Powerware FE-QFE UPS User Manual

Powerware®FERRUPS
FE/QFE UPS
User’s Guide
500 VA–18kVA,50and60Hz
Powerware®FERRUPS
FE/QFE UPS
User’s Guide
500 VA–18kVA,50and60Hz
www.powerware.com
Class A EMC Statements
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
For Users in Germany
We hereby certify that the uninterruptible power system (QFE 500 VA, 700 VA, 850 VA, 1.15 kVA, 1.4 kVA, 1.8 kVA,
2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, 7 kVA, 10 kVA, 12.5 kVA, and 18 kVA) complies with the RFI suppression requirements of Vfg. 243/1991 and Vfg. 46/1992. The German Postal Service was notified that the equipment is being marketed. The German Postal Service has the right to retest the equipment and verify compliance.
Hiermit wird bescheinigt, daß die unterbrechungsfreie Stromversorgung (QFE 500 VA, 700 VA, 850 VA, 1.15 kVA,
1.4 kVA, 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, 7 kVA, 10 kVA, 12.5 kVA, and 18 kVA) in Übereinstimmung mit den Bestimmungen der Vfg. 243/1991 und Vfg. 46/1992 funkentstört ist. Der Deutschen Bundespost wurde das Inverkehrbringen dieses Gerätes angezeigt und die Berechtigung zur Überprüfung der Serie auf Einhaltung der Bestimmung eingeräumt.
Powerware reserves the right to change specifications without prior notice.
Powerware and CheckUPS are registered trademarks and EnviroCom is a trademark of Powerware Corporation. Microsoft and Windows are registered trademarks of Microsoft Corporation. HyperTerminal is a registered trademark of Hilgraeve. TeleVideo is a registered trademark of TeleVideo, Inc. WYSE is a registered trademark of WYSE Technology Inc.
.
Copyright 2002 Powerware, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any
way without the express written approval of Powerware.
TABLE OF CONTENTS
1 Introduction 1....................................................
Identifying Your UPS 1..........................................................
2 Safety Warnings 3................................................
3 UPS Startup 17....................................................
Startup for the FE and QFE 500 VA–3.1 kVA UPS 17.......................................
StartupfortheFEandQFE4.3–18kVAUPS 19..........................................
Rear Panels 23.................................................................
4 Operation 25......................................................
Front Panel Indicators 25..........................................................
Using the Control Panel 27........................................................
Changing Operating Modes 27...................................................
Entering Passwords 28.........................................................
Displaying and Changing Parameters 29............................................
Locking and Unlocking the Control Panel 29..........................................
Using the Configuration Menu 30.................................................
Automatic System Test 31.........................................................
Logic Test 31...............................................................
Inverter Test 31..............................................................
Battery Test 31..............................................................
Parameters 32.................................................................
UPS Shutdown 35..............................................................
Extended Power Outages 37.....................................................
5 Communication 39.................................................
Powerware Software Suite 39......................................................
Communication Port 40...........................................................
Connecting a Terminal or Computerto the RS-232 Port 41..................................
Entering Commands from a Terminal or Computer 44......................................
Remote Monitoring 47...........................................................
Remote Shutdown 47............................................................
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
i
Table of Contents
6 Options 49.......................................................
Bypass Switches 49.............................................................
Control Panel 49...............................................................
Environmental Monitoring 49.......................................................
Extended Runtimes 49...........................................................
Warranties 49.................................................................
7 Maintenance 51...................................................
8 Specifications 53..................................................
9 Troubleshooting 59................................................
Alarms 59....................................................................
Alarm and Inverter Logs 62........................................................
Reading the Alarm Log from a Control Panel 62.......................................
Reading the Inverter Log from a Control Panel 63......................................
Reading the Alarm Log from a Terminal or Computer 64..................................
Reading the Inverter Log from a Terminal or Computer 65................................
Alarm Code Summary 65..........................................................
Service and Support 66...........................................................
ii
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
CHAPTER 1
INTRODUCTION
Welcome to the growing Powerware9FERRUPS uninterruptible power system (UPS) family. This UPS represents a breakthrough in the design of advanced, online UPSs.
Identifying Your UPS
NOTE Before starting up the UPS, verify that it has been installed according to the
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide
FERRUPS UPSs come in different sizes (see Figure 1). If your UPS is a 500 VA–3.1 kVA model, continue with “Startup for the FE and
QFE 500 VA–3.1 kVA UPS” on page 17. If your UPS is a 4.3–18 kVA model, continue with “Startup for the FE and QFE 4.3–18 kVA UPS” on page 19.
.
4.3–18 kVA Models
500 VA–3.1 kVA Models
Figure 1. FERRUPS UPS
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
1
Introduction
2
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
CHAPTER 2
SAFETY WARNINGS
Read the following precautions before you install the UPS.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
This UPS contains LETHAL VOLTAGES. Allrepairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
: This UPS contains its own energysource (batteries). The output receptacles may
carry live voltage even when the UPS is not connected to an AC supply.
: Do not remove or unplug the input cord when the UPS is turned on. This removes
the safety ground from the UPS and the equipment connected to the UPS.
: To reduce the risk of fire or electric shock,install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or
excessive humidity (95% max).
: To comply with international standardsand wiring regulations, the total equipment
connected to the output of this UPS must nothave an earth leakage current greater than 1.5 milliamperes.
DANGER
WARNING
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
3
Safety Warnings
: Batteries can present a risk of electrical shock or burn from high short-circuit
current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteriesand required precautions. Keep unauthorized personnel away from batteries.
: Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
: Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER GEM DISSE ANVISNINGER DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE SIKKERHEDSANVISNINGER
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og vedligeholdelse bør kun udføres afen AUTORISERET SERVICETEKNIKER. Ingen af UPS’ens indvendige dele kan repareres af brugeren.
CAUTION
FARE
ADVARSEL!
: Denne UPS indeholder egen energiforsyning (batterier).Udgangsnetstikkene kan
lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde.
: Netledningen må ikke fjernes og stikketmå ikke trækkes ud, mens UPS’en er
tændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.
: Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit
for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stød. Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær vand eller høj fugtighed (maksimalt 95%).
: I overensstemmelse med internationale normer og bestemmelser for el-installation
må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 1,5 milliampere.
4
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
: Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj
kortslutningsspænding. De korrekte forholdsregler bør overholdes.
: Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for
bortskaffelsesprocedurer.
: Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere
ved åben ild.
Belangrijke Veiligheidsinstructies
BELANGRIJKE VEILIGHEIDSINSTRUCTIES BEWAAR DEZE INSTRUCTIES DEZE HANDLEIDING BEVAT BELANGRIJKE VEILIGHEIDSINSTRUCTIES
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd. Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden GEREPAREERD.
Safety Warnings
ADVARSEL
GEVAAR
WAARSCHUWING
: Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingen
kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten.
: Verwijder de ingangsnoer niet of haalde stekker van de ingangsnoer er niet uit
terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben.
: Teneinde de kans op brand of elektrische schokte verminderen dient deze UPS in
een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40°C niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid (max. 95%).
: Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de
gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van meer dan 1,5 milliampère hebben.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
5
Safety Warnings
: Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als
gevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op.
: De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw
plaatselijke voorschriften.
: Nooit batterijen in het vuur gooien.De batterijen kunnen ontploffen.
Tarkeita Turvaohjeita
TÄRKEITÄ TURVAOHJEITA - SUOMI
SÄILYTÄ NÄMÄ OHJEET TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ.Kaikki korjaukset ja huollot on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.
OPGELET
VAARA
VAROITUS
: Tämä UPS sisältää oman energialähteen (akuston). Ulostuloliittimissä voi olla
jännite, kun UPS ei ole liitettynä verkkojännitteeseen.
: Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaa
turvamaadoituksen UPS-laitteesta ja siihen liitetystä laitteistosta.
: Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin,
joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia epäpuhtauksia. Ympäristön lämpötila eisaa ylittää 40 °C. Älä käytä lähellä vettä ja vältä kosteita tiloja (95 % maksimi).
: Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän
UPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 1,5 milliampeeria (mA).
6
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
: Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään
oikosulkuun. Noudata asianmukaisia ohjeita.
: Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia
määräyksiä.
: Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ. AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.
Safety Warnings
VARO
DANGER!
AVERTISSEMENT!
: Cet onduleur renferme sa propre source d’énergie (batteries). Les prises de sortie
peuvent être sous tension même lorsque l’onduleur n’est pas branché sur le secteur.
: Ne pas retirer le cordon d’alimentation lorsque l’onduleur est soustension sous
peine de supprimer la mise à la terre de l’onduleur et du matériel connecté.
: Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur
uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la température et l’humidité ambiantes sont contrôlées. La température ambiante ne doit pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère excessivement humide (95 % maximum).
: Afin d’être conforme aux normes et règlements internationaux de câblage, le
courant de fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas dépasser 1,5 mA.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
7
Safety Warnings
: Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par
des courts-circuits de haute intensité. Prendre lesprécautions nécessaires.
: Une mise au rebut réglementaire des batteries est obligatoire. Consulter les
règlements en vigueur dans votre localité.
: Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire
exploser.
Sicherheitswarnungen
WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAHREN. DIESES HANDBUCH ENTHÄLT WICHTIGE
SICHERHEITSANWEISUNGEN.
Die USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten sollten nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine vom Benutzer zu wartenden Komponente.
ATTENTION!
WARNUNG
ACHTUNG
: Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An den
Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USV nicht an einer Wechselspannungsquelle angeschlossen ist.
: Das Eingangskabel nicht entfernen oder abziehen,während die USV eingeschaltet
ist, weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Geräten entfernt wird.
: Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden
mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen. Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %) betreiben.
: Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an
den Ausgang dieser USV angeschlossenen Geräte zusammen einen Erdschlußstrom von insgesamt 1,5 Milliampere nicht überschreiten.
8
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
: Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oder
Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind unbedingt zu beachten.
: Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbeisind die örtlichen
Bestimmungen zu beachten.
: Batterien niemals verbrennen, da sie explodieren können.
РспейдпрпйЮуейт БуцЬлейбт
УЗМБНФЙКЕУ ПДЗГЙЕУ БУЦБЛЕЙБУ ЦХЛБОФЕ БХФЕУ ÔÉÓ ПДЗГЙЕУ ÔÏ РБСПН ЕГЧЕЙСЙДЙП РЕСЙЕЧЕЙ УЗМБНФЙКЕУ ПДЗГЙЕУ БУЦБЛЕЙБУ
Áõôü ôï UPS ресйЭчей ИБНБФЗЦПСБ ÔÁÓÇ. ¼ëåò ïé ерйукехЭт êáé ïé ухнфзсЮуейт рсЭрей íá гЯнпнфбй ÌÏÍÏ ÁÐÏ ЕОПХУЙПДПФЗМЕНП ÃÉÁ ÔÇ УХНФЗСЗУЗ РСПУЩРЙКП. Ôï UPS ÄÅÍ РЕСЙЕЧЕЙ КБНЕНБ ЕОБСФЗМБ ÐÏÕ ÍÁ МРПСЕЙ ÍÁ ЕРЙУКЕХБУФЕЙ ÁÐÏ ÔÏ ЧСЗУФЗ.
Safety Warnings
VORSICHT!
КЙНДХНПУ
РСПЕЙДПРПЙЗУЗК
:
Ôï ухгкексймЭнп UPS ресйЭчей ôç äéêÞ ôïõ ðçãÞ енЭсгейбт (ухуущсехфЭт). Ïé сехмбфпдьфет еоьдпх мрпсеЯ íá Эчпхн енесгь ôÜóç бкьмз êáé üôáí ôï UPS äåí еЯнбй ухндедемЭнп óå ðçãÞ енбллбууьменпх сеэмбфпт (AC).
:
Ìçí вгЬжефе áðü ôçí рсЯжб ôï кблюдйп фспцпдпуЯбт üôáí ôï UPS еЯнбй бнпйчфь. Ì UPS êáé áðü ôïí еопрлйумь ðïõ еЯнбй ухндедемЭнпт ìå ôï UPS.
:
Ãéá íá мейюуефе ôïí кЯндхнп рхскбгйЬт Þ злекфспрлзоЯбт, егкбфбуфЮуфе ôï ухгкексймЭнп UPS óå еущфесйкь ÷þñï ìå елегчьменз иесмпксбуЯб êáé хгсбуЯб, ï прпЯпт íá ìçí ресйЭчей бгюгймб хлйкЬ. Ç иесмпксбуЯб ресйвЬллпнфпт äåí рсЭрей íá оереснЬей ôïõò 40 хресвплйкЮ хгсбуЯб (мЭгйуфз ôéìÞ: 95%).
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
áõôü ôïí фсьрп бцбйсеЯфе ôç геЯщуз буцблеЯбт áðü ôï
°
C. Ìç чсзуймпрпйеЯфе ôï UPS кпнфЬ óå íåñü Þ
9
Safety Warnings
:
:
:
:
Avvisi di sicurezza
IMPORTANTI ISTRUZIONI DI SICUREZZA CONSERVARE QUESTE ISTRUZIONI QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONI DI SICUREZZA
Ãéá íá ухмцщнеЯ ìå ôá дйеинЮ рсьфхрб êáé ôïõò кбнпнйумпэт кблщдЯщузт, ôï сеэмб дйбсспЮт ðñïò ôç ãç пльклзспх ôïõ еопрлйумпэ, ðïõ еЯнбй ухндедемЭнпт ìå ôçí Эопдп ôïõ ухгкексймЭнпх UPS, äåí рсЭрей íá еЯнбй мегблэфесп áðü 1,5 mA.
РСПУПЧЗ
Ïé ухуущсехфЭт мрпсеЯ íá рспкблЭупхн злекфспрлзоЯб Þ Эгкбхмб áðü хшзль сеэмб всбчхкхклюмбфпт. ЛбмвЬнефе ôéò кбфЬллзлет рспцхлЬоейт.
БрбйфеЯфбй ущуфЮ дйЬиеуз ôùí ухуущсехфюн. ДеЯфе ôïõò фпрйкпэт кбнпнйумпэт ðïõ бцпспэн ôéò брбйфЮуейт дйЬиеуЮт ôïõò.
ÐïôÝ ìçí рефЬфе ôïõò ухуущсехфЭт óôç цщфйЬ, гйбфЯ мрпсеЯ íá ексбгпэн.
10
PERICOLO
la TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo statico di continuità NON vi sono PARTI RIPARABILI DALL’UTENTE.
AVVERTENZA
: Questo gruppo statico di continuità contiene una fonte di energia autonoma (le
batterie). Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di continuità non è collegato con una fonte di alimentazione a corrente alternata.
: Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di
continuità è acceso poichè in tal modo si disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuità e dell’apparecchiatura ad esso collegata.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Safety Warnings
: Per ridurre il rischio di incendio o discossa elettrica, installare il gruppo statico di
continuità in un ambiente interno a temperatura ed umidità controllata, privo di agenti contaminanti conduttivi. La temperatura ambiente non deve superare i 40°C. Non utilizzare l’unità in prossimità di acqua o in presenza diumidità eccessiva (95% max).
: Per conformità con gli standard internazionali e con le norme in merito al
cablaggio, tutta l’apparecchiatura collegata con l’uscita del gruppo statico di continuità non deve avere una corrente di dispersione di terra superiore a 1,5 milliampere.
ATTENZIONE
: Le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da
alta corrente dovuta a corto circuito. Osservare le apposite istruzioni.
: Le batterie devono essere smaltite in modo corretto. Per irequisiti di smaltimento
fare riferimento alle disposizioni locali.
: Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle
fiamme.
Viktig Sikkerhetsinformasion
FARLIG
Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kun utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE SERVICE PÅ NOEN AV DELENE i UPS’en.
FARLIG
: Denne UPS’en har en egen energikilde (batterier). Stikkontaktene kan være
strømførende selv om UPS’en ikke er tilsluttet en vekselstrømforsyning.
: Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS’en er på, slik at
ikke sikkerhetsjordingen fjernes fra UPS’en og det utstyret somer forbundet med den.
: For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et
innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende, forurensende stoffer. Romtemperaturen må ikke overskride 40°C. Den må ikke brukes i nærheten av vann ellerved meget høy luftfuktighet (95% maks.).
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
11
Safety Warnings
: Alt utstyr som er forbundet med utgangen avdenne UPS’en må ikke ha en sterkere
total lekkasjestrøm enn 1,5 milliampere for å være i overensstemmelse med internasjonale standarder og forkablingsbestemmelser.
: Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy
kortslutningsstrøm. Følg instruksene.
: Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om
fjerning av batterier.
: Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettesfor åpen ild.
Regulamentos de Segurança
INSTRUÇÕES DE SEGURANÇA IMPORTANTES
GUARDE ESTAS INSTRUÇÕES ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA IMPORTANTES
FORSIKTIG
12
CUIDADO
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não há nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.
ADVERTÊNCIA
: Esta UPS contém sua própria fonte de energia (baterias). Os receptáculos de saída
podem conter voltagem ativa quando a UPS não se encontra conectada a uma fonte de alimentação de corrente alternada.
: Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto
removerá o aterramento de segurança da UPS e do equipamento conectado.
: Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente
interno com temperatura e umidade controladas e livres de contaminadores condutíveis. A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em umidade excessiva (máx: 95%).
: Para estar de acordo com os padrões internacionais e os regulamentos de fiação,o
equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 1,5 miliampères.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
PERIGO
: As baterias podem apresentar o risco de choque elétrico, ou queimaduras
provenientes de alta corrente de curto-circuito.Observe as instruções adequadas.
: Siga as instruções apropriadas ao desfazer-se dasbaterias. Consulte os códigos do
local para maiores informações sobre os regulamentos de descarte de produtos.
: Nunca jogue as baterias no fogo, porque há risco de explosão.
Предупреждения по мерам безопасности
ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ СОХРАНИТЕ ЭТИ УКАЗАНИЯ ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ
ОПАСНО
В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ. Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ. Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.
Safety Warnings
ПРЕДУПРЕЖДЕНИЕ
: Данный ИБП содержит собственные источники энергии
(аккумуляторы). На выходных розетках может иметься напряжение, даже когда ИБП не подключен к сети переменного тока.
: Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки
при включенном ИБП. При этом защитное заземление отключается от ИБП и от оборудования, подключенного к ИПБ.
: Для снижения опасности пожара или поражения электрическим
током устанавливайте ИБП в закрытом помещении с контролируемыми температурой и влажностью, в котором отсутствуют проводящие загрязняющие вещества. Температура окружающего воздуха не должна превышать 40°С. Не эксплуатируйте устройство около воды или в местах с повышенной влажностью (макс. 95%).
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
13
Safety Warnings
: Для обеспечения соблюдения требований международных
стандартов и требований к разводке электрических цепей, суммарная величина тока утечки на землю всего оборудования, подключенного к выходу ИБП, не должна превышать 1,5 миллиампера.
: Аккумуляторы могут вызвать опасность поражения электрическим
током или ожога от тока короткого замыкания. Соблюдайте соответствующие меры предосторожности.
: Необходимо соблюдать правила утилизации аккумуляторов.
Обратитесь к местным нормативным актам за информацией о требованиях к утилизации.
: Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут
взорваться под воздействием огня.
Advertencias de Seguridad
ОСТОРОЖНО
14
INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IMPORTANTES
PELIGRO
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.
ADVERTENCIA
: Este SIE contiene su propia fuente de energía (las baterías). Los receptáculos de
salida pueden transmitir corriente eléctrica aun cuando el SIE no esté conectado a un suministro de corriente alterna (c.a.).
: No retire o desenchufe el cable de entrada mientras el SIE se encuentre
encendido. Esto suprime la descarga a tierra de seguridad del SIE y de losequipos conectados al SIE.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Safety Warnings
: Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un
lugar cubierto, con temperatura y humedad controladas, libre de contaminantes conductores. La temperatura ambiente no debe exceder los40°C. No trabaje cerca del agua o con humedad excesiva (95% máximo).
: Para cumplir con los estándares internacionales y las normas de instalación, la
totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 1,5 miliamperios.
PRECAUCIÓN
: Las baterías pueden presentar un riesgo de descargaseléctricas o de quemaduras
debido a la alta corriente de cortocircuito. Preste atención a las instrucciones correspondientes.
: Es necesario desechar las baterías de un modo adecuado. Consulte las normas
locales para conocer los requisitos pertinentes.
: Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las
expone a la llama.
Säkerhetsföreskrifter
VIKTIGA SÄKERHETSFÖRESKRIFTER
SPARA DESSA FÖRESKRIFTER DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA SÄKERHETSFÖRESKRIFTER
FARA
Denna UPS-enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD SERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar som ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten.
VARNING
: Denna UPS-enhet har en egen energikälla (batterier). De utgående kontakterna kan
vara strömförande när UPS-enheten inte är ansluten till en växelströmkälla.
: Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort
skyddsjordningen från både UPS-enheten och den anslutna utrustningen.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
15
Safety Warnings
: Minska risken för brand eller elektriska stötar genom att installera denna
UPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).
: För att överensstämma med internationell standard och installationsföreskrifter får
inte den totala utrustning som anslutits till uttagen på denna UPS-enhet ha läcksström som överstiger 1,5 milliampere.
VIKTIGT
: Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström.
Följ tillämpliga anvisningar.
: Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. : Använda batterier får aldrig brännas upp. De kan explodera.
16
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
CHAPTER 3
UPS STARTUP
This section provides step-by-step instructions for starting the Powerware FERRUPS UPS. Follow these procedures closely to avoid potential damage to your equipment or the UPS and to protect yourself and others from hazardous operating conditions.
Startup for the FE and QFE 500 VA–3.1 kVA UPS
To start the FE and QFE 500 VA–3.1 kVA UPS, use the following steps:
1. Confirm the equipment to be protected by the UPS is powered off.
For FE Plug-Receptacle UPSs: Plug the UPS power cord into a
2.
power outlet.
NOTE If the plug does not match your receptacle outlet, ask your electrician to install the proper outlet.
For QFE Plug-Receptacle UPSs: Disconnect the power cord from
the computer or other equipment to be protected by the UPS and plug it into the UPS. Plug the other end of the power cord into a power outlet.
NOTE Do not use the cord supplied with the UPS; this cord is for plugging the equipment into the UPS output receptacles.
NOTE If the plug does not match your receptacle outlet, ask your electrician to install the proper outlet.
NOTE If you need to order a UPS power cord, please call yourservice representative.
For Hardwired UPSs: Confirm that an electrician has completed
and tested the connection to the proper power source and connected your protected equipment according to the
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide. Turn the AC line disconnect switch to the ON position.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
17
UPS Startup
3. The AC LINE indicator illuminates (see Figure 2).
NOTE The AC LINE indicator does not illuminate for FE models with serial numbers 25000 and greater until the UPS ON/OFF switch is turned to the ON position.
AC LINE READY CHARGING
BATTERY
POWER
ALARM
Figure 2. Front PanelIndicators
4. If you have an external battery cabinet with a DC switch, turn the switch to the ON position.
5. Turn the UPS ON/OFF switch to the ON position. After a short startup test, the READY indicator flashes for a few seconds and then remains illuminated. The UPS is ready to supply output power.
NOTE The UPS and external battery cabinets are shipped with the batteries charged. However, batteries may lose some of the charge during shipping and storage. You can use the UPS immediately after unpacking,but it may not provide the full-rated backup time during a power failure. Upon initial startup, the UPS may need to operate for 24 hours before the battery is fully charged and full battery-backup time isavailable. If the CHARGING indicator is illuminated, operate the UPS for 24 hours to fully charge the battery.
6. For Plug-Receptacle UPSs: Plug the equipment to be protected into the UPS output receptacles.
NOTE For QFE models, use the supplied UPS cord to connect your equipment to the UPS output receptacles.
18
For Hardwired UPSs: Turn the bypass switch to the UPS position.
7. Turn on the equipment that is connected to the UPS.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Startup for the FE and QFE 4.3–18 kVA UPS
To start the FE and QFE 4.3–18 kVA UPS, use the following steps:
1. Confirm the equipment to be protected by the UPS is powered off.
For Plug-Receptacle UPSs: Verify that the AC input power is off
2.
at the service panel. Plug the UPS power cord into a power outlet.
NOTE If the plug does not match your receptacle outlet, ask your electrician to install the proper outlet.
For Hardwired UPSs: Confirm that an electrician has completed
and tested the connection to the proper power source and connected your protected equipment according to the
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide. Confirm that your AC line disconnect switch and the
UPS ON/OFF switch are both in the OFF position.
3. If your UPS has a DC switch, turn on the switch according to the UPS model:
4.3–7 kVA: If you have an external battery cabinet(s) with a DC
switch, turn the switch to the ON position. If you do not have an external battery cabinet(s): unlock the
UPS front cover panel using the FERRUPS key and remove the front cover panel. Locate the DC switch behind the UPS front cover panel. If there is a precharge button next to the switch, press it for a few seconds. Turn the DC switch to the ON position and reinstall the UPS front cover panel.
10–18 kVA: If you have an external battery cabinet(s) with a DC
switch, turn the switch to the ON position.
Starting the UPS on battery power: Use the key to turn the
4.
ON/OFF switch to the ON position. After a brief self-check, the BATTERY POWER and READY indicators illuminate. The UPS beeps every 20 seconds, indicating the UPS is running on battery power. The control panel scrolls this display:
)(55836 0RGH $XWR &KDUJHU 2II %HHSHU (QDEOHG
UPS Startup
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
19
UPS Startup
NOTE If the ALARM indicator is on, read the alarm message on the control panel display, turn the ON/OFF and DC switches to the OFFposition, and call your service representative.
For Plug-Receptacle UPSs: Turn the AC input power on at the
service panel. The AC LINE indicator illuminates. After a few seconds, the UPS switches from battery power to AC input power. The BATTERY POWER indicator turns off.
For Hardwired UPSs: Turn the AC line disconnect switch to the
ON position. The AC LINE indicator illuminates. After a few seconds, the UPS switches from battery power to AC input power. The BATTERY POWER indicator turns off. Now, turn the UPS bypass switch (either on the back of the UPS or mounted nearby) to the UPS position.
NOTE The UPS and external battery cabinets are shipped with the batteries charged. However, batteries may lose some of the charge during shipping and storage. You can use the UPS immediately after unpacking,but it may not provide the full-rated backup time during a power failure. Upon initial startup, the UPS may need to operate for 24 hours before the battery is fully charged and full battery-backup time isavailable. If the CHARGING indicator is illuminated, operate the UPS for 24 hours to fully charge the battery.
20
5. For Plug-Receptacle UPSs: Plug the equipment you want to
protect into the UPS receptacles and turn on the equipment. If the ALARM indicator illuminates, see “Alarms” on page 59.
For Hardwired UPSs: Turn on the equipment connected to the
UPS. If the ALARM indicator illuminates, see “Alarms” on page 59.
6. Set the time and date using the control panel.
NOTE The correct time and date for is needed for the UPS alarm and inverter logs. Reset the time and date whenever the UPS hasbeen shut down.
Time is parameter 0; see “Parameters” on page 32 for more information. To set the time, follow these steps:
Press this key: Display shows: [DISPLAY]
'LVSOD\
[0] 'LVSOD\ [ENTER]  7LPH  [PROGRAM]  3JP
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
UPS Startup
The date is parameter 10. To display the date, follow these steps:
Press this key: Display shows: [DISPLAY]
'LVSOD\
[1][0] 'LVSOD\  [ENTER]  'DWH  [PROGRAM]  3JP
7. If your FERRUPS UPS is configured to use an external battery cabinet, you must program the battery capacity in ampere-hour (Ah) for the total number of battery packs used in the UPS. If you purchased one of the FERRUPS battery pack options available from Powerware, select the Ah value from Table 1.
Before programming the battery Ah, enter the user password following the instructions in “Entering Passwords” on page 28.
To change the battery Ah, parameter 69 (Batt Ah), follow these steps:
Press this key: Display shows: [DISPLAY] [6] [9] [ENTER]
 %DWW $+ >'HIDXOW@
[PROGRAM]  3JP [Ah Value from Table 1]  3JP >[[[@ [ENTER]  3JP >QHZ YDOXH@
where [[[ is the Battery Ah value from Table 1.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
21
UPS Startup
Table 1. External Battery Pack Ah Values
Battery Pack Battery Ah Battery Pack Battery Ah
1ME 100 1FE 100 2ME 150 2FE 150 3ME 200 3FE 200 4ME 225 4FE 225 5ME 300 5FE 300 6ME 400 6FE 400 7ME 600 7FE 600 8ME 75 8FE 75
9ME 100 9FE 100 10ME 150 10FE 150 11ME 200 11FE 200 12ME 225 12FE 225 13ME 300 13FE 300 14ME 400 14FE 400 15ME 600 15FE 600 21ME 75 16FE 100 24ME 150 17FE 150 25ME 200 18FE 200
EBPS10 33 19FE 225
EBPS12.5 75 20FE 300
EBPS18 75 21FE 400
22FE 600
22
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Rear Panels
UPS Startup
This section shows the rear panels of the FERRUPS models.
RS-232 Communication Port
Alarm Silence Switch
On/Off Switch
Power Cord
Figure 3. FERRUPS 500–850 VA UPS Rear Panel
On/Off Switch
Figure 4. FERRUPS 1.15–1.4 kVA Rear Panel
Output Receptacles
RS-232 Communication Port
Alarm Silence Switch
Output Receptacles
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
23
UPS Startup
Communication Port
RS-232
ON/OFF Switch
RS-232 Communication Port
Alarm Silence Switch
Output Receptacles
Figure 5. FERRUPS 1.8–3.1 kVA Rear Panel
Receptacle Panel (Optional for 7 kVA)
RS-232 Communication Port
Optional Receptacle
24
Panel
4.3–5.3 kVA Models 7–18 kVA Models
Figure 6. FERRUPS 4.3–18 kVA Rear Panels
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
CHAPTER 4
OPERATION
This section describes:
The UPS front panel indicators
:
Using the control panel
:
Automatic system testing
:
Parameters
:
Shutting down the UPS
:
Front Panel Indicators
The UPS front panel indicators indicate how the UPS is operating and also alert you of potential power problems. Figure 7 shows the UPS front panel indicators. Table 2 explains the status of each indicator.
AC LINE READY CHARGING
Figure 7. Front PanelIndicators
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
BATTERY
POWER
ALARM
25
Operation
Table 2. IndicatorStatus
Indicator Status Explanation
AC LINE
READY
CHARGING
BATTERY POWER
ALARM
On The UPS is getting power from the AC input power source.
NOTE
The AC LINE indicator does not illuminate for FE models with serial numbers
25000 and greater until the UPS ON/OFF switch is turned to the ON position.
Off : The UPS is not getting input power.
: There is a power outage. : The AC input breaker is tripped. : The UPS is unplugged. : For FE models with serial numbers 25000 and greater, the ON/OFF switch is not in
the ON position.
Flashing Not applicable.
On The UPS is ready to provide battery backup power when needed. Off The UPS cannot provide battery backup power because:
: It is in the Line Condition mode or the Off mode (see “Using the Control Panel” on
page 27).
: The batteries may be discharged. : It may be running on battery power.
Flashing The UPS is testing the batteries as part of the automatic system test (see “Automatic
System Test” on page 31); or, you have started a timed shutdown (see Table 8 on
page 44). On The UPS is charging its batteries. Off The battery charger is off; batteries are at full charge.
Flashing Not applicable.
On The UPS is providing power from its batteries; it is in the Inverter On mode. Off The UPS is providing conditioned power from the AC input power source, or the UPS is
off.
Flashing The UPS is testing the inverter as part of the automatic system test (see “Automatic
System Test” on page 31). On The UPS is warning you that an alarm exists. If you have not silenced the alarm, the
beep sequence identifies the problem (see “Alarms” on page 59.) If you have a control
panel, an alarm message appears on its display. Off No alarm exists.
Flashing Not applicable.
26
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Using the Control Panel
The control panel comes with all FE/QFE 4.3–18 kVA models. If you have an FE/QFE 500 VA–3.1 kVA, you may have ordered the control panel as an option (refer to TIP 407 to connect the control panel).
The control panel is attached to the front of the UPS with a 6-ft (1.8m) cable, providing hand-held operation. The control panel’s READY, BATTERY POWER, and ALARM indicators work like the READY, BATTERY POWER, and ALARM indicators on the front of the UPS (see “Front Panel Indicators” on page 25.)
You can use the control panel to change UPS system modes and display and change parameters. You can also lock the control panel and change some of its features. If you press the wrong key at any time, press [CLEAR] and then the correct key. The control panel makes a clicking noise each time you press a key.
Changing Operating Modes
There are four UPS operating modes:
Auto
:
Inverter On
:
Line Condition
:
Off
:
The FERRUPS UPS selects the appropriate operating mode automatically; however, there may be times when you need to set the operating mode manually from the control panel. Notice that names of the operating modes appear in red on the bottom of keys 1–4.
Operation
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
27
Operation
Table 3. Operating Modes
Operating Mode How to Select It What It Means
Off Press [CTRL]-[1]
[ENTER] [ENTER].
Auto Press [CTRL]-[2]
[ENTER] [ENTER].
Line Condition Press [CTRL]-[3]
[ENTER] [ENTER].
Inverter On (Battery Power)
Press [CTRL]-[4] [ENTER] [ENTER].
Entering Passwords
Before you can change some parameter values, you must enter a password. You must also enter a password before you enter some of the commands listed on page 44.
NOTE Some parameters, such as Time, Date, and User ID,are not password-protected initially. If you change parameter 39 to “Yes,” a User password is
required to change these parameters, use [CTRL] keys, or use some commands. See “Parameters” on page 32 and “Entering Commands froma Terminal or Computer” on page 44 for more information.
The UPS does not provide power to your equipment, but you can still use the control panel if battery power is present. The READY indicator is off.
This is the normal operating mode. The UPS conditions AC input power and provides the conditioned power to your equipment. The UPS is ready to switch to battery power if necessary. The AC LINE and READY indicators are illuminated.
The UPS is conditioning AC input power and providing the conditioned power to your equipment, but if there is a brownout or power outage, the UPS does not switch to battery power. Instead, the UPS shuts down its output until AC input power is available again. The READY indicator is off when the UPS is in this mode.
The UPS converts battery power to AC power for your equipment. It does not charge the batteries. The BATTERY POWER indicator is on. The UPS calculates the runtime remaining and sounds an alarm when runtime starts to get low.
28
The User Password is 377. If you need a higher password, call your service representative. To enter the User Password, follow these steps:
Press this key: Display shows: [CLEAR]
)(55836
[PROGRAM] 3DVVZRUG [3] [7] [7] 3DVVZRUG  [ENTER] /HYHO 8VHU
To clear the password, press [CLEAR] until 3DVVZRUG &OHDUHG appears on the control panel display.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Operation
Displaying and Changing Parameters
The names of the first 11 parameters appear in green on the top of the number keys. To display a parameter, press [DISPLAY], the parameter number, and [ENTER]. For example, to display parameter 0 (time), follow these steps:
Press this key: Display shows: [DISPLAY] [0] 'LVSOD\ [ENTER]  7LPH 
To change a parameter, display it first. Then, press [PROGRAM], enter the new value for the parameter, and press [ENTER]. For example, to change parameter 0 (time), follow these steps:
Press this key: Display shows: [DISPLAY] [0] [ENTER] [PROGRAM]  3JP [9] [3] [0]  3JP  [ENTER]  7LPH 
'LVSOD\
 7LPH 
Locking and Unlocking the Control Panel
You may need to lock the control panel if you want to limit its use. When disabled the control panel does not respond to the key functions until it is enabled again. To disable the panel, press the keys shown in the following example (verify that you have the necessary code to unlock the control panel).
Press this key: Display shows: [CLEAR] and [ENTER] together
When you lock the control panel, it beeps and shows the display above for approximately two seconds. The control panel beeps and shows this display whenever you try to use the keys. The front panel indicators continue to show the UPS status, and the control panel shows UPS alarms. To enable the control panel again,
Press this key: Display shows: [CLEAR] and [ENTER] together [8] [2] [0] [4] [9] 8QORFN   [ENTER] .H\SDG 8QORFNHG
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
.H\SDG /RFNHG
8QORFN 
29
Operation
After approximately two seconds, the control panel shows the same display it showed before you unlocked it. If you enter the wrong unlock number, the control panel displays
.H\SDG /RFNHG for two
seconds, and the control panel remains locked.
Using the Configuration Menu
The control panel includes a Configuration Menu that lets you adjust its baud rate and brightness, turn the beeper on or off, turn on and off the click you hear when you press keys, and control other features. The label on the back of your control panel includes more information on this menu (see Figure 8).
5HPRWH &RQWURO 3DQHO 5&3
$FFHVV ,QVWUXFWLRQV IRU &RQILJXUDWLRQ 0HQX
6LPXOWDQHRXVO\ SUHVV DQG WR HQWHU 5&3
&RQILJXUDWLRQ PHQX
$W DQ\ WLPH 3UHVV WR GLVSOD\HGLW QH[W PHQX LWHP
3UHVV WR H[LW PHQX DQG VDYH FKDQJHV 3UHVV WR H[LW PHQX ZLWKRXW VDYLQJ FKDQJHV
>&21752/@ >352*5$0@
>(17(5@ >352*5$0@
>&/($5@
0HQX ,WHP 5DQJH 1RWHV
%DXG 5DWH %ULJKWQHVV %HHSHU .H\FOLFN 5HSHDW &RQQHFW
     
            'LVSOD\ EULJKWQHVV  0LQ  0D[ %HHSHU HQDEOHG"  1R  <HV .H\FOLFN HQDEOHG"  1R  <HV $XWRUHSHDW RI GHSUHVVHG NH\"  1R  <HV 6HQG ´'&3µ DW VWDUWXS"  1R  <HV
Figure 8. Remote Control Panel
30
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Automatic System Test
The UPS performs an automatic system test every seven days to test the memory, batteries, and inverter. During the system test, the BATTERY POWER and READY indicators Flash. For the results of the last system test, you can display parameter 26 (see page 35).
Logic Test
First, the UPS checks its memory. If it finds a problem, the UPS sounds alarm O, Memory Check (
Inverter Test
The inverter converts DC battery power into the AC power your equipment uses. During the inverter test, the UPS pulses its inverter to see if it delivers the proper amount of current. If not, the UPS sounds alarm N, Check Inverter (
Although it is testing the inverter, the UPS is not in Inverter On mode. The UPS continues to condition input power and is ready to provide battery power if there is a power outage. The BATTERY POWER indicator flashes during this part of the test.
Operation
–––). See “Alarms” on page 59.
– :). See “Alarms” on page 59.
NOTE FE models with serial numbers 25000 and greater do not perform an individual inverter test.
Battery Test
The UPS also checks its batteries to verify that they can support your equipment for the minimum specified runtime. If not, the UPS sounds alarm M, Check Battery ( indicator flashes during this part of the test.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
––). See “Alarms” on page 59. The READY
31
Operation
Parameters
Table 4 shows the first 26 parameters. You can view or reset the parameters using the control panel or a terminal or computer.
If you plan to view or change parameters from the control panel, see
“Using the Control Panel” on page 27 for instructions. If you plan to view or change parameters from a terminal or computer
that you have connected to the RS-232 port, see “Entering Commands from a Terminal or Computer” on page 44. When you use commands to display or change parameters, identify the parameter with either its number or name (see Table 4). If you use the name, you can enter the entire parameter name or just the short form; you can also abbreviate the parameter name as long as your abbreviation includes the letters in the short form.
Although you do not need a password to view any of the first 26 parameters, all of them require a password to change (see the password column in Table 4.) See “Entering Passwords” on page 28 or “Entering Commands from a Terminal or Computer” on page 44 for password information.
NOTE All changeable parameters except 0 (Time), 10 (Date), and 15 (Unit ID) are set at the factory. Only qualified technicians using the proper metering equipment should change other parameters. Improper calibration may cause the FERRUPS UPS to malfunction. Call your service representative before you attempt to change any parameters except 0, 10, and 15.
Table 4. Parameters
Parameter
Number
0 00 Time 07:04:00 None time
1 01 V In 120.7 Service acvoltsin
2 02 V Out 120.7 Service acvoltsout
32
Sample Display Password Parameter Name
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
(Short Form)
(t)
(vi)
(vo)
Explanation
System Time. The UPS uses this time to record alarms and inverter runs. When the DC power has been off and you restart the UPS, the time shown is the last recorded time before shutdown. Reset time when DC power has been off.
The input voltage the UPS is receiving. When this value drops below the brownout voltage, the UPS switches to inverter.
The voltage the UPS is providing to your equipment.
Operation
PasswordSample DisplayParameter
Number
3 03 --Reserved-- Reserved 4 04 I Out 3.1 Service acampsiout
5 05 VA Out 374 Change Not
Allowed
6 06 I Batt 0.0 Service ibatt
7 07 V Batt 48.51 Service vbatt
8 08 Freq 60.43 Hz Change Not
Allowed
9 09 RunTime 12m Change Not
Allowed
10 10 Date 06/01/93 None date
11 or
[DISPLAY]
[1] [1] [ENTER]
12 12 SinkTemp 26c Change Not
13 13 --Reserved-- Reserved
11 Amb Temp 23c Change Not
Allowed
Allowed
(Short Form)
(o)
vaout
(va)
(ib)
(vb)
frequency
(f)
runtime
(rt)
(d)
ambtemp
(at)
heatsinktemp
(st)
ExplanationParameter Name
The current your equipment is drawing from the UPS.
Volt-Amps Out. The total “apparent power”
your equipment is drawing from the UPS. This value is based on parameter 2 multiplied by parameter 4, and should be less than or equal to the VA or kVA rating of the UPS. See VA Limit, parameter 19.
Battery Current. When the UPS is running on AC input, this is the charging current inA. When the UPS runs on battery power (inverter), this is the amount of current (inA) the batteries are supplying to the UPS.
Battery Volts. The present battery voltage. The UPS sounds an alarm if this value is too low.
In normal operation, this is the frequency of power the UPS is receiving from the AC input source. If this value falls outside preset limits, the UPS goes to battery power. When the UPS is running on battery power, this is the frequency the UPS is supplying to your equipment.
Estimated Runtime Remaining. The amount of time the UPS continues to support your equipment when the UPS is running on battery power. The UPS sounds an alarm when this value falls below a preset limit.
System Date. The UPS uses this date to record alarms and inverter runs. The date must be reset when you restart the UPS after DC power is turned off.
The temperature (in Celsius) inside the UPS. The UPS sounds an alarm and shuts down if this value is too high.
The temperature of the heatsink. The UPS sounds an alarm if this value is too high.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
33
Operation
PasswordSample DisplayParameter
Number
14 14 XfmrTemp 28c Change Not
Allowed
15 15 Unit ID
Network #1 UPS
(See “Entering
Passwords” on
page 28.)
16 16 FullLoad% 075 Change Not
Allowed
17 17 Watts 374 Change Not
Allowed
18 18 PF 0.73 Dist Change Not
Allowed
19 19 VALimit 500 Change Not
Allowed
20 20 #PwrOut 1 Change Not
Allowed
21 21 #OvrLds 0 Change Not
Allowed
22 22 SysHrs 00000 Change Not
Allowed
23 23 InvMin 0000.0 Change Not
Allowed
None
(Short Form)
xfmrtemp
(xt)
unitident
(id)
fullload
(l)
watts
(w)
powerfact
(pf)
valimit
(val)
powerout
(po)
overloads
(ol)
syshours
(sh)
invmin
(im)
ExplanationParameter Name
The temperature of the transformer. The UPS sounds an alarm and shuts down if this value is too high.
NOTE
This parameter is only active on some models; for other models, the display always shows -63c.
UPS ID. An identification string that can be configured for use with your network.
Percent of Full Load. The percentage of the UPS’s total capacity that is actually being used by your equipment.
The total “real power” your equipment is drawing from the UPS.
The power factor of your equipment; the difference in the way it draws voltage and current. Power factor is equal to Watts Out (parameter 17) divided by VA Out (parameter 5). This parameter also tells whether the power factor is leading (Lead), lagging (Lag), or distortion (Dist).
The maximum volt-amps the UPS can supply to your equipment at the present power factor. The UPS sounds an alarm when VA Out (parameter 5) is higher than this value.
The number of times there has been a loss of input power since you started the UPS.
The number of times the UPS has sensed an overload; that is, the number of times VA Out has been greater than VA Limit.
The total number of hours the UPS has been operating, regardless of mode. This number does not increase when the UPS ON/OFF switch is in the OFF position.
The total number of minutes the inverter has run since startup.
34
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Operation
PasswordSample DisplayParameter
Number
24 24 Inverter Log
L 0319 2127 1215
25 25 Alarm Log
A 0319 2127 1215
26 26 Test Results
(See explanation.)
Additional Parameters
above are alarm and operation set points, calibration factors and other settings. You usually do not need access to these parameters for normal operation of the UPS. If you need information about the full range of UPS parameters, call your service representative to ask for TIP 407 or TIP 503. TIP 407 describes communication from a control panel. TIP 503 describes communication through the RS-232 port.
The microprocessor in the UPS keeps track of more than 100 parameters. Parameters 27 and
Change Not
Allowed
Change Not
Allowed
Change Not
Allowed
(Short Form)
inverterlog
(il)
alarmlog
(al)
testresults
(tr)
ExplanationParameter Name
A record of the date, time, duration and reason for the last 20 inverter (battery power) runs (see “Alarm and Inverter Logs” on
page 62). A record of the date, time, duration and
reason for the last 20 alarms (see “Alarm and Inverter Logs” on page 62).
This parameter records the results of the last system test. The parameter display includes the time and date of the test and the results of each part of the system test (see “Automatic System Test” on page 31.)
UPS Shutdown
The FERRUPS UPS is designed for many years of round-the-clock operation. Usually, you do not need to shut down the UPS, even if your equipment is shut down for several days. Even when it’s not powering
your equipment, the UPS monitors its internal condition and keeps the Time and Date parameters current.
There are times, though, when you want to shut down the UPS, such as:
1. When you do not expect to use it for an extended period of time.
2. When it is being serviced.
3. Before you move it.
4. When it has gone into the Off mode because the batteries have
been discharged during an extended outage.
5. When a system malfunction requires a UPS shutdown.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
35
Operation
CAUTION
When AC input voltage is present, the UPS system can provide output voltage even though its batteries are disconnected. To confirm that there is no UPS output voltage, always disconnect the AC input source; if the UPS has one or more separate battery cabinets, open the DC disconnect switch on each battery cabinet or disconnect the battery cabinet from the UPS.
1. UPSs with no bypass switch: Turn off the protected equipment.
Continue to Step 2. If you need to use the equipment while the UPS is off, plug the
equipment into standard wall outlets and restart the equipment.
UPSs with a Break-Before-Make (BBM) bypass switch (see the label
on the side of the switch): Shut down the protected equipment. Turn the bypass switch to the LINE position. Continue to Step 2.
If you need to use the equipment while the UPS is off, restart the equipment. The equipment receives direct AC line instead of conditioned power from the UPS.
UPSs with a Make-Before-Break (MBB) bypass switch (see the label
on the side of the switch): Verify that the AC LINE indicator is on, the BATTERY POWER indicator is off, and the UPS is providing output. If all three of these conditions are present, turn the bypass switch to the LINE position. Your equipment receives direct AC line instead of conditioned power from the UPS. Continue to Step 2.
If all three of these conditions are not present, follow Steps 2–4
before you turn the bypass switch to the LINE position. This causes a break in power to your equipment between shutting down the UPS and turning the bypass switch to the LINE position.
36
CAUTION
Equipment can be damaged if you change the switch position when line is applied and the UPS is off or on battery! Refer to TIP 410.
2. Turn the UPS ON/OFF switch to the OFF position.
3. If the UPS is plugged in, unplug it. For hardwired models, turn
the AC line disconnect switch to the OFF position.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Operation
4. 500 VA–3.1 kVA: If you have a battery cabinet that has a DC
switch on the front, turn the switch to the OFF position. If your battery cabinet does not have a DC switch on the front, unplug the connector between the battery cabinet(s) and the UPS; be sure to reconnect this connector before you start the UPS again.
4.3–18 kVA: Unlock the lock in the center of the front panel and
remove the panel. If there is a DC switch behind the panel, turn it to the OFF position. Reattach the panel to the UPS. If your UPS has separate battery cabinets, turn the DC switch at each battery cabinet to the OFF position.
If the UPS is turned off for an extended period of time, recharge the
5.
batteries every 90–120 days to prevent battery damage. To restart the UPS, see “Startup” on page 17.
Extended Power Outages
If the power is out for an extended time, the UPS continues to provide power for your equipment until it gets near the end of its runtime. You can check the remaining battery runtime by reading parameter 9 (see page 33.) At a preset number of minutes before the end of the runtime (factory-default setting is five minutes), the UPS sounds a Low Runtime alarm (– conserve the remaining battery power (see “UPS Shutdown” on page 35). When AC input power returns, turn on the UPS to recharge the batteries.
If your UPS shuts itself down because its battery voltage is too low, shut down the UPS until the AC input power returns (see “UPS Shutdown” on page 35).
::). Shut down your equipment and turn off the UPS to
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
37
Operation
38
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
CHAPTER 5
COMMUNICATION
The FERRUPS UPS is capable of full-duplex communication and can communicate with a computer, a Local Area Network (LAN), or a multi-user computer system. If your system comes with UPS monitoring and automatic shutdown software, the FERRUPS UPS can communicate with that software. If your system does not have software, you can use the CheckUPS II Power Management Software included on the Powerware Software Suite CD-ROM.
If you do not plan to use CheckUPS II software or other UPS monitoring software, you can still set up RS-232 communication with the UPS and use commands and parameters to control UPS operation.
Powerware Software Suite
Each UPS ships with the Powerware Software Suite CD-ROM and a communication cable. To begin installing CheckUPS to the instructions accompanying the Powerware Software Suite CD-ROM.
CheckUPS II software uses an RS-232 serial link to communicate with the UPS, and (using Microsoft up-to-date graphics of UPS power and system data and power flow. It also gives you a complete record of critical power events and notifies you of important UPS or power information. If there is a power outage and the UPS system battery power becomes low, CheckUPS II software can automatically shut down your computer system to protect your data before the UPS Low Battery shutdown occurs.
NOTE You can download the latest software version from www.powerware.com.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
9
Windows9)itprovidesyouwith
9
II software, refer
39
Communication
gpy
gpg
Moni
toring”
47)
Communication Port
The communication port cable pins are identified in Figure 9 and the pin functions are described in Table 5.
Figure 9. Communication Port
Table 5. Communication Port Pin Functions
Pin Function Function
2 Transmit Data (in) 3 Receive Data (out) 4 Request to Send 5 Clear to Send 6 +12V Level (0.01A) when the UPS is operating 7 Signal Ground
11 Contact opens when on
inverter
12 Contact closes when on
inverter
13 Common Inverter Signal
Contact 14 +12V, 0.5A (500 VA–3.1 kVA) or 0.3A (4.3–18 kVA) Do not use for setting logic levels. 18 +12V Level (0.01A) when UPS is operating 20 AS/400 Option 21 Remote Shutdown 23 Contact closes on alarm
24 Common Alarm Signal Contact
25 Contact opens on alarm
NOTE
Pins 2–5 and 7 are for RS-232 communication, Pins 11–13 and 23–25 are for remote monitoring, and Pin 21 (used with 6 or 18) is for remote shutdown. The following sections describe how to take advantage of these features. Pin 20 is for option use only.
To enable hardware handshaking on these pins, call your service representative.
These relay contacts are rated at 25 Vac/Vdc and 250 mA (see “Remote
Monitoring” on page 47).
NOTE
FE 500 VA–3.1 kVA models with serial numbers 25000 and greater have
equivalently rated DC solid state switches.
These relay contacts are rated at 25 Vac/Vdc and 250 mA (see “Remote
on page
Pins 23 and 25 change status when the UPS is turned off.
NOTE
FE 500 VA–3.1 kVA models with serial numbers 25000 and greater have
equivalently rated DC solid state switches.
.
40
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Connecting a Terminal or Computer to the RS-232 Port
CAUTION
Do not make connections to the RS-232 communication port if the UPS is connected to a positive ground battery system. The RS-232 ground must be isolated or equipment damage will result. For help, contact your service representative.
If you are connecting a terminal to the RS-232 port, the terminal must be capable of serial communication.
If you are connecting a computer, the computer must be running terminal emulation software (such as HyperTerminal software packages can emulate a terminal; if you do not have a terminal emulation program, please contact your service representative for more information.
1. To connect the FERRUPS UPS DB-25S (female) RS-232 port to your terminal or computer, you need a cable designed specifically for this purpose. (See Figure 10 and Figure 11.) Powerware offers cables for computers or terminals using 25-pin or 9-pin serial ports; call your service representative to order one of these cables. If you would like to build your own cable, follow these requirements:
Use a high-quality, shielded cable.
:
Do not use a standard 25-conductor straight-through cable;
:
only include straight-through connections for the pins shown in Figure 10 and Figure 11.
For RS-232 communication, use Pins 2 (transmit data), 3 (receive data), and 7 (signal ground). For hardware handshaking (request to send on Pin 4 and clear to send on Pin
5), contact your service representative. No other pins should be connected from the UPS RS-232 port to your terminal or computer.
For more information on pin connections and the function of the non-serial pins on the RS-232 port, see Table 5 on page 40 and “Remote Monitoring” and “Remote Shutdown” on page 47.
Communication
9
). Most modem
NOTE To connect a modem, see TIP 503.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
41
Communication
Figure 10. DB-9 to UPSPinout
Figure 11. DB-25 to UPSPinout
42
2. Connect the cable from the RS-232 port on the back of the UPS to the serial port on your terminal or computer.
3. Your terminal or computer should be set to: 1200 baud, 8 bits, No parity, 1 stop bit, and full duplex.
The terminal or terminal emulation software should also be set to full duplex. If you are using a terminal, note that the
9
FERRUPS UPS supports the Televideo
9
WYSE
50 emulation.
900 series, ADM3A and
Table 6 shows the standard settings at the UPS DB-25S port and the settings that can be adjusted. Call your service representative if you need to adjust any of the settings.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Communication
Table 6. DB-25 Port Settings
Specification Standard Setting Adjustable to
Connector 25 pin D (female) wired as DCE.
Format ASCII, 8 bits, 1 stop bit.
Most significant bit set to 0.
Baud Rate 1200 50–38400
Parity None Odd, Even, or None
Duplex Full Full or Half
Standard setting or
7/8 bits, 1/2 stop
4. Turn your terminal on or run your terminal emulation software. Then press [ENTER] on your keyboard; a prompt appears on the screen. The prompt varies depending on your current password level:
=> Normal prompt User=> User Password has been entered
5. Press [ENTER] on your keyboard a few times to verify that the UPS responds.
6. To control or monitor the UPS, simply type the desired command and press [ENTER].
Table 7 shows what keystrokes to use as you type commands or view displays. See Table 8 for more information on UPS commands.
Table 7. Keystroke Commands
Action Key Sequence
Delete last character typed. [BACKSPACE] or [CTRL]-[H]
Delete line. [CTRL]-[X]
Pause displays that take more than one screen. [CTRL]-[S]
Resume scrolling. (Turn Pause off.) [CTRL]-[Q]
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
43
Communication
Entering Commands from a Terminal or Computer
To monitor or control the FERRUPS UPS from a terminal or computer, simply type in one of the commands and press [ENTER] (see Table 8). Use the following command syntax:
type the command in uppercase or lowercase
:
use the entire command or the short form (you can also abbreviate
:
the command as long as you include the letters in the short form use a semicolon to separate more than one command on a line
:
Table 8. Commands
Command Short
Form
alarmshelp ah None Shows a list of all possible alarm messages, the audio code and letter for
alarmlog al None Displays Alarm Log. See “Alarm and Inverter Logs” on page 62.
alarmtest at None Allows you to test the alarm function.
alarmtest cancel at c None Turns the User Test alarm off. chargermode chm None* Shows the UPS battery charger mode. By entering a mode after the
clearalarms ca None Clears all active alarms. clearhistory ch None Clears the minimum and maximum parameter values shown when you
clearpassword cp None Clears the current password. commands cm None Displays a list of all valid commands. contdisplay cd Depends
contstatus cs None Continuously displays the Status information (see the *If you change parameter 39 to “Yes,” this command requires a User password.
Password Function
each alarm and whether the alarm is active.
alarm (J). See page 61.
chargermode
: chargermode off (chm f) or chargermode disable (chm d) = charger off : chargermode on (chm o) or chargermode enable (chm e) = charger on : chargermode auto (chm a) = charger enabled if AC input voltage and
battery voltage are acceptable
use the
Continuously displays the parameter that you are currently displaying.
on
You can specify other parameters for the continuous display by entering
parameter
password
the name or number of each parameter after the
Alarmtest
command, you can change the charger mode:
extendedhistoryorhistory
commands.
sounds the User Test
contdisplay
status
command.
command.)
44
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Communication
Command
FunctionPasswordShort
Form
date da None* Displays system time and date. To set the date, enter
[month]/[day]/[year]
.
delay dl None Delays next command when you enter a number after
display d Depends
on
parameter
password
represents 2.5 milliseconds, so delay. For a 1-second delay, enter
Displays the values of one or more parameters (see Table 4 on page 32). Format: display [parameter # or name] [parameter # or name] Example:
d 1 fullload ol
delay 1
would cause a 2.5millisecond
delay 400
.
displays the values of parameters 1, 16 and 21
date
delay
. Each unit
extendedhistory xh None Displays the minimum and maximum values of parameters 1 (Vac In),
2 (Vac Out), 7 (Vdc) and 5 (VA Out); the command then clears the minimum and maximum values (see Table 4 on page 32).
format f None Displays an 80-character line containing information on the FERRUPS
status. CheckUPS II and other UPS monitoring software use this data. help ?orhe None Shows a list of terminal/computer commands. history h None Displays the minimum and maximum values of parameter 1 (Vac In); the
command then clears the minimum and maximum values. identify I None Shows Powerware’s address and telephone number and the software
version. inverterlog il None Displays the Inverter Log. See “Alarm and Inverter Logs” on page 62. logs l None Displays both the Alarm and Inverter Logs. See “Alarm and Inverter Logs”
on page 62. off [time] o [time] None* Shuts down the UPS a given number of seconds. The READY indicator
flashes until the UPS shuts down, and the UPS beeps five seconds before
shutdown. Example:
OFF 60
shuts down the UPS in 60 seconds.
off [time] autostart o [time]aNone* Shuts down the UPS in a given number of seconds (see above), and
restarts the UPS shortly after power returns. off cancel oc None* Cancels timed shutdown. parameters p Depends
parameter
password
Shows a list of system parameters. See “Parameters” on page 32. You
on
can also display a range of parameters by entering the starting and
ending parameter number or name after the command.
Example:
Parameters 1 10
displays parameters 1 through 10.
*If you change parameter 39 to “Yes,” this command requires a User password.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
45
Communication
Command
FunctionPasswordShort
Form
paramkeywords pk Depends
parameter
Displays all parameters and their keywords (the names you can use with
on
commands). You can also display a range of parameters by entering the numbers or names of the starting and ending parameters.
password
password pw None Allows you to enter the User Password. Typing
password
alone clears
the current password.
program pr Depends
on
parameter
password
Example:
password 377
Lets you set the value of any parameter. You must enter the appropriate password before you reset the value. See the Password command above. Format: PR [parameter # or name] [newvalue] Example:
PR 0 815
enters the User Password.
resets the time (parameter 0) to 8:15 a.m.
remote rm None Configures the RS-232 port so the connected terminal works like a
control panel.
shutdown or shutdown autostart
sd
sd a
None* Shuts down the UPS output in 60 seconds (if you enter shutdown alone)
or the number of seconds you specify after the command. The READY indicator flashes until the UPS shuts down. If you specify autostart,the UPS restarts shortly after power returns.
shutdown cancel sd c None* Cancels a shutdown started with the shutdown command. shutup sh None Turns off audible alarm. status s None Shows date, time, system status, present system mode, active alarms,
and the value of various system parameters.
systemmode _ sm None* Typing
systemmode
You can use
alone displays which system mode is now active.
systemmode
witha,o,i,orlto enter one of the modes
below.
systemmode auto sm a None* Enters the Auto mode. This is the normal FERRUPS UPS mode. In this
mode, the UPS provides conditioned AC power to your equipment; if there is a power outage, the UPS is ready to switch to battery power.
systemmode off sm f None* Enters the Off mode. In this mode, the UPS is not providing power to your
equipment, but you can still use the UPS control panel.
systemmode inverter sm I None* Enters the Inverter On mode. In this mode, the UPS is converting DC
battery power to AC power for your equipment.
systemmode linecondition
sm l None* Enters the Line Condition mode. In this mode, the UPS provides
conditioned AC power to your equipment, but it does not switch to battery power if there is a power outage. Instead, the UPS sounds a Low AC Out alarm.
*If you change parameter 39 to “Yes,” this command requires a User password.
46
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Communication
Command
Form
systemtest stst None* Starts a system test of the logic, inverter and battery. time t None Shows the current UPS time. To set the time, enter
unshutup u None Turns audible alarm back on. *If you change parameter 39 to “Yes,” this command requires a User password.
FunctionPasswordShort
the command.
Remote Monitoring
Alarm Signal Contacts: These are relay contacts (rated at 25 Vac/Vdc and
250 mA) that change status on any alarm condition or when the UPS is turned off. Contacts that close on an alarm are available between Pins 23 and 24. Contacts that open on an alarm are available between Pins 24 and 25.
Inverter On Signal Contacts: These are relay contacts (rated at 25 Vac/Vdc
and 250 mA) that change status when the inverter turns on. Contacts that close on inverter operation are available between Pins 12 and 13. Contacts that open on inverter operation are available between Pins 11 and 13.
NOTE FE 500 VA–3.1 kVA models with serialnumbers 25000 and greater have equivalently rated DC solid state switches.
[hour]:[minutes]
after
Remote Shutdown
The FERRUPS UPS can be connected to a remote shutdown switch to shut off output from the UPS to your protected equipment. The shutdown switch must have a set of contacts that can apply the UPS’s
+12 Vdc on Pin 6 to the UPS’s Pin 21. (You can use Pin 18 instead of
do not use Pin 14.) Use a shielded, single twisted-pair cable to
Pin 6; connect the switch to the UPS pins. A connection between Pins 6 and 21 (or 18 and 21) shuts down UPS output power to the protected equipment.
When the UPS Remote Shutdown feature has been activated, the UPS is in the Off mode and the Emergency Power Off alarm sounds. A control panel or a terminal connected to the UPS displays “Emergency PwrOff.”
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
47
Communication
To restart the UPS, break the connection between Pins 6 and 21 (or between Pins 18 and 21) at the UPS’s RS-232 port. Then, follow the
steps in “Startup” on page 17 for your model. Note that the 12V level on Pin 6 or Pin 18 is only available when the UPS is operating.
You can change the type of signal that the UPS responds to and how quickly it responds. You can also set up the UPS to restart automatically when the shutdown signal stops. See TIP 503 or contact your service representative for more information.
48
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
CHAPTER 6
OPTIONS
Powerware offers many options for your FERRUPS UPS. If you would like more information, contact your local Powerware office or distributor.
Bypass Switches
If your UPS does not have a plug, a bypass switch lets you transfer your protected equipment to direct AC input power conveniently when it’s
time to service the UPS. Contact your local Powerware office or distributor for recommendations and additional information on the different bypass switches.
Control Panel
Control panels and extension cables are available that provide UPS monitoring and operation from a remote location.
Environmental Monitoring
Powerware’s EnviroComZmonitors office and UPS conditions and phones you when there is a problem. EnviroCom II also lets you:
call the UPS for an update on its status and environment
:
control and communicate with the UPS through a modem
:
Extended Runtimes
If you want extended runtimes, call your local Powerware office or distributor for information on adding additional battery capacity or an optional battery charger.
Warranties
Besides our standard two-year warranty, Powerware offers several warranty enhancement plans to meet your service and maintenance needs. Contact your local Powerware office or distributor for more information.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
49
Options
50
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
CHAPTER 7
MAINTENANCE
NOTE Technicians must observe important safety precautions while performing these
checks.
The FERRUPS UPS is designed to provide years of trouble-free operation. Its internal control system checks the batteries and inverter periodically to ensure reliable operation. In fact, you’ll probably find
that your FERRUPS system requires less maintenance than any of your other computer peripherals.
Nevertheless, the FERRUPS UPS and optional external battery cabinets do require some attention to assure continued reliable service. Powerware recommends that you schedule preventive maintenance checks at least every six months. At these checks, the service technician should follow Powerware’s recommended maintenance schedule, which includes the following items:
Check operating environment for clean, cool, dry conditions.
:
Inspect and clean the unit.
:
View and record the alarm and inverter logs.
:
Check the batteries.
:
Check the AC and DC meter functions and recalibrate if necessary.
:
Perform an outage test.
:
Check and record the values of the first 19 parameters while the UPS
:
is online and on battery.
For more information on preventive maintenance checks, contact your service representative.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
51
Maintenance
52
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
CHAPTER 8
SPECIFICATIONS
Table 9. FE and QFE 500 VA–3.1 kVA
Model 500 VA/
350W
FE: 120 Vac
208 Vac
1
220 Vac
1
240 Vac
QFE:
120 Vac
220 Vac
230 Vac
240 Vac
Recommended AC Input Service: 60 Hz with
1
120 Vac
FE: 120 Vac
208 Vac
220 Vac
240 Vac
20 Vac
QFE: 1
220 Vac
230 Vac
240 Vac
Efficiency on AC Line
On Line BTU/hour: kW/hour:
Audible Noise (dB)
4.6A
2.4A
2.3A
2.1A
4.4A
2.6A
2.5A
2.4A
10A 10A 10A 15A 15A 20A 20A 30A
4.1A
2.3A
2.1A
4.1A
2.2A
2.2A
2.1A
85% 86% 85% 88% 88% 90% 90% 91%
210
.062
41 41 47 49 49 51 51 51
700 VA/
500W
AC Input Voltage and Current, Standard Charger
5.6A
2.8A
2.7A
2.5A
5.8A
3.9A
3.8A
3.5A
Output Voltage and Maximum Output Current
5.9A
3.3A —
2.8A
5.7A
3.2A
3.1A
2.9A
277
.081
850 VA/
600W
6.6A
3.7A
2.5A
3.2A
7.0A
4.4A
4.2A
4.0A
7.0A
4.0A —
3.4A
7.1A
3.8A
3.6A
3.5A
361
.106
1.15 kVA/ 800W
8.9A
5.0A
4.6A
4.2A
8.4A
4.9A
4.6A
4.4A
9.3A
5.3A
5.0A
4.7A
9.4A
5.0A
4.8A
4.6A
372
.109
1.4 kVA/ 1kW
11A
6.0A
5.8A
5.3A 11A
5.7A
5.4A
5.2A
12A
6.5A
6.1A
5.6A 12A
6.4A
6.2A
5.9A
465
.136
2
1.8 kVA/
1.25 kW
16A
9.2A
7.8A
8.2A 15A
7.9A
7.5A
7.2A
15A
8.4A
8.0A
7.3A 14A
7.9A
7.6A
7.2A
474
.139
2.1 kVA/
1.5 kW
19A 11A
9.4A
9.2A 16A
8.2A
7.8A
7.4A
17A
9.9A
9.0A
8.6A 17A
9.3A
8.9A
8.5A
568
.166
3.1 kVA/
2.2 kW
25A 14A 12A 12A 24A 13A 12A 12A
26A 15A 14A 13A 25A 14A 13A 13A
742
.217
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
53
Specifications
Model
500 VA/
350W
700 VA/
500W
850 VA/
600W
1.15 kVA/ 800W
1.4 kVA/ 1kW
1.8 kVA/
1.25 kW
2.1 kVA/
1.5 kW
3.1 kVA/
2.2 kW
Runtime (minutes) QFE Full Load:
Half Load:
FE Full Load:
9
25
9
14 35 11
11 28
9
18 48
8
14 37 11
11 30 11
9
25
9
Weight :
Without Battery:
60 Hz Models: 50 Hz Models:
44 lb
22.2 kg
46 lb
25 kg
51 lb
27.7 kg
92 lb
41.7 kg
106 lb
45.4 kg
120 lb
58.1 kg
132 kg
63.5 kg
144 lb
With Battery:
60 Hz Models: 50 Hz Models:
54 lb
28 kg
Dimensions (HxWxD)
1
Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown
30.5 x 25.5 x 54.0 cm
62 lb
36.3 kg
12x10” x 21.25”
67 lb
39 kg
102 lb
59.9 kg
122 lb
69.9 kg
15.1x 15.2x 20.2
38.5 x 39.0 x 51.5 cm
176 lb
83 kg
188 lb
89 kg
21.2x 15.25x 22.9
54.0 x 39.0 x 58.5 cm
248 lb
116.1 kg
are for the U.S. and Canada.
2
At 0.7 leading power factor.
Table 10. FE and QFE 4.3–18kVA
Model 4.3 kVA/
3kW
FE: 120 Vac
208 Vac
220 Vac
240 Vac
20 Vac
QFE: 2
230 Vac
240 Vac
Recommended Input Service for 60 Hz
2
Models
32A 18A 17A 16A 19A 18A 17A
120 = 40A
208 = 25A 240 = 20A
1
5.3 kVA/
3.7 kW
7kVA/
5kW
10 kVA/
7.5 kW
AC Input Voltage and Current, Standard Charger
1
1
38A 22A 21A 19A 21A 20A 19A
120 = 50A
208 = 30A 240 = 25A
1
1
51A 30A 27A 26A 27A 26A 24A
120 = 65A
208 = 40A 240 = 35A
1
208 = 60A 240 = 50A
— 45A 41A 39A 43A 41A 39A
12.5 kVA/ 10 kW
— 58A 53A 50A 55A 53A 51A
208 = 75A 240 = 65A
18 kVA/
15 kW
— 86A 81A 76A 81A 78A 75A
208 = 115A 240 = 100A
14 35 14
69 kg
54
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Specifications
Model
FE: 120 Vac
208 Vac
220 Vac
240 Vac
20 Vac
QFE: 2
230 Vac
240 Vac
Efficiency On AC
4.3 kVA/ 3kW
34A 20A 19A 17A 19A 18A 17A
5.3 kVA/
3.7 kW
7kVA/
5kW
10 kVA/
7.5 kW
Output Voltage and Maximum Output Current
44A 26A 24A 22A 23A 22A 21A
58A 34A 31A 29A 31A 30A 28A
82A 48A 46A 41A 45A 43A 41A
3
12.5 kVA/ 10 kW
103A
58A 55A 51A 56A 52A 51A
90% 90% 90% 90% 91% 92%
18 kVA/
15 kW
149A
84A 82A 73A 84A 76A 73A
Line On Line BTU/hour:
kW/hour:
1138 .333
1403
.411
1896
.556
2844
.833
3375
.989
4452
1.3 Audible Noise (dB) 50 51 54 55 56 57 Runtime (minutes)
Full Load: Half Load:
8
20
20 50
12 33
11 26
18 48
10 26
Weight :
Without Battery:
60 Hz Models: 50 Hz Models:
243 lb
115.7 kg
268 lb
131.1 kg
362 lb
176.5 kg
442 lb
217.7 kg
505 lb
251.3 kg
625 lb
312.1 kg
With Battery:
60 Hz Models: 50 Hz Models:
348 lb
163.3 kg
484 lb
229.1 kg
578 lb
274.4 kg
— —
— —
— —
N Cabinet with
Standard Batteries
Dimensions (HxWxD)
1
FE 4.3 kVA,5.3 kVA, and 7 kVA models have optional 120 Vac input voltage.
2
Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown
5
29.5” x 15.5” x 25”
75.0 x 39.5 x 63.5 cm
395 lb
(179.2 kg)
36.5” x 19” x 32”
93.0 x 48.5 x 81.5 cm
535 lb
(242.7 kg)
675 lb
(306.2 kg)
are for the U.S. and Canada.
3
At 0.7 to 0.83 leading power factor.
4
FE and QFE 10 kVA, 12.5 kVA, and 18 kVA models do not have internal batteries. Batteries are in a separate battery
cabinet or rack.
5
If your model has an internal bypass switch, add 8” (20.0 cm) to the depth.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
55
Specifications
Table 11. Electrical Input and Output
Nominal Frequency Online: 60 Hz (FE) or 50 Hz (QFE) with nominal power line grid stability of ±0.005 Hz.
On inverter: 60 Hz (FE) or 50 Hz (QFE) ±0.03 Hz. Output frequency tracks input line frequency up to limit, which is adjustable from ±0.01 Hz to ±3.00 Hz. Inverter turns on if line frequency exceeds the selected limit.
Regulation ±3% load regulation (under any line, load, or battery condition to within -8.3% and +5% of
nominal)
Voltage Waveform Sine wave; <5% THD at rated linear loads, computer-grade power Overload Capability On line (nominal Vac in): 150% surge and 125% for 10 minutes.
On inverter (nominal Vdc in): 150% surge and 110% for 10 minutes. Overload operation is not thermally limited. The FERRUPS UPS microprocessor continuously
monitors output VA and sounds an alarm before loss of output voltage regulation occurs.
DC Input Protection DC fuse and battery charger fuse Output Protection Output Protection: The ferroresonant transformer inherently limits current and provides
overload protection. The FERRUPS UPS has high AC and low AC output voltage alarms, as well as an overload alarm. If the AC output voltage falls below the low AC output voltage alarm setpoint, the UPS sounds an alarm after five seconds. If the AC output voltage falls below the low AC output shutdown setpoint, the UPS sounds an alarm and shuts down. Some models have output receptacles protected by fuses or circuit breakers.
Lightning and Surge Protection
Isolation, Including Output Neutral to Ground Bonding
The FERRUPS UPS provides 2000-to-1 spike attenuation. Tested using lightning standard per ANSI/IEEE C62.41 Category A (6000V spike and 200A) and Category B (6000V spike and 3000A) test, and ANSI/IEEE C62.45 test procedures.
The FERRUPS UPS provides a true separately derived power source, as defined by National Electrical Code Article 250-5d, with output neutral bonded to ground. There is no direct connection between input and output, and less than 2 pF of effective input to output capacitance.
56
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Specifications
Table 12. Environmental and Safety
Operating Temperature 0°C to 40°C (32°F to 104°F) Storage Temperature UPS with batteries: -20° to +40°C (-4° to 104°F)
UPS without batteries: -20° to +60°C (-4° to 140°F)
Relative Humidity 0–95% noncondensing Operating Altitude Up to 3,050 meters above sea level (10,000 ft)
The maximum operating ambient temperature decreases 1°C per 300m above 1525m (2°F per 1000 ft above 5000 ft)
Ventilation The air around the UPS must be clean and free of dust, corrosive chemicals, and other
contaminants. The FERRUPS UPS uses internal fans to circulate the air for cooling. The air must be free to circulate around the UPS and battery cabinet(s). Do not operate the UPS in a sealed room or container.
Noise Rejection Common Mode: Greater than 120 dB with output neutral bonded to ground
Transverse (Normal) Mode: Greater than 60 dB
Table 13. Battery
Voltage 500–850 VA models: Nominal battery voltage is 24 Vdc for 60 Hz, 12 Vdc for 50 Hz.
Standard battery charger output is rated at 2A.
1.15–1.4 kVA models: Nominal battery voltage is 48 Vdc Vdc for 60 Hz, 12 Vdc for 50 Hz. Standard battery charger output is rated at 2A.
1.8–3.1 kVA models: Nominal battery voltage is 48 Vdc. Standard battery charger output is rated at 4A.
4.3–7 kVA models: Nominal battery voltage is 48 Vdc. Standard battery charger output is rated at 5A.
10–18 kVA models: Nominal battery voltage is 120 Vdc. Standard battery charger output is rated at 5A.
Type Standard batteries are sealed, gas recombinant, lead-acid type, especially designed for
UPS use.
NOTE
Optional battery chargers at higher current ratings are available. Call your local Powerware office or distributor for
more information.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
57
Specifications
58
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
CHAPTER 9
TROUBLESHOOTING
When your FERRUPS UPS detects an alarm condition, the UPS displays the alarm with the following indications:
the ALARM indicator on the front panel (and the control panel if you
:
have one) illuminates sounds an audible alarm
:
displays an alarm message on the control panel (if you have one).
:
NOTE If the control panel does not display the message, press [CLEAR] until you reach the scrolling display.
Alarms
When an alarm occurs, follow these steps:
1. Find out which alarm condition the UPS is detecting. If you have a control panel, you can read the alarm on the
:
display. If you do not have a control panel, listen to the alarm code;
:
the UPS sounds the Morse Code for the alarm letter.
2. Find the alarm in Table 14 and follow the instructions to
resolve the problem.
3. To silence the alarm:
FE/QFE 500 VA–3.1 kVA models: Turn the Alarm Silence Switch on
the UPS rear panel to the OFF position.
FE/QFE 4.3–18 kVA models: Press [CTRL]-[5] [ENTER] [ENTER]
on the control panel.
4. After the alarm condition is cleared, turn the alarm beep back
on (using either the switch or the control panel).
NOTE If you do not turn the alarm beep back on, the UPS is not able to sound an alarm code the next time there is an alarm.
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
59
Troubleshooting
Table 14. Alarms
Letter Audio
Code
Alarm
Message
What It Means What To Do
A : – Low
Battery
B – ::: Near Low
Battery
C – : – : High
Battery
D – :: Low
Runtime
E : Low AC
Output
F ::– : High AC
Output
G ––: Output
Overload
H :::: Hi Ambient
Temp
I :: Hi
Heatsink
Temp
The UPS has shut down after running on battery and discharging the batteries.
The battery voltage has reached the Near Low Battery setpoint.
The battery voltage is too high because of a problem with the charging circuit or parameter settings.
The UPS is running on battery power, and the battery runtime remaining is low.
The output voltage is below a preprogrammed setpoint.
The output voltage is higher than the alarm setting.
Power requirements exceed UPS capacity (check the UPS VA rating) or the load is defective.
The temperature inside the UPS is too high. If the temperature reaches a preset point, the UPS shuts down.
The inverter temperature is too high. If the temperature reaches a preset point, the UPS shuts down.
Wait for AC input power to be restored. When AC input power returns, turn on the UPS. The CHARGING indicator illuminates as the UPS begins recharging batteries.
The alarm should clear itself when the battery charger has charged the batteries enough.
Contact your service representative.
Shut down your equipment and turn off the UPS to conserve battery power. When AC input power returns, turn the UPS on again.
The UPS shuts down. Shut down your equipment or bypass the UPS, and turn the UPS switch off. Contact your service representative.
Contact your service representative.
Turn off and unplug the UPS. Remove some of the equipment from the UPS. Restart the UPS. If the overload condition persists (125% for 10 minutes), the UPS automatically shuts down.
If the UPS has shut down, contact your service representative. If not, shut down the protected equipment and the UPS, correct the cause of the high temperature if possible, and turn the UPS on again. If the problem persists, contact your service representative.
If the UPS has shut down, contact your service representative. If not, shut down your equipment or bypass the UPS; turn the UPS off. Contact your service representative.
60
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Troubleshooting
Letter
Audio
Code
J : ––– User Test
K – : – Hi
L : – :: Check
M –– Check
N – : Check
O ––– Memory
P : ––: Emergency
Message
Alarm
Transfmr
Temp
Charger
Battery
Inverter
Check
PwrOff
What To DoWhat It MeansAlarm
The user is testing the alarm feature. To start the user test alarm from the
control panel, press [CTRL]-[8] [ENTER] [ENTER]. Repeat the procedure to turn the alarm off.
The transformer temperature is too high. If the temperature reaches a preset point, the UPS shuts down.
The UPS has detected a charger problem. Contact your service representative.
The batteries have failed the automatic system test.
The inverter has failed the automatic system test.
Possible microprocessor problem. Shut down your equipment or bypass the
The Remote Shutdown feature has been activated at the RS-232 port (see “Remote Shutdown” on page 47.)
The UPS may have shut down; if so, contact your service representative. If the UPS has not shut down, shut down your equipment or bypass the UPS; then, turn the UPS off and contact your service representative.
Contact your service representative.
Contact your service representative.
UPS; turn off the UPS. Contact your service representative.
To restart the UPS, disconnect the signal to Pin 21 on the RS-232 port. If you have a control panel, put the UPS in Auto mode. If not, turn the On/Off switch off and then on again.
Q ––: – Hi PFM
Res
Temp
R : – : Probe
Missing
S ::: High AC
Input
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
The Power Factor Module’s temperature is too high. If the temperature reaches a preset point, the UPS shuts down.
A temperature probe is missing or damaged.
The input voltage is higher than the alarm setting.
If the UPS has shut down, contact your service representative. If not, shut down your equipment or bypass the UPS; then, turn the UPS off and contact your service representative.
The UPS may shut down. Contact your service representative.
Contact your service representative.
61
Troubleshooting
Letter
Audio
Code
T Call
W : –– Fan Alarm The fan has stopped. The UPS may have shut down; if so,
Message
Service
The UPS has detected a problem that requires service.
What To DoWhat It MeansAlarm
The UPS shuts down. Contact your service representative.
contact your service representative. If the UPS has not shut down, shut down your equipment or bypass the UPS; then, turn the UPS off and contact your service representative.
Alarm and Inverter Logs
Your FERRUPS UPS makes an entry in its logs every time it sounds an alarm or switches to inverter (battery power). This information can be helpful in diagnosing problems.
You can view the Alarm and Inverter Logs from either the UPS control panel or a terminal or computer that you have connected to the RS-232 port (see “Connecting a Terminal or Computer to the RS-232 Port” on
page 41).
Reading the Alarm Log from a Control Panel
The Alarm Log is parameter 25. To display the Alarm Log from a control panel, follow these steps:
Press this key: Display shows: [DISPLAY] [2][5] 'LVSOD\  [ENTER]  $ODUP /RJ
The display scrolls through the 20 most recent entries in the Alarm Log. If you have not had 20 alarm conditions, the display scrolls through the entries FERRUPS has recorded. You can use the number keys as you view this scrolling display:
Use this key: To do this: [0] Pause the scrolling and start it again. [1] through [9] Go to the next log entry.
'LVSOD\
62
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Troubleshooting
Each log entry consists of four pieces of information: the alarm code, the date (month/day) of the alarm, the time (in 24-hour time) and the duration (in hours and minutes).
For instance, one entry might look like this: B 0205 1017 0005 In this example, “B” means the alarm was “Near Low Battery” (see
“Alarms” on page 59); if alarm B was active, there would be an asterisk (*) after “B.” “0205” means the alarm occurred on February 5 (2/5). “1017” means the alarm occurred at 10:17 a.m. “0005” means the alarm condition lasted for 0 hours and 5 minutes.
Reading the Inverter Log from a Control Panel
The Inverter Log is parameter 24. To display the Inverter Log, follow these steps:
Press this key: Display shows: [DISPLAY] [2][4] 'LVSOD\  [ENTER]  ,QYHUWHU /RJ
The display scrolls through the 20 most recent entries in the Inverter Log. If the inverter has not run 20 times, the display scrolls through the entries the UPS has recorded. You can use the number keys as you view this scrolling display:
Use this key: To do this: [0] Pause the scrolling and start it again. [1] through [9] Go to the next log entry.
Each entry includes four pieces of information: the inverter code, the date (month/day) of the inverter run, the time (in 24-hour time) and the duration (in hours and minutes). For instance, one entry might look like this:
L 0205 0951 0015 In this example, “L” means the the UPS went to inverter because it lost
AC input power; if the inverter was still running, there would be an asterisk (*) after the “L.” “0205” means the inverter ran on February 5 (2/5). “0951” means the inverter ran at 9:51 a.m. “0015” means the inverter ran for 0 hours and 15 minutes.
'LVSOD\
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
63
Troubleshooting
Table 15. Inverter Codes
Inverter Code Meaning Explanation
T System Test UPS went to inverter to test the batteries. B Brownout AC input voltage was too low.
L Line Loss AC input power was lost.
M Manual The inverter was started manually.
F Frequency Input frequency was too high or too low.
R Reset A system reset was performed.
Reading the Alarm Log from a Terminal or Computer
To display the Alarm Log on a terminal or computer, you can use the alarmlog or logs command (see “Entering Commands from a Terminal
or Computer” page 44). These commands display up to 20 log entries in a table. For example, the log might look like this table:
Active EventDate EventTime Duration Code/Event No 08/25/1993 11:25:32 00:00:45 J-User Test Alarm No 08/24/1993 12:13:18 00:01:08 A-Low Battery No 08/24/1993 12:05:07 00:08:11 B-Near Low Battery
The table shows whether the alarm is active now (Active), the date and time of each alarm, how long it lasted (Duration), and what caused the alarm (Code/Event).
You can also display parameter 25 to view the Alarm Log; this display is the same as the control panel display.
64
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Reading the Inverter Log from a Terminal or Computer
To display the Inverter Log on a terminal or computer, you can use the inverterlog or logs command (see “Entering Commands from a
Terminal or Computer” page 44). These commands display up to 20 log entries in a table. For example, the log might look like this:
Active EventDate EventTime Duration Code/Event No 08/25/1993 11:25:32 00:00:45 M-Manual turnon No 08/24/1993 12:13:18 00:01:08 L-Line fault
The table shows whether the UPS is running on inverter (battery power) now (Active), the date and time that the UPS ran on battery power, the length of time the UPS ran on battery power (Duration), and the reason (Code/Event).
You can also display parameter 24 to view the Inverter Log; this display is the same as the control panel display.
Alarm Code Summary
Troubleshooting
A B C D E F G H I J K
: –
:::
– : – : – ::
: ::– :
––:
:::: :: :
–––
: –
Low Battery Near Low Battery High Battery Low Runtime Low AC Output High AC Output Output Overload Hi Ambient Temp Hi Heatsink Temp User Test Alarm Hi Transfmr Temp
Figure 12. Alarm Code Summary
L M N O P Q R S T W
: – ::
––
:
– –––
: ––:
––: –
: – : :::
: ––
Check Charger Check Battery Check Inverter Memory Check Emergency PwrOff Hi PFM Res Temp Probe Missing High AC Input Call Service Fan Alarm
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
65
Troubleshooting
Service and Support
If you have any questions or problems with the UPS, call your Local
Distributor
and ask for a UPS technical representative.
or the Help Desk at one of the following telephone numbers
In the United States: Europe, Middle East, Africa: Asia: Australia:
1-800-356-5737or1-608-565-2100 +44-17 53 608 700 +852-2830-3030 +61-3-9706-5022
Please have the following information ready when you call the Help Desk:
Model number
:
Serial number
:
Version number (if available)
:
Date of failure or problem
:
Symptoms of failure or problem
:
Customer return address and contact information
:
If repair is required, you will be given a Returned Material Authorization (RMA) Number. This number must appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging or request packaging from the Help Desk or distributor. Units damaged in shipment as a result of improper packaging are not covered under warranty. A replacement or repair unit will be shipped, freight prepaid for all warrantied units.
NOTE For critical applications, immediate replacement may be available. Callthe
Help Desk for the dealer or distributor nearest you.
66
Powerware®FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
Loading...