Red Lion PAX2C, PX2FCA0, PX2FCA1 Technical Data

PAX2C, PX2FCA0, and PX2FCA1 Modbus Register Tables LP0905D
PAX2C Ver 1.5 Modbus Register Table REVISED 2015-07-20
REGISTER
ADDRESS
FREQUENTLY USED REGISTERS
40001 Process Value N/A N/A N/A Read 1 = 1 Display Unit 40002 Maximum Value -1999 9999 N/A Read 1 = 1 Display Unit 40003 Minimum Value -1999 9999 N/A Read 1 = 1 Display Unit 40004 Active Setpoint Value SPLO SPHI 0 Read/Write 1 = 1 Display Unit; Limited by setpoint low/high limits 40005 Setpoint 1 Value SPLO SPHI 0 Read/Write 1 = 1 Display Unit; Limited by setpoint low/high limits 40006 Setpoint 2 Value SPLO SPHI 0 Read/Write 1 = 1 Display Unit; Limited by setpoint low/high limits 40007 Setpoint Deviation N/A N/A N/A Read Only 1 = 1 Display Unit 40008 Output Power -1000 1000 N/A Read/Write Output Power: Heat/Cool; * writable only in manual mode; 1 = 0.1% 40009 Active Proportional Band 0 9999 700 Read/Write 1 = 1 Display Unit 40010 Active Integral Time 0 65000 120 Read/Write 1 = 0.1 Second 40011 Active Derivative Time 0 9999 30 Read/Write 1 = 0.1 Second 40012 Active Power Filter 0 600 10 Read/Write 1 = 0.1 Second
40013 Auto-Tune Code 0 4 2 Read/Write
40014 Auto-Tune Request 0 1 0 Read/Write 0 = Off, 1 = Invoke Auto-Tune 40015 Auto-Tune Phase 0 4 0 Read 0 = Off, 4 = Last Phase of Auto-Tune 40016 Auto-Tune Done 0 1 0 Read 1 = Successful Auto-Tune since last power cycle. 40017 Auto-Tune Fail 0 1 0 Read 0 = Off, 1 = Auto-Tune failed 40018 Control Mode 0 1 0 Read/Write 0 = Automatic, 1 = Manual Mode 40019 Setpoint Selection 0 1 0 Read/Write 0 = Setpoint 1, 1 = Setpoint 2 40020 Remote/Local Setpoint Selection 0 1 0 Read/Write 0 = Local, 1 = Remote 40021 PID Parameter Selection 0 1 0 Read/Write 0 = Primary PID Values, 1 = Alternate PID Values 40022 Disable Integral Action 0 1 0 Read/Write 0 = Enabled, 1 = Disabled 40023 Disable Setpoint Ramping 0 1 0 Read/Write 0 = Enabled, 1 = Disabled 40024 Setpoint Ramping In Process 0 1 0 Read/Write 0 = Off, 1 = In Process 40025 Setpoint Ramp Rate Value -1999 9999 0 Read/Write 1 = 0.1 Setpoint Ramping @ Timebase unit selection 40026 Alarm (1-16) Status Register 0 65535 0 Read Bit 15 = A16, Bit 0 = A1 40027 Input Range Alarm 0 1 0 Read 0 = Off, 1 = Alarm active 40028 User Input Status 0 2 0 Read Bit 1 = User Input 2, Bit 0 = User Input 1
40029 Output Status 0 15 N/A Read/Write
40030 Output Manual Mode Register (MMR) 0 31 0 Read/Write
40031 Alarm Reset Register 0 65535 0 Read/Write
40032 Analog Output Register (AOR) 0 4095 0 Read/Write
40033 Active Alarm 1 Value -1999 9999 0 Read/Write Active List (A or B) 40034 Active Alarm 2 Value -1999 9999 0 Read/Write Active List (A or B) 40035 Active Alarm 3 Value -1999 9999 0 Read/Write Active List (A or B) 40036 Active Alarm 4 Value -1999 9999 0 Read/Write Active List (A or B) 40037 Active Alarm 5 Value -1999 9999 0 Read/Write Active List (A or B) 40038 Active Alarm 6 Value -1999 9999 0 Read/Write Active List (A or B) 40039 Active Alarm 7 Value -1999 9999 0 Read/Write Active List (A or B) 40040 Active Alarm 8 Value -1999 9999 0 Read/Write Active List (A or B)
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = Very Aggressive, 1 = Aggressive, 2 = Default, 3 = Conservative, 4 = Very Conservative
Status of Outputs. Bit State: 0 = Off, 1 = On. Bit 3 = Out1, Bit 2 = Out2, Bit 1 = Out3, Bit 0 = Out4. Outputs can only be activated/reset with this register when the respective bits in the Manual Mode Register (MMR) are set. Bit State: 0 = Auto Mode, 1 = Manual Mode Bit 4 = SP1, Bit 3 = SP2, Bit 2 = SP3, Bit 1 = SP4, Bit 0 = Linear Output Bit State: 1= Reset Alarm, bit is returned to zero following reset processing; Bit 15 = A16, Bit 0 = A1 Functional only if Linear Output is in Manual Mode.(MMR bit 0 = 1) Linear Output Card written to only if Linear Out (MMR bit 0) is set.
REGISTER
ADDRESS
40041 Active Alarm 9 Value -1999 9999 0 Read/Write Active List (A or B) 40042 Active Alarm 10 Value -1999 9999 0 Read/Write Active List (A or B) 40043 Active Alarm 11 Value -1999 9999 0 Read/Write Active List (A or B) 40044 Active Alarm 12 Value -1999 9999 0 Read/Write Active List (A or B) 40045 Active Alarm 13 Value -1999 9999 0 Read/Write Active List (A or B) 40046 Active Alarm 14 Value -1999 9999 0 Read/Write Active List (A or B) 40047 Active Alarm 15 Value -1999 9999 0 Read/Write Active List (A or B) 40048 Active Alarm 16 Value -1999 9999 0 Read/Write Active List (A or B) 40049 Active Alarm 1 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40050 Active Alarm 2 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40051 Active Alarm 3 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40052 Active Alarm 4 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40053 Active Alarm 5 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40054 Active Alarm 6 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40055 Active Alarm 7 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40056 Active Alarm 8 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40057 Active Alarm 9 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40058 Active Alarm 10 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40059 Active Alarm 11 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40060 Active Alarm 12 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40061 Active Alarm 13 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40062 Active Alarm 14 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40063 Active Alarm 15 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action. 40064 Active Alarm 16 Band/Dev. Value -1999 9999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Alarm Action.
40065 Remote SP Value -1999 9999 0 Read Only
INPUT PARAMETERS SEE INPUT MODULE FOR PARAMETER DESCRIPTIONS Analog Input Parameters
40101 Input Range 0 26 16 Read/Write
40102 Square Root Linearization 0 1 0 Read/Write 0 = No, 1 = Yes (Valid on Process Inputs) 40103 Temperature Scale (TC or RTD only) 0 1 1 Read/Write 0 = °C, 1 = °F 40104 Ice Point Compensation (TC only) 0 1 1 Read/Write 0 = Off, 1 = On 40105 ADC Conversion Rate (samples/sec) 0 5 2 Read/Write 0 = 5, 1 = 10, 2 = 20, 3 = 40, 4 = 80, 5 = 160 40106 Decimal Point 0 3 1 Read/Write 0 = 0, 1 = 0.0, 2 = 0.00, 3 = 0.000 40107 Rounding Factor 0 6 0 Read/Write 0 = 1, 1 = 2, 2 = 5, 3 = 10, 4 = 20, 5 = 50, 6 = 100 40108 Input Offset Value -1999 9999 0 Read/Write 1 = 1 Display Unit 40109 Digital Input Filter 0 250 10 Read/Write 1 = 0.1 Second 40110 Input Scaling Points in List Function 0 1 0 Read/Write 0 = No, 1 = Yes
User Input / Function Keys
40151 User Input Active State 0 1 0 Read/Write 0 = Active Low, 1 = Active High
40152 User Input 1 Action 0 17* 0 Read/Write
40153 User Input 1 Alarm Mask 0 65535 0 Read/Write
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = 250µA 5 = 250mV 11 = 100Ω 17 = TC-K 23 = RTD 385 1 = 2.5mA 6 = 2V 12 = 1KΩ 18 = TC-R 24 = RTD 392 2 = 25mA 7 = 10V 13 = 10KΩ 19 = TC-S 25 = RTD 672
3 = 250mA 8 = 25V 14 = TC-T 20 = TC-B 26 = RTD 427 4 = 2A 9 = 100V 15 = TC-E 21 = TC-N 10 = 200V 16 = TC-J 22 = TC-C
0 = NONE 4 = SPSL 8 = d-HI 12 = r-HL 16 = LISt 1 = PLOC 5 = rSPt 9 = r-HI 13 = r-AL 17 = Prnt 2 = ILOC 6 = PSEL 10 = d-Lo 14 = dLEV 18 = FlexCard 3 = TrnF 7 = SPrP 11 = r-Lo 15 = dISP Functions Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40154 User Input 2 Action 0 17* 0 Read/Write Same as User Input 1 Action 40155 User Input 2 Alarm Mask 0 65535 0 Read/Write Same as User Input 1 Alarm Mask
40156 User F1 Key Action 0 14* 0 Read/Write
40157 User F1 Key Alarm Mask 0 65535 0 Read/Write Same as User Input 1 Alarm Mask 40158 User F2 Key Action 0 14* 0 Read/Write Same as User F1 Key Action 40159 User F2 Key Alarm Mask 0 65535 0 Read/Write Same as User Input 1 Alarm Mask 40160 User F1 Second Action 0 14* 0 Read/Write Same as User F1 Key Action 40161 User F1 Second Alarm Mask 0 65535 0 Read/Write Same as User Input 1 Alarm Mask 40162 User F2 Second Action 0 14* 0 Read/Write Same as User F1 Key Action 40163 User F2 Second Alarm Mask 0 65535 0 Read/Write Same as User Input 1 Alarm Mask
Advanced Input Parameters
List A List B Input Scaling Points Parameters
40171 40211 Number of Scaling Points 2 16 2 Read/Write Number of Linearization Scaling Points 40172 40212 Reserved N/A N/A N/A N/A 40173 40213 Scaling Pt.1 Input Value -1999 9999 0 Read/Write 1 = 0.001 40174 40214 Scaling Pt.1 Display Value -1999 9999 0 Read/Write 1 = 1 Display Unit 40175
40202 40203 40243 Scaling Pt.16 Input Value -1999 9999 0 Read/Write 1 = 0.001 40204 40244 Scaling Pt.16 Display Value -1999 9999 0 Read/Write 1 = 1 Display Unit
40215
thru
thru
Scaling Pts. 2 thru 15 Values -1999 9999 0 Read/Write
40242
OUTPUT PARAMETERS
40251 Output 1 Assignment 0 11* 1 Read/Write
40252 Output 1 Logic/Alarm Logic Mode 0 2 0 Read/Write
40253 Output 1 Alarm Mask 0 65535 0 Read/Write
40254 Output 1 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 40255 Output 2 Assignment 0 11* 0 Read/Write Same as Output 1 Assignment 40256 Output 2 Logic/Alarm Logic Mode 0 2 0 Read/Write Same as Output 1 Logic/Alarm Logic Mode 40257 Output 2 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 40258 Output 2 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 40259 Output 3 Assignment 0 11* 0 Read/Write Same as Output 1 Assignment 40260 Output 3 Logic/Alarm Logic Mode 0 2 0 Read/Write Same as Output 1 Logic/Alarm Logic Mode 40261 Output 3 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 40262 Output 3 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second 40263 Output 4 Assignment 0 11* 0 Read/Write Same as Output 1 Assignment 40264 Output 4 Logic/Alarm Logic Mode 0 2 0 Read/Write Same as Output 1 Logic/Alarm Logic Mode 40265 Output 4 Alarm Mask 0 65535 0 Read/Write Same as Output 1 Alarm Mask 40266 Output 4 Cycle Time 0 600 20 Read/Write 1 = 0.1 Second
Analog Output
40271 Non-Linear Analog Output Scaling 0 1 0 Read/Write 0 = No, 1 = Yes (Use Non-Linear Analog Output Scaling Parameters) 40272 Type 0 2 1 Read/Write 0 = 0-20 mA, 1 = 4-20 mA, 2 = 0-10 V
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = NONE 4 = rSPt 8 = r-Lo 12 = dISP 1 = ILOC 5 = PSEL 9 = r-HL 13 = LISt 2 = TrnF 6 = SPrP 10 = r-AL 14 = Prnt 3 = SPSL 7 = r-HI 11 = dLEV 15 = FlexCard Functions
Registers 40175-40202 and 40215-40242 hold values for Scaling Points 2 thru 15, and follow the same ordering as Scaling Point 1.
0 = NONE 4 = P2C MAN 8 = ILOC 12 = FlexCard 1 = P2C Heat 5 = SPSL 9 = tUNE Assignments 2 = P2C Cool 6 = SPrP 10 = tndn 3 = ALr 7 = RSP Transfer 11 = tnFL If Out Assignment ALr; 0 = NOR, 1 = REV If Output Assignment = ALr; 0 = SINGLE, 1 = AND, 2 = OR Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40273 Assignment 0 6* 0 Read/Write
40274 Analog Low Scale Value -1999 9999 0 Read/Write Display value that corresponds with 0 V, 0 mA or 4 mA output 40275 Analog High Scale Value -1999 9999 1000 Read/Write Display value that corresponds with 10 V or 20 mA output 40276 Update time 0 100 0 Read/Write 0 = Max update rate, 1 = 0.1 Second 40277 Probe Failure Action (TC or RTD only) 0 1 0 Read/Write 0 = Low Scale, 1 = High Scale (only applies for TC or RTD input)
Non-Linear Analog Output Scaling
List A List B Analog Output Scaling Point Parameters
41721 41761 Number of Scaling Points 2 16 2 Read/Write Number of Linearization Scaling Points 41722 41762 Reserved N/A N/A N/A N/A 41723 41763 Output Value for Scaling Point 1 0 2000 0 Read/Write 1 = 0.01 41724 41764 Parameter Value for Scaling Point 1 -1999 9999 0 Read/Write 1 = 1 Analog Output Assignment value unit
41725 to
141754
41765 to
141794
40281 Display Intensity Level 0 4 4 Read/Write 0 = Min.(off), 4 = Max. 40282 Display Contrast Level 0 15 7 Read/Write 40283 Display Update (readings per second) 0 4 1 Read/Write 0 = 1, 1 = 2, 2 = 5, 3 = 10, 4 = 20 40284 Conguration Mode 0 1 1 Read/Write 0 = Advanced, 1 = Basic (Caution: Affects other parameters, see manual)
40291 Line 1 Display Assignment 0 3* 1 Read/Write 0 = NO, 1 = PV, 2 = HI, 3 = LO, 4+ = FlexCard Assignments 40292 Line 1 Default Display Color 0 2 2 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40293 Line 1 Units Mnemonic 0 1 1 Read/Write 0 = Off, 1 = On
40294 Line 1 Units Digit 1 (Left) 0 57 0 Read/Write
40295 Line 1 Units Digit 2 (Center) 0 57 56 Read/Write
40296 Line 1 Units Digit 3 (Right) 0 57 6 Read/Write
40297 Line 1 Bargraph Assignment 0 3* 1 Read/Write
40298 Line 1 Bargraph Low Scale Value 0 9999 0 Read/Write 40299 Line 1 Bargraph High Scale Value 0 9999 1000 Read/Write
40300 Line 1 Green Backlight Assignment 0 13* 0 Read/Write
40301 Line 1 Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40302 Line 1 Green Backlight Alarm Mask 0 65535 0 Read/Write
40303 Line 1 Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 1 Green Backlight Assignment 40304 Line 1 Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40305 Line 1 Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask 40306 Line 1 Red Backlight Assignment 0 13* 0 Read/Write Same as Line 1 Green Backlight Assignment 40307 Line 1 Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40308 Line 1 Red Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask
Scaling Pts. 2 thru 16 Values
DISPLAY CONFIGURATION PARAMETERS General
Line 1
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = NONE, 1 = PV, 2 = Hi, 3 = Lo, 4 = Output Power, 5 = Active Setpoint, 6 = Deviation, 7+ = FlexCard Assignments
Registers 41725-41754 and 41765-41794 hold values for Scaling Points 2 thru 16, and follow the same ordering as Scaling Point 1.
0 = 9 = I 18 = Q 27 = Z 36 = 8 45 = m(r) 54 = ] 1 = A 10 = J 19 = R 28 = 0 37 = 9 46 = o 55 = / 2 = b 11 = K 20 = S 29 = 1 38 = a 47 = q 56 = º 3 = C 12 = L 21 = t 30 = 2 39 = c 48 = r 57 = _ 4 = d 13 = M(l) 22 = U 31 = 3 40 = e 49 = u 5 = E 14 = M(r) 23 = V 32 = 4 41 = g 50 = w(r) 6 = F 15 = N 24 = W(l) 33 = 5 42 = h 51 = ­7 = G 16 = O 25 = W(r) 34 = 6 43 = i 52 = = 8 = H 17 = P 26 = Y 35 = 7 44 = n 53 = [ 0 = NONE, 1 = Output Power, 2 = Deviation, 3 = Setpoint, 4+ = FlexCard Assignments
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40309 Line 1 Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 1 Green Backlight Assignment 40310 Line 1 Green-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40311 Line 1 Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask 40312 Line 1 Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 1 Green Backlight Assignment 40313 Line 1 Red-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40314 Line 1 Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask 40315 Line 1 Red-Green Backlight Assignment 0 13* 0 Read/Write Same as Line 1 Green Backlight Assignment 40316 Line 1 Red-Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40317 Line 1 Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 1 Green Backlight Alarm Mask
Line 2
40331 Line 2 Default Display Color 0 2 0 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40332 Line 2 Units Mnemonic 0 1 0 Read/Write 0 = Off, 1 = On 40333 Line 2 Units Digit 1 (Left) 0 57 0 Read/Write Same as Line 1 Units Selection 40334 Line 2 Units Digit 2 (Center) 0 57 0 Read/Write 40335 Line 2 Units Digit 3 (Right) 0 57 0 Read/Write
40336 Line 2 Bargraph Assignment 0 6* 2 Read/Write
40337 Line 2 Bargraph Low Scale Value 0 9999 0 Read/Write 40338 Line 2 Bargraph High Scale Value 0 9999 0 Read/Write
40339 Line 2 Green Backlight Assignment 0 13* 0 Read/Write
40340 Line 2 Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40341 Line 2 Green Backlight Alarm Mask 0 65535 0 Read/Write
40342 Line 2 Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 2 Green Backlight Assignment 40343 Line 2 Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40344 Line 2 Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 2 Green Backlight Alarm Mask 40345 Line 2 Red Backlight Assignment 0 13* 0 Read/Write Same as Line 2 Green Backlight Assignment 40346 Line 2 Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40347 Line 2 Red Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 2 Green Backlight Alarm Mask 40348 Line 2 Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 2 Green Backlight Assignment 40349 Line 2 Green-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40350 Line 2 Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 2 Green Backlight Alarm Mask 40351 Line 2 Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as Line 2 Green Backlight Assignment 40352 Line 2 Red-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40353 Line 2 Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 2 Green Backlight Alarm Mask 40354 Line 2 Red-Green Backlight Assignment 0 13* 0 Read/Write Same as Line 2 Green Backlight Assignment 40355 Line 2 Red-Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40356 Line 2 Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as Line 2 Green Backlight Alarm Mask
Universal Annunciator 1
40361 UA 1 Default Display Color 0 2 0 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40362 UA 1 Units Mnemonic 0 1 1 Read/Write 0 = Off, 1 = On
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = NONE, 1 = OP, 2 = dEV, 3 = SP, 4 = OP ANY, 5 = dEV ANY, 6 = SP ANY, 7+ = FlexCard Assignments
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40363 UA 1 Units Digit 1 (Left) 0 57 16 Read/Write
40364 UA 1 Units Digit 2 (Right) 0 57 29 Read/Write
40365 UA 1 Units Logic Mode (Active) 0 2 0 Read/Write 0 = nor, 1 = rEv, 2 = FLSh
40366 UA 1 Units Assignment 0 13* 1 Read/Write
40367 UA 1 Assignment Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40368 UA 1 Assignment Alarm Mask 0 65535 0 Read/Write
40368 UA 1 Green Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40369 UA 1 Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40370 UA 1 Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask 40371 UA 1 Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40372 UA 1 Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40373 UA 1 Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask 40374 UA 1 Red Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40375 UA 1 Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40376 UA 1 Red Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask 40377 UA 1 Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40378 UA 1 Green-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40379 UA 1 Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask 40380 UA 1 Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40381 UA 1 Red-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40382 UA 1 Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask 40383 UA 1 Red-Green Backlight Assignment 0 13* 0 Read/Write Same as UA 1 Units Assignment 40384 UA 1 Red-Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40385 UA 1 Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 1 Assignment Alarm Mask
Universal Annunciator 2
40391 UA 2 Default Display Color 0 2 0 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40392 UA 2 Units Mnemonic 0 1 1 Read/Write 0 = Off, 1 = On 40393 UA 2 Units Digit 1 (Left) 0 57 1 Read/Write Same as UA1 Units Selection 40394 UA 2 Units Digit 2 (Right) 0 57 29 Read/Write 40395 UA 2 Units Logic Mode (Active) 0 2 0 Read/Write 0 = nor, 1 = rEv, 2 = FLSh
40396 UA 2 Units Assignment 0 13* 5 Read/Write
40397 UA 2 Assignment Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40398 UA 2 Assignment Alarm Mask 0 65535 0 Read/Write
40399 UA 2 Green Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40400 UA 2 Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40401 UA 2 Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = 9 = I 18 = Q 27 = Z 36 = 8 45 = m(r) 54 = ] 1 = A 10 = J 19 = R 28 = 0 37 = 9 46 = o 55 = / 2 = b 11 = K 20 = S 29 = 1 38 = a 47 = q 56 = º 3 = C 12 = L 21 = t 30 = 2 39 = c 48 = r 57 = _ 4 = d 13 = M(l) 22 = U 31 = 3 40 = e 49 = u 5 = E 14 = M(r) 23 = V 32 = 4 41 = g 50 = w(r) 6 = F 15 = N 24 = W(l) 33 = 5 42 = h 51 = ­7 = G 16 = O 25 = W(r) 34 = 6 43 = i 52 = = 8 = H 17 = P 26 = Y 35 = 7 44 = n 53 = [
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16
REGISTER
ADDRESS
40402 UA 2 Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40403 UA 2 Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40404 UA 2 Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask 40405 UA 2 Red Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40406 UA 2 Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40407 UA 2 Red Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask 40408 UA 2 Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40409 UA 2 Green-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40410 UA 2 Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask 40411 UA 2 Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40412 UA 2 Red-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40413 UA 2 Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask 40414 UA 2 Red-Green Backlight Assignment 0 13* 0 Read/Write Same as UA 2 Units Assignment 40415 UA 2 Red-Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40416 UA 2 Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 2 Assignment Alarm Mask
Universal Annunciator 3
40421 UA 3 Default Display Color 0 2 0 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40422 UA 3 Units Mnemonic 0 1 1 Read/Write 0 = Off, 1 = On 40423 UA 3 Units Digit 1 (Left) 0 57 1 Read/Write Same as UA1 Units Selection 40424 UA 3 Units Digit 2 (Right) 0 57 30 Read/Write 40425 UA 3 Units Logic Mode (Active) 0 2 0 Read/Write 0 = nor, 1 = rEv, 2 = FLSh
40426 UA 3 Units Assignment 0 13* 5 Read/Write
40427 UA 3 Assignment Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR
40428 UA 3 Assignment Alarm Mask 0 65535 0 Read/Write
40429 UA 3 Green Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40430 UA 3 Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40431 UA 3 Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask 40432 UA 3 Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40433 UA 3 Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40434 UA 3 Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask 40435 UA 3 Red Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40436 UA 3 Red Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40437 UA 3 Red Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask 40438 UA 3 Green-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40439 UA 3 Green-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40440 UA 3 Green-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask 40441 UA 3 Red-Orange Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40442 UA 3 Red-Orange Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40443 UA 3 Red-Orange Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask 40444 UA 3 Red-Green Backlight Assignment 0 13* 0 Read/Write Same as UA 3 Units Assignment 40445 UA 3 Red-Green Backlight Alarm Logic Mode 0 2 0 Read/Write 0 = SINGLE, 1 = AND, 2 = OR 40446 UA 3 Red-Green Backlight Alarm Mask 0 65535 0 Read/Write Same as UA 3 Assignment Alarm Mask
Universal Annunciator 4
40451 UA 4 Default Display Color 0 2 0 Read/Write 0 = Grn, 1 = OrNG, 2 = rEd 40452 UA 4 Units Mnemonic 0 1 0 Read/Write 0 = Off, 1 = On 40453 UA 4 Units Digit 1 (Left) 0 57 0 Read/Write Same as UA1 Units Selection 40454 UA 4 Units Digit 2 (Right) 0 57 0 Read/Write
REGISTER NAME
LOW
LIMIT
HIGH LIMIT
FACTORY
SETTING
0 = NO 3 = Out3 6 = MAN 9 = RSPt 12 = tndn 1 = Out1 4 = Out4 7 = SPSL 10 = ILOC 13 = tnFL 2 = Out2 5 = ALr 8 = SPrP 11 = tUNE 14+ = FlexCard
Bit 0 = A1 Bit 4 = A5 Bit 8 = A9 Bit 12 = A13 Bit 1 = A2 Bit 5 = A6 Bit 9 = A10 Bit 13 = A14 Bit 2 = A3 Bit 6 = A7 Bit 10 = A11 Bit 14 = A15 Bit 3 = A4 Bit 7 = A8 Bit 11 = A12 Bit 15 = A16