RATIONAL SCC TRAINING MANUAL

Edition 10-2008a
1
Training Manual
SCC Line
SelfCooking Center - Combi Master
All manuals and user guides at all-guides.com
all-guides.com
2
Edition 10-2008a
All manuals and user guides at all-guides.com
3
Edition 10-2008a
SCC Line
Edition 10 - 2008a
General hints:
Isolate the appliance from mains supply before opening the appliance
When working with chemicals, i.e. aggressive cleaning materials
always wear protective clothing, goggles and gloves!
After maintenance / repair the appliance must be checked for electric
safety in accordance with your national, state and local requirements!
Whenever working on any gas component like:
Gas valve, gas blower and / or changing connected type of gas a detailed
ue gas analysis MUST be done using adequate CO and CO2
measuring equipment! This shall ONLY be done by trained technicians!
Always check appliance for possible gas leakages!
All manuals and user guides at all-guides.com
4
Edition 10-2008a
Structure of serial number 6 CM Control Panel 7 CM Technique 8 Water level control Steam Generator 9 RATIONAL SC Automatic 10 Steam Control CM 11 Additional functions CM 12 CM PCB 14 Fan motor 40.00.274 15 CM - Sequence of events 16 Failure Codes CM 21 Service level CM 23 Software update CM units 31 Fault tree: Changing CM pcb / replace EEPROM 33
List of content
Part 1: CM
Part 2: SCC
SCC Control panel 35 Comparing display of software version 36 Display since software version SCC 02-01-01 37 CleanJet 41 Display Cleanjet +Care Index “G” (10-2008) 44 SCC Electric - Basic principle 45 Parts identification 46 General information to software version SCC 04-01-01 48 Difference SCC Index „E“ versus Index „G“ SCC Care Control 51 SCC pcb (42.00.002) 54 New I/O PCB SCC (42.00.064) 55 Fan motor SCC 40.00.274 56 Clima Plus Control SCC 57 SCC - Sequence of events 59 Service level SCC 65 Diagnostic mode SCC 67 Running Times SCC 73 Basic Settings 79 Function test SCC 87 Error code SCC 93 Flash SCC Software 98 SCC pcb change - EEPROM change 99 Download of unit service data 101 Download of HACCP data 105 Calibration SCC 107 Control Drain Valve 54.00.357 111
All manuals and user guides at all-guides.com
5
Edition 10-2008a
Gas burner principle 11 2 Gas Valve 113 Identification of gas burners / Gas blowers: 114 Sequence of events of Burner and Ignition control 115 CO
2
Values 116
CM Gas principle 117 Check Gas Type / Gas Conversion 118 Changing installation altitude: CM gas 119 Checking of dynamic input gas flow pressure 120 Flue gas analysis 121 Burner adjustment SCC - CM 07-2008 124 Changing Gas blower speed 125
SCC Gas principle 127 Gas conversion / fitting new gas valve 128 Adjustment of installation altitude above sea level 129 Checking of dynamic input gas flow pressure 130 Flue gas analysis 131 Burner adjustment SCC - CM 07-2008 134 Changing gas blower speed SCC Gas 135
Ultravent 136 Water info 140 Intruction for manual descaling 141 Installation and Commissioning checklist 146 COMMISSIONING CHECKLIST SCC / CM 146 Preventative maintenance 150
List of fault tree for SCC - CM 154
Circuit diagram Training 178
Part 3: GAS
Part 4: Common information
Part 5: Fault trees
Part 6: Circuit diagram Training
Part 7: Service reference
SCC Service Reference 196 CM Service Reference 198
All manuals and user guides at all-guides.com
6
Edition 10-2008a
Structure of serial number
Energy Unit size Model Version Year Month Serial
number
E - Electric
G - Gas
61 - 6x1/1GN
62 - 6x2/1GN 11 - 10x1/1GN 12 - 10x2/1GN 21 - 20x1/1GN 22 - 20x2/2GN
S - SCC
M - CM
E - initial unit
F only CM, new
pcb
G -SCC + CM
SCC Care Control
04 - 2004
10-2008
07 - Juli 7-digit
number
Energy Unit size Model Version Year Month Serial
number
E - Eletric
G - Gas
61 - 6x1/1GN
62 - 6x2/1GN 11 - 10x1/1GN 12 - 10x2/1GN 21 - 20x1/1GN 22 - 20x2/2GN
C - CPC
M - CM
D - CD
A - initial unit
B - new humidity
C - CleanJet, CDS
D - Motor control
03 - 2003 07 - Juli 4-digit
number until
12.1998 7-digit
number from
01.1999
C-Line Unit size Model Year Month Serial number
61 - 6x1/1GN 11 - 10x1/1GN 12 - 10x2/1GN 21 - 20x1/1GN 22 - 20x2/2GN
C - CCC
M - CCM
D - CCD
95 - 1995 05 - Mai 4-digit number
CD Unit size Model Year Month Serial number
00694071234 10194071234 20194071234 02094071234
14G94071234 21G94071234
06 - 6x1/1GN 11 - 10x1/1GN 21 - 20x1/1GN 22 - 20x2/2GN
C - CC
M - CM
CM 101Gas CM 201Gas
94 - 1994 07 - Juli 4-digit number
SCC Line: E 61 S E 04 07 2345678
from 04.2004
CPC Line: E 61 C B 03 07 2345678
from 06.1997 until 04.2004
C Line: C 61 C 95 05 1234
from 10.1993 until 05.1997
Classic Line: 06 M 94 07 1234
from 1986 until 05.1997
All manuals and user guides at all-guides.com
all-guides.com
7
CM
Edition 10-2008
Steam (100°C / 212°F)
Hot Air (30°C - 300°C / 86 - 572°F)
Combi Steam (30°C - 300°C / 86 - 572°F)
Low Temp. Steam (30°C - 99°C / 86 - 210°F)
Finishing (30°C - 300°C / 86 - 572°F)
Cool Down
Cabinet temperature display
Cabinet temperature setting
Timer
Set-Temp. -control
Gas: Reset key
Core temperature Set-Temp. -control
Timer - Core temperature display
Timer - Core temperature dial
CM Control Panel
All manuals and user guides at all-guides.com
8
CM
Edition 10-2008
CM Technique
B1 Thermocouple cabinet B2 Thermocouple quenching / Steam control B3 Thermocouple core temperature B5 Thermocouple steam generator (preheating, 180°C (356°F) max)
F3 Safety temperature limiter steam generator 160°C / 320°F F4 Safety temperature limiter cabinet 360°C / 680°F
Y1 Solenoid valve lling Y2 Solenoid valve quenching
M1 Fan motor (without jumper) M4 Pump SC-Automatic
S2 Level electrode S3 Door contact switch
CM 201/202 only: M2 Fan motor top (with jumper)
B1
B3
F4
M4
Y1
Y2
B2
M1
S2
B5
F3
S3
All manuals and user guides at all-guides.com
9
CM
Edition 10-2008
Water level control Steam Generator
V
AC
S2
M4
Y1
Y2
B2
S2
B5
F3
Center S2 ==> Ground: 2 - 6V AC: water level too low steam heating must switch OFF solenoid valve lling Y1 ON
Center S2 ==> Ground: 0V AC: water level reached steam heating can switch ON
solenoid valve  lling Y1 switched OFF
Every 2 minutes steam elements will switch off for water level control
PCB
X12
1 2 3 4
All manuals and user guides at all-guides.com
10
CM
Edition 10-2008
RATIONAL SC Automatic
During the production of steam, the concentration of minerals inside the steam generator will increase over time. These minerals settle on the heating elements and heat exchanger as well as the interior steam generator walls.
In order to reduce this effect the steam generator will be pumped off and  ushed regularly depending on the duration of steam production. This process needs approximately 45 seconds. After emptying the steam generator it will be  lled automatically with fresh water.
There are 4 conditions to start this SC Automatic:
1. Heating time of the steam generator must exceed 60 min.* (SCC Care Control: 120min) and
2. the temperature of the thermocouple inside steam generator (B5) must be below 65°C (149°F) and
3. the temperature of the thermocouple inside interior cabinet (B1) must be below 70°C (158°F) and
4. the unit is switched ON.
* - can be adjusted from 20-120min
In case the unit is used permanently the above mentioned temperature conditions can not be met.
In this case the following 2 conditions apply:
1. The heating time of the steam generator reaches the twice the set duration*, i.e. 120 min. and
2. the unit door is open for longer than 30 seconds
After completion of the SC-Automatic the accumulated steam heating time is re-set to zero.
SC-Automatic does not replace the need for descaling and/or installing water treatment lter
All manuals and user guides at all-guides.com
11
CM
Edition 10-2008
Y1
Y2
B2
B1
Steam Control CM
Intelligent steam control via quenching sensor
Temp.
t (s)
B1 - 100°C(212°F)
70°C
(158°F)
1. Filling of interior cabinet based on time and temperature control of B2 quenching sensor; (cabinet if fully  lled with steam and all sur- faces have reached steam temperature).
2. After steam saturation inside cabinet steam will also  ll quenching chamber
3. After reaching quenching temperature (B2) quenching solenoid Y2 will be activated.
Depending on the frequency of temperature raise of the quenching sensor B2 the duration of the next steam supply is calculated.
B2 temperature with partial load B2 temperature with full load
4. The amount of steam inside the cabinet is directly depending on the temperature varia- tion of quenching sensor B2.
Y1
Y2
B2
B1
Y1
Y2
B2
B1
All manuals and user guides at all-guides.com
all-guides.com
12
CM
Edition 10-2008
Additional functions CM
Below are listed the additionaly functions for the user / operator:
1. Cleaning program
1) Cool down cabinet below 60°C / 140°F
2) Spray inside cabinet with Rational cleaner
3) Close cabinet door
4) Select „Cool Down
5) Press core temperature key for 10 sec.
6) „CLEn“ will show in cabinet temperature display
7) Press timer key 1x; Cleaning program starts automatically (open cabinet door and rinse interior cabinet after 40 min.) Close door again. Since Software ver- sion C1-06-05 a 10 min step hot air will follow to dry the interior cabinet.
8) After end of program, leave cabinet door open over night.
2. Empty steam generator
1) Open cabinet door
2) Select „Cool Down“
3) Press core temperature key for 10 sec.
4) „CLEn“ will be shown in cabinet temperature display
5) Select „SC“ with temperature dial
6) Close water tap
7) Press timer key 1x and remain on „Cool Down“ position for about 45 sec.
3. Descaling program
1) Open cabinet door
2) Select „Cool Down“
3) Press core temperature key for 10 sec.
4) „CLEn“ will be shown in cabinet temperature display
5) Select „CALC“ with temperature dial
6) Press timer key 1x and follow procedure of the decalci cation instruction. (See user manual CM).
This should be done after each installation to verify free drain connection and prior to disconnection the unit for storage.
All manuals and user guides at all-guides.com
13
CM
Edition 10-2008
Additional functions CM
4. Changing temperature display from °C to °F
1) Select any mode
2) Press timer and core temperature key simultaneously for 10 sec. until Display changes from °C to °F or vice versa
3) Release both keys
Aborting of descaling program CM:
- Switch unit off and on again
- press core temperature key 1x
- remaining time of 20 minutes will be displayed. During this time the steam generator will be ushed and the unit will be operated in steam mode for a couple of minutes to eliminate all re- maining chemical residues.
All manuals and user guides at all-guides.com
14
CM
Edition 10-2008
X7
X19
X20
F1 F2
Transformer
0,1 AT
2 AT
1
1
X7
X19
X20
X18
X23
X31
RS 485
X8
X12
X26
X27
X32X24
X30
RS 232
X63
X3X4X6
X2
X50
2 AT
1
2
3
4
on
off
1
1
1
1
1
1
1
F6.1
F6.1
2 AT
2 AT
X16
X16
F6
F6
42.00.004
42.00.047
X2 B3 Core temperature
X3 B1 Interior cabinet
X4 B2 Quenching / Steam control
X6 B5 Steam generator
X7 ON - OFF switch
X8 Buzzer
X12 Level electrode
X 16 power supply from transformer (42.00.047)
X18 SC - pump
X19 Solenoid valves
X20 Energy management system / Sicotronic
X23 Vent hood (signal door open / closed)
X24 SSR
X26 SSR pulsing (USA version only)
X27 Door contact switch
X30 Serial interface (RS232)
X31 BUS interface
X32 Timer / Core Temp. Potentiometer
X50 external EEPROM
X63 Not used
Since February 2006 PCB 42.00.004 is replaced by 42.00.047. (Conversion kit: 87.00.139, pls. see Technical info 04-2006)
The transformer on the new PCB 42.00.047 is no more existing and replaced by external transformer 40.00.227
CM PCB
1
Temperatur
Poti
42.00.004 from 04-2004 ---- 42.00.047 from 02-2006
Counting sequence
All manuals and user guides at all-guides.com
15
CM
Edition 10-2008
Fan motor 40.00.274
Jumper 40.01.581 is used on  oor model 201 and 202 for top position motor only!
Jumper is not used on models 61 - 102 with one motor only!
If jumper is not set correctly E12 will be displayed!
LED code fan motor SCC and CM from 04/2004
Reason Remedy
1x Motor doesn’t start, no changing
signal from hallsensor
Check for motor blockage or change motor.
2x Voltage too low on motor pcb Check supply voltage or
change motor.
3x Voltage too high on motor pcb Check supply voltage or
change motor.
4x rpm measurement defective Change motor.
5x Motor pcb temperature >105°C Check cooling system (cooling fan, air
intake  lter), otherwise change motor
6x Supply voltage <80V Check power supply
(F1-F2)
7x Motor pcb defective Change motor.
8x Motor pcb defective Change motor.
Units 3AC400-480V (without neutral) are equipped with motor 40.00.276 (3-phase supply)
This motor is equipped with a 4 pole plug for the supply voltage.
LED
Jumper
All manuals and user guides at all-guides.com
16
CM
Edition 10-2008
Function Step Responsible sensor
1. Select Steam mode
2. Select time or core temperature
3. Close cabinet door Reed switch S3
4. Check water level inside steam generator Level electrode S2 inside Steam Generatorr
5. Time based preheating of steam generator, Thermocouple B5 inside Steam Generator if B5 is below 85°C (185°F);
6. Timer starts after successful preheating Logic on PCB (blinking dot in Display)
7. Steam supply up to steam saturation Quenching sensor B2 inside cabinet (Steam control)
8. Hot Air supply (only 50%) when set Cabinet sensor B1 temperature (100°C/212°F) can not be reached in time by Steam alone
9. Quenching (set to 70°C/158°F) Quenching sensor B2
CM - Sequence of events
Mode: Steam 100°C (212°F), Temp. preset, not adjustable
B1
B3
F4
M4
Y1
Y2
B2
M1
S2
B5
F3
S3
All manuals and user guides at all-guides.com
all-guides.com
17
CM
Edition 10-2008
CM - Sequence of events
Mode: Low temperature steam; Temp. range 30-99°C (86-210°F)
Function Step Responsible sensor
1. Select Low temperature steam mode
Set temperature 30-99°C (86-210°F)
2. Select time or core temperature
3. Close cabinet door Reed switch S3
4. Check water level inside steam generator Level electrode S2 inside Steam Generatorr
5. Time based preheating of steam generator, Thermocouple B5 inside Steam Generator
if B5 is below 85°C (185°F);
6. Timer starts after successful preheating Logic on PCB
(blinking dot in Display)
7. Steam supply until set temperature Cabinet sensor B1
inside cabinet is reached
8. Hot Air supply (only 50%) when set Cabinet sensor B1
temperature can not be reached in time by Steam alone
9. Quenching (set to 70°C/158°F) Quenching sensor B2
Note: Reduction of fan motor speed In case the actual temperature is 2°C / 4°F higher than the set temperature for longer than 2
minutes, the fan speed will be reduced automatically.
B1
B3
F4
M4
Y1
Y2
B2
M1
S2
B5
F3
S3
All manuals and user guides at all-guides.com
18
CM
Edition 10-2008
Function Step Responsible sensor
1. Select Combi mode Set temperature 30-300°C (86-572°F)
2. Select time or core temperature
3. Close cabinet door Reed switch S3
4. Check water level inside steam generator Level electrode S2 inside Steam Generatorr
5. Time based preheating of steam generator, Thermocouple B5 inside Steam Generator if B5 is below 85°C (185°F);
6. Timer starts after successful preheating Logic on PCB (blinking dot in Display)
7. Hot Air supply until set temperature Cabinet sensor B1 inside cabinet. Hot air has priority
8. Steam supply up to steam saturation Quenching sensor B2 inside cabinet (Steam Control)
9. Quenching (set to 70°C/158°F) Quenching sensor B2
Note: Reduction of fan motor speed In case the actual temperature in the range of 30-99°C (86 - 210°F) is 2°C / 4°F higher than the set temperature for longer than 2 minutes, the fan speed will be reduced automati- cally.
CM - Sequence of events
Mode: Combination; Temp. range 30-300°C (86-572°F)
B1
B3
F4
M4
Y1
Y2
B2
M1
S2
B5
F3
S3
All manuals and user guides at all-guides.com
19
CM
Edition 10-2008
F
CM - Sequence of events
Mode: Finishing; Temp. range 30-300°C (86-572°F)
Function Step Responsible sensor
1. Select Finishing mode Recommended temperature
30-300°C (86-572°F)
2. Select time or core temperature
3. Close cabinet door Reed switch S3
4. Check water level inside steam generator Level electrode S2 inside Steam Generator
5. Time based preheating of steam generator, Thermocouple B5 inside Steam Generator if B5 is below 85°C (185°F);
6. Timer starts after successful preheating Logic on PCB (blinking dot in Display)
7a. Electric units: alternating 12 sec. Hot Air Cabinet sensor B1 6 sec. Steam Quenching sensor B2
7b Gas units: alternating 30 sec. Hot Air Cabinet sensor B1 15 sec. Steam Quenching sensor B2
8. Quenching (set to 70°C/158°F) Quenching sensor B2
Note: Reduction of fan motor speed
In case the actual temperature in the range of 30-99°C (86 - 210°F) is 2°C / 4°F higher than the set temperature for longer than 2 minutes, the fan speed will be reduced automati-
cally.
B1
B3
F4
M4
Y1
Y2
B2
M1
S2
B5
F3
S3
All manuals and user guides at all-guides.com
20
CM
Edition 10-2008
CM - Sequence of events
Mode: Hot Air; Temp. range 30-300°C (86-572°F)
Function Step Responsible sensor
1. Select Hot Air mode Set temperature 30-300°C (86-572°F)
2. Select time or core temperature
3. Close cabinet door Reed switch S3
4. Timer starts immediately Logic on PCB
5. Hot Air supply unitl set temperature Cabinet sensor B1 is reached
6. Quenching (set to 90°C/194°F) Quenching sensor B2
Note: Reduction of fan motor speed
In case the actual temperature in the range of 30-99°C (86-210°F) is 2°C / 4°F higher than the set temperature for longer than 2 minutes, the fan speed will be reduced automatically.
B1
B3
F4
M4
Y1
Y2
B2
M1
S2
B5
F3
S3
All manuals and user guides at all-guides.com
21
CM
Edition 10-2008
Failure Codes CM
The following error codes are shown to the operator: For showing information of the cabinet display press core temperature key
Time
display
Cabinet
display
Failure explanation Description / remedy
H2O open Lack of water / open water tap
Change Polarity Phase / Neutral (only gas units)
Reset Gas Flame detection after ignition faulty
external EEPROM Not initialised
Timeout of external power optimising system
Heating blocked by the extern. energy- optimising system for longer 2 min.
B1 Interior cabinet sensor Sensor broken
B2 Quenching sensor Sensor broken
B3 Core sensor Sensor broken
B5 Sensor steam generator Sensor broken
Thermocouple on PCB Sensor broken
Poti interior cabinet Defective
Poti timer/core temperature Defective
external EEPROM Defective
Mode switch
After 5 sec switching on the unit, a cooking mode couldn‘t be identi ed
Fan motor 1 (bottom) Fan motor 1 (bottom) Fan motor 2 (top) Fan motor 2 (top)
St = Status (probably Motor defect) Co = Communication, (Bus failure)
M4 SC-pump Mal function
Solenoid valve  lling Y1 (failure can only occur during the descaling program)
Mal function
PCB temperature above 85°C (185°F)
Steam generator Temperature B5 above 180°C (356°F)
Steam generator Temperature B5 below -5°C (23°F)
Interior cabinet temp. Temperature B1 above 340°C (644°F)
Free
All manuals and user guides at all-guides.com
all-guides.com
22
CM
Edition 10-2008
Failure Codes CM (cont.)
For showing information of the cabinet display press core temperature key
Time
display
Cabinet
display
Failure explanation Description / remedy
Ignition box 1 Ignition box 2 Ignition box does not reply, Bus failure
Ignition box 1 Steam Ignition box 1 Hot air Ignition box 2 Hot air
Ignition box defective (change box)
Ignition box 1 Steam Ignition box 1 Hot air Ignition box 2 Hot air
Testing of ignition and monitoring necessary
Free
EEPROM
Actual data structure of the EEPROM does not match with the software; flash pcb first
All manuals and user guides at all-guides.com
23
CM
Edition 10-2008
Service level CM
1) Switch unit ON
2) On operator PCB set DIP switch 1 to „ON“ position
3) Select service package with timer dial:
Diagnostic Program
Error code history
Running times
Basic settings
4)
Activate with core temperature key the desired service package
5) Select with timer dial the desired step
6) Activate selected step by pressing timer key
7)
To de-activate service package set DIP switch 1 to „OFF“ position
.
Function Test
1) Switch unit ON
2) On operator PCB set DIP switch 3 to „ON“ position
First step of function test is displayed.
3) Select desired step of function test with timer dial
4) Activate preselected step by pressing timer key
5) Activate selected function step with core temperature key
6)
To de-activate function test set DIP switch 3 to „OFF“ position
.
X7
X19
X20
F1 F2
Transformer
0,1 AT
2 AT
1
1
X7
X19
X20
X18
X23
X31
RS 485
X8
X12
X26
X27
X32X24
X30 RS 232
X63
X3X4X6
X2
X50
2 AT
1
2
3
4
on
off
1
1
1
1
1
1
1
F6.1
F6.1
2 AT
2 AT
X16
X16
F6
F6
42.00.004
42.00.047
1
234
on
1
234
on
1
234
on
1
234
on
All manuals and user guides at all-guides.com
24
CM
Edition 10-2008
Service level: dP -- Diagnostic Program
Description Connection
Cabinet Display
Time display
Software Version
Software
Version: C - 1
Software
07.01
B1 Cabinet sensor X 3 actual value max value
Reset by pressing for 5 sec.
B2 Quenching sensor X 4 actual value max value
Reset by pressing for 5 sec.
B3 Core sensor X 2 actual value max value
Reset by pressing for 5 sec.
B5 Steam generator sensor
X 6 actual value max value
Reset by pressing for 5 sec.
PCB temperature actual value max value
Reset by pressing for 5 sec.
S3 Door contact X27:(1-2) 1 - 0
0 = door open 1 = door closed
S2 Water level steam generator
X12:(1-4) S2 X19:(1-3) Y1
S2: 0 - 1 Y1: 1 - 0
Steam elements 0 - off; 1 - 50%; 2 - 100%
actual Temp.
B5
0 - 1 - 2
Hot Air elements 0 - off; 1 - 50%; 2 - 100%
actual Temp.
B1
0 - 1 - 2
Speed fan motor bottom BUS Set rpm actual rpm
Speed fan motor top BUS Set rpm actual rpm
only  oor model 201/202
Energy management (Sicotronic)
X 20 1 - 0
SSR control (US version)
X24
1 - 0 0 = US version only
Unit size and type
61 - 202 ELE - GAS
Flame current Steam x.x A*
since SW Version: C1-06-05 ( ame current)
Flame current Hot air top
Hot air top
x.x A*
since SW Version: C1-06-05 ( ame current)
Flame current Hot air bottom
Hot air bottom
x.x A*
since SW Version: C1-06-05 ( ame current)
*
With SW Version C1-06-05 the  ame current will show as 20-24A
(This value must be divided by 4 to get the correct  ame current e. g. 22:4 = 5,5A.) Starting with SW version C1-07-01 the actual  ame current is shown .
+
+
+
+
+
All manuals and user guides at all-guides.com
25
CM
Edition 10-2008
Service Level: ER -- Error code history
Since software version C1-07-01 the last 10 general error messages are shown (applies for electric and gas models)
Er When timer key is pressed the error code will be displayed. i.e.:
Error number Error Code Description
Er1 3 B1 Cabinet sensor defective Er2 14 Y1 Filling solenoid defective Er3 ---- ER10
Gas error GE: (gas units only!)
Since software version C1-07-01 the last 16 gas error messages (GE11 - GE26) are shown in addition to the general error messages. These error codes are generated by the ignition box
Error number Error Code Description
GE11 20 No rpm signal GE12 32 No  ame after 5 ignition sequences GE13 --- GE26
Indication of ignition box error messages (1-32 is shown to the operator as „rES“):
1 Hot air or Steam no gas, gas valve or electrode defective 14 Hot air gas valve control, change ignition box 19 Hot air no  ame because  ame current is too low check burner setting,  ame current, ignition cable and plug 20 Hot air wrong or no rpm signal from gas blower check gas blower, power supply gas blower and control harness of gas blower 22 Hot air no  ame after 5 ignition sequences no gas, gas valve or electrode defective 24 Steam gas valve control, change ignition box 29 Steam no  ame because  ame current is too low check burner setting,  ame current, ignition cable and plug 30 Steam wrong or no rpm signal from gas blower check gas blower, power supply gas blower and control harness of gas blower 32 Steam no  ame after 5 ignition sequences no gas, gas valve or electrode defective
Possible failure in case of „E21“
33, 36 Change ignition box 35 Check frequency of main 39 Hot air Check burner setting, ignition electrode and distance, and  ame current 40 Hot air Check ignition cable 42 Steam Check burner setting, ignition electrode and distance, and  ame current 43 Steam Check ignition cable
Is shown on display „CHnG PoL“
34 Change polarity of mains
All other numbers (2-13, 15-18, 21, 23, 25-28, 31): change ignition box
All manuals and user guides at all-guides.com
26
CM
Edition 10-2008
Service Level: rt -- Running Time
Description Timer display: 1-999
Temp. display: >1000
Comment
Total S3 door openings number
Reset by pressing for 5 sec.
Total time Y1 valve  lling min
Reset by pressing for 5 sec.
Total time Y2 valve quenching min
Reset by pressing for 5 sec.
Total time M4 SC-pump min
Reset by pressing for 5 sec.
Total time steam heating time hrs
Reset by pressing for 5 sec.
Total time hot air heating time hrs
Reset by pressing for 5 sec.
Total time steam mode hrs Can not be reset
Total time hot air mode hrs Can not be reset
Total time combination mode hrs Can not be reset
Total time vario steam mode hrs Can not be reset
Total time  nishing mode hrs Can not be reset
Total time cleaning program hrs Can not be reset
Total running time unit hrs Can not be reset
+
+
+
+
+
+
All manuals and user guides at all-guides.com
all-guides.com
27
CM
Edition 10-2008
Service level: SE -- Basic settings
Switch unit OFF and ON again after any changes made!
Select desired step with timer dial (fan motor and heating elements are automatically OFF)
Activate selected step with timer key
Steam heating time since last SC-Automatic
Press time and core key simultaneously for 5 seconds to set steam heating time (SE2) to preset steam heating time plus 1 minute (default 45+1min) => test function for SC-Automatic
Preset Steam heating time until SC-Automatic (default 60min)
Press time key and adjust preset steam heating time from 20 - 120 minutes with timer dial
Flushing time SC-Automatik (default 45 seconds)
Press time key and adjust  ushing time of SC-Automatik from 30 - 90 seconds with timer dial
Operation SC pump (oFF - continuous or on - pulsing)
Press time key and select „on“ or „oFF“ with timer dial
Show mode (on - oFF) SHO
Press time key and select „on“ or „oFF“ with timer dial
Setting new gas type (G20, G25, G30, G31, 13A)
Press time key, keep it pressed and select new gas type with timer dial
Con rm new gas type by pressing core temperature key once. Corresponding gas blower speed is automatically adjusted NOTE: After changing gas type a waste gas analysis must be carried out in the func- tion test.
Presetting of CO2 screw in mm on gas valve after gas type modi cation / changing gas valve
Press time key, keep it pressed and select with timer dial “ST“ for steam, “HA1“ for hot air top or “HA2“ for hot air bottom (only 201/202) with timer dial; Average lenght in mm of CO
2
screw on gas valve is shown on timer display
+
+
+
+
+
+
+
All manuals and user guides at all-guides.com
28
CM
Edition 10-2008
Service level: SE -- Basic settings
Adjustment of installation altitude above sea level (since SW C1-06-05) - 500m - 4500m
Press time key, keep it pressed and select installaton altitude in 500m steps by timer dial. Con rm altitude setting by pressing simultaneously core temperature key once
Adjusting speed of blower motor steam (+/ -10%) (After blower speed adjustment the original rpm is shown in the temp. display, the changed rpm is shown in the time display)
Press time key, keep it pressed and adjust displayed rpm with timer dial SE9 = MIN rpm; SE10 = Start rpm; SE11 = MAX rpm NOTE: After changing speed of blower motor a waste gas analysis MUST be carried out in the function test.
Adjusting speed of blower motor hot air top (+/ -10%) (After blower speed adjustment the original rpm is shown in the temp. display, the changed rpm is shown in the time display)
Press time key, keep it pressed and adjust displayed rpm with timer dial SE12 = MIN rpm; SE13 = Start rpm; SE14 = MAX rpm NOTE: After changing speed of blower motor a waste gas analysis MUST be carried out in the function test.
Adjusting speed of blower motor hot air bottom (+/ -10%) (After blower speed adjustment the original rpm is shown in the temp. display, the changed rpm is shown in the time display)
Press time key, keep it pressed and adjust displayed rpm with timer dial SE15 = MIN rpm; SE16 = Start rpm; SE17 = MAX rpm NOTE: After changing speed of blower motor a waste gas analysis MUST be carried out in the function test.
+
+
+
+
All manuals and user guides at all-guides.com
29
CM
Edition 10-2008
Service level: F -- Function test
NOTE: In Function test components are NOT protected against overload!
Set DIP switch 3 to „ON“ position!
Function Connection
PCB
Cabinet
display
Time
display
Comment
Steam 50%, Electric unit X24:(1-2)
actual temp.B5
steam generator
1 / 0
Gas: no function
Steam 100% Electric unit
X24:(1-2)+(5-6)
actual temp.B5
steam generator
1 / 0
Gas: no function
Hot air 50% Electric unit
X24:(7-8)
actual temp.B1
cabinet
1 / 0
Gas: no function
Hot air 100% Electric unit
X24:(7-8)+(3-4)
actual temp.B1
cabinet
1 / 0
Gas: no function
Steam Gas unit BUS
actual temp.B5
B5 Dampfgenerator
1 / 0
Electric: no function
Hot air top Gas unit
BUS
actual temp.B1
cabinet
1 / 0
Electric: no function
Hot air bottom Gas unit
BUS
actual temp.B1
cabinet
1 / 0
Electric: no function
Bottom Motor MAX rpm
BUS Set rpm Act. rpm
Bottom Motor MIN rpm
BUS Set rpm Act. rpm
Top Motor MAX rpm
BUS Set rpm Act. rpm
Top Motor MIN rpm
BUS Set rpm Act. rpm
Solenoid valve quenching
X19:(2-4)
actual temp.
B2 quenching
Y2
1 / 0
Solenoid valve lling
X19:(1-3) Level electrode
S2, 1 / 0
Y1
1 / 0
SC Pump
X18:(1-2) M4 X12:(1-4) S2
Level electrode
S2, 1 / 0
M4
1 / 0
Buzzer X8:(1-2) 1 / 0
All Displays / LED
Relais Ultravent (door open / close)
X 23: (1-2-3) 1 / 0
only existing with connected UV
no function
All manuals and user guides at all-guides.com
30
CM
Edition 10-2008
Service Level: F -- Function Test
Note: In function test components are NOT protected against overload!
Set DIP switch 3 to „ON“ position!
Function Connection
I/O pcb
Cabinet
display
Time
Display
Comment
Gas blower Steam MIN rpm
BUS actual rpm Set CO
2
Check CO2 value
Gas blower Steam Start rpm
BUS actual rpm
Gas blower Steam MAX rpm
BUS actual rpm Set CO
2
Adjust CO2 value with CO
2
screw
Gas blower Hot air top MIN rpm
BUS actual rpm Set CO
2
Check CO2 value
Gas blower Hot air top Start rpm
BUS actual rpm
Gas blower Hot air top MAX rpm
BUS actual rpm Set CO
2
Adjust CO2 value with CO
2
screw
Gas blower Hot air bottom MIN rpm
BUS actual rpm Set CO
2
Check CO2 value
Gas blower Hot air bottom Start rpm
BUS actual rpm
Gas blower Hot air bottom MAX rpm
BUS actual rpm Set CO
2
Adjust CO2 value with CO
2
screw
All manuals and user guides at all-guides.com
Loading...
+ 170 hidden pages