small accessory circuit board near the
rear of the unit on the main circuit board (see Figure 6, Hardware, or label on
outside of case).
Select AC Power (115/230 VAC)
The AC power to the unit must be s elected for either 115 VAC or 230 VAC.
The selector switch is located inside the case near the rear of the unit on the
main circuit board (see Figure 6, Hardware, or label on inside or outside of
case). The unit is shipped from the factory with the switch in the 230 VAC
position.
Caution: Damage to the controller may occur if the AC selector switch is set
incorrectly.
Figure 6, Hardware
7
EMC INSTALLATION GUIDELINES
Although this unit is designed with a high degree of immunity to
ElectroMagnetic Interference (EMI), proper installation and wiring methods
must be followed to ensure compatibility in each application. The type of
electrical noise, source or coupling method into the unit may be different for
various installations. In extremely high EMI environments, additional
measures may be needed. The unit becomes more immune to EMI with fewer
I/O connections. Cable length, routing and shield termination are very
important and can mean the d ifference between a successful or a troublesome
installation. Listed below are some EMC guidelines for successful
installation in an industrial environment.
1. The unit should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The
shield (screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in
order of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually
when the noise source frequency is above 1 MHz.
c. Connect the shield to common of the unit and leave the other end of the
shield unconnected and insulated from earth ground.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are
long and portable two-way radios are used in close proximity or if the
installation is near a commercial radio transmitter.
4. Signal or Control cables within an enclosure should be routed as far away
as possible from contactors, control relays, transformers, and other noisy
components.
5. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on
Signal and Control cables as close to the unit as possible. Loop the cable
through the core several times or use multiple cores on each cable for
additional protection. Install line filters on the power input cable to the
unit to suppress power line interference. Install them near the power entry
point of the enclosure. The following EMI suppression devices (or
equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:
Note: Reference manufacturer’s instructions when installing a line filter.
6. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
7. Switching of inductive loads produces high EMI. Use of snubbers across
inductive loads suppresses EMI.
Snubbers:
RLC #SNUB0000
Wiring Connections
After the unit has been mechanically mounted, it is ready to be wired. All
conductors should meet voltage and current ratings for each terminal. Also
cabling should conform to appropriate standards of good installation, local
codes and regulations. It is recommended that power supplied to the unit (AC
or DC) be protected by a fuse or circuit breaker.
All wiring connections are made on a fixed terminal block. When wiring
the unit, use the numbers on the label to identify the position number with the
proper function. Strip the wire, leaving approximately 1/4" (6 mm) bare wire
exposed (stranded wires should be tinned with solder). Insert the wire into
the terminal and tighten the screw until the wire is clamped tightly. Each
terminal can accept up to two, 18-gauge wires. Wire each terminal block in this
8
Signal Wiring
When connecting the thermocouple or RTD leads, be certain that the
connections are clean and tight, refer to Figures 7 and 8 f or terminal
connections. If the thermocouple probe cannot be connected directly to the
controller, thermocouple wire or thermocouple extension-grade wire must be
used to extend the connection points (copper wire does not work). Always
refer to the thermocouple manufacturer’s recommendations for mounting,
temperature range, shielding, etc. For multi-probe temperature averaging
applications, two or more thermocouple probes may be connected to the
controller (always use the same type). Paralleling a single thermocouple to
more than one controller is not recommended. Generally, the red wire from
the thermocouple is negative and connected to the controller’s common.
RTD sensors are used where a higher degree of accuracy and stability is
required than is obtained with thermocouples. Most RTD sensors available
are the three wire type. The third wire is a sense lead for canceling the effects
of lead resistance of the probe. Four wire RTD elements may be used by
leaving one of the sense leads disconnected. Two wire RTD sensors connect
between terminals #8 and #10. A sense wire connected to terminal #9, is
required for operation. The sense wire can be connected in either of two ways:
A) Install a copper sense wire of the same wire gauge as the RTD leads.
Connect one end of the sense wire at terminal #9, and connect the other end
of the sense wire at the probe (on the terminal #8 side). Complete lead wire
compensation is obtained. This is the preferred method.
B) Connect a shorting wire directly from terminal #9 to terminal #8, as shown
in Figure 8, RTD Connection. A temperature offset error of 2.5°C/ohm of
lead resistance exists. The error may be compensated for by programming a
temperature offset.
Note: With extended cable runs, be sure the lead resistance is less than 10
ohms/lead.
Figure 7, Thermocouple Connection
Figure 8, RTD Connection
9
Valve Positioner Wiring
Units with Valve Positioner option have three output connections for
controlling the valve motor and three input connections for slidewire
feedback. The valve motor output connects to terminals labeled “Valve
Position Outputs”, terminals 1, 2 and 3. See Figure 9 , Valve Positioner
Wiring for more details. Terminal 1 is the Valve motor supply common.
Terminal 2 is the Valve Close or CW output. Terminal 3 is the Valve Open or
CCW output. The valve motor common must be fused with a suitable value.
Figure 9, Valve Positioner Wiring
Although RC snubbers are employed inside the controller to suppress
inductive “kicks” from the motor, it may be necessary to take further action to
reduce noise effects:
1) Use Triac Output Modules wherever possible. The Triac device
significantly reduces radiated EMI (Electromagnetic Interference).
The Triac Output Module also does not suffer from mechanical wear of the
contacts.
2) Use RC snubbers directly across the valve motor.
3) Use a separate AC supply for the valve motor.
Where possible, the valve motor control outputs and the slidewire
feedback input routing should be physically separated. Noise interference
from the outputs could couple into the slidewire f eedback inputs, disrupting
proper operation.
The slidewire feedback inputs connect to the terminals labeled “Slidewire
Feedback Inputs”. The terminal placement varies with each model, see the
controller label for the actual terminals. For Velocity mode valve control the
slidewire feedback inputs are not necessary.
In some cases, it may be desirable to have an independent valve position
indicator. Red Lion Controls Model IMD1 can be wired in parallel with the
slidewire input’s Wiper and Comm. terminals for this purpose. The
approximate 0 to 0.9 V signal can be scaled to indicate percent valve position.
Linear DC Output Wiring
Units with Linear DC output option have two terminals to output a 4 to 20
mA or 0 to 10 VDC signal. The type of Linear DC output is determined by the
model ordered. (See Ordering Information page 90, for available models.)
These terminals are labeled “4-20 mA (or 0-10 VDC) Analog Output Option,
Out+ and Out-”. The common of this output is isolated from thermocouple
common , but is not isolated from the Second Analog Input Option common.
For proper operation always keep these commons isolated.
Second Analog Input Wiring
Units with Second Analog Input option have two input terminals to receive
a 4 to 20 mA signal. These terminals are labeled “Second Input, 4-20 mA+ and
4-20 mA-”. Terminal placement varies with model. See unit label for actual
terminals. The common of this input is isolated from thermocouple common,
but is not isolated from the Linear DC Output common. For proper operation
always keep these commons isolated.
10
Heater Current Monitor Wiring
Units with Heater Current Monitor option have two input terminals to
receive the output directly from a 100 mA current transformer.
Caution: Never connect a currenttransformer with a rating other than 100 mA.
These terminals are labeled “Second Input CT”, see Figure 10, Heater
Current Wiring. Terminal placement varies with model. See controller label
for actual terminals. There is no polarity observation for these inputs.
Figure 10, Heater Current Wiring
Program Disable Or User Input Wiring
Some models have Terminal #7 as the User Input, which is programmable
for a variety of functions. Other models have Terminal #7 dedicated to the
program disable function. Any form of mechanical switch may be connected
to terminal #7. Sinking open collector logic with less than 0.7 V saturation
may also be used (no pull-up resistance is necessary).
Note: Do not tie the commons of multiple units to a single switch. Use either a
multiple pole switch for ganged operation or a single switch for each unit.
AC Power Wiring
Primary AC power is connected to the separate two position terminal block
labeled AC. To reduce the chance of noise spikes entering the AC line and
affecting the controller, an AC feed separate from that of the load should be
used to power the controller. Be certain that the AC power to the controller is
relatively “clean” and within the -15%, +10% variation limit. Connecting
power from heavily loaded circuits or circuits that also power loads that cycle
on and off, (contacts, relays, motors, etc.) should be avoided.
11
FRONT PANEL DESCRIPTION
The front panel bezel material is
flame and scratch resistant, tinted
plastic. An optional NEMA
4X/IP65 bezel version is available
that meets NEMA 4X/IP65
requirements, when properly
installed. There are two 4-digit
LED displays, a red upper Main
Display and a lower green
Secondary Display.
There are up to six annunciators
depending on options installed,
with red backlighting, that
illuminate to inform the operator of
the controller and output status. See
Figure 11, Front Panel for a
description of the available
annunciators.
Four front panel buttons are used
to access different modes and
parameters. The following is a
description of each button.
Button Functions
DSP - In the normal operating
mode, the Display (DSP) button
is used to select one of the
operational parameters in the
secondary display or the
temperature unit’s (°F or °C). In
the Configuration Parameter
Modes, pressing this button causes the unit to exit (escape) to the normal
operating mode with no changes made to the selected parameter.
UP, DN - In the normal operating mode, the Up/Down buttons can be used to
directly modify the setpoint value or % output power (manual mode only),
Figure 11, Front Panel
when viewed in the secondary display. Otherwise, the parameter must be
called to alter the value.
PAR - The Parameter (PAR) button is used to access, enter the change, and
scroll through the available parameters in any mode.
12
OPERATION OVERVIEW
Controller Power-up
Upon applying power, the controller delays control action and temperature
indication for five seconds to perform several self-diagnostic tests and
display basic controller information. Initially, the controller illuminates both
displays and all annunciators to verify that all display elements are
functioning. The controller then displays the programmed input sensor type
in the main display (verify that the input select sensor jumper matches the
programming). Concurrently, it displays the current revision number of the
operating system software in the bottom display. The controller checks for
correct internal operation and displays an error message (E-XX) if an intern al
fault is detected (see Troubleshooting, page 78, for further information).
Upon completion of this sequence, the controller begins control action by
displaying the temperature and updating the outputs based upon the PID
control calculation.
Controller Power Down
At power down, the steady state control value as well as all parameters and
control modes are saved, to provide a quick and predictable temperature
response on the next power-up.
When powering down the process, it is important to power down the
controller at the same time. This prevents the reset action of the controller
from shifting the proportional band while the temperature is dropping and
prevents excessive overshoot on the next process start-up.
Process Start-up
After starting the process, the controller’s PID settings must be initially
“tuned” to the process for optimum temperature control. Minimal tuning
consists of adjusting the Proportional Band, Integral Time, and Derivative
Time parameters to achieve the optimum response to a process disturbance.
The controller can be tuned once, but must be re-tuned if the process has been
changed significantly. Several options exist for tuning these parameters:
A) Use the controller’s built-in Auto-Tune feature (see Auto-Tune, page 68).
B) Use a manual tuning technique (see Manual Tuning, page 81).
C) Use a third party tuning software package (generally expensive and not
always precise).
D) Use values based on control loop experience, calculated values or values
from a similar process.
If the controller is a replacement, the PID settings from the unit being
replaced may be used as good initial values. Be sure to consider any
differences in the units and the PID settings when replacing. The PID settings
may be fine tuned by using the techniques outlined in the PID Control section.
After tuning the controller to the process, it is important to power the load and
the controller at the same time for best start-up response.
Manual (User) & Automatic Operation
The controller can be transferred between Automatic control (closed loop;
PID or ON/OFF control) and Manual control (open loop). In the Hidden
Function Mode, the “trnf” parameter allows the operator to select the desired
operating mode. To allow front panel switching between control modes,
program the transfer (trnf) parameter to “Enbl” in the Lockout Module. The
user input or RS485 serial interface option may also be used to perform the
auto/manual transfer function, independent of the setting in the Lockout
Module.
Manual operation provides direct control of the output(s) from 0 to +100%,
or -100% to +100% if cooling output is installed. For Valve Positioner
models with slidewire f eedback, this mode allows manual valve positioning.
The MAN (REM for Remote Setpoint models) annunciator flashes to indicate
that the unit is in manual operation. When transferring the controller mode
from/to automatic, the control power output(s) remain constant, exercising
true “bumpless” transfer. When transferring from manual to automatic, the
power initially remains steady but integral action corrects (if necessary) the
closed loop power demand at a rate proportional to the Integral Time. The
programmable high and low power limit values are ignored when the unit is in
manual operation.
13
Remote And Local Setpoint Operation
The controller setpoint mode can be switched between Local Setpoint
operation and Remote Setpoint operation. In the Hidden Function Mode, the
“SPSL” parameter allows the operator to select the desired setpoint operating
mode. To allow front panel switching between setpoint modes, program the
setpoint select parameter (SPSL) to “Enbl” in the Lockout Module. The user
input or RS485 serial interface option may also be used to perform the
setpoint selection function, independent of the setting in the Lockout
Module. Front panel annunciator REM is on for Remote setpoint operation
and is off for Local setpoint operation. When transferring the controller mode
from/to the setpoint modes, various controller response options are available
(see SPtr parameter, page 38).
14
Configuration Of Parameters
As supplied from the factory, the controller parameters have been
programmed to the values listed in the Programming Quick Reference
Tables. The user must modify the v alues, if necessary, to suit the application.
Operation and configuration of the controller is divided into five distinct
operational/programming modes to simplify the operation of the controller:
Normal Display Mode, Unprotected Parameter Mode, Protected Parameter
Mode, Hidden Function Mode, and Configuration Parameter Modules. See
Figure 12, Operational/Programming Modes.
Figure 12, Operational/Programming Modes
15
Parameter Entry
The PAR button is used to select the desired parameter. To modify the
parameter setting use the UP and DOWN buttons. Press PAR to enter the new
value. The controller progresses to the next parameter. In a Configuration
Parameter Module, pressing the DSP button causes the new value to be
rejected, the controller displays “End”, and returns to the Normal Display
Mode. For those parameters outside the Configuration Parameter Modules,
the new value takes effect and is committed into controller memory WHILE
the value is keyed in. The following is a list o f commonly modified
parameters:
Setpoint
Output Power
Output Power Offset
Proportional Band
Integral Time
Derivative Time
Proportional Band #2
Integral Time #2
Derivative Time #2
Directed Setpoint (Cascade)
Ratio
Bias
Alarm 1 Value
Alarm 2 Value
Note: While in a Configuration Parameter Module, all new parameters are
rejected and the old ones recalled if power is removed from the controller. If
power is removed while modifying any parameter, be certain to check the
parameter for the proper value.
Normal Display Mode
In the normal display mode, the process temperature is always displayed in
the main display. By successively pressing the DSP button, one of these
operational parameters can be viewed in the secondary display (model
dependent):
Temperature Setpoint
% Output Power
Heater Current
Second Analog Input (Remote Setpoint)
Temperature Setpoint Deviation
Temperature Units Symbol (°F or °C).
Each of these displays can be independently locked out from appearing or
from being modified by the user (see Lockouts Module, page 28). Only from
the normal display mode can access be gained to the other modes
(Unprotected, Protected, or Hidden).
Modifying A Secondary Display Parameter From The Front
Panel
The controller must be in the normal display mode to modify the secondary
display parameters. The Temperature Setpoint value and % output power (in
manual mode) are the two parameters which may be modified. The other
parameters are read-out values only.
Temperature Setpoint Value - Use the up and down arrow buttons to modify
the setpoint value when viewed, if not locked. If locked, the setpoint can be
changed in the unprotected mode when “SP” is viewed, independent of
viewing in the secondary display. The setpoint value is confined to the
% Output Power - The % Output Power can only be changed when the unit is
in the manual mode. See Manual (User) and Automatic Operations, page
13. The annunciator %PW lights, and the Manual annunciator flashes
when viewed. Use the up and down arrow buttons to modify the % Output
Power if not locked. If locked, the % output power can be changed in the
unprotected mode when “OP” is viewed, independent of viewing in the
secondary display. The % output power is not confinedto the programmable
output power limit values (OPLO & OPHI, Output Module 2).
16
UNPROTECTED PARAMETER MODE
The Unprotected Parameter Mode is accessed by pressing the PAR button
from the normal display mode with program disable inactive. In this mode,
the operator has access to the list of the most commonly modified controller
parameters. At the end of the list, a configuration “access point” allows the
operator to enter the configuration parameter modules. These modules allow
access to the fundamental set-up parameters of the controller. When the
program list has been scrolled through, the controller displays “End” and
returns to the normal display mode. The unit automatically returns to the
normal display mode if no action is taken.
Unprotected Parameter Mode Reference Table
Display Parameter
SPTemperature
Setpoint
OPOF%Output
Power
Offset
OPOutput
Power
PropProportional
Band
InttIntegral
Time
dErtDerivative
Time
Pb-2Proportional
Band #2
(Secondary)
It-2Integral
Time #2
(Secondary)
Range and
Units (Factory
Setting Value)
Confined to
range of limits
SPLO, SPHI, 1
or 0.1 degree
(0)
-99.9% to
100%
(0.0)
-99.9% to
100%
(0.0)
0.0 to 999.9% of
selected input
range
(4.0)
0 to 9999 sec.
(120)
0 to 9999 sec.
(30)
0.0 to 999.9% of
Scaled input
range
(4.0)
0 to 9999 sec.
(0)
Appears only if setpoint value is
locked (LOC) or read only (rEd).
Appears only if integral time
(Intt) = 0 and controller is in
automatic mode.
Appears only if controller is in
user (manual) mode and %
output power is (LOC) or read
only (rEd). This parameter is not
limited to output power limits
(OPLO & OPHI).
0.0% is ON/OFF control. If using
ON/OFF mode, set control
hysteresis appropriately.
0 is off. This parameter does not
appear if proportional band =
0.0%.
0 is off. This parameter does not
appear if proportional band =
0.0%.
0.0% is ON/OFF control.
Second Analog Input models
only.
0 is off. This parameter does not
appear if proportional band #2 =
0.0%. Second Analog Input
models only.
Description/
Comments
17
Display Parameter
dt-2Derivative
Time #2
(Secondary)
SP-2Internal
Cascade
Directed
Setpoint
rtioRemote
Setpoint ratio
multiplier
bIASRemote
Setpoint bias
offset
AL-1Alarm 1
Value
AL-2Alarm 2
Value
CNFPConfiguration
Access
Point
EndUnit returns
to Normal
Display Mode
Range and
Units (Factory
Setting Value)
0 to 9999 sec.
(0)
-999 to 9999
(N/A)
0.001 to 9.999
(1.000)
0 to 9999
(0)
-999 to 9999, 1
or 0.1 degree
(0)
-999 to 9999, 1
or 0.1 degree
(0)
____Brief display message.
0 is off. This parameter does not
appear if proportional band #2 =
0.0%. Second Analog Input
models only.
Second Analog Input models
only. Read only parameter.
Second Analog Input models.
Second Analog Input models.
Alarm option models only.
This parameter does not appear if
the alarm option is not specified,
the cooling option is installed, or
if locked (LOC).
Return to normal display mode.
NO
Enter Configuration modules.
Configure input parameters.
1-IN
Configure output parameters.
2-OP
Configure parameter lockouts.
3-LC
Configure alarm parameters (opt.)
4-AL
Configure cooling output (opt.)
5-02
Configure serial communication
6-SC
parameters (optional)
Configure second analog input
7-2N
parameters (optional)
Configure valve positioner
8-VP
parameters (optional)
Factory service operations
9-FS
(Qualified technicians only)
Description/
Comments
18
PROTECTED PARAMETER MODE
The Protected Parameter Mode is accessed from the normal display mode
by pressing the PAR button with program disable active. In this mode, the
operator h as access to the list of the most commonly modified controller
parameters that have been “unlocked” in the configuration parameter
lockouts module. Depending on the code number entered in the lockout
Protected Parameter Mode Reference Table
Display Parameter
PropProportional
Band
InttIntegral
Time
dErtDerivative
Time
Pb-2Proportional
Band #2
(Secondary)
It-2Integral
Time #2
(Secondary)
dt-2Derivative
Time #2
(Secondary)
SP-2Internal
Cascade
Directed
Setpoint
Range and
units (Factory
Setting Value)
0.0 to 999.9%
of selected
input range
(4.0)
0 to 9999 sec.
(120)
0 to 9999 sec.
(30)
0.0 to 999.9%
of scaled input
range
(4.0)
0 to 9999 sec.
(0)
0 to 9999 sec.
(0)
-999 to 9999
(N/A)
Description/Comments
0.0% is ON/OFF control. If using
ON/OFF mode, set control
hysteresis appropriately. This
parameter does not appear if
locked (LOC).
0 is off. This parameter does not
appear if proportional band = 0.0%
or locked (LOC).
0 is off. This parameter does not
appear if proportional band = 0.0%
or locked (LOC).
0.0% is ON/OFF control. Second
Analog Input models only.
0 is off. This parameter does not
appear if proportional band #2=
0.0%, or if locked (LOC). Second
Analog Input models only.
0 is off. This parameter does not
appear if proportional band #2=
0.0%, or if locked (LOC). Second
Analog Input models only.
Second Analog Input models only.
Read only parameter.
module, access to the unprotected parameter mode and hence, the
configuration parameter modules is possible. The controller returns to the
normal display mode if the unprotected mode and configuration modules
cannot be accessed. This mode cannot be accessed if all parameters are locked
out in Configuration Module 3.
Display Parameter
rtioRemote
setpoint
ratio
multiplier
bIASRemote
setpoint
bias offset
AL-1Alarm 1
value
AL-2Alarm 2
value
CodeAccess
code to
unprotected
mode
EndUnit returns
to normal
display
mode.
Range and
units (Factory
Setting Value)
0.001 to 9.999
(1.000)
0 to 9999
(0)
-999 to 9999
1 or 0.1 degree
(0)
-999 to 9999
1 or 0.1 degree
(0)
0 to 250
(0)
Description/Comments
Second Analog Input models only.
Second Analog Input models only.
Alarm option models only.
This parameter does not appear if
the alarm option is not specified,
the cooling option is installed, or if
locked (LOC).
To gain access to unprotected
mode, enter the same value for
Code as entered in parameter
lockouts. This parameter does not
appear if zero is entered in code
parameter lockout.
Brief display message display
mode.
19
Front Panel Program Disable
There are several ways to limit the programming of parameters from the
front panel buttons. The settings of the parameters in the Lockout Module, the
code number entered, and the state and/or function programmed for the User
Input (Terminal #7) affect front panel access.
It is possible to have the program disable function on versions with the
User Input, even if the User Input is not programmed for program disable
(PLOC), by the use of a code number. Versions that do not have the User Input
are dedicated to the program disable function.
The f ollowing charts describe the possible program disable settings
depending on your model.
Models With User Input
User Input StateCode NumberDescription
Inactive or User
Input not
programmed for
PLOC
Active with User
Input programmed
for PLOC
Active with User
Input programmed
for PLOC
OR
User Input not
programmed for
PLOC
Note: A universal code number 222 can be entered to gain access to the
unprotected mode and configuration modules, independent of the
programmed code number.
0Full access to all modes and
0Access to protected parameter
Any # between
1 & 250
parameter modules.
mode only. Code number does not
appear.
Access to protected parameter
mode. Correct programmed code
number allows access to
unprotected parameter mode and
configuration modules.
Models With Program Disable
Program DisableCode NumberDescription
Inactive0Full access to all modes and
Active0Access to protected parameter
ActiveAny # between
1 & 250
Note: A universal code number 222 can be entered to gain access to the
unprotected mode and configuration modules, independent of the
programmed code number.
parameter modules.
mode only. Code number does not
appear.
Access to protected parameter
mode. Correct programmed code
number allows access to
unprotected parameter mode and
configuration modules.
20
HIDDEN FUNCTION MODE
The Hidden Function Mode is only accessible from the normal display
mode by pressing and holding the PAR button for three seconds. These
functions must be unlocked in Configuration Module #3. Factory settings are
locked. In this mode, these controller functions can be performed.
Local/Remote Setpoint Selection
Automatic/Manual Transfer
Initiate/Cancel Auto-tune
Reset Alarm Events
Each function may be “locked out” in the Configuration parameter
lockouts module. The PAR button is used to scroll to the desired function and
the up and down buttons are used to select the operation. Pressing the PAR
button while the function is displayed executes the function, and returns the
unit to the normal display mode. Pressing the DSP button exits this mode with
no action taken. The unit automatically returns to the normal display mode if
no action is taken.
Hidden Function Mode Reference Table
Display Parameter
SPSLSelect
Local or
Remote
Setpoint
trnFTransfer
mode of
operation
tUNEAuto-tune
invocation
ALrSAlarm reset UP key resets Alarm 1
Range and Units
(Factory Setting Value)
LOC - Local Setpoint
rE_t - Remote Setpoint
(LOC)
Auto - Automatic control
User - Manual control
(Auto)
Yes: starts the
auto-tune sequence.
No: terminates the
auto-tune sequence.
Prl - tune primary
(Cascade)
SEC - tune secondary
(Cascade)
(NO)
DOWN key resets
Alarm 2
Description/
Comments
Appears only for models
with Second Analog Input.
“SPtr” determines nature of
controller response.
This step does not appear
if locked (LOC). Exits to
normal display mode if
executed.
This step does not appear
if locked (LOC) or exits to
normal display mode if
executed.
These parameters appear
only if Second Analog
Input Internal Cascade is
selected.
This step does not appear
if alarm option not
installed, if locked (LOC) or
previous step performed.
21
CONFIGURATION PARAMETER MODULES
Accessible from the unprotected parameter mode, the configuration
parameter modules allow the operator access to the controller’s fundamental
set-up parameters. There are nine possible configuration stages that can be
accessed. At the configuration stage access point “CNFP”, the operator uses
the UP & DOWN arrow buttons to select the desired configuration parameter
module. Press the PAR button to enter the module where the settings can be
viewed or modified. The PAR button is used to scroll through the parameters
and the UP and DOWN buttons are used to modify the parameter value. The
PAR button enters the desired choice, advancing to the next parameter. The
operator can press the DSP button to exit (escape) without modifying the
parameter. The unit returns to the normal display mode. After the parameters
in a module are viewed or modified, the unit returns to the configuration
access point, allowing access to other modules.
Input Module (1- In)
The controller has several input set-up parameters that must be
programmed prior to setting any other controller parameters.
Input Type (type)
Select from the list of various thermocouple and RTD sensors. Be sure to
set the internal input select jumper to the appropriate position (TC or RTD,
see Select Input Sensor Type, page 7, or the label on outside of case f or
location of jumper).
The following is a list of the possible sensors:
tc-t- Type T TC
tc-E- Type E TC
tc-J- Type J TC
tc-k- Type K TC
tc-r- Type R TC
tc-S- Type S TC
tc-B- Type B TC
tc-N- Type N TC
LIN- Linear mV display
r385- 385 curve RTD
r392- 392 curve RTD
rLIN- Linear ohms display
Temperature Scale (SCAL)
Select either degrees Fahrenheit (F) or degrees Celsius (C). If changed, be
sure to check All parameters.
Temperature Resolution (dCPt)
Select either 1 or 0.1 degree resolution. If changed, be sure to check All
parameters.
Input Signal Filter and Display Update Rate (FLtr)
Select the relative degree of input signal filtering and display update rate.
The filter is an adaptive digital filter thatdiscriminates between measurement
noise and actual process changes. Therefore, the influence on step response
time is minimal. If the signal is varying too greatly due to measurement noise,
increase the filter value. Additionally, with large derivative times, control
action may be too unstable f or accurate control. Increase the filter value.
Conversely, if the fastest controller response is desired, decrease the filter
value.
The Auto-tune procedure sets the filter v alue appropriate to the process
characteristics. Also see Output Power Dampening parameter (OPdP), page
26, for filtering the output.
Fltr- 0 to 4
0 = least input filtering
3 = most input filtering
4 = most input filtering and slower (2/sec) display update rate
(outputs update at 10/sec rate)
22
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.