RAIN BIRD DAS-075 ASVF 3, DAS-100 ASVF 1 Operation Manual

ANTI-SIPHON VALVE
OPERATION MANUAL: DAS-075 / ASVF 3/4” DAS-100 / ASVF 1”
For use with all standard sprinkler controllers with 24 volt AC out­put. The DAS / ASVF valves are diaphragm anti-siphon valves with flow control and atmospheric vacuum breaker.
NOTE: These Rain Bird valves are designed for use with static water pressures of a MAXIMUM of 150 PSI. For higher pressures, a pressure regulator should be installed. These valves are for outdoor watering use only.
For dirty water systems-using wells, lakes, ditches, etc. for your water supply, be sure to install a 100 mesh (or finer) wire filter or screen filter before the electric valves. For use in cold water, less than 110°F (43.3°C), applications only.
ANTI-SIPHON VALVES FOR BACKFLOW PREVENTION
The DAS/ASVF models meet or exceed most building code requirements for connecting a sprinkler system to a city water supply.
These valves prevent the possibility of back siphoning of water from sprinkler lines into the drinking water.
The anti-siphon valves must be installed at least 6 inches above the highest sprinkler or elevated piping in the circuit to meet most codes, (See Diagram 1). (Consult local building code.)
CAUTION: Do not use this anti-siphon valve as a main line backflow device, nor as a master valve. It is not designed nor approved to be under constant wa­ter pressure on both sides of valve. This valve must not be operated continu­ously for more than twelve (12) hours. Do not install any other valves down stream. If installed incorrectly with constant pressure on both sides of valve, it is possible that the valve will fail or burst.
#1
Outlet to Sprinklers
Wires to Controller
Test this connection for water tightness before attaching outlet pipe.
6”
6”
Inlet
The valve must be mounted at least six inches above the highest sprinkler on the circuit.
HOW TO SELECT THE RIGHT VALVE SIZE
The valve size (3/4" or 1 ") is determined by the water flow (measured in gallons per minute, or GPM) of the main line or the sprinkler circuit.
3/4" VALVES: 13 GPM or less. 1" VALVES: 14 GPM or more.
1 " valves and pipes allow longer runs and more sprinkler heads per circuit, as well as potentially reducing the total number of valves required.
ASSEMBLY OF SPRINKLER VALVES TO PIPE
A sprinkler system is made up of one or more groups of sprinklers (called circuits) each operated by its own control valve. Study the illustrations and follow the instructions for proper assembly.
1
1. Before connecting and testing the assembly, thor­oughly flush the main line to prevent debris from dam­aging the valves.
2. On the inlet side of the control valve, use galvanized steel pipe or thick-walled, Schedule 40 PVC, white plastic pipe, as this pipe is under constant pressure. On the outlet side of the control valve, thin-walled PVC pipe or flexible potyethylene pipe may be used.
3. To assure a watertight connection, use only one to two turns of Teflon tape on the threaded valve-to-pipe con­nections. DO NOT USE PIPE SOLVENT (CEMENT) OR PIPE DOPE. THIS MAY DAMAGE THE VALVE. DO NOT OVER-TIGHTEN. Screw adapters into place finger tight. Tighten adapters one to two additional turns.
4. Install a master shutoff valve before all electric valves, so that the water can be conveniently turned off if a valve needs servicing.
5. When grouping valves, allow sufficient spacing be­tween valves to unscrew the valve from the pipe (about 6 inches).
6. Do not connect the outlet side (piping to sprinkler heads) without first testing for leaks. If the outlet side is connected and there is a leak, the pipe would have to be cut in order to tighten the connection.
VALVE OPERATION
Your Rain Bird valve offers two features with which you should become familiar.
FLOW CONTROL: This feature allows you to control the amount of water going to your sprinklers. To allow more water through the valve, turn the black knob counter clockwise UNTIL RESISTANCE IS FELT. This is fully open position.
To reduce the amount of water, turn the black knob clock­wise. If you keep turning, you can turn the valve all the way off. In this case, the valve will not open.
MANUAL CONTROL: This allows you to override your automatic controller and turn your sprinklers on AT THE VALVE. The valve can be turned on manually with the external bleed screw or with the internal solenoid bleed. The solenoid (block cylinder with wires) is wired to your controller and turns the valve off and on electronically.
To operate manually with the internal bleed, turn the solenoid 1/4 turn counterclockwise; this opens the valve. The sprinklers will continue to run until you turn the solenoid back in the clockwise direction(snugly), but do not over-tighten.
To turn on (open) the valve with the external bleed, turn the external bleed screw counterclockwise, 1/2 turn. Wa­ter will exit the external bleed while the valve is on. To turn off the valve, turn the external bleed screw clockwise until snug. Do not over-tighten.
TO OPERATE YOUR VALVE ELECTRONI­CALLY, BE SURE THE SOLENOID IS TURNED ALL THE WAY TO THE CLOCKWISE POSI­TION.
CONNECTION, TESTING AND WIRING THESE VALVES
1. Shut off the water main or the master shutoff valve and connect the valve or valve assembly to the main supply pipe. Be sure the water lines are flushed and clean.
2. Test the pipe and valve connections for water tightness as follows:
A. Turn the flow control clockwise (down) to off before turning on the water supply.
B. Turn on the water and check for leaks.
3. Now complete the hookup by connecting the outlet pipes from the valves to the sprinklers.
4. Set flow control adjustment before making wiring con­nections.
5. WIRE CONNECTIONS (Diagram 2). Use 18 gauge wire to connect the wires to the controller. Wiring that is to be buried alongside the pipes should be AP­PROVED for UNDERGROUND use. For all splices, use water tight connectors. (Do not exceed 600 ft.)
Each valve has two wires. Either one may serve as the “HOT” wire which is connected directly to a station out­put terminal in the controller. The other wire is "COMMON" and may be joined to the common wires of other valves with one wire running to the common termi­nal of the controller. Check operation using the con­troller.
#2
Common 4 3 2 1
Valve Solenoid
Controller Terminals
Common Wire
Hot
Wires
2
Loading...
+ 2 hidden pages