Powerware P93 User Manual

Features
P93 features
A UPS is pre-architected, tested and
optimized for eServer and storage applications
A Pre-installation site evaluation* A Includes UPS installation and
start-up service*
cables and receptacles
A ProActive 1-year service plan A Exclusive 5-year onsite warranty
offered through IBM with IBMSERV coordination
UPS benefits
A Maximum availability – with true
double-conversion online design, the proven technology that is used for the most mission-critical applications in the world
A Maximum efficiency – the
Powerware P93’s advanced design features efficiency of up to 93%, the highest for a double-conver­sion online UPS in its kVA range
A Maximum performance – the
Powerware P93 delivers the high­est performance by using digital signal processing, true pulse­width-modulation and maximum IGBT responsiveness. This provides easy setup, drift-free operation and a pristine output
*When purchased with Powerware Field Installation, PN 103003671, IBM PN 97P3604
Powerware P93 (9330-20) UPS
Designed specifically to meet the high-availability needs of critical 24x7 applications for small to medium-size business, the Powerware P93 delivers enhanced system reliability and the highest efficiency ratings of any online UPS in the 20 kVA range. The P93 also contains high-end features and benefits that only existed in larger capacity UPS, until now.
The advanced features of the Powerware P93 include:
Digital signal processing and pulse-width modulation
True pulse-width modulation is achieved through the use of digital signal processing, which enables the IGBTs to works at their highest capacity, increasing system reliability and ensuring perfect power on the output.
Built-in control area network (CAN)
An integral internal and external Control Area Network (CAN) is incorporated into the Powerware P93 that assists in seamlessly integrating peripherals and options, controllable from the control panel. It also reduces the internal wiring connections required therefore increasing overall system reliability.
Superior cooling design
The superior cooling design of the Powerware P93 draws from Powerware’s extensive, almost 40 years of industry and product development experience. This design, which features redundant fans, ensures that more thermally sensitive areas are cooled first.
Comprehensive communications and user interface
A large display, mimic and control panel is ergonomically situated for operator interface with the unit. The soft keypad helps guide the operator through all menus and setups. A dedicated micro-processor had been designed and engineered to provide full-featured monitoring and extensive alarm history. It allows for additional communica­tion options like Internet accessibility, Ethernet, network links, and modems.
Internal battery
The Powerware P93 comes with internal batteries that provide up to 17 minutes of backup at full load. The batteries are easily accessible and main­tained through front access slide-out trays. DC Expert Plus™ internal battery management system significantly enhances battery life.
Ideal applications
A iSeries 870 and 890 A pSeries 655, 670 and 690 A Enterprise Storage Server Model 800 A Cluster Server 1650
Powerware P93 - Advanced Technology
Advanced ergonomically designed user interface panel
A
Easily accessed from a standing position, panel is tilted 15 degrees for optimum viewing
A
Large LCD panel for graphic displays (4 line by 40 characters)
A
LED status indicators
A
Soft keys provide easy navigation through info screens
A
Smart Load Off button prevents unintentional load losses
A
Multi-lingual LCD panel meets global requirements
A
Current status, history, events and alarms and an active mimic bus can be viewed
The Powerware P93 offers a complete feature set to deliver the highest performance in the 20 kVA range of UPS. Whether chosen for an IT or facility environment, locally or remotely located, the Powerware P93 is the only choice to keep your business in business – around the clock.
Superior cooling design
A
Air filters prevent contaminants from entering the UPS
A
Redundant fans provide continuous operation without derating if a fan fails
A
Fan failure detection and notification
A
Load-based fan speed control maximizes fan life and efficiency while minimizing audible noise and heat dissipation
A
Fans easily replaced while online
Easy installation
A
Casters provide for easy placement of unit
A
Multiple wire entry locations
A
Simple installation of communication option cards
A
Terminal blocks for input/output wiring
A
Front covers designed with magnetic latches for effortless removal and replacement
Exceptional design for service
A
Front and top access for service
A
Dedicated service port prevents any disturbance to the customer’s communication setup
A
Battery circuit breaker
A
Internal maintenance bypass switch provides isolation for safe servicing
A
Input circuit breaker
A
Slide out battery trays with quick disconnects
Bundled communications package
A
iSeries interface port and cable (25 ft.)
A
Modem for 7x24 remote monitoring and Advance Response Service
1
A
RS-232 port (DB-9)
A
(4) Building alarm inputs
A
(2) Summary contacts
A
(2) Unused communication slots, supports up to two different communications options
Other standard features include:
A
UL 1778
A
cUL CAN/CSA C22.2 No 107.1
A
Exceeds IEC 62040-3, UPS definition
A
Double-conversion online technology
A
Cold-start capability from battery
A
Wide input voltage and frequency window
A
Dual source input to rectifier and bypass
A
Quiet operation, less than 60 dBA
A
ProActive 1 year service plan
2
A
THD input filter
A
Installation
3
A
7x24 startup
A
Line up and match options cabinet containing
A
External maintenance bypass
A
42-pole distribution panel
A
Branch output breakers with output distribution cables and receptacles (outlets) with various configurations to support a variety of device
configurations.
A
Support dual redundant power needs of IBM devices
Powerware P93
1. Requires customer provided phone line. Includes one-year ProActive Service. 2. Additional years of ProActive Service available. See Options section for details. 3. When purchased with Powerware Field Installation, PN 10300671, IBM PN 973604.
Connectivity - what you need by application
Solution zSeries iSeries pSeries xSeries Storage Networking
LanSafe software x x LanSafe software & ConnectUPS MultiServer card, IBM FC 2933 x x NetWatch software & ConnectUPS Web/SNMP card, IBM FC 2934 x LPARS
1
x x x IBM Director Snap-in x x x PowerVision software x x x x x FORESEER Software x x x x x ConnectUPS relay card & AS400 cable, IBM FC 2936 x
NOTE: One (1) X-Slot relay card and interface cable included with P93. 1. Use ConnectUPS Web/SNMP/xHub card, IBM FC 2934 to support LPAR (POWER 4 Chip Set) servers. For pSeries configurations: each LPAR needs a network connection and will install Powerware provided NetWatch or LanSafe V software.
DC Expert Plus™Built-in Battery Monitoring
Real-world business applications require a complete range of battery management and testing features, including battery runtime remaining, lifetime remaining, battery health, and notification, to help make critical decisions, from scheduling preventive maintenance to load shedding. Advances in firmware, digital technology and battery monitoring techniques enable the Powerware P93 to offer sophisticated battery management features, previously available only in expensive add-on systems. By ensuring optimal battery health and availability, DC Expert Plus raises the reliability of the Powerware P93 far beyond any other UPS in this kVA range.
DC Expert Plus advanced features include:
A
Powerware Battery Lifetime Monitor uses measures of chronological time, number of battery discharges, battery temperature, and system loading
to determine battery lifetime remaining.
A
Battery Runtime Remaining Monitor uses system loading plus internal sensing points for voltage and current data to calculate runtime remaining.
A
Advanced Battery Management (ABM®) uses patented three-stage charging technique that not only increases battery service life, but also optimizes
recharge time.
A
Battery Circuit Test (BCT) performs a periodic test of the battery string to ensure that there are no open circuits that would jeopardize battery
performance and system availability.
A
Temperature Compensated Charging (TCC) monitors the battery temperature and through sophisticated algorithms adjusts the rate of charge,
compensating for the ambient temperature to prolong the life of the battery.
A
Intelligent Battery Protection (IBP) automatically adjusts the shutdown voltage of the batteries based on the length of the AC outage. This prevents
severe battery discharge if the system is lightly loaded.
The intelligent communications capability of the Powerware P93 family of UPS means improved reliability, easier network power management and expanded network communications. With both hardware and software communications options, Powerware provides the right communications solution for your specific situation.
LanSafe
LanSafe version 5 delivers comprehensive support including graceful, remote shutdown of UPS systems and network monitoring tools via serial, USB, and network connectivity options. LanSafe's exclusive SafetyNet Technology provides Network Shutdown functionality and enables network administrators to shut down the most critical equipment last.
Powerware Extensions for IBM Director
Powerware Extensions for IBM Director provide seamless integration of Powerware UPSs into the Director management system. The Extensions for IBM Director simplify network management tasks for critical elements of server power protection. System administrators can easily monitor, diagnose, configure, set alarms, schedule self-tests, check battery, gather inventory information, and control Powerware UPSs network wide from a single console within IBM Director.
PowerVision
®
PowerVision power management software can monitor up to 64 network devices, provide data archiving and analysis to pre­vent power problems, and offers sophisticated notification, plus Modbus®connectivity. Through its easy-to-use graphical user interface, PowerVision provides critical information about the power, network-wide, in real time.
FORESEER
®
FORESEER environmental monitoring software puts an end to worries about risks to your critical foundation equipment and systems. From air conditioners to water cooling systems, generators to UPS, FORESEER gives you up-to-the-minute information about any system or device that is fundamental to your system availability. Plus, with its unique data archiving capabilities, FORESEER can identify potential problems before they occur,
and notify you so you can implement a solution before a crisis.
ConnectUPS Adapters
Powerware’s ConnectUPS-X and communications adapters provide a self-contained link between the UPS and the Ethernet
LAN/WAN. Using HTTP, Telnet or SNMP, you can easily monitor, manage, and shut down or reboot remote UPS-protected
servers, routers, hubs and other key network devices in a controlled manner. These adapters are also compatible with many
third-party network management software packages.
Intelligent Communications
P93 Options
ProActive service – additional year(s) plan description
A 7x24 corrective maintenance coverage A 7x24 annual performance check A Annual power protection audit A 7x24 remote monitoring advance response A Monthly UPS performance report with web access to account information and site service activity
Powerware IBM IBM Per P93
Part Number Feature Code Part Number Minimum Maximum
Concurrent with UPS purchase 155102012-001 7001 97P2657 0 4 Non-concurrent to UPS purchase 155102013-001 7002 97P2658 0 4
Connectivity
ConnectUPS X-Slot Web/SNMP/xHub card (10/100Mb)
The ConnectUPS-X Web/SNMP/xHub card provides real-time UPS monitoring and control of power throughout both 100Mb and 10Mb networks. When used in conjunction with NetWatch Client software, it also provides graceful shutdown of the operating system of up to 255 computers powered by a single UPS. The advanced features of the ConnectUPS-X include:
A Real-time, enterprise-wide monitoring provides valuable information for analysis of critical power conditions and problem identification A Supports 100Mb and 10Mb Ethernet networks A Built-in three ports switching hub adds three 10/100Mb network connections with no additional expense A Monitoring via Web using computer (through standard Web Browsers, e.g. Internet Explorer and Netscape). PDA or cell phone provides easy, anywhere,
anytime access
A Monitoring via SNMP using Network Management Software packages (e.g. Tivoli, CA Unicenter and HP Openview) A Analysis of chronic power problems and determination of trends through data logging and sophisticated graphic tools
ConnectUPS MultiServer Card
The ConnectUPS MultiServer card is an X-Slot connectivity device that provides serial connection to up to five computers for unattended, graceful shutdown and power monitoring. The card operates in conjunction with LanSafe software (included with UPS). The advanced features of the MultiServer card include:
A Real-time monitoring of critical power parameters A Graceful, unattended shutdown of multiple computers A Maximizes uptime of more critical loads through operation in tandem with load segment feature of UPS A Supports simple signaling (relay contacts) through additional DB-9 port
Relay Interface Card
The Powerware Relay Interface card is an X-Slot connectivity device that provides monitoring of UPS status through isolated, dry contact, Form-C relays. It also provides the interface for AS/400 computers as well as many industrial applications. The advanced features of the Relay Interface card include:
A Isolated, dry contact, Form-C relays for “utility failure”, “low battery”, “UPS alarm /OK” or “on bypass” A User-selectable “normally open” or “normally closed” contacts A Remote shutdown of UPS through integrated shutdown function A Hot-swappable – UPS maintains power to critical applications while changing cards
Powerware IBM IBM Per P93
Part Number Feature Code Part Number Minimum Maximum
ConnectUPS X-Slot Web/SNMP card 103002974-5501 2934 53P4619 0 2* ConnectUPS X-Slot MultiServer card 05146447-3901 2933 04N7027 0 2* ConnectUPS Relay Interface card & cable 103003564 2936 97P3886 0 2*
*Maximum combination of FC 2933, 2934, 2936 and other ConnectUPS X-Slot card options is two. ConnectUPS cards are installed onsite and concurrently with P93 startup by Powerware Service Technician. Customer responsible for software installation.
Output connections
Three (3) NEMA non or locking receptacles (outlets) with breakers and connectors. Each connector shall be on a cord with maximum length of 50 feet. Choose from:
pSeries pSeries zSeries
Feature Code IBM Plug Type iSeries Feature Code Part Number Feature Code Part Number
5-15R duplex 4 1412, 1413, 2960 + 9082 86G7648 9800 31L7061, 2, 4 5-20R duplex - - - - ­L5-15R 7 2960 + 9083, + 9082 - - 31L7067, 8 L5-20R - - - - ­L5-30R - - - - ­6-15R 5 1410, 1403, 1411, 1451, 1452, 1457, 2961 & 9082 183576, 4, 3 9909, 9833 ­L6-15R 10 1414, 1416, 1453, 1454, 1458 186G7878, 9 - 31L7070, 1 6-20R 29 1400, 1401, 1423 - - ­L6-20R 11 1404, 1406, 1428 - - ­L6-30R 12 1424, 1426 11F0113, 4 - -
Powerware IBM IBM Per P93
Part Number Feature Code Part Number Minimum Maximum
Output power cords (NEMA) 103003673 9881 97P2660 0 6*
*Hardware installed onsite and concurrent to P93 installation.
Battery runtimes (in minutes)
iSeries pSeries Storage Cluster
870 890 655 670 690 2105 1350 1600
with
CEC + CEC + CEC + 1 2 3 expansion
I/O I/O I/O node nodes nodes up to 8 way 32 way standard enclosure
10 kVA 15 kVA 20 kVA 16 way 16 way 32 way 1 I/O 2 I/O 3 I/O 32 way 1 I/O 3 I/O
7 kW 10.5 kW 14 kW 6.8 kW 4.9 kW 8.3 kW 3.2 kW 6.4 kW 9.6 kW 6.5 kW 3.2 kW 10.5 kW 6.4 kW 13.8 kW Internal battery 45 26 17 48 79 31 110 50 27 49 110 26 50 17 (1) External battery cabinet 90 65 48 98 150 75 240 110 70 108 240 65 110 48 (2) External battery cabinets 155 90 75 166 240 130 400 180 96 172 400 90 180 75
Contact Powerware for runtime, application or configuration assistance.
A DC rated circuit breaker in each battery cabinet allows multiple battery strings to be serviced independently of each other, assuring back up power is always available to the UPS
Removable battery slide-out tray assembles provide “front access only” and reduce battery maintenance time.
Manufacturer-supplied wiring with quick disconnects provides plug-and-play capability for line-up and match configurations.
Quick disconnects between battery tray assemblies reduce battery maintenance time.
A
Battery cabinets may be daisy-chained together for extended battery runtimes, (up to 2).
A
Integral configuration, which line up and match, is standard.
1
A
Front-access-only enhances servicing and installation.
A
Slide trays and modular battery packaging makes periodic servicing easy.
A
Cabinets are UL 1778 listed.
A
Flame retardant batteries meet UL 94V2 for computer room installations.
A
Wiring installation.
2
Powerware offers a full line of battery cabinets for the Powerware P93.
Extended Battery Cabinets
1. Battery cabinets can be configured as line up and match or remotely located. Customer must provide wiring for remotely located cabinets. 2. If concurrent to P93 Field Installation, Powerware PN 103003671, IBM PN 97P3604.
Calculating runtime - a guide
Typical runtime is 15 minutes Formula (runtime in minutes) = [business + (2 x system shutdown) + safety] Business = _____ Shutdown ____ x 2 = _____ Safety = _____ Total = _____
Powerware IBM IBM Per P93
Part Number Feature Code Part Number Minimum Maximum
External Battery Cabinet A13031 6635 97P2663 0 2
Additional options
A
Input/output galvanic isolation
A
Voltage matching transformers
A
Remote status panel
A
Remote EPO button
Contact
Powerware
Revised 01/04 Reprint 01/04
WORLDWIDE HEADQUARTERS 8609 Six Forks Road Raleigh, NC 27615 U.S.A. Toll Free: 1.800.925.4426 www.oem.powerware.com/ibm-ups
CANADA Ontario: 416.798.0112
EUROPE/MIDDLE EAST/AFRICA Denmark: 45.3677.7910 Finland: 358.9.452.661 France: 33.1.60.12.74.00 Germany: 49.7841.6660 Italy: 39.02.66.04.05.40 Norway: 47.23.03.65.50 Sweden: 46.8.598.940.00 United Kingdom: 44.1753.608.700
ASIA PACIFIC Australia/NZ: 612.9878.5000 China: 86.21.6350.0606 HK/Korea/Taiwan: 852.2745.6682 India: 91.11.2649.9414 to 18 Singapore/SEA: 65.6829.8888
LATIN AMERICA Argentina: 5411.4343.6323 Brazil: 55.11.3616.8500 México: 5255.9171.7777
Powerware
Powerware P93 Specifications
Options ProActive X-Slot X-Slot X-Slot
P93 Cabinet EBC Service Web/SNMP Multi Server Relay Output power cords
IBM feature code 6635 7001 7002 2934 2933 2936 9880 9881 IBM part number 97P2653 97P2654 97P2663 97P2657 97P2658 53P4619 04N7027 97P3886 97P2659 97P2660 Input Voltage Volts 208 - - - - - - ­Output voltage Volts 208 - - - - - - ­Input/output frequency Hz 50/60 - - - - - - ­Input voltage range -
Minimum Volts 177 - - - - - - -
Maximum Volts 228 - - - - - - ­Rectifier input Amps 52 - - - - - - ­Bypass input
Nominal amps Amps 55.5 - - - - - - ­AC output
Nominal Amps 55.5 - - - - - - -
10 minutes Amps 69.4 - - - - - - ­Battery
Nominal voltage Volts 288 - 288 - - - - -
Max. charge
voltage @ 25°C Volts 340 - 340 - - - - -
Charge current Amps 7 - - - - - - -
Nominal discharge current Amps 52 - - - - - - -
Total cell count 144 - 144 - - - - ­System efficiency
@100% load % 92.4 - - - - - - -
@75% load % 92.7 - - - - - - -
@50% load % 92.9 - - - - - - ­Maximum heat dissipation
BTU/hr. (x1000) 3.9 - - - - - - -
kcal/hr. 990 - - - - - - -
Inverter efficiency
(full load) % 94 - - - - - - ­Physical attributes (max.)
Width in/cm 22/56 17/52 17/52 - - - - - 50 ft. (maximum cord)
Height in/cm 45/114 45/114 45/114 - - - - -
Depth in/cm 31/79 38/97 31/79 - - - - ­Weight installed lb/kg 958/435 200/90 600/272 - - .5/.2 .5 .5/.2 20 lb. each connector
6 @ 4 @ 6 @ Point loading lb/kg 160/73 50/230 145/100 N/A N/A N/A N/A N/A - ­Min/max qty per P93 - 1/1 0/2 0/4 0/4 0/2 0/2 0/2 1/1 0/6
Quantity (2) 60 A, 3-phase,
4-wire,
IEC-309,
460R9W
with
breakers
and
connec-
tors.
Quantity
(3). See
FC 9881
description.