Red Lion PAXDP Technical Data

PAXDP Modbus Register Table REVISED 12/03/12 LP0916A
1
For Input Registers, replace the 4xxxx with a 3xxxx in the below register address. The 3xxxx are a mirror of the 4xxxx Holding Registers.
2
An attempt to exceed a limit will set the register to its high or low limit value.
REGISTER
ADDRESS
1
REGISTER NAME
LOW
LIMIT
HIGH
2
LIMIT
2
FACTORY
ACCESS COMMENTS
FREQUENTLY USED REGISTERS
40001 Input A Relative Value (Hi word) 40002 Input A Relative Value (Lo word) 40003 Input B Relative Value (Hi word) 40004 Input B Relative Value (Lo word) 40005 Calculation Value (Hi word) 40006 Calculation Value (Lo word) 40007 Maximum Value (Hi word) 40008 Maximum Value (Lo word) 40009 Minimum Value (Hi word) 40010 Minimum Value (Lo word) 40011 Total Value (Hi word) 40012 Total Value (Lo word) 40013 Setpoint 1 Value (Hi word) 40014 Setpoint 1 Value (Lo word) 40015 Setpoint 2 Value (Hi word) 40016 Setpoint 2 Value (Lo word) 40017 Setpoint 3 Value (Hi word) 40018 Setpoint 3 Value (Lo word) 40019 Setpoint 4 Value (Hi word) 40020 Setpoint 4 Value (Lo word)
40021 Setpoint Output Register (SOR) 0 15 N/A
N/A N/A N/A Read Only
N/A N/A N/A Read Only
N/A N/A N/A Read Only Calculation Result of Math Function
-19999 99999 N/A Read/Write
-19999 99999 N/A Read/Write
-199999000 999999000 N/A Read/Write
-19999 99999 100 Read/Write
-19999 99999 200 Read/Write
-19999 99999 300 Read/Write
-19999 99999 400 Read/Write
Read/Write
See Note
40022 Manual Mode Register (MMR) 0 31 0 Read/Write
40023 Reset Output Register 0 15 0 Read/Write
40024 Analog Output Register (AOR) 0 4095 0 Read/Write
40025 Input A Absolute Value (Hi word) 40026 Input A Absolute Value (Lo word) 40027 Input B Absolute Value (Hi word) 40028 Input B Absolute Value (Lo word) 40029 Input A Offset Value (Hi word) 40030 Input A Offset Value (Lo word) 40031 Input B Offset Value (Hi word) 40032 Input B Offset Value (Lo word) 40033 Main Setpoint 1 Value (Hi word) 40034 Main Setpoint 1 Value (Lo word) 40035 Main Setpoint 2 Value (Hi word) 40036 Main Setpoint 2 Value (Lo word) 40037 Main Setpoint 3 Value (Hi word) 40038 Main Setpoint 3 Value (Lo word) 40039 Main Setpoint 4 Value (Hi word) 40040 Main Setpoint 4 Value (Lo word)
N/A N/A N/A Read Only
N/A N/A N/A Read Only
-19999 99999 0 Read/Write
-19999 99999 0 Read/Write
-19999 99999 100 Read/Write Setpoint List A
-19999 99999 200 Read/Write Setpoint List A
-19999 99999 300 Read/Write Setpoint List A
-19999 99999 400 Read/Write Setpoint List A
Process value of present input level. This value is affected by Input Type, Resolution, Scaling & Offset Value (Relative Value = Absolute Input Value + Offset Value)
Process value of present input level. This value is affected by Input Type, Resolution, Scaling & Offset Value (Relative Value = Absolute Input Value + Offset Value)
Status of Setpoint Outputs: Bit State: 0=Off, 1=On, Bit 3 = SP1, Bit 2 = SP2, Bit 1 = SP3, Bit 0 = SP4 Outputs can only be activated/reset with this register when respective bits in Manual Mode (MMR) register are set Bit State: 0=Auto Mode, 1=Manual Mode Bit 4 = SP1, Bit 3 = SP2, Bit 2 = SP3, Bit 1 = SP4, Bit 0 = Linear Output Bit State: 1= Reset Output; Bit is returned to zero following reset processing Bit 3 = SP1, Bit 2 = SP2, Bit 1 = SP3, Bit 0 = SP4 Functional only if Linear Output is in manual mode (MMR bit 0 = 1). Linear Output Card is written to only if Linear Out (MMR bit 0) is set Gross value of present Input A level. This value is affected by Input Type, Resolution, Scaling, but not affected by Offset Value
Gross value of present Input B level. This value is affected by Input Type, Resolution, Scaling, but not affected by Offset Value
Relative Input Value (standard meter value) is sum of Input Offset Value and Input Absolute Value
Relative Input Value (standard meter value) is sum of Input Offset Value and Input Absolute Value
REGISTER
ADDRESS
1
REGISTER NAME
40041 Alternate Setpoint 1 Value (Hi word) 40042 Alternate Setpoint 1 Value (Lo word) 40043 Alternate Setpoint 2 Value (Hi word) 40044 Alternate Setpoint 2 Value (Lo word) 40045 Alternate Setpoint 3 Value (Hi word) 40046 Alternate Setpoint 3 Value (Lo word) 40047 Alternate Setpoint 4 Value (Hi word) 40048 Alternate Setpoint 4 Value (Lo word)
LOW
LIMIT
HIGH
2
LIMIT
2
FACTORY
ACCESS COMMENTS
-19999 99999 100 Read/Write Setpoint List B
-19999 99999 200 Read/Write Setpoint List B
-19999 99999 300 Read/Write Setpoint List B
-19999 99999 400 Read/Write Setpoint List B
CH A CH B INPUT PARAMETERS SEE MODULE 1 FOR PARAMETER DESCRIPTIONS
40101 40201 Input Range 0 1 0 Read/Write 0 = Volt, 1 = Current, 2 = Volt Square Root Extraction, 3 = Current Square Root Extraction 40102 40202 ADC Conversion Rate (samples/sec) 0 6 3 Read/Write 0 = 5.3, 1 = 7.5, 2 = 16.7, 3 = 19.8, 4 = 20, 5 = 30, 6 = 105 40103 40203 Decimal Point 0 4 3 Read/Write 0 = 0, 1 = 0.0, 2 = 0.00, 3 = 0.000, 4 = 0.0000 40104 40204 Rounding Factor 0 6 0 Read/Write 0 = 1, 1 = 2, 2 = 5, 3 = 10, 4 = 20, 5 = 50, 6 = 100 40105 40205 Digital Input Filter 0 250 10 Read/Write 1 = 0.1 Second 40106 40206 Filter Band 0 250 10 Read/Write 1 = 1 display unit 40107 40207 Number of Scaling Points 2 16 2 Read/Write Number of Linearization Scaling Points 40108 40208 Reserved N/A N/A N/A N/A
Scaling Points Parameters
40109 40209 Input 1 Input Value (Hi word) 40110 40210 Input 1 Input Value (Lo word) 40 111 40211 Display 1 Input Value (Hi word) 40112 40212 Display 1 Input Value (Lo word)
thru thru . . . . . . . . . . . .
40169 40269 Input 16 Input Value (Hi word) 40170 40270 Input 16 Input Value (Lo word) 40171 40271 Input 16 Input Value (Hi word) 40172 40272 Input 16 Input Value (Lo word)
-19999 99999 0 Read/Write 1 = 0.001
-19999 99999 0 Read/Write
Registers 40113-40168, 40213-40268 not shown but follow ordering as shown for Input 1, Display 1
-19999 99999 0 Read/Write 1 = 0.001
-19999 99999 0 Read/Write
USER INPUT & FUNCTION KEY PARAMETERS SEE MODULE 2 FOR PARAMETER DESCRIPTIONS User Inputs
0 = NO 6 = d-HLd 12 = E-tot 18 = dSP-b 24 = r-2 30 = Print 1 = PLOC 7 = A-HLd 13 = r-HI 19 = dSP-C 25 = r-3
40301 User Input 1 Action 0 30 0 Read/Write
2 = A-rEL 8 = SYNC 14 = r-Lo 20 = dSP-_ 26 = r-4 3 = b-rEL 9 = bAt 15 = r-HL 21 = d-LEV 27 = r-34 4 = A-drL 10 = rtot1 16 = dISP 22 = LISt 28 = r-234 5 = b-drL 11 = rtot2 17 = dSP-A 23 = r-1 29 = r-ALL
40302 User Input 2 Action 0 30 0 Read/Write See User Input 1 above
Function Keys
0 = NO 4 = b-drL 8 = r-Lo 12 = r-1 16 = r-34
40303 User F1 Key Action 0 19 0 Read/Write
1 = A-rEL 5 = bAt 9 = r-HL 13 = r-2 17 = r-234 2 = b-rEL 6 = rtot 10 = d-LEV 14 = r-3 18 = r-ALL
3 = A-drL 7= r-HI 11 = LISt 15 = r-4 19 = Print 40304 User F2 Key Action 0 19 0 Read/Write See User F1 Key Description 40305 User Reset Key Action 0 19 0 Read/Write See User F1 Key Description 40306 User F1 Second Action 0 19 0 Read/Write See User F1 Key Description 40307 User F2 Second Action 0 19 0 Read/Write See User F1 Key Description
DISPLAY/QUICK PRO MENU LOCKS SEE MODULE 3 FOR PARAMETER DESCRIPTIONS
40311 Input A Display Lock 0 5 3 Read/Write 0 = Loc, 1 = Red, 2 = Disp _, 3 = Disp A, 4 = Disp B, 5 = Disp C 40312 Input B Display 0 5 4 Read/Write 0 = Loc, 1 = Red, 2 = Disp _, 3 = Disp A, 4 = Disp B, 5 = Disp C 40313 Calculation Display 0 5 5 Read/Write 0 = Loc, 1 = Red, 2 = Disp _, 3 = Disp A, 4 = Disp B, 5 = Disp C 40314 Maximum (Hi) Value 40315 Minimum (Lo) Value
0 5 0 Read/Write 0 = Loc, 1 = Red, 2 = Disp _, 3 = Disp A, 4 = Disp B, 5 = Disp C
Loading...