Red Lion PAX2C, PX2FCA0, PX2FCA1 Technical Data

PAX2C, PX2FCA0, and PX2FCA1 Modbus Register Tables LP0905D
PAX2C Ver 1.5 Modbus Register Table REVISED 2015-07-20
REGISTER
ADDRESS
FREQUENTLY USED REGISTERS
40001 Process Value N/A N/A N/A Read 1 = 1 Display Unit 40002 Maximum Value -1999 9999 N/A Read 1 = 1 Display Unit 40003 Minimum Value -1999 9999 N/A Read 1 = 1 Display Unit 40004 Active Setpoint Value SPLO SPHI 0 Read/Write 1 = 1 Display Unit; Limited by setpoint low/high limits 40005 Setpoint 1 Value SPLO SPHI 0 Read/Write 1 = 1 Display Unit; Limited by setpoint low/high limits 40006 Setpoint 2 Value SPLO SPHI 0 Read/Write 1 = 1 Display Unit; Limited by setpoint low/high limits 40007 Setpoint Deviation N/A N/A N/A Read Only 1 = 1 Display Unit 40008 Output Power -1000 1000 N/A Read/Write Output Power: Heat/Cool; * writable only in manual mode; 1 = 0.1% 40009 Active Proportional Band 0 9999 700 Read/Write 1 = 1 Display Unit 40010 Active Integral Time 0 65000 120 Read/Write 1 = 0.1 Second 40011 Active Derivative Time 0 9999 30 Read/Write 1 = 0.1 Second 40012 Active Power Filter 0 600 10 Read/Write 1 = 0.1 Second
40013 Auto-Tune Code 0 4 2 Read/Write
40014 Auto-Tune Request 0 1 0 Read/Write 0 = Off, 1 = Invoke Auto-Tune 40015 Auto-Tune Phase 0 4 0 Read 0 = Off, 4 = Last Phase of Auto-Tune 40016 Auto-Tune Done 0 1 0 Read 1 = Successful Auto-Tune since last power cycle. 40017 Auto-Tune Fail 0 1 0 Read 0 = Off, 1 = Auto-Tune failed 40018 Control Mode 0 1 0 Read/Write 0 = Automatic, 1 = Manual Mode 40019 Setpoint Selection 0 1 0 Read/Write 0 = Setpoint 1, 1 = Setpoint 2 40020 Remote/Local Setpoint Selection 0 1 0 Read/Write 0 = Local, 1 = Remote 40021 PID Parameter Selection 0 1 0 Read/Write 0 = Primary PID Values, 1 = Alternate PID Values 40022 Disable Integral Action 0 1 0 Read/Write 0 = Enabled, 1 = Disabled 40023 Disable Setpoint Ramping 0 1 0 Read/Write 0 = Enabled, 1 = Disabled 40024 Setpoint Ramping In Process 0 1 0 Read/Write 0 = Off, 1 = In Process 40025 Setpoint Ramp Rate Value -1999 9999 0 Read/Write 1 = 0.1 Setpoint Ramping @ Timebase unit selection 40026 Alarm (1-16) Status Register 0 65535 0 Read Bit 15 = A16, Bit 0 = A1 40027 Input Range Alarm 0 1 0 Read 0 = Off, 1 = Alarm active 40028 User Input Status 0 2 0 Read Bit 1 = User Input 2, Bit 0 = User Input 1
40029 Output Status 0 15 N/A Read/Write
40030 Output Manual Mode Register (MMR) 0 31 0 Read/Write
40031 Alarm Reset Register 0 65535 0 Read/Write
40032 Analog Output Register (AOR) 0 4095 0 Read/Write
40033 Active Alarm 1 Value -1999 9999 0 Read/Write Active List (A or B) 40034 Active Alarm 2 Value -1999 9999 0 Read/Write Active List (A or B) 40035 Active Alarm 3 Value -1999 9999 0 Read/Write Active List (A or B) 40036 Active Alarm 4 Value -1999 9999 0 Read/Write Active List (A or B) 40037 Active Alarm 5 Value -1999 9999 0 Read/Write Active List (A or B) 40038 Active Alarm 6 Value -1999 9999 0 Read/Write Active List (A or B) 40039 Active Alarm 7 Value -1999 9999 0 Read/Write Active List (A or B) 40040 Active Alarm 8 Value -1999 9999 0 Read/Write Active List (A or B)
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = Very Aggressive, 1 = Aggressive, 2 = Default, 3 = Conservative, 4 = Very Conservative
Status of Outputs. Bit State: 0 = Off, 1 = On. Bit 3 = Out1, Bit 2 = Out2, Bit 1 = Out3, Bit 0 = Out4. Outputs can only be activated/reset with this register when the respective bits in the Manual Mode Register (MMR) are set. Bit State: 0 = Auto Mode, 1 = Manual Mode Bit 4 = SP1, Bit 3 = SP2, Bit 2 = SP3, Bit 1 = SP4, Bit 0 = Linear Output Bit State: 1= Reset Alarm, bit is returned to zero following reset processing; Bit 15 = A16, Bit 0 = A1 Functional only if Linear Output is in Manual Mode.(MMR bit 0 = 1) Linear Output Card written to only if Linear Out (MMR bit 0) is set.
REGISTER
ADDRESS
40041 Active Alarm 9 Value -1999 9999 0 Read/Write Active List (A or B) 40042 Active Alarm 10 Value -1999 9999 0 Read/Write Active List (A or B) 40043 Active Alarm 11 Value -1999 9999 0 Read/Write Active List (A or B) 40044 Active Alarm 12 Value -1999 9999 0 Read/Write Active List (A or B) 40045 Active Alarm 13 Value -1999 9999 0 Read/Write Active List (A or B) 40046 Active Alarm 14 Value -1999 9999 0 Read/Write Active List (A or B) 40047 Active Alarm 15 Value -1999 9999 0 Read/Write Active List (A or B) 40048 Active Alarm 16 Value -1999 9999 0 Read/Write Active List (A or B) 40049 Active Alarm 1 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40050 Active Alarm 2 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40051 Active Alarm 3 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40052 Active Alarm 4 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40053 Active Alarm 5 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40054 Active Alarm 6 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40055 Active Alarm 7 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40056 Active Alarm 8 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40057 Active Alarm 9 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40058 Active Alarm 10 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40059 Active Alarm 11 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40060 Active Alarm 12 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40061 Active Alarm 13 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40062 Active Alarm 14 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40063 Active Alarm 15 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40064 Active Alarm 16 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40065 Remote SP Value -1999 9999 0 Read Only
INPUT PARAMETERS SEE INPUT MODULE FOR PARAMETER DESCRIPTIONS Analog Input Parameters
40101 Input Range 0 26 16 Read/Write
40102 Square Root Linearization 0 1 0 Read/Write 0 = No, 1 = Yes (Valid on Process Inputs) 40103 Temperature Scale (TC or RTD only) 0 1 1 Read/Write 0 = °C, 1 = °F 40104 Ice Point Compensation (TC only) 0 1 1 Read/Write 0 = Off, 1 = On 40105 ADC Conversion Rate (samples/sec) 0 5 2 Read/Write 0 = 5, 1 = 10, 2 = 20, 3 = 40, 4 = 80, 5 = 160 40106 Decimal Point 0 3 1 Read/Write 0 = 0, 1 = 0.0, 2 = 0.00, 3 = 0.000 40107 Rounding Factor 0 6 0 Read/Write 0 = 1, 1 = 2, 2 = 5, 3 = 10, 4 = 20, 5 = 50, 6 = 100 40108 Input Offset Value -1999 9999 0 Read/Write 1 = 1 Display Unit 40109 Digital Input Filter 0 250 10 Read/Write 1 = 0.1 Second 40110 Input Scaling Points in List Function 0 1 0 Read/Write 0 = No, 1 = Yes
User Input / Function Keys
40151 User Input Active State 0 1 0 Read/Write 0 = Active Low, 1 = Active High
40152 User Input 1 Action 0 17* 0 Read/Write
40153 User Input 1 Alarm Mask 0 65535 0 Read/Write
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = 250µA 5 = 250mV 11 = 100Ω 17 = TC-K 23 = RTD 385 1 = 2.5mA 6 = 2V 12 = 1KΩ 18 = TC-R 24 = RTD 392 2 = 25mA 7 = 10V 13 = 10KΩ 19 = TC-S 25 = RTD 672
3 = 250mA 8 = 25V 14 = TC-T 20 = TC-B 26 = RTD 427 4 = 2A 9 = 100V 15 = TC-E 21 = TC-N 10 = 200V 16 = TC-J 22 = TC-C
0 = NONE 4 = SPSL 8 = d-HI 12 = r-HL 16 = LISt 1 = PLOC 5 = rSPt 9 = r-HI 13 = r-AL 17 = Prnt 2 = ILOC 6 = PSEL 10 = d-Lo 14 = dLEV 18 = FlexCard 3 = TrnF 7 = SPrP 11 = r-Lo 15 = dISP Functions Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40154 User Input 2 Action 0 17* 0 Read/Write Same as User Input 1 Action 40155 User Input 2 Alarm Mask 0 65535 0 Read/Write Same as User Input 1 Alarm Mask
40156 User F1 Key Action 0 14* 0 Read/Write
40157 User F1 Key Alarm Mask 0 65535 0 Read/Write Same as User Input 1 Alarm Mask 40158 User F2 Key Action 0 14* 0 Read/Write Same as User F1 Key Action 40159 User F2 Key Alarm Mask 0 65535 0 Read/Write Same as User Input 1 Alarm Mask 40160 User F1 Second Action 0 14* 0 Read/Write Same as User F1 Key Action 40161 User F1 Second Alarm Mask 0 65535 0 Read/Write Same as User Input 1 Alarm Mask 40162 User F2 Second Action 0 14* 0 Read/Write Same as User F1 Key Action 40163 User F2 Second Alarm Mask 0 65535 0 Read/Write Same as User Input 1 Alarm Mask
Advanced Input Parameters
List A List B Input Scaling Points Parameters
40171 40211 Number of Scaling Points 2 16 2 Read/Write Number of Linearization Scaling Points 40172 40212 Reserved N/A N/A N/A N/A 40173 40213 Scaling Pt.1 Input Value -1999 9999 0 Read/Write 1 = 0.001 40174 40214 Scaling Pt.1 Display Value -1999 9999 0 Read/Write 1 = 1 Display Unit 40175
40202 40203 40243 Scaling Pt.16 Input Value -1999 9999 0 Read/Write 1 = 0.001 40204 40244 Scaling Pt.16 Display Value -1999 9999 0 Read/Write 1 = 1 Display Unit
40215
thru
thru
Scaling Pts. 2 thru 15 Values -1999 9999 0 Read/Write
40242
OUTPUT PARAMETERS
40251 Output 1 Assignment 0 11* 1 Read/Write
40252 Output 1 Logic/Alarm Logic Mode 0 2 0 Read/Write
40253 Output 1 Alarm Mask 0 65535 0 Read/Write
40254 Output 1 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 40255 Output 2 Assignment 0 11* 0 Read/Write Same as Output 1 Assignment 40256 Output 2 Logic/Alarm Logic Mode 0 2 0 Read/Write Same as Output 1 Logic/Alarm Logic Mode 40257 Output 2 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 40258 Output 2 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 40259 Output 3 Assignment 0 11* 0 Read/Write Same as Output 1 Assignment 40260 Output 3 Logic/Alarm Logic Mode 0 2 0 Read/Write Same as Output 1 Logic/Alarm Logic Mode 40261 Output 3 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 40262 Output 3 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 40263 Output 4 Assignment 0 11* 0 Read/Write Same as Output 1 Assignment 40264 Output 4 Logic/Alarm Logic Mode 0 2 0 Read/Write Same as Output 1 Logic/Alarm Logic Mode 40265 Output 4 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 40266 Output 4 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second
Analog Output
40271 Non-Linear Analog Output Scaling 0 1 0 Read/Write 0 = No, 1 = Yes (Use Non-Linear Analog Output Scaling Parameters) 40272 Type 0 2 1 Read/Write 0 = 0-20 mA, 1 = 4-20 mA, 2 = 0-10 V
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = NONE 4 = rSPt 8 = r-Lo 12 = dISP 1 = ILOC 5 = PSEL 9 = r-HL 13 = LISt 2 = TrnF 6 = SPrP 10 = r-AL 14 = Prnt 3 = SPSL 7 = r-HI 11 = dLEV 15 = FlexCard Functions
Registers 40175-40202 and 40215-40242 hold values for Scaling Points 2 thru 15, and follow the same ordering as Scaling Point 1.
0 = NONE 4 = P2C MAN 8 = ILOC 12 = FlexCard 1 = P2C Heat 5 = SPSL 9 = tUNE Assignments 2 = P2C Cool 6 = SPrP 10 = tndn 3 = ALr 7 = RSP Transfer 11 = tnFL If Out Assignment ALr; 0 = NOR, 1 = REV If Output Assignment = ALr; 0 = SINGLE, 1 = AND, 2 = OR Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40273 Assignment 0 6* 0 Read/Write
40274 Analog Low Scale Value -1999 9999 0 Read/Write Display value that corresponds with 0 V, 0 mA or 4 mA output 40275 Analog High Scale Value -1999 9999 1000 Read/Write Display value that corresponds with 10 V or 20 mA output 40276 Update time 0 100 0 Read/Write 0 = Max update rate, 1 = 0.1 Second 40277 Probe Failure Action (TC or RTD only) 0 1 0 Read/Write 0 = Low Scale, 1 = High Scale (only applies for TC or RTD input)
Non-Linear Analog Output Scaling
List A List B Analog Output Scaling Point Parameters
41721 41761 Number of Scaling Points 2 16 2 Read/Write Number of Linearization Scaling Points 41722 41762 Reserved N/A N/A N/A N/A 41723 41763 Output Value for Scaling Point 1 0 2000 0 Read/Write 1 = 0.01 41724 41764 Parameter Value for Scaling Point 1 -1999 9999 0 Read/Write 1 = 1 Analog Output Assignment value unit
41725 to
141754
41765 to
141794
40281 Display Intensity Level 0 4 4 Read/Write 0 = Min.(off), 4 = Max. 40282 Display Contrast Level 0 15 7 Read/Write 40283 Display Update (readings per second) 0 4 1 Read/Write 0 = 1, 1 = 2, 2 = 5, 3 = 10, 4 = 20 40284 Conguration Mode 0 1 1 Read/Write 0 = Advanced, 1 = Basic (Caution: Affects other parameters, see manual)
40291 Line 1 Display Assignment 0 3* 1 Read/Write 0 = NO, 1 = PV, 2 = HI, 3 = LO, 4+ = FlexCard Assignments 40292 Line 1 Default Display Color 0 2 2 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40293 Line 1 Units Mnemonic 0 1 1 Read/Write 0 = Off, 1 = On
40294 Line 1 Units Digit 1 (Left) 0 57 0 Read/Write
40295 Line 1 Units Digit 2 (Center) 0 57 56 Read/Write
40296 Line 1 Units Digit 3 (Right) 0 57 6 Read/Write
40297 Line 1 Bargraph Assignment 0 3* 1 Read/Write
40298 Line 1 Bargraph Low Scale Value 0 9999 0 Read/Write 40299 Line 1 Bargraph High Scale Value 0 9999 1000 Read/Write
40300 Line 1 Green Backlight Assignment 0 13* 0 Read/Write
40301 Line 1 Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40302 Line 1 Green Backlight Alarm Mask 0 65535 0 Read/Write
40303 Line 1 Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 1 Green Backlight Assignment 40304 Line 1 Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40305 Line 1 Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask 40306 Line 1 Red Backlight Assignment 0 13* 0 Read/Write Same as Line 1 Green Backlight Assignment 40307 Line 1 Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40308 Line 1 Red Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask
Scaling Pts. 2 thru 16 Values
DISPLAY CONFIGURATION PARAMETERS General
Line 1
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = NONE, 1 = PV, 2 = Hi, 3 = Lo, 4 = Output Power, 5 = Active Setpoint, 6 = Deviation, 7+ = FlexCard Assignments
Registers 41725-41754 and 41765-41794 hold values for Scaling Points 2 thru 16, and follow the same ordering as Scaling Point 1.
0 = 9 = I 18 = Q 27 = Z 36 = 8 45 = m(r) 54 = ] 1 = A 10 = J 19 = R 28 = 0 37 = 9 46 = o 55 = / 2 = b 11 = K 20 = S 29 = 1 38 = a 47 = q 56 = º 3 = C 12 = L 21 = t 30 = 2 39 = c 48 = r 57 = _ 4 = d 13 = M(l) 22 = U 31 = 3 40 = e 49 = u 5 = E 14 = M(r) 23 = V 32 = 4 41 = g 50 = w(r) 6 = F 15 = N 24 = W(l) 33 = 5 42 = h 51 = ­7 = G 16 = O 25 = W(r) 34 = 6 43 = i 52 = = 8 = H 17 = P 26 = Y 35 = 7 44 = n 53 = [ 0 = NONE, 1 = Output Power, 2 = Deviation, 3 = Setpoint, 4+ = FlexCard Assignments
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40309 Line 1 Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 1 Green Backlight Assignment 40310 Line 1 Green-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40311 Line 1 Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask 40312 Line 1 Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 1 Green Backlight Assignment 40313 Line 1 Red-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40314 Line 1 Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask 40315 Line 1 Red-Green Backlight Assignment 0 13* 0 Read/Write Same as Line 1 Green Backlight Assignment 40316 Line 1 Red-Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40317 Line 1 Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask
Line 2
40331 Line 2 Default Display Color 0 2 0 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40332 Line 2 Units Mnemonic 0 1 0 Read/Write 0 = Off, 1 = On 40333 Line 2 Units Digit 1 (Left) 0 57 0 Read/Write Same as Line 1 Units Selection 40334 Line 2 Units Digit 2 (Center) 0 57 0 Read/Write 40335 Line 2 Units Digit 3 (Right) 0 57 0 Read/Write
40336 Line 2 Bargraph Assignment 0 6* 2 Read/Write
40337 Line 2 Bargraph Low Scale Value 0 9999 0 Read/Write 40338 Line 2 Bargraph High Scale Value 0 9999 0 Read/Write
40339 Line 2 Green Backlight Assignment 0 13* 0 Read/Write
40340 Line 2 Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40341 Line 2 Green Backlight Alarm Mask 0 65535 0 Read/Write
40342 Line 2 Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 2 Green Backlight Assignment 40343 Line 2 Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40344 Line 2 Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 2 Green Backlight Alarm Mask 40345 Line 2 Red Backlight Assignment 0 13* 0 Read/Write Same as Line 2 Green Backlight Assignment 40346 Line 2 Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40347 Line 2 Red Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 2 Green Backlight Alarm Mask 40348 Line 2 Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 2 Green Backlight Assignment 40349 Line 2 Green-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40350 Line 2 Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 2 Green Backlight Alarm Mask 40351 Line 2 Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 2 Green Backlight Assignment 40352 Line 2 Red-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40353 Line 2 Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 2 Green Backlight Alarm Mask 40354 Line 2 Red-Green Backlight Assignment 0 13* 0 Read/Write Same as Line 2 Green Backlight Assignment 40355 Line 2 Red-Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40356 Line 2 Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 2 Green Backlight Alarm Mask
Universal Annunciator 1
40361 UA 1 Default Display Color 0 2 0 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40362 UA 1 Units Mnemonic 0 1 1 Read/Write 0 = Off, 1 = On
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = NONE, 1 = OP, 2 = dEV, 3 = SP, 4 = OP ANY, 5 = dEV ANY, 6 = SP ANY, 7+ = FlexCard Assignments
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40363 UA 1 Units Digit 1 (Left) 0 57 16 Read/Write
40364 UA 1 Units Digit 2 (Right) 0 57 29 Read/Write
40365 UA 1 Units Logic Mode (Active) 0 2 0 Read/Write 0 = nor, 1 = rEv, 2 = FLSh
40366 UA 1 Units Assignment 0 13* 1 Read/Write
40367 UA 1 Assignment Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40368 UA 1 Assignment Alarm Mask 0 65535 0 Read/Write
40368 UA 1 Green Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40369 UA 1 Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40370 UA 1 Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask 40371 UA 1 Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40372 UA 1 Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40373 UA 1 Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask 40374 UA 1 Red Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40375 UA 1 Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40376 UA 1 Red Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask 40377 UA 1 Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40378 UA 1 Green-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40379 UA 1 Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask 40380 UA 1 Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40381 UA 1 Red-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40382 UA 1 Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask 40383 UA 1 Red-Green Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40384 UA 1 Red-Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40385 UA 1 Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask
Universal Annunciator 2
40391 UA 2 Default Display Color 0 2 0 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40392 UA 2 Units Mnemonic 0 1 1 Read/Write 0 = Off, 1 = On 40393 UA 2 Units Digit 1 (Left) 0 57 1 Read/Write Same as UA1 Units Selection 40394 UA 2 Units Digit 2 (Right) 0 57 29 Read/Write 40395 UA 2 Units Logic Mode (Active) 0 2 0 Read/Write 0 = nor, 1 = rEv, 2 = FLSh
40396 UA 2 Units Assignment 0 13* 5 Read/Write
40397 UA 2 Assignment Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40398 UA 2 Assignment Alarm Mask 0 65535 0 Read/Write
40399 UA 2 Green Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40400 UA 2 Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40401 UA 2 Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = 9 = I 18 = Q 27 = Z 36 = 8 45 = m(r) 54 = ] 1 = A 10 = J 19 = R 28 = 0 37 = 9 46 = o 55 = / 2 = b 11 = K 20 = S 29 = 1 38 = a 47 = q 56 = º 3 = C 12 = L 21 = t 30 = 2 39 = c 48 = r 57 = _ 4 = d 13 = M(l) 22 = U 31 = 3 40 = e 49 = u 5 = E 14 = M(r) 23 = V 32 = 4 41 = g 50 = w(r) 6 = F 15 = N 24 = W(l) 33 = 5 42 = h 51 = ­7 = G 16 = O 25 = W(r) 34 = 6 43 = i 52 = = 8 = H 17 = P 26 = Y 35 = 7 44 = n 53 = [
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40402 UA 2 Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40403 UA 2 Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40404 UA 2 Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask 40405 UA 2 Red Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40406 UA 2 Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40407 UA 2 Red Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask 40408 UA 2 Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40409 UA 2 Green-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40410 UA 2 Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask 40411 UA 2 Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40412 UA 2 Red-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40413 UA 2 Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask 40414 UA 2 Red-Green Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40415 UA 2 Red-Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40416 UA 2 Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask
Universal Annunciator 3
40421 UA 3 Default Display Color 0 2 0 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40422 UA 3 Units Mnemonic 0 1 1 Read/Write 0 = Off, 1 = On 40423 UA 3 Units Digit 1 (Left) 0 57 1 Read/Write Same as UA1 Units Selection 40424 UA 3 Units Digit 2 (Right) 0 57 30 Read/Write 40425 UA 3 Units Logic Mode (Active) 0 2 0 Read/Write 0 = nor, 1 = rEv, 2 = FLSh
40426 UA 3 Units Assignment 0 13* 5 Read/Write
40427 UA 3 Assignment Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40428 UA 3 Assignment Alarm Mask 0 65535 0 Read/Write
40429 UA 3 Green Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40430 UA 3 Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40431 UA 3 Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask 40432 UA 3 Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40433 UA 3 Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40434 UA 3 Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask 40435 UA 3 Red Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40436 UA 3 Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40437 UA 3 Red Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask 40438 UA 3 Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40439 UA 3 Green-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40440 UA 3 Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask 40441 UA 3 Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40442 UA 3 Red-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40443 UA 3 Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask 40444 UA 3 Red-Green Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40445 UA 3 Red-Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40446 UA 3 Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask
Universal Annunciator 4
40451 UA 4 Default Display Color 0 2 0 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40452 UA 4 Units Mnemonic 0 1 0 Read/Write 0 = Off, 1 = On 40453 UA 4 Units Digit 1 (Left) 0 57 0 Read/Write Same as UA1 Units Selection 40454 UA 4 Units Digit 2 (Right) 0 57 0 Read/Write
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40455 UA 4 Units Logic Mode (Active) 0 2 0 Read/Write 0 = nor, 1 = rEv, 2 = FLSh
40456 UA 4 Units Assignment 0 13* 0 Read/Write
40457 UA 4 Assignment Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40458 UA 4 Assignment Alarm Mask 0 65535 0 Read/Write
40459 UA 4 Green Backlight Assignment 0 13* 0 Read/Write Same as UA 4 Units Assignment 40460 UA 4 Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40461 UA 4 Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 4 Assignment Alarm Mask 40462 UA 4 Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 4 Units Assignment 40463 UA 4 Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40464 UA 4 Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 4 Assignment Alarm Mask 40465 UA 4 Red Backlight Assignment 0 13* 0 Read/Write Same as UA 4 Units Assignment 40466 UA 4 Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40467 UA 4 Red Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 4 Assignment Alarm Mask 40468 UA 4 Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 4 Units Assignment 40469 UA 4 Green-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40470 UA 4 Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 4 Assignment Alarm Mask 40471 UA 4 Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 4 Units Assignment 40472 UA 4 Red-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40473 UA 4 Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 4 Assignment Alarm Mask 40474 UA 4 Red-Green Backlight Assignment 0 13* 0 Read/Write Same as UA 4 Units Assignment 40475 UA 4 Red-Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40476 UA 4 Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 4 Assignment Alarm Mask
Mnemonics
40501 Mnemonic Default Display Color 0 2 0 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd
40502 Mnemonic Green Backlight Assignment 0 13* 0 Read/Write
40503 Mnemonic Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40504 Mnemonic Green Backlight Alarm Mask 0 65535 0 Read/Write
40505 Mnemonic Orange Backlight Assignment 0 13* 0 Read/Write Same as Mnemonic Green Backlight Assignment 40506 Mnemonic Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40507 Mnemonic Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask 40508 Mnemonic Red Backlight Assignment 0 13* 0 Read/Write Same as Mnemonic Green Backlight Assignment 40509 Mnemonic Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40510 Mnemonic Red Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask 40511 Mnemonic Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as Mnemonic Green Backlight Assignment
40512
40513 Mnemonic Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask 40514 Mnemonic Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as Mnemonic Green Backlight Assignment
40515
40516 Mnemonic Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask 40517 Mnemonic Red-Green Backlight Assignment 0 13* 0 Read/Write Same as Mnemonic Green Backlight Assignment
Mnemonic Green-Orange Backlight Alarm Logic Mode
Mnemonic Red-Orange Backlight Alarm Logic Mode
REGISTER NAME
LOW
LIMIT
0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
HIGH LIMIT
FACTORY
SETTING
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40518
40519 Mnemonic Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask
40541 Line 2 Input Display Access 0 21 0 Read/Write 0 = LOC; Bit 0 = dREd, Bit 2 = PrEd, Bit4 = HrEd; Other bits N/A
40542 Line 2 Maximum (Hi) Value Access 0 42 0 Read/Write
40543 Line 2 Minimum (Lo) Value Access 0 42 0 Read/Write
40551 Display Intensity Level Access 0 42 0 Read/Write
40552 Display Contrast Level Access 0 42 0 Read/Write
40561 Line 2 Alarm 1 Value Access 0 42 0 Read/Write
40562 Line 2 Alarm 1 Band/Dev.Value Access 0 42 0 Read/Write
40563 Line 2 Alarm 2 Value Access 0 42 0 Read/Write
40564 Line 2 Alarm 2 Band/Dev.Value Access 0 42 0 Read/Write
40565 Line 2 Alarm 3 Value Access 0 42 0 Read/Write
40566 Line 2 Alarm 3 Band/Dev.Value Access 0 42 0 Read/Write
40567 Line 2 Alarm 4 Value Access 0 42 0 Read/Write
40568 Line 2 Alarm 4 Band/Dev.Value Access 0 42 0 Read/Write
40569 Line 2 Alarm 5 Value Access 0 42 0 Read/Write
40570 Line 2 Alarm 5 Band/Dev.Value Access 0 42 0 Read/Write
40571 Line 2 Alarm 6 Value Access 0 42 0 Read/Write
40572 Line 2 Alarm 6 Band/Dev.Value Access 0 42 0 Read/Write
40573 Line 2 Alarm 7 Value Access 0 42 0 Read/Write
40574 Line 2 Alarm 7 Band/Dev.Value Access 0 42 0 Read/Write
40575 Line 2 Alarm 8 Value Access 0 42 0 Read/Write
40576 Line 2 Alarm 8 Band/Dev.Value Access 0 42 0 Read/Write
40577 Line 2 Alarm 9 Value Access 0 42 0 Read/Write
40578 Line 2 Alarm 9 Band/Dev.Value Access 0 42 0 Read/Write
Mnemonic Red-Green Backlight Alarm Logic Mode
Line 2 Input LOCS
Line 2 Display LOCS
Line 2 Alarm LOCS
REGISTER NAME
LOW
LIMIT
0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
HIGH LIMIT
FACTORY
SETTING
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt
REGISTER
ADDRESS
40579 Line 2 Alarm 10 Value Access 0 42 0 Read/Write
40580 Line 2 Alarm 10 Band/Dev.Value Access 0 42 0 Read/Write
40581 Line 2 Alarm 11 Value Access 0 42 0 Read/Write
40582 Line 2 Alarm 11 Band/Dev.Value Access 0 42 0 Read/Write
40583 Line 2 Alarm 12 Value Access 0 42 0 Read/Write
40584 Line 2 Alarm 12 Band/Dev.Value Access 0 42 0 Read/Write
40585 Line 2 Alarm 13 Value Access 0 42 0 Read/Write
40586 Line 2 Alarm 13 Band/Dev.Value Access 0 42 0 Read/Write
40587 Line 2 Alarm 14 Value Access 0 42 0 Read/Write
40588 Line 2 Alarm 14 Band/Dev.Value Access 0 42 0 Read/Write
40589 Line 2 Alarm 15 Value Access 0 42 0 Read/Write
40590 Line 2 Alarm 15 Band/Dev.Value Access 0 42 0 Read/Write
40591 Line 2 Alarm 16 Value Access 0 42 0 Read/Write
40592 Line 2 Alarm 16 Band/Dev.Value Access 0 42 0 Read/Write
Line 2 PID LOCS
40601 Line 2 Actual Setpoint Value Access 0 42 0 Read/Write
40602 Line 2 Setpoint 1 Value Access 0 42 0 Read/Write
40603 Line 2 Setpoint 2 Value Access 0 42 0 Read/Write
40604 Line 2 Remote Setpoint Value Access 0 42 0 Read/Write
40605 Line 2 Output Power Value Access 0 42 0 Read/Write
40606 Line 2 Deviation Value Access 0 42 0 Read/Write 0 = LOC; Bit 0 = dREd, Bit 2 = PrEd, Bit4 = HrEd
40607 Line 2 Setpoint Ramp Rate Value Access 0 42 0 Read/Write
40608 Line 2 Remote Setpoint Ratio Value Access 0 42 0 Read/Write 0 = LOC, 1 = drEd, 2 = dEnt, 3 = PrEd, 4 = PEnt, 5 = HrEd, 6 = HEnt 40609 Line 2 Remote Setpoint Bias Value Access 0 42 0 Read/Write 0 = LOC, 1 = drEd, 2 = dEnt, 3 = PrEd, 4 = PEnt, 5 = HrEd, 6 = HEnt 40610 Line 2 Actual PID Offset Power Value Access 0 42 0 Read/Write 0 = LOC, 1 = drEd, 2 = dEnt, 3 = PrEd, 4 = PEnt, 5 = HrEd, 6 = HEnt
40611 Line 2 Actual PID Proportional Band Value Access 0 42 0 Read/Write
40612 Line 2 Actual PID Integral Time Value Access 0 42 0 Read/Write
40613 Line 2 Actual PID Derivitive Time Value Access 0 42 0 Read/Write
40614 Line 2 Primary PID Offset Power Value Access 0 42 0 Read/Write
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt
REGISTER
ADDRESS
40615
40616 Line 2 Primary PID Integral Time Value Access 0 42 0 Read/Write
40617 Line 2 Primary PID Derivitive Time Value Access 0 42 0 Read/Write
40618 Line 2 Alternate PID Offset Power Value Access 0 42 0 Read/Write
40619
40620 Line 2 Alternate PID Integral Time Value Access 0 42 0 Read/Write
40621 Line 2 Alternate PID Derivitive Time Value Access 0 42 0 Read/Write
40631 Line 2 Setpoint Selection Value Access 0 42 0 Read/Write
40632 Line 2 Remote Setpoint Transfer (Local/Remote) 0 42 0 Read/Write
40633 Line 2 Setpoint Ramping Disable 0 42 0 Read/Write
40634 Line 2 Integral Lock Access 0 42 0 Read/Write
40635 Line 2 Auto/Manual Mode Selection Value Access 0 42 0 Read/Write
40636 Line 2 PID Bank Selection Value Access 0 42 0 Read/Write
40637 Line 2 Tune Selection Value Access 0 42 0 Read/Write
40638 Line 2 Reset Max Display Access 0 21 0 Read/Write 0 = LOC; Bit 1 = dEnt, Bit 3 = PEnt, Bit5 = HEnt 40639 Line 2 Reset Min Display Access 0 21 0 Read/Write 0 = LOC; Bit 1 = dEnt, Bit 3 = PEnt, Bit5 = HEnt 40640 Line 2 Reset Max and Min Access 0 21 0 Read/Write 0 = LOC; Bit 1 = dEnt, Bit 3 = PEnt, Bit5 = HEnt 40641 Line 2 Reset Alarm Access 0 21 0 Read/Write 0 = LOC; Bit 1 = dEnt, Bit 3 = PEnt, Bit5 = HEnt
40642 Line 2 List Selection Access 0 42 0 Read/Write
40643 Line 2 Print Request Access 0 42 0 Read/Write
40644 Line 2 Reset Alarm Mask 0 65535 0 Read/Write
40651 Max (HI) Capture Delay Time 0 9999 0 Read/Write 0 = Max Update Rate, 1 = 0.1Sec 40652 Min (LO) Capture Delay Time 0 9999 0 Read/Write 0 = Max Update Rate, 1 = 0.1Sec
40661 Line 2 Security Code Value 0 250 0 Read/Write
40671 Assign 0 1* 0 Read/Write 0 = None, 1 = P2C PV, 2+ - Flex Card Assignments 40672 Control Type 0 2 0 Read/Write 0 = Heat, 1 = Cool, 2 = Both 40673 Control Mode 0 1 0 Read/Write 0 = Automatic, 1 = Manual 40674 Manual Power -1000 1000 0 Read/Write Output Power: Heat/Cool; * writable only in manual mode; 1 = 0.1%
Line 2 Primary PID Proportional Band Value Access
Line 2 Alternate PID Proportional Band Value Access
Line 2 Function LOCS
Max (HI)/Min(LO) Values
Line 2 Code Conguration
PID CONFIGURATION PARAMETERS Control
REGISTER NAME
LOW
LIMIT
0 42 0 Read/Write
0 42 0 Read/Write
HIGH LIMIT
FACTORY
SETTING
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt 0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt, Bit4 = HrEd, Bit5 = HEnt Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
Remote Setpoint
40676 Remote SP Assignment 0 3* 0 Read/Write
0 = NONE, 1 = P2C SP, 2 = P2C PV, 3 = P2C OP, 4+ = Flex Card
Assignments 40677 Reserved for future use. 40678 Ratio 1 9999 1000 Read/Write 1 = 0.1 40679 Bias -1999 9999 0 Read/Write 1 = 1 Display Unit 40680 Select Local / Remote SP 0 1 0 Read/Write
0 = LOC, 1 = REM
Setpoint
40681 Setpoint Selection 0 1 0 Read/Write 0 = Setpoint 1, 1 = Setpoint 2 40682 Sepoint 1 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 40683 Setpoint 2 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 40684 Setpoint Lo Limit Value -1999 9999 0 Read/Write 1 = 1 Display Unit 40685 Setpoint Hi Limit Value -1999 9999 9999 Read/Write 1 = 1 Display Unit 40686 Ramp Timebase 0 3 0 Read/Write 0 = Off, 1 = Seconds, 2 = Minutes, 3 = Hours 40687 Ramp Rate 0 9999 0 Read/Write 1 = 0.1 Ramp Timebase unit
PID Parameters
40691 PID Parameter Selection 0 1 0 Read/Write 0 = Primary PID Values, 1 = Alternate PID Values 40692 Primary Proportional Band 0 9999 700 Read/Write 1 = 1 Display Unit 40693 Primary Integral Time 0 65000 120 Read/Write 1 = 0.1 Second 40694 Primary Derivative Time 0 9999 30 Read/Write 1 = 0.1 Second 40695 Primary Power Filter Value 0 600 10 Read/Write 1 = 0.1 Second 40696 Primary Output Power Offset -1000 1000 0 Read/Write 1 = 0.1 %; Applicable when Primary Integral Time is 0 40697 Alternate Proportional Band 0 9999 700 Read/Write 1 = 1 Display Unit 40698 Alternate Integral Time 0 65000 120 Read/Write 1 = 0.1 Second 40699 Alternate Derivative Time 0 9999 30 Read/Write 1 = 0.1 Second 40700 Alternate Power Filter Value 0 600 10 Read/Write 1 = 0.1 Second 40701 Alternate Output Power Offset -1000 1000 0 Read/Write 1 = 0.1 %; Applicable when Secondary Integral Time is 0
Power Transfer
40711 Input Fault Power Value -1999 2000 0 Read/Write 1 = 0.1 % 40712 Output Deadband -1000 1000 0 Read/Write 1 = 0.1 % 40713 Output Heat Gain 0 5000 1000 Read/Write 1 = 0.1 % 40714 Heat Low Limit 0 2000 0 Read/Write 1 = 0.1 % 40715 Heat High Limit 0 2000 1000 Read/Write 1 = 0.1 % 40716 Output Cool Gain 0 5000 1000 Read/Write 1 = 0.1 % 40717 Cool Low Limit 0 2000 0 Read/Write 1 = 0.1 % 40718 Cool High Limit 0 2000 1000 Read/Write 1 = 0.1 %
ON/OFF Control
40741 On-Off Hysteresis 0 500 2 Read/Write 1 = 1 Display Unit 40742 On-Off Deadband -1999 9999 0 Read/Write 1 = 1 Display Unit
Tuning
40751 Tuning Code 0 4 2 Read/Write
0 = Very Aggressive, 1 = Aggressive, 2 = Default, 3 = Conservative,
4 = Very Conservative 40752 Auto-Tune Start 0 1 0 Read/Write 0 = NO 1 = YES
Slave ID / GUID
<'P' 'X'> <'2' 'C'> <'1' '5'> <2020h> <2020h> <'a' 'b'> <00h 'c'> <0040h>
<0040h> <0010h>
a = SP Card Status. '0'-No Card, '2'-Dual SP, '4'-Quad SP
41001-41010 Slave ID N/A N/A N/A Read Only
b = Linear Card Status. "0"-Not Installled, "1"-Installed
c = Version Number (1.50 or higher)
<0040h> <0040h> = 64 Register Writes, 64 Register Reads (Max.)
<0010h> = 16 Register GUID/Scratch
41101-41116 GUID/Scratch N/A N/A N/A Read/Write Reserved (may be used in future RLC software)
REGISTER
ADDRESS
FACTORY SERVICE
41151-41156 Factory Service Registers N/A N/A N/A Read/Write Factory Use Only - Do Not Modify
Math / Logic
41121-1200 Reserved for Math/Logic Operations
ALARM PARAMETERS Alarm 1
41201 Assign 0 1* 1 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41202 Action 0 9 1 Read/Write
41203 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41204 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41205 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41206 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41207 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41208 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41209 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 2
41221 Assign 0 1* 1 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41222 Action 0 9 1 Read/Write
41223 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41224 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41225 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41226 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41227 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41228 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41229 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 3
41241 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41242 Action 0 9 0 Read/Write
41243 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41244 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41245 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41246 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41247 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41248 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41249 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 4
41261 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41262 Action 0 9 0 Read/Write
41263 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41264 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41265 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41266 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41267 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41268 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41269 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 5
41281 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
REGISTER
ADDRESS
41282 Action 0 9 0 Read/Write
41283 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41284 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41285 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41286 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41287 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41288 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41289 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 6
41301 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41302 Action 0 9 0 Read/Write
41303 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41304 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41305 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41306 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41307 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41308 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41309 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 7
41321 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41322 Action 0 9 0 Read/Write
41323 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41324 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41325 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41326 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41327 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41328 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41329 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 8
41341 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41342 Action 0 9 0 Read/Write
41343 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41344 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41345 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41346 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41347 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41348 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41349 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 9
41361 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41362 Action 0 9 0 Read/Write
41363 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41364 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41365 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41366 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41367 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41368 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
REGISTER
ADDRESS
41369 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 10
41381 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41382 Action 0 9 0 Read/Write
41383 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41384 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41385 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41386 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41387 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41388 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41389 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 11
41401 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41402 Action 0 9 0 Read/Write
41403 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41404 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41405 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41406 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41407 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41408 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41409 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 12
41421 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41422 Action 0 9 0 Read/Write
41423 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41424 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41425 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41426 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41427 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41428 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41429 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 13
41441 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41442 Action 0 9 0 Read/Write
41443 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41444 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41445 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41446 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41447 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41448 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41449 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 14
41461 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41462 Action 0 9 0 Read/Write
41463 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41464 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41465 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
REGISTER
ADDRESS
41466 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41467 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41468 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41469 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 15
41481 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41482 Action 0 9 0 Read/Write
41483 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41484 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41485 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41486 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41487 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41488 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41489 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
Alarm 16
41501 Assign 0 1* 0 Read/Write 0 = None, 1 = Process Input Value, 2+ = FlexCard Assignments
41502 Action 0 9 0 Read/Write
41503 Hysteresis Value 1 9999 2 Read/Write 1 = 1 Display Unit 41504 On Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41505 Off Time Delay 0 9999 0 Read/Write 1 = 0.1 Second 41506 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 41507 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 41508 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 41509 Probe Failure Action (TC or RTD Only) 0 1 0 Read/Write 0 = Off, 1 = On (Applies for TC or RTD input)
ALARM SCALING PARAMETERS
List A List B Alarm Values
41551 41651 Alarm 1 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41552 41652 Alarm 2 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41553 41653 Alarm 3 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41554 41654 Alarm 4 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41555 41655 Alarm 5 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41556 41656 Alarm 6 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41557 41657 Alarm 7 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41558 41658 Alarm 8 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41559 41659 Alarm 9 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41560 41660 Alarm 10 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41561 41661 Alarm 11 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41562 41662 Alarm 12 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41563 41663 Alarm 13 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41564 41664 Alarm 14 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41565 41665 Alarm 15 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41566 41666 Alarm 16 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 41567 41667 Alarm 1 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41568 41668 Alarm 2 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41569 41669 Alarm 3 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41570 41670 Alarm 4 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41571 41671 Alarm 5 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41572 41672 Alarm 6 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41573 41673 Alarm 7 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41574 41674 Alarm 8 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO, 5 = dEHI, 6 = dELO,
7 = bANd, 8 = bdIn, 9=HCur
REGISTER
ADDRESS
41575 41675 Alarm 9 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41576 41676 Alarm 10 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41577 41677 Alarm 11 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41578 41678 Alarm 12 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41579 41679 Alarm 13 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41580 41680 Alarm 14 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41581 41681 Alarm 15 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit 41582 41682 Alarm 16 Band/Dev. Value -1999 9999 0 Read/Write Applicable only for Band or Deviation Alarm Action. 1 = 1 Display Unit
SERIAL COMMUNICATION PARAMETERS
41701 USB Mode 0 1 0 Read/Write 0 = Conguration, 1 = Serial 41702 Type 0 2 2 Read/Write 0 = RLC Protocol (ASCII), 1 = Modbus RTU, 2 = Modbus ASCII
41703 Baud Rate 0 5 5 Read/Write
41704 Data Bits 0 1 1 Read/Write 0 = 7 Bits, 1 = 8 Bits 41705 Parity 0 2 0 Read/Write 0 = None, 1 = Even, 2 = Odd
41706 Address
41707 Transmit Delay 0 250 10 Read/Write 1 = 0.001 Second 41708 Abbreviated Transmission (RLC only) 0 1 0 Read/Write 0 = No, 1 = Yes (Not used when communications type is Modbus)
41709 Print Options (RLC only) 0 8191 1 Read/Write
41710 Load Serial Settings 0 1 0 Read/Write
REGISTER NAME
LOW
LIMIT
0 99 0 Read/Write RLC Protocol: 0-99 1 247 247 Modbus: 1-247
HIGH LIMIT
FACTORY
SETTING
0 = 1200, 1 = 2400, 2 = 4800, 3 = 9600, 4 = 19200,
5 = 38400
0 = No, 1 = Yes (Not used when communications type is Modbus) Bit 0 –
Print Input Value, Bit 1 – Print SP Value, Bit 2 – Print Setpoint Ramp Rate
Value, Bit 3 – Print Output Power, Bit 4 – Print Proportional Value, Bit 5 –
Print Integral Value, Bit 6 - Print Derivative Value, Bit 7 – Print Alarm Status,
Bit 8 – Print Alarm 1 Value, Bit 9 – Print Alarm 2 Value, Bit 10 – Print Alarm
3 Value, Bit 11 – Print Alarm 4 Value, Bit 12 – Print Control Status Bits
Changing 41701-41710 will not update the PAX2C until this register
is written with a 1. After the write, the communicating device must be
changed to new PAX2C settings and this register returns to 0.
* Higher limit is applicable with FlexCard installed.
PX2FCA0 Modbus Register Table REVISED 01/30/15
REGISTER
ADDRESS †
FREQUENTLY USED REGISTERS
4n001 Input Process Value (Hi word) 4n002 Input Process Value (Lo word) 4n003 Input Process Maximum (Hi word) 4n004 Input Process Maximum (Lo word) 4n005 Input Process Minimum (Hi word) 4n006 Input Process Minimum (Lo word) 4n007 Active SP -1999 9999 N/A Read/Write 1 = 0.1% 4n008 Active Remote SP -1999 9999 N/A Read Only 1 = 0.1%
4n009 Status Flags 0 255 N/A Read Only
4n010 Output Status Register 0 15 0 Read/Write
4n011 Heat Power 0 1000 0 Read Only 1 = 0.1% 4n012 Cool Power 0 1000 0 Read Only 1 = 0.1%
4n013-4n0024 Reserved
4n035 Control Flags 0 1000 0 Read/Write
REGISTER NAME
LOW
LIMIT
-1999 9999 N/A Read Only
-1999 9999 N/A Read Only 1 = 1 Display Unit
-1999 9999 N/A Read Only 1 = 1 Display Unit
HIGH LIMIT
FACTORY
SETTING
1 = 1 Display Unit
ADC Overrange Value = 1048576, Underrange Value = -1048576
Bit 8 Set = ADC Underrange,
Bit 7 Set = ADC Overrange.
Bit 6 Set = SP Ramping
Bit 5 Set = Auto Tune Fail
Bit 4 Set = Auto Tune Done
Bit 3:0 = Auto Tune Phase
Status of Solid-State Outputs. Bit State: 0 = OFF, 1 = ON.
Bit 3 = O4, Bit 2 = O3, Bit 1 = O2, Bit 0 = O1.
Bit 6: AutoTune; 0 = NO, 1 = YES
Bit 5: MAN; 0 = PID Auto Mode, 1 = PID Manual (User) Mode;
Bit 4: PSEL; 0 = Primary PID, 1 = Alternate PID,
Bit 3: ILOC; 0 = Enable Integral Action, 1 = Disable Integral Action;
Bit 2: RSPt; 0 = Local SP, 1 = Remote SP;
Bit 1: SPSL; 0 = SP1, 1 = Req. SP2;
Bit 0: SPrP; 0 = SP Ramping Enable, 1 = SP Ramping Disable
INPUT PARAMETERS SEE INPUT MODULE FOR PARAMETER DESCRIPTIONS Analog Input Parameters
4n071 Input Type 0 1 0 Read/Write 0 = 0 to 10V DC, 1 = 0 to 20mA DC 4n072 Input Square Root Linearization 0 1 0 Read/Write 0 = No, 1 = Yes 4n073 Input Decimal Point 0 3 3 Read/Write 0 = 0, 1 = 0.0, 2 = 0.00, 3 = 0.000 4n074 Input Rounding 0 6 0 Read/Write 0 = 1, 1 = 2, 2 = 5, 3 = 10, 4 = 20, 5 = 50, 6 = 100 4n075 Input Offset Value (Hi word) 4n076 Input Offset Value (Lo word) 4n077 Input Filter Value 0 250 10 Read/Write 1 = 0.1 Second 4n078 Input Filter Band Value 0 250 10 Read/Write 1 = 1 display unit 4n079 Max (HI) Capture Delay Time 0 9999 0 Read/Write 0 = Max Update Rate, 1 = 0.1Sec 4n080 Min (LO) Capture Delay Time 0 9999 0 Read/Write 0 = Max Update Rate, 1 = 0.1Sec
Input Scaling Point Parameters
4n101 Number of Scaling Points 2 15 2 Read/Write Number of Linearization Scaling Points 4n102 Reserved N/A N/A N/A N/A Reserved for future use 4n103 Scaling Pt.1 Input Value (Hi word) 4n104 Scaling Pt.1 Input Value (Lo word) 4n105 Scaling Pt.1 Display Value (Hi word) 4n106 Scaling Pt.1 Display Value (Lo word) 4n107 Scaling Pt.2 Input Value (Hi word) 4n108 Scaling Pt.2 Input Value (Lo word)
-1999 9999 0 Read/Write 1 = 1 Display Unit
0 9999 0 Read/Write 1 = 0.001
-1999 9999 0 Read/Write 1 = 1 Display Unit
0 9999 1000 Read/Write 1 = 0.001
REGISTER
ADDRESS †
4n109 Scaling Pt.2 Display Value (Hi word) 4n110 Scaling Pt.2 Display Value (Lo word) 4n 111
thru 4n162
4n201 Line 2 Input Display Access 0 21 0 Read/Write 0 = LOC; Bit 0 = dREd, Bit 2 = PrEd, Bit4 = HrEd; Other bits N/A
4n202 Line 2 Maximum (Hi) Value Access 0 42 0 Read/Write
4n203 Line 2 Maximum (Hi) Value Access 0 42 0 Read/Write
4n211 Line 2 Actual Setpoint Value Access 0 42 0 Read/Write
4n212 Line 2 Remote Setpoint Value Access 0 21 0 Read/Write 0 = LOC; Bit 0 = dREd, Bit 2 = PrEd, Bit4 = HrEd; Other bits N/A 4n213 Line 2 Output Power Value Access 0 42 0 Read/Write 0 = LOC; Bit 0 = dREd, Bit 2 = PrEd, Bit4 = HrEd; Other bits N/A 4n214 Line 2 Deviation Value Access 0 42 0 Read/Write 0 = LOC; Bit 0 = dREd, Bit 2 = PrEd, Bit4 = HrEd; Other bits N/A
4n215 Line 2 Setpoint Ramping Value Access 0 42 0 Read/Write
4n216 Line 2 Remote Setpoint Ratio 0 42 0 Read/Write
4n217 Line 2 Remote Setpoint Bias 0 42 0 Read/Write
4n218 Line 2 Active Output Power Offset Access 0 42 0 Read/Write
4n219 Line 2 Active Proportional Band Access 0 42 0 Read/Write
4n220 Line 2 Active Integral Time Access 0 42 0 Read/Write
4n221 Line 2 Active Derivative Time Access 0 42 0 Read/Write
4n230 Line 2 Reset Max Display Access 0 42 0 Read/Write 0 = LOC; Bit 1 = dEnt, Bit 3 = PEnt, Bit5 = HEnt; Other bits N/A 4n231 Line 2 Reset Min Display Access 0 42 0 Read/Write 0 = LOC; Bit 1 = dEnt, Bit 3 = PEnt, Bit5 = HEnt; Other bits N/A 4n232 Line 2 Reset Max and Min Access 0 42 0 Read/Write 0 = LOC; Bit 1 = dEnt, Bit 3 = PEnt, Bit5 = HEnt; Other bits N/A
4n233 Line 2 Setpoint Selection Value Access 0 42 0 Read/Write
4n234 Line 2 Local / Remote Transfer Access 0 42 0 Read/Write
4n235 Line 2 Setpoint Ramping Disable 0 42 0 Read/Write
4n236 Line 2 Integral Lock Access 0 42 0 Read/Write
4n237 Line 2 Auto/Manual Mode Selection Value Access 0 42 0 Read/Write
4n238 Line 2 PID Bank Selection Value Access 0 42 0 Read/Write
4n239 Line 2 Tune Selection Value Access 0 42 0 Read/Write
Scaling Pts. 3 thru 15 Values
DISPLAY CONFIGURATION PARAMETERS Line 2 Input LOCS Parameters
Line 2 PID LOCS Parameters
Line 2 Function LOCS Parameters
REGISTER NAME
LOW
LIMIT
-1999 9999 1000 Read/Write 1 = 1 Display Unit
0 (input)
-1999 (dsp)
HIGH LIMIT
9999 0 Read/Write
FACTORY
SETTING
Registers 40111-40162 hold values for Scaling Points 3 thru 15,
and follow the same ordering as Scaling Points 1 and 2.
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
REGISTER
ADDRESS †
OUTPUT PARAMETERS
4n251 Output 1 Assignment 0
4n252 Output 1 Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
4n253 Output 1 Alarm Mask 0 65535 0 Read/Write
4n254 Output 1 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 4n255 Output 2 Assignment 0 6 0 Read/Write Same as Output 1 Assignment 4n256 Output 2 Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 4n257 Output 2 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 4n258 Output 2 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 4n259 Output 3 Assignment 0 6 0 Read/Write Same as Output 1 Assignment 4n260 Output 3 Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 4n261 Output 3 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 4n262 Output 3 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 4n263 Output 4 Assignment 0 6 0 Read/Write Same as Output 1 Assignment 4n264 Output 4 Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 4n265 Output 4 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 4n266 Output 4 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second
PID CONFIGURATION PARAMETERS Control Parameters
4n301 Assign 0 2* 0 Read/Write
4n302 Control Type 0 2 0 Read/Write 0 = Heat, 1 = Cool, 2 = Both 4n303 Control Mode 0 1 0 Read/Write 0 = Automatic, 1 = Manual 4n304 Manual Power -1999 2000 0 Read/Write Output Power: Heat/Cool; 1=0.1%; *-writeable only in manual mode
Remote Setpoint Parameters
4n306 Remote SP Assignment 0 1* 0 Read/Write
4n307 Reserved Register -32768 -32768 N/A Was SP Transfer Mode 4n308 Ratio 1 9999 1000 Read/Write 1 = 0.1 4n309 Bias -1999 9999 0 Read/Write 1 = 1 Display Unit 4n310 Select Local / Remote SP 0 1 0 Read/Write
Setpoint Parameters
4n311 Setpoint Selection 0 1 0 Read/Write 0 = Setpoint 1, 1 = Setpoint 2 4n312 Sepoint 1 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 4n313 Setpoint 2 Value -1999 9999 0 Read/Write 1 = 1 Display Unit 4n314 Setpoint Lo Limit Value -1999 9999 0 Read/Write 1 = 1 Display Unit 4n315 Setpoint Hi Limit Value -1999 9999 0 Read/Write 1 = 1 Display Unit 4n316 Ramp Timebase 0 3 0 Read/Write 0 = Off, 1 = Seconds, 2 = Minutes, 3 = Hours 4n317 Ramp Rate 0 9999 0 Read/Write 1 = 0.1 Ramp Timebase unit
PID Parameters
4n321 PID Parameter Selection 0 1 0 Read/Write 0 = Primary PID Values, 1 = Alternate PID Values 4n322 Primary Proportional Band 0 9999 40 Read/Write 1 = 1 Display Unit 4n323 Primary Integral Time 0 65000 120 Read/Write 1 = 0.1 Second 4n324 Primary Derivative Time 0 9999 30 Read/Write 1 = 0.1 Second 4n325 Primary Power Filter Value 0 600 10 Read/Write 1 = 0.1 Second
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
PAX2
Unit and
FlexCard
dependent
FACTORY
SETTING
0 Read/Write
Assignments dependent on Pax2 Flex model in which card is installed.
Output Assignment List order = Px2, FC1, FC2, FC3
Number of PX2FCA1 Output Assignments = 0
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13
Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14
Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15
Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
0 = None, 1 = Px2C Process Value, 2 = Px2C Out Pwr,
3+ - Flex Card PID Assignments; FCn Input, FCn OP
0 = NONE, 1 = P2C SP, 2 = P2C PV, 3 = P2C OP, 4+ = Flex Card
Assignments
FCn Input, FCn OP
REGISTER
ADDRESS †
4n326 Primary Output Power Offset -1000 1000 0 Read/Write 1 = 0.1 %; Applicable when Primary Integral Time is 0 4n327 Secondary Proportional Band 0 9999 40 Read/Write 1 = 1 Display Unit 4n328 Secondary Integral Time 0 65000 120 Read/Write 1 = 0.1 Second 4n329 Secondary Derivative Time 0 9999 30 Read/Write 1 = 0.1 Second 4n330 Secondary Power Filter Value 0 600 10 Read/Write 1 = 0.1 Second 4n331 Secondary Output Power Offset -1000 1000 0 Read/Write 1 = 0.1 %; Applicable when Secondary Integral Time is 0
Power Transfer Parameters
4n341 Input Fault Power Value -1999 2000 0 Read/Write 1 = 0.1 % 4n342 Output Deadband -1000 1000 0 Read/Write 1 = 0.1 % 4n343 Output Heat Gain 0 5000 1000 Read/Write 1 = 0.1 % 4n344 Heat Low Limit 0 2000 0 Read/Write 1 = 0.1 % 4n345 Heat High Limit 0 2000 1000 Read/Write 1 = 0.1 % 4n346 Output Cool Gain 0 5000 1000 Read/Write 1 = 0.1 % 4n347 Cool Low Limit 0 2000 0 Read/Write 1 = 0.1 % 4n348 Cool High Limit 0 2000 1000 Read/Write 1 = 0.1 %
ON/OFF Control Parameters
4n371 On-Off Hysteresis 0 500 0 Read/Write 1 = 1 Display Unit 4n372 On-Off Deadband -1999 9999 0 Read/Write 1 = 1 Display Unit
Tuning Parameters
4n381 Tuning Code 0 4 2 Read/Write
4n382 Auto-Tune Start 0 1 0 Read/Write 0 = NO, 1 = YES
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = Very Aggressive, 1 = Aggressive, 2 = Default, 3 = Conservative,
4 = Very Conservative
PX2 USER INPUT / FUNCTION KEYS PARAMETERS
** User Input Action 0
** User Key Action 0
† - n = 1 + FlexCard Address
** - See Modbus Table for PAX2 unit (FlexBus model) in which card is being installed
"FlexCard
Dependent"
"FlexCard
Dependent"
REFER TO PAX2 MANUAL FOR STARTING LOCATION OF FLEX CARD FUNCTIONS (NUMBER OF PAX2 FUNCTIONS + 1)
n+1 = ILOC n+4 = PSL n+7 = r-HI n+10 = r-HL
n+2 = TRNF n+5 = SPrP n+8 = d-Lo
0 Read/Write
0 Read/Write
n+3 = SPSL n+6 = d-HI n+9 = r-Lo
n = Starting location for Flex Card
Function List order = Px2, FC1, FC2, FC3
Number of PX2FCA00 User Functions = 10
1 = ILOC 4 = PSL 7 = r-Lo
2 = TRNF 5 = SPrP 8 = r-HL
3 = SPSL 6 = r-HI
n = Starting location for Flex Card
Function List order = Px2, FC1, FC2, FC3
Number of PX2FCA00 Key Functions = 6
PX2FCA1 Modbus Register Table REVISED 01/30/15
REGISTER
ADDRESS †
FREQUENTLY USED REGISTERS
4n001 Input Process Value (Hi word) 4n002 Input Process Value (Lo word) 4n003 Input Process Maximum (Hi word) 4n004 Input Process Maximum (Lo word) 4n005 Input Process Minimum (Hi word) 4n006 Input Process Minimum (Lo word) 4n007 Input Process Status Flags 0 255 N/A Read Only Bit 3 Set = ADC Underrange, Bit 2 Set = ADC Overrange.
INPUT PARAMETERS SEE INPUT MODULE FOR PARAMETER DESCRIPTIONS Analog Input Parameters
4n071 Heater Current Monitor 0 4* 1 Read/Write
4n072 Input Square Root Linearization 0 1 0 Read/Write 0 = No, 1 = Yes 4n073 Input Decimal Point 0 3 1 Read/Write 0 = 0, 1 = 0.0, 2 = 0.00, 3 = 0.000 4n074 Input Rounding 0 6 0 Read/Write 0 = 1, 1 = 2, 2 = 5, 3 = 10, 4 = 20, 5 = 50, 6 = 100 4n075 Input Offset Value (Hi word) 4n076 Input Offset Value (Lo word) 4n077 Input Filter Value 0 250 10 Read/Write 1 = 0.1 Second 4n078 Input Filter Band Value 0 250 10 Read/Write 1 = 1 display unit 4n079 Max (HI) Capture Delay Time 0 9999 0 Read/Write 0 = Max Update Rate, 1 = 0.1Sec 4n080 Min (LO) Capture Delay Time 0 9999 0 Read/Write 0 = Max Update Rate, 1 = 0.1Sec
Input Scaling Point Parameters
4n101 Number of Scaling Points 2 15 2 Read/Write Number of Linearization Scaling Points 4n102 Reserved N/A N/A N/A N/A Reserved for future use 4n103 Scaling Pt.1 Input Value (Hi word) 4n104 Scaling Pt.1 Input Value (Lo word) 4n105 Scaling Pt.1 Display Value (Hi word) 4n106 Scaling Pt.1 Display Value (Lo word) 4n107 Scaling Pt.2 Input Value (Hi word) 4n108 Scaling Pt.2 Input Value (Lo word) 4n109 Scaling Pt.2 Display Value (Hi word)
4n110 Scaling Pt.2 Display Value (Lo word) 4n 111
thru 4n162
4n201 Line 2 Input Display Access 0 21 0 Read/Write 0 = LOC; Bit 0 = dREd, Bit 2 = PrEd, Bit4 = HrEd; Other bits N/A
4n202 Line 2 Maximum (Hi) Value Access 0 42 0 Read/Write
4n203 Line 2 Maximum (Hi) Value Access 0 42 0 Read/Write
4n230 Line 2 Reset Max Display Access 0 42 0 Read/Write 0 = LOC; Bit 1 = dEnt, Bit 3 = PEnt, Bit5 = HEnt; Other bits N/A 4n231 Line 2 Reset Min Display Access 0 42 0 Read/Write 0 = LOC; Bit 1 = dEnt, Bit 3 = PEnt, Bit5 = HEnt; Other bits N/A 4n232 Line 2 Reset Max and Min Access 0 42 0 Read/Write 0 = LOC; Bit 1 = dEnt, Bit 3 = PEnt, Bit5 = HEnt; Other bits N/A
Scaling Pts. 3 thru 15 Values
DISPLAY CONFIGURATION PARAMETERS Line 2 Input LOCS Parameters
Line 2 Function LOCS Parameters
REGISTER NAME
LOW
LIMIT
-1999 9999 N/A Read Only
-1999 9999 N/A Read Only 1 = 1 Display Unit
-1999 9999 N/A Read Only 1 = 1 Display Unit
-1999 9999 0 Read/Write 1 = 1 Display Unit
0 9999 0 Read/Write 1 = 0.001
-1999 9999 0 Read/Write 1 = 1 Display Unit
0 9999 1000 Read/Write 1 = 0.001
-1999 9999 1000 Read/Write 1 = 1 Display Unit
0 (input)
-1999 (dsp)
HIGH LIMIT
9999 0 Read/Write
FACTORY
SETTING
1 = 1 Display Unit
ADC Overrange Value = 1048576, Underrange Value = -1048576
0 = None, 1 = P2C Out1, 2 = P2C Out2, 3 = P2C Out3, 4=P2C Out4, 5+ =
FlexCard 1, 2, or 3 Outputs
Registers 40111-40162 hold values for Scaling Points 3 thru 15,
and follow the same ordering as Scaling Points 1 and 2.
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
0 = LOC; Bit 0 = dREd, Bit 1 = dEnt, Bit 2 = PrEd, Bit 3 = PEnt,
Bit4 = HrEd, Bit5 = HEnt
REGISTER
ADDRESS †
OUTPUT PARAMETERS
4n250 Output 1 Assignment 0
4n251 Output 1 Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
4n252 Output 1 Alarm Mask 0 65535 0 Read/Write
4n253 Output 1 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 4n254 Output 2 Assignment 0 6 0 Read/Write Same as Output 1 Assignment 4n255 Output 2 Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 4n256 Output 2 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 4n257 Output 2 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 4n258 Output 3 Assignment 0 6 0 Read/Write Same as Output 1 Assignment 4n259 Output 3 Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 4n260 Output 3 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 4n261 Output 3 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 4n262 Output 4 Assignment 0 6 0 Read/Write Same as Output 1 Assignment 4n263 Output 4 Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 4n264 Output 4 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 4n265 Output 4 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
PAX2
Unit and
FlexCard
dependent
FACTORY
SETTING
0 Read/Write
Assignments dependent on Pax2 Flex model in which card is installed.
Output Assignment List order = Px2, FC1, FC2, FC3
Number of PX2FCA1 Output Assignments = 0
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13
Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14
Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15
Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
PX2 USER INPUT / FUNCTION KEYS PARAMETERS
** User Input Action 0
** User Key Action 0
† - n = 1 + FlexCard Address
** - See Modbus Table for PAX2 unit (FlexBus model) in which card is being installed
FlexCard
Dependent
FlexCard
Dependent
REFER TO PAX2 MANUAL FOR STARTING LOCATION OF FLEX CARD FUNCTIONS (NUMBER OF PAX2 FUNCTIONS + 1)
n+0 = ILOC n+3 = PSL n+6 = r-HI n+9 = r-HL
n+1 = TRNF n+4 = SPrP n+7 = d-Lo
0 Read/Write
0 Read/Write
n+2 = SPSL n+5 = d-HI n+8 = r-Lo
n = Starting selection number for Flex Card
Function List order = Px2, FC1, FC2, FC3
Number of PX2FCA00 User Functions = 10
n+0 = ILOC n+3 = PSL n+6 = r-Lo
n+1 = TRNF n+4 = SPrP n+7 = r-HL
n+2 = SPSL n+5 = r-HI
n = Starting selection number for Flex Card
Function List order = Px2, FC1, FC2, FC3
Number of PX2FCA00 Key Functions = 6
Loading...