MODEL PAXLHV - PAX LITE AC VOLTAGE MONITOR
3-DIGIT, 0.56" (14.2 mm) HIGH RED LED DISPLAY AUTO ZEROING CIRCUIT NEMA 4X/IP65 SEALED FRONT BEZEL OPTIONAL CUSTOM UNITS OVERLAY W/BACKLIGHT UP TO 600 VAC MAX
Bulletin No. PAXLHV-C Drawing No. LP0568 Released 12/09
U
R
C
L
US LISTED
IND. CONT. EQ.
51EB
GENERAL DESCRIPTION
The Model PAXLHV is designed for AC voltage monitoring. The half-wave rectified input signal is calibrated to indicate the RMS value of a pure sinusoidal wave-form. The front bezel meets NEMA 4X/IP65 requirements when properly installed.
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
CAUTION: Risk of electric shock.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
DEFINITION OF TERMS
INSTALLATION CATEGORY (overvoltage category) I:
Signal level, special equipment or parts of equipment, telecommunication, electronic, etc. with smaller transient overvoltages than Installation Category (overvoltage category) II.
INSTALLATION CATEGORY (overvoltage category) II:
Local level, appliances, portable equipment, etc. with smaller transient overvoltages than Installation Category (overvoltage category) III.
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is
2.1" (53.4) H x 5.0" (127) W.
1
TABLE OF CONTENTS
Ordering Information . . . . . . . . . . . . . . . . . . . .2
General Meter Specifications . . . . . . . . . . . . .3
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . .3
ORDERING INFORMATION
Meter Part Numbers
PAXL
HV 0
0
Installing the Meter . . . . . . . . . . . . . . . . . . . . . 4
Setting the Switches . . . . . . . . . . . . . . . . . . . . 4
Wiring the Meter . . . . . . . . . . . . . . . . . . . . . . . 5
HV - AC Voltage Input
Accessories Part Number
TYPE PART NUMBERSDESCRIPTIONMODEL NO.
PAXLBK30Units Label Kit Accessory PAXLBKAccessories
2
GENERAL METER SPECIFICATIONS
1. DISPLAY: 3-digit, 0.56" (14.2 mm) high character, 7-segment Red LED
2. POWER: 115 or 230 VAC, switch selectable. Allowable power line variation
±10%, 50/60 Hz, 6 VA. Installation Category II, Pollution Degree 2.
Isolation: 2300 Vrms for 1 min. to input Working Voltage: 300 V max., CAT II
3. ACCURACY: At 23°C, 85% R.H.; ±(0.1% of Reading + 2 digits)
4. INPUT IMPEDANCE: 1 M
5. INPUT RANGE: 0 to 600 VAC max. @ 45 to 500 Hz. Installation Category I
6. RESOLUTION: 1 VAC
7. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0° to 60°C Storage Temperature Range: -40° to 80°C Operating and Storage Humidity: 85% max. relative humidity (non-
condensing)
Temperature Coefficient: ±150 PPM/°C Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
direction for 1.5 hours, 2 g’s.
Shock According to IEC 68-2-27: Operational 30 g’ s, 11 msec in 3 directions. Altitude: Up to 2000 meters
8. READING RATE: 400 msec., nominal
9. RESPONSE TIME: 1 sec. nominal for a step change input.
10. CERTIFICA TIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL61010A-1, CSA C22.2 No. 61010-1
Recognized to U.S. and Canadian requirements under the Component Recognition Program of Underwriters Laboratories Inc.
UL Listed, File #E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Report #04ME11209-20041018
Issued by Underwriters Laboratories, Inc. IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY:
Emissions and Immunity to EN 61326: Electrical Equipment for
Measurement, Control and Laboratory use.
Immunity to Industrial Locations:
Criterion AEN 61000-4-2Electrostatic discharge 4 kV contact discharge 8 kV air discharge Criterion B EN 61000-4-3Electromagnetic RF fields 10 V/m Criterion AEN 61000-4-4Fast transients (burst) 2 kV power 2 kV signal Criterion AEN 61000-4-5Surge 1 kV L-L, 2 kV L&N-E power Criterion AEN 61000-4-6RF conducted interference 3 V/rms Criterion AEN 61000-4-11Voltage dip/interruptions
0.5 cycle; 40 % variation
Emissions:
Class BEN 55011Emissions
Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self­recovers.
11. CONNECTIONS: High compression cage-clamp terminal block Wire Strip Length: 0.3" (7.5 mm) Wire Gage: 30-14 AWG copper wire Torque: 4.5 inch-lbs (0.51 N-m) max.
12. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use. Installation Category II, Pollution Degree 2. One piece bezel/case. Flame resistant. Panel Gasket and mounting clip included.
13. WEIGHT: 0.65 lbs. (0.24 Kg)
ACCESSORIES
UNITS LABEL KIT (PAXLBK)
Each meter has a units indicator with backlighting that can be customized
using the Units Label Kit. The backlight is controlled by a DIP switch.