MODEL PSDR - 24 V POWER SUPPLIES @ 2 OR 4 A
DESCRIPTION
The compact PSDR power supplies are industrial input voltage supplies with
primary switched-mode regulator technology. They feature low output ripple
and adjusted output voltage from 22.5 to 28.5 VDC. The output is electronically
protected against overloads and short circuits.
The modules snap onto standard 35 mm flat DIN rails and use removable
terminal blocks for easy wiring.
Bulletin No. PSDR-B
Drawing No. LP0604
Released 01/14
SPECIFICATIONS
1. POWER REQUIREMENTS:
Nominal Input Voltage: 100 to 240 VAC
Input Voltage Range: 85 to 264 VAC or 90 to 350 VDC
Current Consumption at nominal input voltage:
PSDR0200: 0.82 A to 0.33 A @ 100 to 240 VAC, 0.65 to 0.19 A @ 90 to 350 VDC
PSDR0400: 1.8 A to 0.7 A @ 100 to 240 VAC, 1.3 to 0.4 A @ 90 to 350 VDC
2. FREQUENCY: 50 to 60 Hz
3. INPUT RECOMMENDED BACKUP FUSE:
Power Circuit Breaker: 6 A or 10 A
Characteristic: B (EN 60898)
4. SURGE VOLTAGE PROTECTION: Varistor
5. POWER OUTPUT: Nominal value of 24 VDC ±1%. Adjustable from 22.5
to 28.5 VDC via potentiometer
6. EFFICIENCY AT 230 VAC AND NOMINAL VALUES: > 80 %
7. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -25 to 60°C
Storage Temperature: -40 to 85°C
Humidity, no moisture condensation: 95 % at 25°C
Vibration in acc. with IEC 68-2-6: < 15 Hz, amplitude ±2.5 mm;
15 Hz - 150 Hz, 2.3 g
Shock in all directions acc. with IEC 68-2-27: 30 g
Contamination in acc. with EN 50178: Degree of pollution 2
8. STANDARDS AND CERTIFICATIONS:
Electrical Safety (of information
technology equipment)
Industrial regulating devices
Electronic equipment for use in
electrical power installations
(surge voltage category III)
Limitation of output power
Safe isolation
Protection against electric shock
EN 60950 / VDE 0805
UL Recognized UL 60 950
UL 508 listed
U
R
L
EN 50178 / VDE 0160
NEC Class 2
VDE 0100-410
DIN VDE 0106-101
DIMENSIONS In inches (mm)
4.50
(114.5)
3.89
(99.0)
C
MODEL C
PSDR0200 1.77 (45)
PSDR0400 2.66 (67.5)
In conformance with EMC guideline 89/336/EEC
and low-voltage directive 73/23/EEC
EMC (Electromagnetic compatibility)
Immunity in accordance with EN 61000-6-2
Discharge of static electricity (ESD)
Electromagnetic HF field
Fast transients (Burst)
Surge voltage capacities (Surge)
Conducted disturbance
Voltage dips
Noise emission according to EN 50081-2
Emitted radio interference
Radio interference voltage
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
ENV 50204Simulation mobile phones
2)
Housing > Level 3
Contact discharge: 8 kV
Discharge in air: 8 kV
1)
Housing Level 3
Frequency/Field intensity: 80-1000
MHz / 10 V/m
2)
Input: 4 kV (Level 4) 4)
Output: 2 kV (Level 3) 4)
Signal: 1 kV (Level 2)
2)
Input: 4 kV 4) / 2 kV
Output: 0.5 kV 4) / 0.5 kV
Signal: 0.5 kV 4) (Level 1)
1)
I/O/S: Level 3
Frequency/Uo: 0.15-80 MHz / 10 V
2)
Input: see mains buffering
> 20 ms
Frequency: 900 MHz, 1800 MHz
Field intensity: 20 V/m
EN 55011 (EN 55022) Class B
EN 55011 (EN 55022) Class B
4)
4)
(Level 4)
3)
(Level 1)
5)
5)
EN 55011 corresponds to CISPR11 / EN 55022 corresponds to CISPR22
EN 61000 corresponds to IEC 1000
1)
Criterion A: Normal operating behavior within the defined limits.
2)
Criterion B:
3)
Symmetrical: Conductor to conductor.
4)
Asymmetrical: Conductor to ground.
5)
Class B: Area of application industry and residential.
Temporary impairment to operational behavior, that is
corrected by the device itself.
9. ISOLATION VOLTAGE: Input/Output 3 kVAC
10. INSTALLATION POSITION: On horizontal mounting rail according to
EN 50022-35
11. CONNECTIONS: 24 to 14 AWG max. Torque 4.5 to 5.3 inch-lbs
(0.5-0.6 Nm).
12. MOUNTING: Standard DIN rail top hat (T) profile rail according to
EN50022 - 35 X 7.5 and 35 X 15. Can be mounted in rows with vertical
Spacing > 5 cm or horizontally with no space.
13. CONSTRUCTION: Case body is black, high impact plastic. IP20 touch
safe. Protection Class II.
14. MTBF (Mean Time Between Failure): >500000 h in acc. with IEC 1709 (SN
29500)
15. WEIGHT:
PSDR0200: 8.8 oz. (250 g)
PSDR0400: 14.1 oz. (400 g)
CONNECTION AND OPERATION
INSTRUCTIONS
Caution: Danger! Never work on live equipment!
Caution: When the device is opened, a dangerous voltage may remain
at the electrolytic capacitors for up to 2 minutes after shutdown!
The installation must be performed by a specialist in accordance with
the requirements of EN 60950.
For vertical installations we recommend a minimum spacing of 5 cm
(1.97 in.) between other modules and this power supply to ensure
sufficient convection.
No minimum spacing is required for horizontal alignment.
The mains feed line must have an appropriate fixing or strain relief
outside of the device.
The supply-side installation and the connection via screw terminal
blocks must be done in a way that ensures protection against electric
shock.
PROTECTION
The device must be installed in accordance with the specifications of EN
60950.
It must be possible to switch off the device using a suitable disconnecting
device outside the power supply. For example, primary side line protection
could be used.
In case of DC applications it is necessary to connect in series an adequate fuse.
RAIL MOUNTING
The power supply unit can be snapped onto all mounting rails in accordance
with EN 50022-35. Installation should be made horizontally (input terminal
blocks below).
CABLE CONNECTION
The device is equipped with COMBICON plug connectors.
This easy-to assemble connection method allows devices to be exchanged
easily and the electrical connection to be visibly isolated.
Connecting Cables:
Cable cross sections from 0.2 to 2.5 mm2 rigid (solid)/flexible (stranded)
(AWG 24-14) may be used.
To maintain UL, use copper cable rated for an operating temperature of
75°C/170°F.
For Reliable And Touch-proof Contacts:
Strip the connection ends (7 mm - See Figure).
INPUT
The input con nection is made by the screw
connections “L(+)” and “N(-)” (torque 0.5 Nm) on
the COMBICON plug connection.
For device protection, there is an internal fuse.
+
--
OUT DC 24V 2A
DC
OK
Additional device protection is not necessary.
Recommended backup fuses are power circuitbreakers 6 A or 10 A, charactistic B (or identical
function). In DC applications, a suitable backup fuse
must be wired in.
If the internal fuse is triggered, there is
most probably a malfunction in the device.
22.5-28.5
VDC
IN AC 100-240V
L(+)
NC
www.redlion.net
DC
OK
N(-)
NC
In this case, the device must be inspected
in the factory!
OUTPUT
The 24 VDC connection is made by the screw connections “+” and
“-” (torque 0.5 Nm) on the COMBICON plug connection. At the time of
delivery, the output voltage is 24 VDC. The output voltage can be set from 22.5
to 28.5 VDC on the potentiometer.
The device is electronically protected against short circuits and idling. In the
event of an error, the output voltage is limited to max 35 VDC.
Function Monitoring
For function monitoring, there is the active DC OK switching output and the
DC OK LED.
The 24 VDC signal is measured between the “DC OK” and “-” connection
terminal blocks and can be loaded with 20 mA maximum. This signal output
indicates that the output voltage has fallen below 21.5 VDC when “active high”
changes to “low”.
The DC OK signal is isolated from the power output.
STATUS 1 STATUS 2
Green LED “ DC OK”
Active DC OK switching
output
Status
Output Characteristic Curve
The device functions following the U-I characteristic curve. Under load, the
operating point follows this curve. In the event of a short circuit or overload, the
out put current is limited to I
short circuit on the secondary side has been remedied.
OUT
[V]
4
N
on off
U = +24 V
(in reference to “-”)
Normal operation of the
power supply.
U
> 21.5 V
OUT
. The secondary voltage is reduced until the
BOOST
U = 0 V
(in reference to “-”)
U
< 21.5 V
OUT
• Secondary consumer
short-circuit or overload
• No mains voltage or
device faulty
ORDERING INFORMATION
PSDR2 24 VDC @ 2A PSDR0200
PSDR4 24 VDC @ 4A PSDR0400
Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
OUTPUT
PART NUMBERMODEL NO.
Red Lion Controls
Europe
Softwareweg 9
NL - 3821 BN Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
I
I
60°C
40°C
I
BOOST
OUT
[A]
I
I
N
PSDR0200
PSDR0400
N
2 4
4 6
Thermal Behavior
In the case of ambient temperatures above +60ºC, the output capacity has to
be reduced by 2.5% per Kelvin increase in temperature.
From +70°C or a thermal overload, the device reduces the output power for
its own protection, and returns to normal operation when it has cooled down.