Q-Logic 9200 User Manual

SANbox 9000 Series
Stackable Chassis Switch
HyperStack Cable Installation Guide
1. HyperStack Cables, 25 inch (2) 2. License Key Upgrade, HyperStack (1)
HyperStacking connects two SANbox® 9200 model switches through the Inter-Chassis Connection (ICC) ports on the two pairs of CPU blades. Two HyperStack kits are required to successfully connect two switches. Each HyperStack™ kit contains one HyperStack license key and two cables. HyperStacking is not disruptive and can be done with both switches operational or both switches powered off.
Tools Required
Crosshead screwdriver, medium
Tie wraps (6)
59238-01 A 1
*59238-01 A*
SANbox 9000 Series Stackable Chassis Switch HyperStack Cable Installation
Mount the Switches
Mount the switches in a rack, one on top of the other with no more than 1U of space between them. A cable loom can be installed in this space.
Horizontal clearance from the CPU blades to the rack opening or door should be 7–8 inches to allow for HyperStack cabling.
Refer to the SANbox 9000 Series Stackable Chassis Switch Rack Mounting Guide for detailed mounting instructions.
1U Maximum
D
Verify Domain IDs
Verify that the two switches have different domain IDs. If they do not, change the domain ID of one of the switches using the Set Config Switch command.
Verify Firmware Version 7.8
Enter the Show Version command to verify that the two switches have firmware version 7.8 or later.
SANbox #> show domains
Principal switch is (local): 10:00:00:c0:dd:07:4a:e8 Domain ID List:
Domain 1 (0x1 ) WWN = 10:00:00:c0:dd:07:4a:e8
SANbox #>show version
**************************************************** * * * * Command Line Interface SHell (CLISH) * * *
**************************************************** *
SystemDescription SANbox 9000 Series HostName <undefined> EthIPv4NetworkAddress 10.20.11.192 EthIPv6NetworkAddress :: MACAddress 00:c0:dd:00:71:ee WorldWideName 10:00:00:c0:dd:00:71:ed ChassisSerialNumber FAM033100024 SymbolicName SANbox ActiveSWVersion V7.8.x.x.xx.xx ActiveTimestamp day month date time year POSTStatus Passed PrimaryCPU CPU0 SecondaryCPUStatus HotStandby
2 59238-01 A
D
SANbox 9000 Series Stackable Chassis Switch HyperStack Cable Installation Guide
Install version 7.8 firmware, if necessary. Enter the Image command to download and unpack the firmware. Enter the Hotreset command to perform a non-disruptive activation.
Install HyperStack Licenses
Follow the directions on the License Key Upgrade document for each switch. Apply the
respective license keys to each switch using the Feature Add command.
SANbox #> admin start SANbox (admin) #> image fetch account_name ip_address
filename
SANbox (admin) $> image unpack filename Wait for the unpack to complete. Image unpack command result: Passed
SANbox (admin) $> hotreset
SANbox #> admin start SANbox (admin) #> feature add #-XXXXXXXXXXXXX License upgradefor HyperStack(tm) capability. This feature upgrade does NOT require a switch reset. Do you want to continue with license upgrade procedure? (y/n): [n] y
Log Msg: [day mon date hh:mm:ss.sss CST year][C][8400.006B][Switch][Upgrading License for HyperStack(tm)capability]
Log Msg: [day mon date hh:mm:ss.sss CST year][C][8400.0047][Switch][New licenses are being installed]
Connect the HyperStack Cables
Use a screwdriver to remove the covers from all ICC ports.
Connect a HyperStack cable to one of the ICC ports with the label side up as shown.
Secure the cable connector with the captive screws.
1
2
1. ICC Port Cover 2. Label facing up
59238-01 A 3
SANbox 9000 Series Stackable Chassis Switch HyperStack Cable Installation
Complete the HyperStack Cable Connections
Connect the remaining HyperStack cable connectors as shown in the illustration. These copper cables are very flexible and can be bent as needed without damage.
NOTE:
This is the only cabling configuration that is supported. Any other configuration will result in an error.
Secure the HyperStack Cables
Secure the cables in place using ties wraps as shown. Secure the outer cables to the rack posts; secure the inner cables to each other. This reduces cable clearance to 7–8 inches and provides room for the removal of the Power Supply and Fan blades on the lower switch.
D
1
1. Tie Wraps
4 59238-01 A
D
SANbox 9000 Series Stackable Chassis Switch HyperStack Cable Installation Guide
Confirm HyperStack Operation
Confirm that the ICC port Logged-In LEDs on all CPU blades are illuminated. This indicates that the switches are communicating.
Enter the Show Interconnect command to confirm each ICC port is online.
Enter the Show Fabric command to confirm that both SANbox 9000 Series switches are in the fabric.
SANbox #> show fabric
Domain WWN Enet IP Addr FC IP Addr SymbolicName
------ --- ------------ ---------- -----------­*1 (0x01) 10:00:00:c0:dd:07:4a:e8 10.20.83.203 0.0.0.0 SANbox 9000 2 (0x02) 10:00:00:c0:dd:00:6a:2d 10.20.68.12 0.0.0.0 SANbox 9000
* indicates principal switch
1
1. Logged-In LEDs
SANbox #> show interconnect
Blade ID ICC ID State LSDB ID ISOREASON
-------- ------ ----- ------- --------­ CPU0 ICC0 Online 0x1000 NotApplicable ICC1 Online 0x1001 NotApplicable
CPU1 ICC0 Online 0x1010 NotApplicable ICC1 Online 0x1011 NotApplicable
1
59238-01 A 5
SANbox 9000 Series Stackable Chassis Switch HyperStack Cable Installation
D
Corporate Headquarters QLogic Corporation 26650 Aliso Viejo Parkway Aliso Viejo, CA 92656 949.389.6000 www.qlogic.com
D
© 2008 QLogic Corporation. Specifications are subject to change without notice. All rights reserved worldwide. QLogic, the QLogic logo, SANbox, and HyperStack are trademarks or registered trademarks of QLogic Corporation. All other brand and product names are trademarks or reg istered trademarks of their respective owners. Information supplied by QLogic Corporation is believed to be accurate and reliable. QLogic Corporation assumes no responsibility for any errors in this brochure. QLogic Corporation reserves the right, without notice, to make changes in product design or specifications.
Europe Headquarters QLogic (UK) LTD. Quatro House Lyon Way, Frimley Camberley Surrey, GU16 7ER UK +44 (0) 1276 804 670
Loading...