The Powerware9Expansion Chassis is a connectivity device that
contains a Modbus
devices, providing greater power management control and flexible
monitoring.
Refer to the respective user’s guide for operation of the X-Slot cards to
be used in the chassis.
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping
cartons and packing materials for the carrier or place of purchase and
file a claim for shipping damage. If you discover damage after
acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with
the carrier within 15 days of receipt of the equipment; 2) Send a copy of
the damage claim within 15 days to your service representative.
Safety Precautions
Read the following precautions before you install the Expansion
Chassis.
: To reduce the risk of fire or electric shock,install the chassis in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient
temperature must not exceed 40C (104F). Do not operate near water or
excessive humidity (95% max).
: For rack installationsonly. The rack should be connected to a reliable earth
ground in accordance with local regulations.
9
Card and two slots for other X-SlotZconnectivity
CAUTION
Powerware®Expansion Chassis User’s Guide Rev A : www.powerware.com
3

Installation
Installing Additional X-Slot Cards
NOTE Refer to the individual X-Slot card user’s guide before installation. There may
be specific instructions that need to be completed first, such as changing default
jumpers. Also verify that the X-Slot card you are using with the chassis is compatible
with the communication port on your UPS.
For the Powerware 9315 UPS. The Powerware 9315 UPS is not compatible with the
Relay Interface Adapter or the Single Port Serial Card. Both cards require open
collector signals (AC Fail and Low Battery), and the 9315 only provides RS-232 serial
data through the communication port. Only the RS-232 capability of the Single Port
Serial Card is supported. Refer to the UPS user’s guide for more information.
The Modbus Card is factory-installed in Slot 1 and must remain in
Slot 1. To install additional X-Slot cards:
1. Remove the X-Slot cover on the chassis rear panel. Retain the
screws (see Figure 1).
2. To prevent electrostatic discharge (ESD), place one hand on an
unpainted metal surface such as the UPS rear panel.
Align the X-Slot card with the slot guides and slide the card
into the slot until it is firmly seated.
3. Secure the card with the screws removed in Step 1.
Figure 1. Installing Additional X-Slot Cards
4
Powerware®Expansion Chassis User’s Guide Rev A : www.powerware.com