Powerware 9170+ User Manual

Relay Interface Card for Powerware 9120 and 9170+

General

This Relay Interface Card (p/n 1014018) provides potential free true relay interface for AS/400 and other relay connected computers and industrial applications. This relay interface uses a 15-pin D-sub connector and this Relay Interface Card is installed in the slot on rear panel of the UPS.

Installation

1. Remove the cover on the option slot on the back of UPS to install the Relay Interface Card.
2. Put the Relay Interface Card into the slot and attach it to the rear panel by using the screws removed.
The following information is available from the Relay Interface Card:
1018946 Rev. A
1/2
Table 1. Relay information available.
Relay # System state D15 pin # NC / NO * on board connected K1: Line Line OK 1 - 2 NC
Line failure 1 - 3 NO
K2: Battery Battery normal 4 - 5 NC
Battery low 4 - 6 NO
K3: UPS Alarm UPS alarm 7 - 8 NC
UPS ON / OK 7 - 9 NO
K4: Bypass UPS on bypass 10 - 12 NC
UPS normal / On inverter 10 - 11 NO UPS shutdown ** 13 - 15
Table 1
* Normally closed (NC) /open (NO) connection state when the Relay Interface Card is not powered.
** The shutdown pin (15) needs minimum of 5 seconds high level signal (connection to +12VDC) to perform the UPS shutdown.
NOTICE: The relay contacts must not be galvanically connected to any mains connected circuits. Do not use +12VCD (Pin13) of the Relay Interface Card for any power supply purposes for external devices. Reinforced insulation to the mains is required for equipment and cables connected to these connections.
The relay contacts are rated for maximum 1A/30VAC or 200mA/60VDC. All relay outputs are galvanically isolated from the other circuits of the UPS (IEC 950, EN 50091-1).

Shut down function

The Relay Interface Card shut down functionality depends on the jumper (JP1, JP2 & JP3) selected on the board and on the UPS mode (Normal or On Battery). The functions are described in table 2.
Table 2. Shut down options.
JP1 (factory default) JP2 JP3
PW
9110
PW
9120
PW
9170+
UPS
Normal
On Battery - UPS Off immediately, back
UPS
Normal
On Battery Shut down as in RS-232
port. Output off after 120
sec, back on line when
UPS
Normal
On Battery - Immediate output off Immediate output off
- - -
online when power returns.
- Immediate output off, back on line when shut down pins are opened Immediate output off, back on line when shut down pins are opened
power returns.
- - Immediate output off
Immediate output off
Immediate output off
-
Table 2