40033Active Alarm 1 Value-199999990Read/Write Active List (A or B)
40034Active Alarm 2 Value-199999990Read/Write Active List (A or B)
40035Active Alarm 3 Value-199999990Read/Write Active List (A or B)
40036Active Alarm 4 Value-199999990Read/Write Active List (A or B)
40037Active Alarm 5 Value-199999990Read/Write Active List (A or B)
40038Active Alarm 6 Value-199999990Read/Write Active List (A or B)
40039Active Alarm 7 Value-199999990Read/Write Active List (A or B)
40040Active Alarm 8 Value-199999990Read/Write Active List (A or B)
REGISTER NAME
LOW
LIMIT
HIGH
LIMIT
FACTORY
SETTING
ACCESSCOMMENTS
0 = Very Aggressive, 1 = Aggressive, 2 = Default, 3 = Conservative,
4 = Very Conservative
Status of Outputs. Bit State: 0 = Off, 1 = On.
Bit 3 = Out1, Bit 2 = Out2, Bit 1 = Out3, Bit 0 = Out4.
Outputs can only be activated/reset with this register when the respective
bits in the Manual Mode Register (MMR) are set.
Bit State: 0 = Auto Mode, 1 = Manual Mode
Bit 4 = SP1, Bit 3 = SP2, Bit 2 = SP3, Bit 1 = SP4, Bit 0 = Linear Output
Bit State: 1= Reset Alarm, bit is returned to zero following reset processing;
Bit 15 = A16, Bit 0 = A1
Functional only if Linear Output is in Manual Mode.(MMR bit 0 = 1)
Linear Output Card written to only if Linear Out (MMR bit 0) is set.
REGISTER
ADDRESS
40041Active Alarm 9 Value-199999990Read/Write Active List (A or B)
40042Active Alarm 10 Value-199999990Read/Write Active List (A or B)
40043Active Alarm 11 Value-199999990Read/Write Active List (A or B)
40044Active Alarm 12 Value-199999990Read/Write Active List (A or B)
40045Active Alarm 13 Value-199999990Read/Write Active List (A or B)
40046Active Alarm 14 Value-199999990Read/Write Active List (A or B)
40047Active Alarm 15 Value-199999990Read/Write Active List (A or B)
40048Active Alarm 16 Value-199999990Read/Write Active List (A or B)
40049Active Alarm 1 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40050Active Alarm 2 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40051Active Alarm 3 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40052Active Alarm 4 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40053Active Alarm 5 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40054Active Alarm 6 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40055Active Alarm 7 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40056Active Alarm 8 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40057Active Alarm 9 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40058Active Alarm 10 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40059Active Alarm 11 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40060Active Alarm 12 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40061Active Alarm 13 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40062Active Alarm 14 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40063Active Alarm 15 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40064Active Alarm 16 Band/Dev. Value-199999990Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40065Remote SP Value-199999990Read Only
INPUT PARAMETERSSEE INPUT MODULE FOR PARAMETER DESCRIPTIONS
Analog Input Parameters
0 = NONE 4 = SPSL 8 = d-HI 12 = r-HL 16 = LISt
1 = PLOC 5 = rSPt 9 = r-HI 13 = r-AL 17 = Prnt
2 = ILOC 6 = PSEL 10 = d-Lo 14 = dLEV 18 = FlexCard
3 = TrnF 7 = SPrP 11 = r-Lo 15 = dISP Functions
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13
Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14
Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15
Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40154User Input 2 Action017*0Read/Write Same as User Input 1 Action
40155User Input 2 Alarm Mask0655350Read/Write Same as User Input 1 Alarm Mask
40156User F1 Key Action014*0Read/Write
40157User F1 Key Alarm Mask0655350Read/Write Same as User Input 1 Alarm Mask
40158User F2 Key Action014*0Read/Write Same as User F1 Key Action
40159User F2 Key Alarm Mask0655350Read/Write Same as User Input 1 Alarm Mask
40160User F1 Second Action014*0Read/Write Same as User F1 Key Action
40161User F1 Second Alarm Mask0655350Read/Write Same as User Input 1 Alarm Mask
40162User F2 Second Action014*0Read/Write Same as User F1 Key Action
40163User F2 Second Alarm Mask0655350Read/Write Same as User Input 1 Alarm Mask
Advanced Input Parameters
List A List B Input Scaling Points Parameters
4017140211 Number of Scaling Points2162Read/Write Number of Linearization Scaling Points
4017240212 ReservedN/AN/AN/AN/A
4017340213 Scaling Pt.1 Input Value-199999990Read/Write 1 = 0.001
4017440214 Scaling Pt.1 Display Value-199999990Read/Write 1 = 1 Display Unit
40175
Registers 40175-40202 and 40215-40242 hold values for Scaling Points 2
thru 15, and follow the same ordering as Scaling Point 1.
0 = NONE 4 = P2C MAN 8 = ILOC 12 = FlexCard
1 = P2C Heat 5 = SPSL 9 = tUNE Assignments
2 = P2C Cool 6 = SPrP 10 = tndn
3 = ALr 7 = RSP Transfer 11 = tnFL
If Out Assignment≠ALr; 0 = NOR, 1 = REV
If Output Assignment = ALr; 0 = SINGLE, 1 = AND, 2 = OR
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13
Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14
Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15
Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40273Assignment06*0Read/Write
40274Analog Low Scale Value-199999990Read/Write Display value that corresponds with 0 V, 0 mA or 4 mA output
40275Analog High Scale Value-199999991000Read/Write Display value that corresponds with 10 V or 20 mA output
40276Update time01000Read/Write 0 = Max update rate, 1 = 0.1 Second
40277Probe Failure Action (TC or RTD only)010Read/Write 0 = Low Scale, 1 = High Scale (only applies for TC or RTD input)
Non-Linear Analog Output Scaling
List A List B Analog Output Scaling Point Parameters
4172141761 Number of Scaling Points2162Read/Write Number of Linearization Scaling Points
4172241762 ReservedN/AN/AN/AN/A
4172341763 Output Value for Scaling Point 1020000Read/Write 1 = 0.01
4172441764 Parameter Value for Scaling Point 1-199999990Read/Write 1 = 1 Analog Output Assignment value unit
40300Line 1 Green Backlight Assignment013*0Read/Write
40301Line 1 Green Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40302Line 1 Green Backlight Alarm Mask0655350Read/Write
40303Line 1 Orange Backlight Assignment013*0Read/Write Same as Line 1 Green Backlight Assignment
40304Line 1 Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40305Line 1 Orange Backlight Alarm Mask0655350Read/Write Same as Line 1 Green Backlight Alarm Mask
40306Line 1 Red Backlight Assignment013*0Read/Write Same as Line 1 Green Backlight Assignment
40307Line 1 Red Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40308Line 1 Red Backlight Alarm Mask0655350Read/Write Same as Line 1 Green Backlight Alarm Mask
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13
Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14
Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15
Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40309Line 1 Green-Orange Backlight Assignment013*0Read/Write Same as Line 1 Green Backlight Assignment
40310Line 1 Green-Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40311Line 1 Green-Orange Backlight Alarm Mask0655350Read/Write Same as Line 1 Green Backlight Alarm Mask
40312Line 1 Red-Orange Backlight Assignment013*0Read/Write Same as Line 1 Green Backlight Assignment
40313Line 1 Red-Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40314Line 1 Red-Orange Backlight Alarm Mask0655350Read/Write Same as Line 1 Green Backlight Alarm Mask
40315Line 1 Red-Green Backlight Assignment013*0Read/Write Same as Line 1 Green Backlight Assignment
40316Line 1 Red-Green Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40317Line 1 Red-Green Backlight Alarm Mask0655350Read/Write Same as Line 1 Green Backlight Alarm Mask
Line 2
40331Line 2 Default Display Color020Read/Write 0 = Grn, 1 = OrNG, 2 = rEd
40332Line 2 Units Mnemonic010Read/Write 0 = Off, 1 = On
40333Line 2 Units Digit 1 (Left)0570Read/Write Same as Line 1 Units Selection
40334Line 2 Units Digit 2 (Center)0570Read/Write
40335Line 2 Units Digit 3 (Right)0570Read/Write
40339Line 2 Green Backlight Assignment013*0Read/Write
40340Line 2 Green Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40341Line 2 Green Backlight Alarm Mask0655350Read/Write
40342Line 2 Orange Backlight Assignment013*0Read/Write Same as Line 2 Green Backlight Assignment
40343Line 2 Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40344Line 2 Orange Backlight Alarm Mask0655350Read/Write Same as Line 2 Green Backlight Alarm Mask
40345Line 2 Red Backlight Assignment013*0Read/Write Same as Line 2 Green Backlight Assignment
40346Line 2 Red Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40347Line 2 Red Backlight Alarm Mask0655350Read/Write Same as Line 2 Green Backlight Alarm Mask
40348Line 2 Green-Orange Backlight Assignment013*0Read/Write Same as Line 2 Green Backlight Assignment
40349Line 2 Green-Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40350Line 2 Green-Orange Backlight Alarm Mask0655350Read/Write Same as Line 2 Green Backlight Alarm Mask
40351Line 2 Red-Orange Backlight Assignment013*0Read/Write Same as Line 2 Green Backlight Assignment
40352Line 2 Red-Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40353Line 2 Red-Orange Backlight Alarm Mask0655350Read/Write Same as Line 2 Green Backlight Alarm Mask
40354Line 2 Red-Green Backlight Assignment013*0Read/Write Same as Line 2 Green Backlight Assignment
40355Line 2 Red-Green Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40356Line 2 Red-Green Backlight Alarm Mask0655350Read/Write Same as Line 2 Green Backlight Alarm Mask
Universal Annunciator 1
40361UA 1 Default Display Color020Read/Write 0 = Grn, 1 = OrNG, 2 = rEd
40362UA 1 Units Mnemonic011Read/Write 0 = Off, 1 = On
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13
Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14
Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15
Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
40367UA 1 Assignment Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40368UA 1 Assignment Alarm Mask0655350Read/Write
40368UA 1 Green Backlight Assignment013*0Read/Write Same as UA 1 Units Assignment
40369UA 1 Green Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40370UA 1 Green Backlight Alarm Mask0655350Read/Write Same as UA 1 Assignment Alarm Mask
40371UA 1 Orange Backlight Assignment013*0Read/Write Same as UA 1 Units Assignment
40372UA 1 Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40373UA 1 Orange Backlight Alarm Mask0655350Read/Write Same as UA 1 Assignment Alarm Mask
40374UA 1 Red Backlight Assignment013*0Read/Write Same as UA 1 Units Assignment
40375UA 1 Red Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40376UA 1 Red Backlight Alarm Mask0655350Read/Write Same as UA 1 Assignment Alarm Mask
40377UA 1 Green-Orange Backlight Assignment013*0Read/Write Same as UA 1 Units Assignment
40378UA 1 Green-Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40379UA 1 Green-Orange Backlight Alarm Mask0655350Read/Write Same as UA 1 Assignment Alarm Mask
40380UA 1 Red-Orange Backlight Assignment013*0Read/Write Same as UA 1 Units Assignment
40381UA 1 Red-Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40382UA 1 Red-Orange Backlight Alarm Mask0655350Read/Write Same as UA 1 Assignment Alarm Mask
40383UA 1 Red-Green Backlight Assignment013*0Read/Write Same as UA 1 Units Assignment
40384UA 1 Red-Green Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40385UA 1 Red-Green Backlight Alarm Mask0655350Read/Write Same as UA 1 Assignment Alarm Mask
Universal Annunciator 2
40391UA 2 Default Display Color020Read/Write 0 = Grn, 1 = OrNG, 2 = rEd
40392UA 2 Units Mnemonic011Read/Write 0 = Off, 1 = On
40393UA 2 Units Digit 1 (Left)0571Read/Write Same as UA1 Units Selection
40394UA 2 Units Digit 2 (Right)05729Read/Write
40395UA 2 Units Logic Mode (Active)020Read/Write 0 = nor, 1 = rEv, 2 = FLSh
40396UA 2 Units Assignment013*5Read/Write
40397UA 2 Assignment Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40398UA 2 Assignment Alarm Mask0655350Read/Write
40399UA 2 Green Backlight Assignment013*0Read/Write Same as UA 2 Units Assignment
40400UA 2 Green Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40401UA 2 Green Backlight Alarm Mask0655350Read/Write Same as UA 2 Assignment Alarm Mask
REGISTER NAME
LOW
LIMIT
HIGH
LIMIT
FACTORY
SETTING
ACCESSCOMMENTS
0 = 9 = I 18 = Q 27 = Z 36 = 8 45 = m(r) 54 = ]
1 = A 10 = J 19 = R 28 = 0 37 = 9 46 = o 55 = /
2 = b 11 = K 20 = S 29 = 1 38 = a 47 = q 56 = º
3 = C 12 = L 21 = t 30 = 2 39 = c 48 = r 57 = _
4 = d 13 = M(l) 22 = U 31 = 3 40 = e 49 = u
5 = E 14 = M(r) 23 = V 32 = 4 41 = g 50 = w(r)
6 = F 15 = N 24 = W(l) 33 = 5 42 = h 51 = 7 = G 16 = O 25 = W(r) 34 = 6 43 = i 52 = =
8 = H 17 = P 26 = Y 35 = 7 44 = n 53 = [
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13
Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14
Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15
Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13
Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14
Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15
Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40402UA 2 Orange Backlight Assignment013*0Read/Write Same as UA 2 Units Assignment
40403UA 2 Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40404UA 2 Orange Backlight Alarm Mask0655350Read/Write Same as UA 2 Assignment Alarm Mask
40405UA 2 Red Backlight Assignment013*0Read/Write Same as UA 2 Units Assignment
40406UA 2 Red Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40407UA 2 Red Backlight Alarm Mask0655350Read/Write Same as UA 2 Assignment Alarm Mask
40408UA 2 Green-Orange Backlight Assignment013*0Read/Write Same as UA 2 Units Assignment
40409UA 2 Green-Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40410UA 2 Green-Orange Backlight Alarm Mask0655350Read/Write Same as UA 2 Assignment Alarm Mask
40411UA 2 Red-Orange Backlight Assignment013*0Read/Write Same as UA 2 Units Assignment
40412UA 2 Red-Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40413UA 2 Red-Orange Backlight Alarm Mask0655350Read/Write Same as UA 2 Assignment Alarm Mask
40414UA 2 Red-Green Backlight Assignment013*0Read/Write Same as UA 2 Units Assignment
40415UA 2 Red-Green Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40416UA 2 Red-Green Backlight Alarm Mask0655350Read/Write Same as UA 2 Assignment Alarm Mask
Universal Annunciator 3
40421UA 3 Default Display Color020Read/Write 0 = Grn, 1 = OrNG, 2 = rEd
40422UA 3 Units Mnemonic011Read/Write 0 = Off, 1 = On
40423UA 3 Units Digit 1 (Left)0571Read/Write Same as UA1 Units Selection
40424UA 3 Units Digit 2 (Right)05730Read/Write
40425UA 3 Units Logic Mode (Active)020Read/Write 0 = nor, 1 = rEv, 2 = FLSh
40426UA 3 Units Assignment013*5Read/Write
40427UA 3 Assignment Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40428UA 3 Assignment Alarm Mask0655350Read/Write
40429UA 3 Green Backlight Assignment013*0Read/Write Same as UA 3 Units Assignment
40430UA 3 Green Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40431UA 3 Green Backlight Alarm Mask0655350Read/Write Same as UA 3 Assignment Alarm Mask
40432UA 3 Orange Backlight Assignment013*0Read/Write Same as UA 3 Units Assignment
40433UA 3 Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40434UA 3 Orange Backlight Alarm Mask0655350Read/Write Same as UA 3 Assignment Alarm Mask
40435UA 3 Red Backlight Assignment013*0Read/Write Same as UA 3 Units Assignment
40436UA 3 Red Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40437UA 3 Red Backlight Alarm Mask0655350Read/Write Same as UA 3 Assignment Alarm Mask
40438UA 3 Green-Orange Backlight Assignment013*0Read/Write Same as UA 3 Units Assignment
40439UA 3 Green-Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40440UA 3 Green-Orange Backlight Alarm Mask0655350Read/Write Same as UA 3 Assignment Alarm Mask
40441UA 3 Red-Orange Backlight Assignment013*0Read/Write Same as UA 3 Units Assignment
40442UA 3 Red-Orange Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40443UA 3 Red-Orange Backlight Alarm Mask0655350Read/Write Same as UA 3 Assignment Alarm Mask
40444UA 3 Red-Green Backlight Assignment013*0Read/Write Same as UA 3 Units Assignment
40445UA 3 Red-Green Backlight Alarm Logic Mode020Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40446UA 3 Red-Green Backlight Alarm Mask0655350Read/Write Same as UA 3 Assignment Alarm Mask
Universal Annunciator 4
40451UA 4 Default Display Color020Read/Write 0 = Grn, 1 = OrNG, 2 = rEd
40452UA 4 Units Mnemonic010Read/Write 0 = Off, 1 = On
40453UA 4 Units Digit 1 (Left)0570Read/Write Same as UA1 Units Selection
40454UA 4 Units Digit 2 (Right)0570Read/Write
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13
Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14
Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15
Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16