Red Lion PXU User Manual

Tel +1 (717) 767-6511
PROCESS CONTROL EQUIPMENT
Fax +1 (717) 764-0839
www.redlion.net
PXU
Temperature/Process Controller Installation Guide
U
R
C
US LISTED
L
13RW
Drawing No. LP0951B
Released 02/14
See the Red Lion website at www.redlion.net for a complete user manual.
CAUTION: Risk of electric shock.
When the power is on, DO NOT touch the AC terminals, an electric shock may
occur. Make sure the power is disconnected when you check the input power supply.
1. Prevent dust or metallic debris from falling into the controller and causing malfunctions. DO NOT modify the controller.
2. The PXU is an open-type device. Make sure it is installed in an enclosure free of dust and humidity in case of an electric shock.
3. Wait for one minute after the power is switched off to allow the unit to discharge. DO NOT touch the internal wiring within this period of time.
SPECIFICATIONS
POWER:
100 to 240 VAC -20/+8 %, 50/60 Hz, 5 VA
Low Voltage Models:
DC Power: 24 VDC, ±10%, 5 W
INPUT CAPABILITIES: Thermocouple Inputs:
Types: T, E, J, K, R, S, B, N, L, U, and TXK
RTD Inputs:
Type: 2 or 3 wire, 2 wire can be compensated for lead wire resistance Excitation: 180 µA typical Input Type:
100 Ω Pt alpha = .00385 100 Ω Pt alpha = .00392 120 Ω Nickel alpha = .00672 50 Ω Copper alpha = .00428
Process Input Ranges:
0-5 VDC 0-20 mA 0-50 mV 0-10 VDC 4-20 mA
USER INPUT (Optional):
Contact/NPN Open Collector Input:
Response Time: 1 sec max Functions: Programmable
ON Resistance 1 KΩ max. OFF Resistance 100 KΩ min.
OUTPUT:
CONTROL RELAY OUTPUTS (OUT1/OUT2):
Type: Form A Contact Rating: 5 A @ 250 VAC Contact Isolation to all I/O: 2300 VAC for 1 min.
CONTROL SSR DRIVE OUTPUT (OUT1):
Rating: 12 VDC ± 10% @ 40 mA max.
CONTROL OUTPUT (OUT1) Analog Models:
Analog Types: 4 to 20 mA or 0 to 10 VDC Isolation To Sensor & Communication Common: 500 VDC for 1 min. Compliance: 10 VDC: 1 K load min., 20 mA: 500 load max.
ALARMS: 2 relay alarm outputs.
Typ e: Form A or Form C, model and alarm dependent Contact Rating: 3 A @ 250 VAC
ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50 °C Storage Temperature Range: -20 to 65 °C Vibration Resistance: Operational 10 to 55 Hz, 1 g Shock Resistance: Operational 30 g Operating and Storage Humidity: 80% max relative humidity (non-
condensing) from 0°C to 50°C
Altitude: Up to 2000 meters
CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A EN 61010-1
RoHS Compliant UL Listed: File #E179259 IP65 Enclosure rating (Face only)
CONNECTIONS: Wire-clamping screw terminals CONSTRUCTION: Black plastic alloy case and panel latch. Black plastic
textured bezel with transparent display window. Controller meets IP65 requirements for indoor use when properly installed. Installation Category II,
Pollution Degree 2.
WEIGHT:
1/4 DIN: 11.0 oz (312 g) 1/8 DIN: 7.8 oz (221 g) 1/16 DIN: 5.3 oz (150 g)
DIMENSIONS In inches (mm) - 1/16 DIN
1.89
(48.0)
1.89
(48.0)
0.26
(6.70)
3.14 (79.70)
1
0.31
(7.80)
0.47 (11.88)
0.83 (21.0)
PANEL CUT-OUT
1
2
3
4
5
6
1.77
(45.0)
13
14
15
16
17
18
7
8
9
10
11
12
1.77
(45.0)
DIMENSIONS In inches (mm) - 1/8 DIN
FACTORY SETTING
7
8
9
10
11
12
PANEL LATCH
(SUPPLIED W/UNIT)
EXISTING PANEL CUT-OUT
1/16 DIN
1.77” (45.0 mm) X 1.77” (45.0 mm)
PANEL GASKET
3.77
(95.8)
1.89
(48.0)
F2
F1
DP
0.45
(11.4)
2.82 (71.5)
3.60
(91.5)
PANEL CUT-OUT
(44.5)
1
2
3
4
5
6
7
8
9
10
11
12
1.76
13
14
15
16
17
18
19
20
21
22
23
24
3.60
(91.5)
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the controller. If redundant safeguards are not in place, an independent and redundant temperature limit indicator with alarm outputs is strongly recommended.
DIMENSIONS In inches (mm) - 1/4 DIN
3.77 (95.8)
3.77
(95.8)
0.45
(11.4)
2.82 (71.5)
3.58
(91.0)
SETTING THE CURRENT INPUT JUMPER
When Input Type is selected as one of the two current input types (0-20 or 4-20), the current input jumper must be installed. The current input jumper is factory set for Temperature and Voltage input types. To change the jumper to configure the input for a current input type, the inside of the unit must be accessed and the jumper position changed.
To access the jumper, locate the two latches located on top and bottom of the front of the unit. Starting with the top latch, insert a small flat-blade screwdriver between the case latch and bezel while using your thumb to push out on the bezel until the latch is disengaged. Repeat this process with the bottom latch. After the latches are disengaged, using the flat-blade screwdriver, gently pry out on the bezel in several areas until the unit releases from the case.
Look for the Current Input Jumper which will be located close to the pc board area that connects to the input terminals. If a current input type is desired, position the jumper across both pins. If input type is anything other than a current input, position the jumper on only one pin.
PANEL CUT-OUT
3.58 (91.0)
1
2
3
4
5
6
7
8
9
10
11
12
25
26
27
28
29
30
31
32
33
34
35
36
Thermocouple, RTD
or Voltage Input
JUMPER
JP8
PIN HEADER
13
14
15
16
17
18
19
20
21
22
23
24
3.58
(91.0)
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
Current Input
(4-20 mA or 0-20 mA)
JUMPER
JP8
PIN HEADER
INSTALLING THE CONTROLLER
The controller is designed to be mounted into an enclosed panel. The unit must be inserted in the case during installation of the controller.
Instructions:
1. Prepare the panel cutout to the proper dimensions.
2. Assemble the mounting clip by inserting the nut into the slot and then insert
the screw and thread through the nut as shown (See drawing)
3. Slide the panel gasket over the rear of the controller, seating it against the lip
at the front of the case.
4. Insert the controller into the panel cutout. While holding the controller
in place, install the panel latch(es) and then slide it to the farthest
forward slot possible.
5. To achieve a proper seal, tighten the panel latch screws evenly until the
controller is snug in the panel, torquing the screws to 13.9 to 20.8 oz-in
(9.8 to 14.7 N-cm). Overtightening can result in distortion of the
controller, and reduce the effectiveness of the seal.
Note: The installation location of the controller is important. Be sure to
keep it away from heat sources (ovens, furnaces, etc.) and away from
direct contact with caustic vapors, oils, steam, or any other process
by-products in which exposure may affect proper operation.
1/16 DIN Installation
2
L
A
r
+
D-
1/8 DIN Installation
_
(2) PANEL LATCH
(SUPPLIED W/UNIT)
PANEL GASKET
EXISTING PANEL CUT- OUT
1.76" (44.5 mm) X 3.60" (91.5 mm)
1/4 DIN Installation
(4) PANEL LATCH
(SUPPLIED W/UNIT)
13
14
15
16
17
18
19
20
21
22
23
24
PANEL GASKET
EXISTING PANEL CUT- OUT
3.58" (91.0 mm) X 3.58" (91.0 mm)
CONTROLLER POWER CONNECTIONS
For best results, the power should be relatively “clean” and within the specified limits. Drawing power from heavily loaded circuits or from circuits that also power loads that cycle on and off should be avoided. It is recommended that power supplied to the controller be protected by a fuse or circuit breaker.
INPUT CONNECTIONS
For two wire RTDs, install a copper sense lead of the same gauge and length as the RTD leads. Attach one end of the wire at the probe and the other end to input common terminal. This is the preferred method as it provides complete
RTD and Resistance Thermocouple and Millivolt
10
11
12
11
12
CONTROL AND ALARM OUTPUT CONNECTIONS
Alarm 1 and 2 * (1/16 DIN Shown)
COMM
AL 2
NO
AL 1
NO
LOAD
LOAD
AC/DC Power (-)
AC/DC Power (+)
OP1/OP2 Output Control Relay *
NO (+)
COMM (-)
OP1 Output Control Logic/SSR *
NO (+)
COMM (-)
VAC
1
DC 24V
VDC
1
+
C 100-240V 50/60 Hz 5VA
0 V
2
2
N
lead wire compensation. If a sense wire is not used, then use a jumper. A temperature offset error will exist. The error may be compensated by programming a temperature offset.
Voltage and Current
TC+
TC-
11
12
DC+ VOLTAGE/CURRENT
DC- VOLTAGE/CURRENT
OP1 Output Control Analog *
+
-
LOAD
SSR
POWER
UNIT
AC
AC
AC/DC Power
AC Powe
NO (+)
COMM (-)
IN +
IN -
ANALOG INPUT
CONTROL
DEVICE
USER INPUT CONNECTIONS *
User 1
-
+
User 2
RS 485 CONNECTIONS *
-
RS-485
D+
RECEIVING
+
RS485
DEVICE
-
* See unit label for terminal identification.
3
ORDERING INFORMATION
MODEL NO. DIN SIZE
1/16
PXU
1/8
(vertical)
1/4
Only stocked part numbers are listed. Contact factory for availability of non-stock models. In order to program the unit using Crimson, the unit must be purchased with the 485 option.
MAIN CONTROL
OUTPUT 1
Relay - - - PXU10020
Relay Relay 2 Yes PXU11A20
Logic/SSR - - - PXU20020
Logic/SSR Relay 2 Yes PXU21A20
4-20 mA - - - PXU30020
4-20 mA Relay 2 Yes PXU31A20
Relay - - - PXU10030
Relay Relay 2 Yes PXU11A30
Logic/SSR - - - PXU20030
Logic/SSR Relay 2 Yes PXU21A30
4-20 mA Relay 2 Yes PXU31A30
Relay Relay 2 Yes PXU11A50
4-20 mA Relay 2 Yes PXU31A50
ACCESSORIES
MODEL NO. DESCRIPTION PART NUMBERS
External SSR Power Unit (for Logic/SSR models) RLY50000
RLY
25 A Single Phase Din Rail Mount Solid State Relay RLY60000
40 A Single Phase Din Rail Mount Solid State Relay RLY6A000
Three Phase Din Rail Mount Solid State Relay RLY70000
SECONDARY
CONTROL OUTPUT 2
USER INPUT(S) RS 485 100 to 240 VAC
Do not dispose of unit in trash - Recycle
The Company warrants the products it manufactures against defects in materials and workmanship for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company
disclaims all liability for any afrmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing
components manufactured by RLC and based upon personal injuries, deaths, property damage, lost prots,
and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein
and relies on no other warranties or afrmations.
LIMITED WARRANTY
20 Willow Springs Circle | York, PA 17406 USA
+1 (717) 767-6511 | info@redlion.net | www.redlion.net
4