This manual contains important instructions for your Uninterruptible Power
Supply (UPS) system. You should follow these instructions during the
installation and maintenance of the UPS, options, accessories, and batteries.
Cette notice contient des instructions importantes
concernant la sécurité.
This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at
their own expense.
iiPowerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
Figure 40. Location of Communications Ports on the Powerware
BPIII HE UPS (shown without the Environmental Cabinet)86......
Figure 41. Port 1 Pin Assignments87.................................
Figure 42. Port 2 Pin Assignments88.................................
Figure 43. Setup Serial Port 1 Screen89..............................
Figure 44. Event History Log93.....................................
Figure 45. System Meters94........................................
Figure 46. Battery Test Log95.......................................
viii
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 9
Introduction
Powerware BPIII online power protection can be utilized to prevent loss of valuable
electronic information, minimize equipment downtime, and/or minimize the adverse
effect on equipment production due to unexpected power problems.
The Powerware BPIII Harsh Environment (HE) Uninterruptible Power Supply (UPS)
system continually monitors incoming electrical power and removes the surges,
spikes, sags, and other irregularities that are inherent in commercial utility power.
Working with the electrical system, the UPS supplies clean, consistent power that
sensitive electronic equipment requires for reliable operation. During brownouts,
blackouts, and other power interruptions, one or more optional battery cabinets
can provide emergency power to safeguard your operation.
The UPS will function automatically and requires very little attention during normal
operation. However, read and understand the procedures described in this manual
to ensure trouble-free operation.
This manual describes how to install and operate the Powerware BPIII HE
Uninterruptible Power Supply (UPS) system. It contains instructions for installing
and operating both the UPS and Environmental cabinets.
Each component of the Harsh Environment UPS system is housed in a
free-standing cabinet. The system configuration consists of the UPS and the
Environmental cabinets. Figure 1 shows the Powerware BPIII Harsh Environment
UPS system.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
1
Page 10
UPS CABINET
ENVIRONMENTAL
CABINET
Figure 1. Powerware BPIII Harsh E nvironment UPS System
2
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 11
Using This Manual
This manual describes the Powerware BPIII HE UPS installation, operation and
routine maintenance. The information in this manual is divided into the sections
and chapters listed.
Introduction
The Introduction provides a brief description of the UPS system, a description
of the content of each chapter, safety, text conventions used in the manual and
reference information.
Section I -- Installation
•Chapter 1 -- Getting Started -- tells you how to prepare your site for the
installation of your UPS system. It discusses equipment environmental
requirements, inspecting, and unpacking cabinets.
•Chapter 2 -- Installing the Harsh Environment UPS System -- describes
how to install the UPS system.
•Chapter 3 -- Installing a Remote EPO Control -- discusses installing the
optional Remote Emergency Power Off (EPO) control.
•Chapter 4 -- Installing a Remote Monitor Panel -- contains information for
installing the optional Remote Monitor Panel (RMP).
•Chapter 5 -- Installing a Relay Interface Module -- contains information for
installing the optional Relay Interface Module (RIM).
•Chapter 6 -- Installing a Supervisory Contact Module -- contains information
for installing the optional Supervisory Contact Module (SCM).
Section II -- Operation
•Chapter 7 -- Understanding UPS Operation -- provides information on
understanding the operation UPS.
•Chapter 8 -- Controls and Features -- describes the standard features and
controls of the UPS system.
•Chapter 9 -- Using the Monitor Panel -- describes the controls and indicators
found on the Monitor Panel and shows the various information screens
displayed on the LCD screen.
•Chapter 10 -- Operating the UPS-- contains startup and shutdown
procedures for the UPS system.
•Chapter 11 -- Using Features and Options -- contains descriptions and
instructions for the UPS system features and options.
•Chapter 12 -- Responding to System Events -- lists all the alarm, messages
and notices that occur during operation of the UPS system.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
3
Page 12
•Chapter 13 -- Serial Communications -- describes the serial communications
features of the UPS system.
•Chapter 14 -- Remote Notification -- contains instructions for using the
remote notification feature of the UPS system.
•Chapter 15 -- Maintaining the UPS System -- contains maintenance
instructions for the UPS system.
•Chapter 16 -- Product Specifications -- provides detailed specifications for
the UPS system.
•Appendix A --Customer Information -- contains important information on
wiring requirements and recommendations, and important diagrams of the
cabinet’s mechanical details and electrical access.
Read through each procedure before you begin.
Conventions Used in This Manual
The text in this manual uses these conventions:
•Bold type highlights important concepts in discussions, key terms in
procedures, and menu options.
•Rectangular boxes containing bold type are warnings or cautions that pertain to
the UPS system or its electrical connections. This important information alerts
you to possible dangers pertaining to personnel safety, UPS or equipment
damage, critical load protection, or operational concerns.
•Italic type highlights notes and new terms where they are defined.
In this manual, the term UPS or UPS system refers to the UPS cabinet and its
internal elements and the environmental cabinet. The rectifier and inverter are
internal UPS components that are together referred to as the power processing unit(PPU) of the UPS.
4
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 13
Safety Considerations
The UPS and Environmental cabinets are designed for industrial applications in
harsh environments. However, the UPS system is a sophisticated power system
and should be handled with appropriate care, following these guidelines:
•Keep surroundings clean and free from excess moisture.
•Do not operate the UPS system close to gas or electric heat sources.
•The system is not intended for outdoor use.
•The operating environment should be maintained within the parameters
stated in this manual.
•Keep the cabinet doors closed to ensure proper cooling airflow and to
protect personnel from dangerous voltages inside the unit.
•The system contains its own power source. Lethal volt ages are present
even when the UPS is disconnected from utility power.
WARNING:
Only AUTHORIZED SERVICE PERSONNEL should perform service or
maintenance on the parallel redundant system.
If service or routine maintenance is required:
•Ensure all power is disconnected before performing installation or service.
•Ensure the area around the UPS system is clean and uncluttered.
•Observe all DANGER, CAUTION, and WARNING notices affixed to the
inside and outside of the equipment.
Getting Help
If you need to schedule initial startup, need regional locations and telephone
numbers, have a question about any of the information in this manual, or have a
question this manual does not answer, please call Powerware at:
United States1-800-843-9433
Canada1-800-461-9166
Outside the U.S.Call your local representative
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
5
Page 14
This Page Intentionally Left Blank.
6
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 15
Section I
Installation
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
7
Page 16
This Page Intentionally Left Blank.
8Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 17
Getting Started
The Harsh Environment (HE) UPS system is shipped as two separate
cabinets (UPS Cabinet and Environmental Cabinet). Each cabinet is shipped
on a wood/foam and steel pallet. Use a forklift or pallet jack to move the packaged
cabinets to the installation site, or as close as possible to the site, before unloading
from the pallets.
This is the basic sequence of the installation steps:
1. Create an installation plan for the UPS and Environmental cabinets.
1. PrepareyoursitefortheUPSsystem.
2. Inspect, unpack, and unload the cabinets.
3. Wire the cabinets as applicable (Chapter 2).
4. Complete the Installation Checklist (Chapter 2).
5. Have authorized service personnel perform preliminary checks and startup.
After wiring the UPS system to the facility power and critical load(s), be sure to ground
the system according to local and/or national electrical wiring codes, using your own
cabling and conduit.
NOTE: Startup and operational checks should be performed only by authorized
service personnel. This service is usually offered as part of the sales
contract for your UPS system.
Creating an Installation Plan
Before beginning to install your UPS system, you should be sure you understand
the instructions in this manual. Use the procedures and illustrations in the
following sections to create a logical plan for installing the UPS system The
information in this chapter and Chapter 2 will help you plan the installation.
Preparing Your Site
For your UPS system to operate at peak efficiency, your installation site should
meet the environmental parameters outlined in this manual. If you intend to
operate the UPS at an altitude higher than 1500 meters (5000 feet), contact your
local sales or service office for important information about high altitude operation.
The operating environment must meet the size and weight requirements shown in
Table J of Appendix A.
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range: 0 --- 5 0˚ C ( 3 2 --- 1 22 ˚ F)
The UPS and Environmental cabinets use forced air cooling to regulate internal
component temperature. Air inlets are on the right side of the Environmental
Cabinet and outlets are on the top of the UPS cabinet. You must allow clearance in
front of and above each cabinet for proper air circulation.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
9
Page 18
Environment Considerations
The UPS system must be installed o n a sealed concrete floor.
WARNING:
Installation should be performed by qualified personnel.
Inspecting and Unpacking Each Cabinet
The first task in preparing for installation is inspecting and unpacking each cabinet.
Cabinets arrive covered with protective packaging material as shown in Figure 2.
OUTER
PACKA GI N G
FOAM CUSHION
Figure 2. Cabinet as Shipped, with Outer Packaging and Pallet
1. Carefully inspect the outer packaging for evidence of damage during transit.
CAUTION:
Do not install a damaged cabinet. Report any damage to the carrier and
contact your local sales or service office immediately.
10Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 19
2. Use a forklift or other material handling equipment to move the cabinets to a
convenient unpacking area. Insert the forklift jacks between the foam cushions
on the bottom of the unit.
CAUTION:
DO NOT tilt cabinets more than 10 degrees from vertical.
3. Set each pallet on a firm, level surface, allowing a minimum clearance of
4.6m (15 ft) on each side for removing the cabinets from the pallets.
4. Cut the steel bands around each cabinet.
5. Remove the protective cardboard covering from the cabinets, cutting where
indicated, using a knife blade no longer than 25 mm (1 in.).
NOTE: Do not discard the packaging material yet. Instructions for unloading the
cabinet from the pallet are printed on the cardboard, and you will need to
refer to them.
6. Remove the plastic bag and foam packing material, and discard or recycle
them in a responsible manner .
Unloading the UPS System From the Pallet
The UPS and Environmental cabinets are each bolted to sheet metal pallets
consisting of four supports secured to foam cushions. The foam cushions act as
shock absorbers for the cabinet during shipment.
WARNING:
UPS cabinets are extremely heavy. If unloading instructions are no t closely
followed, the cabinet may tip and cause serious injury.
T urning the jacking bolts unevenly may cause the cabinet to become
unbalanced. To prevent tipping, raise and lower the jacking bolts evenly. The
cabinet should only be raised approximately 3 mm (
(just enough to remove foam cushions).
1/8 in.) above the floor
1. Starting with the UPS cabinet, open and remove the cabinet door. Remove the
retaining screw located inside the door at the bottom hinge pivot point, then lift
the door off. Save the retaining screws for reinstallation of the door.
2. Locate the field kit (packed inside of the cabinet or communication panel).
Locate the four ½-in. jacking bolts and install them in the threaded holes in the
front and rear supports. Place a floor protector underneath each jacking bolt,
and screw the bolts down against them. The floor protectors will save the floor
from being marred by the jacking bolts.
3. Loosen, but do not remove the hardware holding the foam cushions to the
front and rear supports (labeled “1” in Figure 3).
4. Turn each jacking bolt consecutively, two full turns, until the foam cushions
clear the floor by approximately 3 mm (
1/8 in.).
5. After the foam cushions clear the floor, remove the hardware loosened in
step 3. Pull the foam cushions out from under the cabinet, and discard or
recycle them in a responsible manner.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
11
Page 20
DOOR
1
FLOOR
PROTECTOR
2
FRONT
SUPPORT
SIDE
SUPPORT
FOAM
CUSHION
2
2
JACKING
BOLT
Figure 3. Removing Front and Rear Supports
WARNING:
Cabinet may fall. Do not loosen hardware attaching the side or front supports
to cabinet base. Also, do not loosen supports from each other. The cabinet
must be lowered using jacking bolts before supports can be removed.
2
1
2
1
6. Carefully and evenly lower the cabinet by turning each jacking bolt
consecutively two full turns (maximum)
the cabinet is no longer supported by the jacking bolts.
until the supports contact the floor, and
7. After the cabinet is resting on the floor, remove the jacking bolts and discard or
supports to the cabinet base. Discard or recycle the hardware and support
brackets in a responsible manner.
9. Replace the door that was removed in step 1. The cabinet is now ready to be
rolled to its final location.
10. Repeat steps 1 through 9 for the Environmental cabinet.
Wiring Requirements
For external wiring requirements, including the minimum AWG size of external
wiring, see Tables A and E of Appendix A. The power wiring for this equipment is
rated at 90˚C.
12Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 21
Installing the Harsh Environment
UPS System
After the UPS system is unpacked and moved to the final installation location, the
UPS and Environmental Cabinets are ready to be joined. Once the cabinets are
joined, internal and external wiring is installed. Figure 4 shows the UPS and
Environmental cabinets assembled. The top view shows the cable entry plate in
the Environmental cabinet.
TOP VIEW
FRONT VIEW
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
Figure 4. UPS and Environmental Cabinets
13
Page 22
WARNING:
Installation should be performed by qualified personnel.
Note the following important information while installing the UPS:
•Dimensions in this manual are provided in millimeters and inches.
•Do not tilt the UPS or other cabinets more than 10˚ during installation.
•Cooling exhaust airflow is approximately 614.0 L/S (1300 CFM).
•The conduit landing plate is to be removed to add conduit landing holes as
required. Plate material is 16 gauge steel (0.06 in. thick).
•TerminalsE9throughE15andE19–E35areULandCSAratedat90˚C. A hex
key tool is required to attach wires to the terminals.
•Details about control wiring are provided in each procedure for connecting
options and features. Table L in Appendix A identifies the control wiring
terminations.
Installing the UPS Cabinet Sections
1. Move the UPS and Environmental cabinets together, placing the UPS cabinet
on the left side of the Environmental Cabinet.
2. Secure the UPS and Environmental cabinets with the leveling feet provide on
each cabinet.
3. Locate the field kit and remove cabinet joining brackets and hardware from the
kit.
4. Install the brackets to the front and rear of each cabinet base, using the
threaded holes provided. Brackets should be mounted so that the tabs at end
of the brackets meet between the two cabinets.
5. Install bolts through the tabs at front and back and secure with washers and
nuts.
6. Secure cabinet sides to each other at the top front and top back with 1/2 inch
bolts, washers and nuts from the field kit. Use the holes provide in the cabinet
sides.
7. Attach a ground to the joined cabinets using the procedure “Grounding Joined
Cabinets” in this chapter.
14Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 23
Grounding Joined Cabinets
Open the door of each cabinet. Locate the grounding stud at the front/side of each
frame. Remove the top nut, lock washer, and flat washer from each stud (if
attached, see Figures 5).
1. Locate the grounding cable (part of the field kit, located in a small bag which is
fastened to the UPS cabinet in the customer terminal area).
2. Mount the grounding cable as shown in Figure 5, attaching it to the frame of
each cabinet using the hardware previously removed.
HARDWARE REMOVED
BEFORE PLACING LUG
GROUNDING CABLE
OVER GROUND STUD
FRONT
CABINET BASE
(side view)
Figure 5. Cabinet-to-Cabinet Grounding
PERMANENTLY
ATTACHED
HARDWARE
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
15
Page 24
Installing UPS Internal Power and Control Wiring
NOTE: The cables used in steps 2 through 12 are coiled inside the Environmental
cabinet and are attached at the factory to the terminals inside this cabinet.
Wiring harness with connectors J20, J22, and J23 are coiled inside the UPS
cabinet. Wiring harness with connectors P20, P22, and P23 are coiled inside
the Environmental cabinet. Refer to Drawings 164201261 ---1 and
164201261 ---4 in Appendix A of this manual for wiring and termination
requirements and terminal locations.
1. Remove the sheet metal shield covering the bottom half of the UPS cabinet.
2. Route DC input cables (cables 205 and 206) from the Environmental cabinet
through the cutout in cabinet sides to the DC UPS Input terminals in the UPS
cabinet.
3. Connect positive DC power cable 205 to the DC input terminal E4. Refer to
Appendix A of this manual for terminal locations and tightening torque.
4. Connect negative DC power cable 206 to the DC input terminal E5. Refer to
Appendix A of this manual for terminal locations and tightening torque.
5. Route AC Input Bypass Transformer cables (cables 227, 228 and 229) from the
Environmental cabinet through the cutout in cabinet sides to the Bypass
Transformer Input terminals in the UPS cabinet.
6. Connect phase A, B, and C power wiring cables 227, 228, and 229 to Bypass
Transformer Input terminals E13, E14, and E15 respectively. Refer to Appendix
A of this manual for terminal locations and tightening torques.
7. Route AC Input to UPS Rectifier cables (cables 250, 251 and 252) from the
Environmental cabinet through the cutout in cabinet sides to the UPS Rectifier
Input terminals in the UPS cabinet.
8. Connect phase A, B, and C power wiring cables 250, 251, and 252 to AC Input
to UPS Rectifier Input terminals E1, E2, and E3 respectively. Refer to Appendix
A of this manual for terminal locations and tightening torques.
9. Route AC Output cables (cables 237, 238 and 239) from the Environmental
cabinet through the cutout in cabinet sides to the AC Output terminals in the
UPS cabinet.
10. Connect phase A, B, and C power wiring cables 237, 238, and 239 to AC
Output terminals E9, E10, and E11 respectively. Refer to Appendix A of this
manual for terminal locations and tightening torques.
11. Route two Neutral cables (cable 600) from the Environmental cabinet through
the cutout in cabinet sides to the Neutral terminal in the UPS cabinet.
12. Connect two Neutral power wiring cables 600 to Neutral terminal E12. Refer to
Appendix A of this manual for terminal locations and tightening torques.
13. Route wiring harness with connectors P20, P22, and P23 from the
Environmental cabinet through the cutout in cabinet sides.
14. Connect connectors P20, P22, and P23 to connectors J20, J22, and J23
respectively.
15. Reinstall UPS Cabinet sheetmetal shield.
16Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 25
Installing UPS External Wiring
1. Install rectifier, bypass, and battery input power wiring to terminals in the
Environmental cabinet. Refer to Drawings 164201261---1 and 164201261---4 in
Appendix A of this manual for wiring and termination requirements and terminal
locations.
2. Install the critical load output power wiring to terminals in the Environmental
cabinet. Refer to Drawings 164201261---1 and 164201261---4 in Appendix A of
this manual for wiring and termination requirements and terminal locations.
3. Reinstall cabinet doors.
Preparing the UPS for Installing
Optional Accessories
If you are installing optional accessories, such as a Remot EPO or an RMP, you
must prepare the UPS cabinet for the installation of these options.
To prepare the UPS for wiring to an RMP, RIM, SCM or Remote EPO:
1. Be sure the UPS is turned off and all power sources are removed. (See the
operator’s manual for instructions.)
2. Open the doors of the UPS.
3. Remove the lower sheetmetal shield. Set the shield and hardware aside for
later reuse.
Initial Startup
Startup and operational checks should be performed only by authorized service
personnel. Contact service in advance (usually a two week notice is required) to
reserve a preferred startup date.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
17
Page 26
Completing the Installation Checklist
The final step in installing the UPS system is completing the following Installation
Checklist. This checklist ensures that all hardware, cables, and other equipment
have been completely installed . Completing all items on the checklist will ensure a
smooth installation. Make a copy of the Installation Checklist before filling it out,
and retain the original.
After the installation is complete, a service representative will be able to verify the
operation of the UPS system and commission it to support the critical load. The
service representative cannot perform any installation tasks other than verifying
software and operating setup parameters. Service personnel may request a copy
of the completed Installation Checklist to be sure you have completed all
applicable equipment installation.
NOTE: The Installation Checklist MUST be completed prior to starting the UPS
system for the first time.
18Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 27
Installation Checklist
-
All packing materials and restraints have been removed from each cabinet.
-Each cabinet in the UPS system is placed in its installed location.
-All cabinets are bolted together.
-A ground bond is installed between all cabinets that are bolted together.
-All switchboards, conduits, and cables are properly routed to the UPS.
-Power cables are terminated on AC Input terminals (UPS Cabinet) (E1---E3).
-Power cables are terminated on Bypass Transformer input terminals (UPS Cabinet)
( E1 3 --- E 1 5 ) .
-Power cables are terminated on AC Output terminals (UPS Cabinet) (E9 ---E12).
-Power cables are terminated on DC Input terminals (UPS Cabinet) (E4---E5).
-Power cables are terminated on bypass terminals (E19 ---E21).
-Power cables are terminated on the CB1 input breaker (E33---E35 ).
-Power cables are terminated on output terminals (E25---E27).
-A ground conductor is properly installed.
-If N is used, no other N ---G bonds exist downstream from the UPS.
-Battery cables and harness are terminated on the CB2 battery breaker E31 and E32.
-The area around the installed UPS system is clean and dust-free. (It is recommended
that the UPS be installed on a sealed concrete pad on a sealed concrete floor.)
-Adequate workspace exists around the UPS and other cabinets.
-Adequate lighting is provided around all UPS equipment.
-A 120V service outlet is located within 25 feet of the UPS equipment.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
19
Page 28
Notes
20Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 29
Installing a Remote EPO Control
Twi
(2)
The Remote EPO control arrives as shown in Figure 6. See Drawing
164201261---7 in Appendix A for enclosure dimensions, side views, and
knockout patterns.
to UPSto other equipment
Figure 6. Remote EPO Control
To install a Remote EPO control:
UNINTERRUPTIBLE POWER SYSTEM
EMERGENCY OFF
1. Securely mount the Remote EPO station. Recommended locations include
operator’s consoles or exit doors.
2. Install wiring from the Remote EPO station using ½-in. conduit through the
7/8-in. knockout in either the top or bottom of the UPS.
3. Connect the Remote EPO wiring as shown in Tables A and B:
From REPO Station(s)
T B1 --- 4T B2 --- 1
T B1 --- 5T B2 --- 2
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
TableA. RemoteEPOWireTerminations
To Communications
Panel in UPS
Remarks
stedwires
1 4 --- 1 8 g a u g e
21
Page 30
TableB. RemoteEPO
1
REMOTE
EPO
SWITCH
TB2
2
TWISTED
WIRES (2)
Remote EPO s witch rating is 24 VDC.
1 Amp minimum if supplied by user.
NOTE: This switch must be a dedicated
switch not tied into any other circuits.
4. If installing multiple Remote EPO stations, wire additional stations in parallel
with the first Remote EPO.
5. If required, install ½-in. conduit and wiring from the Remote EPO station to trip
circuitry of upstream protective devices. A normally open contact is provided,
asshowninTableB. RemoteEPOswitchwiringmustbeinaccordancewith
UL Class II requirements.
6. Secure the UPS by reversing all steps taken to prepare it for Remote EPO
installation.
22Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 31
Installing a Remote Monitor Panel
As an option, a Remote Monitor Panels (RMPs) can be installed to
monitor the operation of the UPS system from virtually any location within
the facility, up to 500 feet from the UPS. Flush-mount or surface-mount an RMP on
a desktop or on a wall, wherever you have a serial interface line. A maximum of
two monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table C
for the number of accessories permitted. Figure 7 shows an RMP. Drawing
164201261---7 in Appendix A shows the enclosure dimensions and knockout
patterns.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
23
Page 32
FLUSH MOUNT
SURFACE MOUNT
(FOR HANGING)
WIRES MUST
BE TWISTED
24
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
Figure 7. Remote Monitor Panel (RMP)
164291261 Rev. F 111503
Page 33
Before installing an RMP, be sure you have prepared the UPS according to the
instructions in Chapter 2.
To i n st a l l a n R M P :
1. Securely mount the RMP(s).
2. Install wiring from the RMP using ½-in. conduit through the cable entry panels
in either the top or bottom of the UPS cabinet.
The top entry connection requires installation of ½-in. flexible conduit within the
UPS. Bottom entry connection requires no additional routing of conduit within
the UPS.
3. In the spare parts kit, locate the RMP adapter cable assembly (see Figure 8).
Mate the DB---9 connector on the back of the terminal block into the DB---9
connector on the Communications Panel of the UPS (see Figure 9). Use two
screws from the spare parts kit to secure the terminal block bracket to the
Communications Panel.
Connect to
Po r t 1 ( D B --- 9 ) o n
Communications Panel
FUSE
TERMINAL
BLOCK
(TB3)
Figure 8. Terminal Block Bracket
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
25
Page 34
D B --- 9 C O N N E C T O R
12TURNSPE
R
12TURNSPE
R
(ON COMMUNICATIONS
PANEL OF T H E UPS )
TB1
TB2
Figure 9. Wiring an RMP to the UPS
4. Connect RMP wiring to the terminal block using terminations shown in Table D.
From RMP ATo U PSRemarks
T B 1 --- 4
T B 1 --- 5
T B 1 --- 6
T B 1 --- 7
From RMP B (if used)To U PSRemarks
T B 1 --- 4
T B 1 --- 5
T B 1 --- 6
T B 1 --- 7
26
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
Tab l e D . R MP W i re Te rm i na t ion s
T B3 --- 1
T B3 --- 2
T B3 --- 3
T B3 --- 4
T B3 --- 5
T B3 --- 6
T B3 --- 7
T B3 --- 8
TWISTED WIRES (4)
1 --- 2 T U R N S P ER
TWISTED WIRES (4)
1 --- 2 T U R N S P ER
3INCHES
3INCHES
164291261 Rev. F 111503
Page 35
5. To check the operation of the RMP, ensure that the UPS is supplying the load
via inverter or bypass. If the indicators on the RMP show the appropriate
status, then it is operating correctly.
If the communications link between the UPS and the RMP is not present, the
RMP will self-test (all indicators flash and the horn beeps at one-second
intervals). If this occurs, check all harness connectors and the fuse for proper
seating. If all connections are secure but the RMP continues to self-test,
replacethefusewiththespareincludedinthehardwarekit. Ifthisdoesnot
correct the problem, contact your local field service office for verification that
the RMP is working correctly.
6. To test the indicator lamps, press the horn silence button and hold it for
3 seconds. All lamps should light, and the horn will sound continuously
until you release the button.
7. Repeat steps 1, 2, and 4 through 6 for each RMP you are installing.
8. If you are installing an RIM or SCM in addition to an RMP, proceed to Chapter 5
or 6, respectively; otherwise, secure the UPS cabinet by reversing the steps
contained in procedure “To Prepare the UPS for Wiring to an RMP, RIM, SCM,
or Remote EPO” of Chapter 2.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
27
Page 36
This Page Intentionally Left Blank.
28
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 37
Installing a Relay Interface Module
The optional Relay Interface Module (RIM) uses relay contact closures to
indicate the operating status and alarm condition of the UPS system. The
module uses an RS422 serial interface line and may support up to eight critical
loads. A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be
installed. Refer to Chapter 4, Table C for the number of accessories permitted.
Figure 10 shows the RIM with its four 15-pin connectors labeled J1 through J4.
Drawing 164201261---8 in Appendix A outlines the enclosure dimensions.
FLUSH MOUNT
J1J2J3J4
15-PIN D-SUB
CONNECTORS
SURFACE
MOUNT
FOR HANGING
Relay Interface Module
CONTINUES
AT UPS
Figure 10. Relay Interface Mod ule
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
29
Page 38
Before installing an RMP, be sure you have prepared the UPS according to the
instructions in Chapter 2.
To i n st a l l a n R I M :
1. Securely mount the RIM.
2. Install wiring from the RIM using ½-in. conduit through the 7/8-in. knockout in
either the top or bottom of the UPS cabinet.
The top entry connection requires installation of ½-in. flexible conduit within the
UPS. Bottom entry connection requires no additional routing of conduit within
the UPS.
3. If not already installed, locate the RMP adapter cable assembly (see Figure 11)
in the spare parts kit. Mate the DB ---9 connector on the back of the terminal
block into the DB ---9 connector on the Communications Panel of the UPS (see
Figure 12). Use two screws from the spare parts kit to secure the terminal
block bracket to the Communications Panel.
Connect to
Po r t 1 ( D B --- 9 ) o n
Communications Panel
FUSE
TERMINAL
BLOCK
(TB3)
Figure 11. Terminal Block Bracket
30Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 39
D B --- 9 C O N N E C T O R
(ON COMMUNICATIONS
PANEL OF T H E UPS )
TB1
TB2
Figure 12. Wiring an RIM to the UPS
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
31
Page 40
4. Connect RIM wiring to the terminal block using the terminations shown in
12TURNSPE
R
12TURNSPE
R
Tab le E .
5. Contact your local field service office for verification and testing of the RIM
and its connections prior to making connections with J1---J4.
You can order interface cables separately for connecting to the 15-Pin D-Sub
Connectors.
7. If you are installing an RMP or SCM in addition to an RIM, proceed to Chapter
4 or 6, respectively; otherwise, secure the UPS cabinet by reversing the steps
contained in procedure “To Prepare the UPS for Wiring to an RMP, RIM, SCM,
or Remote EPO” of Chapter 2.
Tab l e E . R IM W i r e Te r min a ti o ns
From RIM ATo U PSRemarks
T B 1 --- 4
T B 1 --- 5
T B 1 --- 6
T B 1 --- 7
From RIM B (if used)To U PSRemarks
T B 1 --- 4
T B 1 --- 5
T B 1 --- 6
T B 1 --- 7
T B3 --- 1
T B3 --- 2
T B3 --- 3
T B3 --- 4
T B3 --- 5
T B3 --- 6
T B3 --- 7
T B3 --- 8
TWISTED WIRES (4)
1 --- 2 T U R N S P ER
3INCHES
TWISTED WIRES (4)
1 --- 2 T U R N S P ER
3INCHES
32Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 41
Installing a Supervisory
Contact Module
The optional Supervisory Contact Module (SCM) as shown in Figure 13
provides contacts for monitoring UPS status. A maximum of two monitoring
accessories (RMPs, RIMs, or SCMs) can be installed. Refer to Chapter 4, Table C
for the number of accessories permitted. See Drawing 164201261---9 in Appendix
A for enclosure dimensions, side views, and knockout patterns.
WIRES MUST
BE TWISTED
Figure 13. Supervisory Contact Module
SURFACE MOUNT
(FOR HANGING)
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
33
Page 42
Before installing an RMP, be sure you have prepared the UPS according to the
instructions in Chapter 2.
To install a Supervisory Contact Module:
1. Securely mount the SCM.
2. Install wiring from the SCM using ½-in. conduit through the 7/8-in. knockout in
either the top or bottom of the UPS cabinet.
The top entry connection requires installation of ½-in. flexible conduit within the
UPS. Bottom entry connection requires no additional routing of conduit within
the UPS.
3. If not already installed, locate the RMP adapter cable assembly (see Figure 14)
in the spare parts kit. Mate the DB ---9 connector on the back of the terminal
block into the DB ---9 connector on the Communications Panel of the UPS (see
Figure 15). Use two screws from the spare parts kit to secure the terminal
block bracket to the Communications Panel.
Connect to
Po r t 1 ( D B --- 9 ) o n
Communications Panel
FUSE
TERMINAL
BLOCK
(TB3)
Figure 14. Terminal Block Bracket
34Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 43
D B --- 9 C O N N E C T O R
(ON COMMUNICATIONS
PANEL OF T H E UPS )
TB1
TB2
Figure 15. Wiring an SCM to the UPS
4. Connect the SCM wiring to the terminal block using the terminations shown in
Tab le F .
5. Contact your local field service office for verification and testing of the SCM
and its connections prior to making connections to terminal strip shown in
Figure 16.
7. If you are installing an RMP or RIM in addition to an SCM, proceed to Chapter
4 or 5, respectively; otherwise, secure the UPS cabinet by reversing the steps
contained in procedure “To Prepare the UPS for Wiring to an RMP, RIM, SCM,
or Remote EPO” of Chapter 2.
Table F. Supervisory Contact Module Wire Terminations
From SCM ATo U PSRemarks
T B 1 --- 4
T B 1 --- 5
T B 1 --- 6
T B 1 --- 7
From SCM B (if used)To U PSRemarks
T B 1 --- 4
T B 1 --- 5
T B 1 --- 6
T B 1 --- 7
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
T B3 --- 1
T B3 --- 2
T B3 --- 3
T B3 --- 4
T B3 --- 5
T B3 --- 6
T B3 --- 7
T B3 --- 8
TWISTED WIRES (4)
1 --- 2 T U R N S P ER
3INCHES
TWISTED WIRES (4)
1 --- 2 T U R N S P ER
3INCHES
35
Page 44
SYSTEM
NORMAL
NO
REDUNDANCY
ON
GENERATOR
BYPASS NOT
AVAILABLE
ON
BATTERY
UPS
ALARM
ON
BYPASS
SHUTDOWN
IMMINENT
Note: Supervisory contacts are rated at 2.0 amps at 28 Vdc or 120 Vac and 0.15 amp at 115 Vdc.
Supervisory contacts require external power s upply. Internal 24 Vdc is not capable of
supplying contact current.
Figure 16. Supervisory Contact Module TB2
36Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 45
Section II
Operation
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
37
Page 46
This Page Intentionally Left Blank.
38Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 47
Understanding UPS Operation
Your UPS functions automatically to supply AC electrical power to your
critical load. The UPS always operates in one of four modes:
•In Normal mode, the critical load is supplied by the inverter, which derives its
power from rectified utility AC power. In this mode, the rectifier also provides
charging current for the battery.
•In Battery mode, the battery cabinet provides DC power, which maintains
inverter operation. The battery supports the critical load.
•In Bypass mode, the critical load is directly supported by the utility through an
isolation transformer.
•In Maintenance Bypass mode, the critical load is directly supported by the utility
through a Maintenance Bypass circuit breaker..
The UPS continually monitors itself and the incoming utility power, and
automatically switches between Normal, Battery, and Bypass modes as required,
with no operator intervention. The Maintenance Bypass mode is a manual
operation needing operator intervention. The sophisticated detection and
switching logic inside the UPS ensures that operating mode changes are automatic
and transparent to the critical load. The UPS switches automatic operating modes
in response to these system events:
•A command is an intervention that is externally initiated by an operator or by
some site action. A command causes the UPS to switch operating modes; it
usually does not require any further action by you.
•A notice is a minor system event that may or may not require your attention.
•An alarm is a system event that requires immediate operator intervention.
System events, alarm horns, and indicator lights are described in Chapter 12 --Responding to System Events.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
39
Page 48
Looking Inside the UPS
The Powerware BPIII HE is a continuous duty, solid-state UPS that supports the
following equipment: process control, data processing, and
telecommunications/PBX. The Powerware BPIII HE maintains power to the critical
loads during commercial electrical power brownout, blackout, overvoltage,
undervoltage, and out-of-tolerance frequency conditions.
In this manual, the power required by your equipment is called the critical load.The
UPS supplies the critical load with conditioned power that is synchronized with your
utility power. Figure 17 shows the main elements of the UPS.
AC INPUT TO
RECTIFIER/
CHARGER
INPUT
ISOLATION
TRANSFORMER
INPUT
FILTER
DC INPUT
DC/DC
CONVERTER
POWER PROCESSING UNIT
RECTIFIER/
CHARGER
DIGITAL
METERING
INVERTER
STATIC
SWITCH
BYPASS
CONTACTOR
TRANSFORMER
OUTPUT
CONTACTOR
AC OUTPUT
TO CRITICAL
LOAD
OUTPUT
MAINTENANCE
BYPASS
INPUT
BREAKER
(BIB)
ISOLATION
SWITCH
(MIS)
MAINTENANCE
BYPASS
BREAKER
(MBP)
AC INPUT
TO BYPASS
UPS CABINET
If utility power is interrupted or falls outside the parameters specified in the Product
Specifications section of Chapter 16, the UPS uses a backup supply to sustain
power to the critical load for a specified period of time or until the utility power
returns. For extended power outages, the backup supply allows you to either
transfer to an alternative power system (such as a generator) or shut down your
critical load in an orderly manner.
The operation of the UPS system is described in greater detail in the following
paragraphs. The Product Specifications section of Chapter 16 outlines the storage
and operating specifications for the UPS.
40
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
Figure 17. Main Elements of the UPS System
164291261 Rev. F 111503
Page 49
Normal Mode
In Normal mode, utility AC power is supplied to the rectifier. The rectifier supplies
DC power to the inverter, which then supplies the critical load with AC power. The
rectifier also provides charging power to the battery through a DC to DC voltage
converter. The battery charge condition is monitored by the UPS and reported by a
status indicator on the Monitor Panel. The message “System Normal” appears in
the s tatus area of the LCD screen.
Figure 18 shows the path of electrical power through the UPS system when the UPS
is operating in Normal mode.
BYPASS
(BIB)
(closed)
OUTPUT
TRANSFORMER
Bypass
Input
(MBP)
(open)
Rectifier
Input
Tra n s f o r m e r
RECTIFIERINVERTER
K4
K3
(closed)
(MIS)
(closed)
Input
Isolation
CB1
DC/DC
CONVERTER
CB2
(closed)
Path of electrical power
BATTERY
Figure 18. Path of Current Through the UPS in Normal Mode
If the utility AC power is interrupted or is out of specification, the UPS automatically
switches to Battery mode to support the critical load with no interruption. When
utility power returns, the UPS returns to Normal mode.
If the UPS system becomes overloaded, the UPS switches to Bypass mode. The
UPS automatically returns to Normal mode when the error condition is cleared and
system operation is restored within specified limits.
Output
If the UPS suffers an internal failure, it switches automatically to Bypass mode and
remains in that mode until the failure is corrected and the UPS is back in service.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
41
Page 50
Bypass Mode
The UPS automatically switches to Bypass mode if it detects an overload, load
fault, or internal failure. The bypass source supplies the commercial AC power to
the load through an internal switch and an internal transformer.
CAUTION:
The critical load is not protected while the UPS is in Bypass mode.
Figure 19 shows the path of electrical power through the UPS system when the UPS
is operating in Bypass mode.
BYPASS
(BIB)
(closed)
OUTPUT
TRANSFORMER
Bypass
Input
(MBP)
(open)
Rectifier
Input
Tra n s f o r m e r
RECTIFIERINVERTER
K4
K3
(closed)
(MIS)
(closed)
Input
Isolation
CB1
DC/DC
CONVERTER
CB2
(closed)
Path of electrical power
BATTERY
Figure 19. Path of Current Through the UPS in Bypass Mode
You can transfer the UPS from Normal mode to Bypass mode manually. However,
the UPS switches automatically to Bypass mode whenever the inverter can no
longer supply the critical load. If the UPS transfers to Bypass mode from Normal
mode due to any reason other than operator intervention, the UPS automatically
attempts to transfer back to Normal mode (up to three times within a 10-minute
period).
Output
Bypass mode is a normal operating mode, and not an alarm condition. However, if
the UPS is unable to return to Normal mode following an automatic transfer to
Bypass mode, an alarm condition will be recorded.
42
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 51
Battery Mode
The UPS transfers to Battery mode automatically if a utility power outage occurs, or
if the utility power does not conform to specified parameters. In Battery mode, the
battery, through the DC to DC voltage converter, provides emergency DC power
that the inverter converts to AC power. When the UPS switches to Battery mode,
the alarm indications depend on the cause and condition of the battery charge.
The length of time the system can operate in Battery mode depends on loading
and the battery supply capacity.
Figure 20 shows the path of electrical power through the UPS when operating in
Battery mode.
BYPASS
(BIB)
(closed)
OUTPUT
TRANSFORMER
Bypass
Input
(MBP)
(open)
Rectifier
Input
Tra n s f o r m e r
RECTIFIERINVERTER
K4
K3
(closed)
(MIS)
(closed)
Input
Isolation
CB1
DC/DC
CONVERTER
CB2
(closed)
Path of electrical power
BATTERY
Figure 20. Path of Current Through the UPS in Battery Mode
When the discharging battery voltage reaches the lower limit of UPS operation
capability, the critical load transfers to Bypass mode if it is available. If Bypass input
is not available, a “Shutdown Imminent” warning occurs. The warning time before
critical load loss occurs is approximately 2 minutes, depending on battery capacity
and the amount of loading.
If incoming power returns to within specified parameters, the UPS automatically
returns to Normal mode and alarm indications clear. However, the process of returning
to Normal mode is not instantaneous. The rectifier gradually draws increasing power
from the incoming utility until Normal mode is achieved.
Output
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
43
Page 52
Maintenance Bypass Mode
The UPS can be manually switched to Maintenance Bypass mode allowing the
UPS to be electrically isolated from the critical load. The bypass source supplies
the commercial AC power to the load through an internal circuit breaker.
CAUTION:
Critical load is not protected while the UPS is in Maintenance Bypass mode.
Figure 21 shows the path of electrical power through the UPS system when the UPS
is operating in Maintenance Bypass mode.
BYPASS
TRANSFORMER
(BIB)
(open)
OUTPUT
Bypass
Input
(MBP)
(closed)
Rectifier
Input
Tra n s f o r m e r
RECTIFIERINVERTER
Input
Isolation
CB1
K4
K3
(closed)
(MIS)
(open)
DC/DC
CONVERTER
CB2
(closed)
Path of electrical power
BATTERY
Figure 21. Path of Current Through the UPS in Maintenance Bypass Mode
The wrap--- around maintenance bypass is useful during routine UPS maintenance
or repairs, by suppling utility power to the critical load while the UPS inverter and
bypass are de-energized.
The major components of the Maintenance Bypass are described in the following
paragraphs.
Maintenance Bypass (MBP) Circuit Breaker
This breaker is normally open. When closed, it feeds utility power to the critical load
when the MIS breaker is opened.
Maintenance Isolation (MIS) Circuit Breaker
This circuit breaker is normally closed, feeding UPS power to the critical load. This
breaker is opened to isolate the UPS after the MBP breaker is closed.
Maintenance Bypass (MBP) Circuit Breaker
This circuit breaker is normally closed feeding bypass power to the UPS internal
bypass circuit. This breaker is opened to isolate the UPS bypass after the load is
transferred to maintenance bypass.
Output
The MBP and MIS breakers are electrically interlocked to limit the possibility of UPS
system damage from improper operation.
44
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 53
Monitoring and Contro lling UPS Operation
After you start the UPS, operator intervention is unnecessary except for periodic
checks of the UPS status. Manual operation is required only during routine
maintenance or service. Use the Monitor Panel and the Control Panel to monitor
and control the UPS. Figure 22 shows the location of these two panels on the front
of the UPS.
CONTROL
PANEL
MONITOR
PANEL
Figure 22. Location of the Monitor Panel and the Control Panel
The Monitor Panel on the left front of the UPS continually indicates the present
mode of UPS operation. This panel contains an LCD screen, backlit status
indicators, and the EMERGENCY POWER OFF pushbutton. Use the LCD screen
on the Monitor Panel to view performance meters or graphic representations of
UPS operation. The Monitor Panel is described in detail in Chapter 9 --- Using theMonitor Panel. A quick reference label describing how to use the Monitor Panel is
located below the Monitor Panel.
The Control Panel located to the right of the Monitor Panel contains various
controls and switches. These control power to and from the UPS, and allow you to
change the UPS mode manually. The Control Panel is discussed in Chapter 10.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
45
Page 54
This Page Intentionally Left Blank.
46
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 55
UPS Controls
TheUPShasthreeprimarycontrolareasasdescribed in the following paragraphs.
Control Panel
The Contro l Panel on the front of the UPS (see Figure 22) contains the operator
controls to start and stop the UPS and change the operating mode. The Control
Panel is described in Using the Operating Controls section of Chapter 10.
Monitor Panel
The Monitor Panel on the front of the UPS (see Figure 22) contains an LCD screen
to display the current status of the UPS. You can view a statistical history and log
of UPS events and display a real-time graphic representation of power flowing
through the UPS components. Backlit status indicators show the operating mode
of the UPS and alert you to system events.
Maintenance Bypass
Maintenance Bypass (MBP) Circuit Breaker
This breaker is normally open. When closed, it feeds utility power to the critical load
when the MIS breaker is opened.
Maintenance Isolation (MIS) Circuit Breaker
This circuit breaker is normally closed, feeding UPS power to the critical load. This
breaker is opened to isolate the UPS after the MBP breaker is closed.
Maintenance Bypass (MBP) Circuit Breaker
This circuit breaker is normally closed feeding bypass power to the UPS internal
bypass circuit. This breaker is opened to isolate the UPS bypass after the load is
transferred to maintenance bypass.
Controls and Features
UPS Standard Features
The UPS has many standard features that provide cost-effective and consistently
reliable power protection:
Communication Panel
Computer Interface
One combination RS ---232/RS --- 485 serial communication port is standard on all units,
and is electrically isolated from the UPS. An additional RS --- 232 serial communicationport is available (as an option), and is also electrically isolated from the UPS.
Summary Alarm Contacts
Alarm contacts are provided for connection to equipment at your facility, such as a
light, an audible alarm, or a computer terminal. The equipment you connect to these
contacts alerts you to a UPS alarm.
Input Filter
Your unit may be equipped with an input filter.Aninput filter yields power factor
correction that allows you to save on your initial installation and operating costs.
The filter also reduces input harmonic current distortion and minimizes upstream
interference that can damage sensitive hardware components.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
47
Page 56
Emergency Power Off
An EMERGENCY POWER OFF pushbutton is provided for situations where you
must immediately remove all power to your critical load. The pushbutton is located
on the Monitor Panel for quick access and is covered with a clear plastic shield to
prevent inadvertent operation. The shield must be raised before pressing the
pushbutton. The EMERGENCY POWER OFF pushbutton is described in detail in
Chapter 10, “Using the EMERGENCY POWER OFF Pushbutton.”
Automatic Battery Charge Current Limit
A preset limit restricts battery charging current to protect batteries from damage
due to high current charging. Charging at high currents can overheat and damage
batteries.
Installation Features
Power and control wiring can be routed through the top of the Environmental
cabinet. The cabinet has an internal wi reway.
Options and Accessories
Contact your sales representative for information about any of these available
options:
Remote Monitor Panel
An optional Remote Monitor Panel (RMP) contains backlit status indicators and a
local horn, allowing you to monitor the operational status and alarm condition of
the UPS from virtually any location within your facility . You can install multiple
RMPs at remote locations to increase your monitoring capabilities. This option is
described further in Chapter 11, “Using Features and Options.”
Relay Interface Module
An optional Relay Interface Module (RIM) uses relay contact closures to indicate
the operating status and alarm condition of the UPS system. The module uses a
serial interface line and may support up to eight critical loads. This option is
described further in Chapter 11, “Using Features and Options.”
Supervisory Contact Module
An optional Supervisory Contact Module (SCM) establishes an interface between
the UPS manufacturer’s equipment and the customer’s monitor. This interface
allows the customer to monitor operational status of the UPS equipment. This
option is described further in Chapter 11, “Using Features and Options.”
Modem
An optional modem is available for use with the UPS Remote Notification feature
described in Chapter 14, “Optional Remote Notification”. Refer to the manual
supplied with the modem for modem operating instructions.
Customer Convenience Outlet
An uninterruptible 120 VAC, 0.2 amp, fuse-protected convenience outlet is provided
with the optional modem. It is located adjacent to the Communications Panel.
48
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 57
Safety Considerations
The UPS enclosures are designed for industrial or computer room applications,
and contain safety shields behind the doors. However, the UPS is a sophisticated
power system and should be handled with appropriate care, following these
guidelines:
•Keep surroundings clean and free from excess moisture.
•Do not operate the UPS close to gas or electric heat sources.
•The system is not intended for outdoor use.
•The UPS operating environment should be maintained within the
parameters stated in this manual.
•Keep the UPS doors closed to ensure proper cooling airflow and to protect
personnel from dangerous voltages inside the unit.
•The UPS contains i ts own power source. Lethal voltages are present even
when the UPS is disconnected from utility power.
WARNING:
Only AUTHORIZED SERVICE PERSONNEL should perform service or
maintenance on the UPS or battery.
If service or routine UPS maintenance is required:
•Ensure all power is disconnected before performing installation or service.
•Ensure the area around the UPS system is clean and uncluttered.
•Battery cabinet maintenance or battery replacement should be performed
only by authorized service personnel.
•Observe all DANGER, CAUTION, and WARNING notices affixed to the
inside and outside of the equipment.
•Always conform to the more detailed safety precautions described in
“Important Safety Instructions” section of Chapter 15.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
49
Page 58
Symbols, Controls, and Indicators
These symbols may appear on your UPS system or on labels inside the UPS. They
are accepted by most international safety agents. Everyone in your organization
who works with your UPS should understand the meaning of these symbols:
ON
The principal power switch is in the On position.
OFF
The principal power switch is in the Off position.
PHASE
The word phase.
CAUTION: REFER TO MANUAL
Stop and refer to the Operator’s Manual for more information.
RISK OF ELECTRIC SHOCK
There is a risk of electric shock present, and you should observe
associated warnings. The UPS contains high voltages.
50
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 59
Using the Monitor Panel
This chapter describes the Monitor Panel and how to monitor and control
UPS operation. The Monitor Panel is a black rectangular area on the front of
the UPS (see Figure 23).
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
UNINTERRUPTIBLE POWER SYSTEM
Figure 23. UPS Monitor Panel
51
Page 60
The Monitor Panel contains:
1. A flat liquid crystal display (LCD) screen.
2. A horizontal row of pushbuttons.
3. A vertical column of backlit status indicators.
4. AredEMERGENCY POWER OFF pushbutton.
A quick reference label describing how to use the Monitor Panel is located below the
Monitor Panel. The following sections describe the Monitor Panel in detail.
Using the LCD Screen
The LCD screen at the top of the Monitor Panel provides an operator interface with
the UPS. Figure 24 identifies the display fields discussed in the following sections.
System Normal
A
Alarm: None
Notice: None
Uninterruptible Power System
04 MAY 1998 14:23:45
F
B
C
D
E
Battery
Percent
Meters
System
Load Amps
Meters
100%
Events Statistics Graphics Setup
VAB
480
InputOutput
VBCVCA
480480
IAIBIC
88
KVA
73
VAB
480
KW
69
BypassBattery
VBCVCA
480480
8888
PF
0.95
FREQ
60.0
VAB
480
IAIBIC
909090
VBCVCA
480480
KVA75KW60PF
V
540
0.80
I
000
FREQ
60.0
IN
000
Figure 24. Parts of the LCD Screen (Typical for Powerware BPIII HE 75 480/480V Unit)
A The UPS status area contains three lines that display the current state of the UPS. The first
line shows the present operational mode of the UPS. The second line shows the highest level
of the current active alarms, and the t hird line shows any notices the UPS has posted. (For
more information about alarms and notices, refer to Chapter 12 --- Responding to System
Events.)
G
B The battery charge box shows the percentage of battery capacity available.
C The menu box shows t he currently selected menu and lists the options available on that
menu. The title at the top of the menu box is also shown below on the menu bar (E). Press
andpushbuttons to scroll up and down through the options in the menu box.
the
52
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 61
D The currently selected option is highlighted in the menu box. Press theandpushbuttons
to move the highlight up or down. The data in the information area (G) changes accordingly.
E The menu bar lists the titles of the menus. The title of the menu currently displayed in the
menu box is highlighted. When you press the
right or left, the data in the menu box and the information area change accordingly.
andpushbuttons to move the highlight
F The timestamp shows the current date and time. This date and time are recorded in the Event
Log when a notice or alarm is activated.
G The information area contains data about UPS status and operations. Select a menu option to
display statistics or graphics.
You can use the LCD screen and the pushbuttons beneath it to:
•Monitor UPS operation
•Look at a log of UPS events (alarms, notices, and commands).
Using the Pushbuttons
The pushbuttons below the LCD screen are labeled with arrows indicating their
functions:
•Press theandpushbuttons to move through the menu titles on the
menu bar. Press them simultaneously to silence the horn, or to test the lamps
behind the status indicators.
•Press theandpushbuttons to move through the options in a menu, or to
scroll through the list of alarms and notices in the event log.
•Press thepushbutton to toggle the use of theandpushbuttons
between the menu box and the information area.
Adjusting the Contrast
•Use the pushbuttons to adjust the contrast on the LCD screen. Hold down the
pushbutton, then press thepushbutton to increase the contrast or the
pushbutton to decrease the contrast.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
53
Page 62
Reading the Status Indicators
Thesixlightsontheleftsideofthemonitorpanelarestatus indicators.Theyare
backlit by colored light emitting diode (LED) lamps, and work in conjunction with
the alarm horn to let you know the operating status of the UPS.
NormalThis green indicator is lit when the UPS is operating in Normal mode.
The power processing unit (PPU) is supplying power to the critical load.
BatteryThis yellow indicator is lit when the UPS is operating in Battery mode.
Because Battery mode is a normal condition of the UPS, the Normal
indicator also remains lit.
BypassThis yellow indicator is lit w hen the UPS is operating in Bypass mode.
The critical load is supported by the bypass source. The Normal indicator
is not lit when the system is in Bypass mode.
NoticeThis yellow indicator is lit when the system needs attention. The LCD
screen shows all active notices. Some notices may be accompanied by
an audible horn. To silence the horn, press the
simultaneously. The Notice indicator may be lit along with other indicators.
AlarmThis red indicator is lit when a situation requires immediate attention. The
LCD screen shows the highest priority active alarms. All alarms are
accompanied by an audible horn. To silence the horn, press the
andpushbuttons simultaneously. The Alarm indicator may be lit
along with other indicators.
andpushbuttons
StandbyThis yellow indicator is lit when electricity is present in the PPU of the UPS
and the Normal indicator is not lit. During normal startup, this indicator
illuminates until the UPS transfers to Normal mode, at which point the
Normal indicator is lit. During normal shutdown, the Standby indicator is lit
until all energy in the UPS is dissipated and shutdown is complete.
For more information about audible horns, refer to the System Event Horns section of
Chapter 12.
To test the LED lamp status indicators, press the
simultaneously for 3 seconds. All the indicators should light while you hold down
these pushbuttons. If any indicator does not light, its LED may need to be
replaced. Contact Customer Service if you have a problem with the indicator
lamps.
andpushbuttons
54
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 63
Using the Menu Options
The UPS menus allow you to display data in the information area to help you
monitor and control UPS operation. The following menus and options are
available:
•MetersDisplays UPS performance meters for the system or critical load.
•EventsDisplays the list of Active System Events and a historical log of
system events.
•StatisticsDisplays statistical information about UPS operations for the
battery, load, or line.
•GraphicsDisplays a real-time graphic representation of the flow of current
through the internal UPS components.
•SetupAllows you to configure the UPS communications port and set
the date and time for the timestamp.
Figure 25 shows the LCD screen as it appears when you first start the UPS. The Meters
menu is displayed in the menu box, with the System option highlighted. In the
information area, the system meters show their current readings.
Uninterruptible Power System
System Normal
Alarm: None
Notice: None
04 MAY 1998 14:25:45
Battery
Percent
Meters
System
Load Amps
Meters
100%
Events Statistics Graphics Setup
VAB
480
InputOutput
VBCVCA
480480
IAIBIC
88
KVA
VAB
480
KW
69
73
BypassBattery
VBCVCA
480480
8888
PF
0.95
FREQ
60.0
VAB
480
IAIBIC
909090
VBCVCA
480480
KVA75KW60PF
V
540
0.80
I
000
FREQ
60.0
IN
000
Figure 25. System Meters Screen (Typical for Powerware BPIII HE 75 480/480V Unit)
The Input area shows the phase-to-phase voltage, frequency, and phase current of the
incoming utility, followed by the KVA, KW, and power factor measurements. The output
area shows the same information for the power being output by the UPS.
TheBypassareashowsthephase-to-phasevoltageofthebypasssource. TheBattery
area displays the D C voltage (V) and the DC current (I) at the inverter side of the DC
to DC voltage converter.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
55
Page 64
Select Load Amps from the Meters menu to see a real-time bar graph of the output
current of the UPS. The graph shows the current for each phase.
Figure 26 shows the Load Amps Meters screen.
Uninterruptible Power System
System Normal
Alarm: None
Notice: None
04 MAY 1998 14:25:45
Battery
Percent
100%
Meters
System
Load Amps
Events Statistics Graphics SetupMeters
Output Current
125%
100%
75%
50%
25%
0%
Phase APhase BPhase C
Figure 26. Load Amps Meters Screen
56
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 65
Select History from the Events menu to display the Event History Log. The Event
History Log lists up to 400 system events in chronological order, with the most
recent event listed last. The end of the log (the most recent events) appears when
you display the screen, and you must scroll upward to view older event listings.
Figure 27 shows the Event History Log screen.
Uninterruptible Power System
System Normal
Alarm: None
Notice: None
04 MAY 1998 14:25:48
Battery
Percent
100%
Events
History
Active
EventsMeters
Date / Time
May
03
16:41:19.3
03
16:41:20.1
03
16:41:22.4
03
16:41:25.5
03
16:41:26.8
03
16:41:27.8
03
16:41:30.4
16:41:29.1
03
16:41:36.6STATUS: Inverter Normal
Statistics Graphics Setup
Event History Log
Event Description
COMMAND: Keyswitch On
STATUS: Auto Mode
COMMAND: Rectifier Commanded On
STATUS: Inverter On
STATUS: Rectifier On
STATUS: Battery Contactor (K2) Closed
STATUS: Inverter Contactor (3) Closed
STATUS: Bypass Contactor (K4) Open03
Figure 27. Event History Log Screen
A small return arrow ( ) appears in the upper right corner of the information area of
the Event History Log screen. This arrow is a reminder that you can press the
pushbutton on the Monitor Panel to toggle the scroll bar between the menu box
and the information area. When the scroll bar is in the information area, the return
arrow is in the menu box. When the scroll bar is in the menu box, the return arrow
is in the information area.
When the scroll bar is in the information area, you can press the
to scroll through the Event History log.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
andpushbuttons
57
Page 66
Select Active from the Events menu to display a listing of all system events that are
currently active. The most recent system event is listed first. As events clear, they
areremovedfromtheActiveSystemEventslisting.
Figure 28 shows the Active System Events screen.
Uninterruptible Power System
Alarm: On BatteryShutdown Imminent
Notice: None
04 MAY 1998 14:25:50
Battery
Minutes
001.3
Events
History
Active
Events Statistics Graphics SetupMeters
Active System Events
NOTICE: Input power unavailable
NOTICE: Bypass Not Available
ALARM:Shutdown Imminent
Figure 28. Active System Events Screen
58
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 67
Select Unit from the Statistics menu to display a listing of statistics about UPS
operation.
Figure 29 shows the Unit Statistics screen.
Uninterruptible Power System
UPS System Normal
Alarm: None
Notice: None
04 MAY 1998 14:23:50
Battery
Percent
100%
Statistics
Unit
Events Statistics Graphics SetupMeters
Number of Incidents:
On Battery < 1 Min.
On Battery 1-4 Min.
On Battery > 4 Min.
Full Batt. Discharge
Building Alarm 1
Building Alarm 2
Building Alarm 3
Building Alarm 4
Building Alarm 5
Building Alarm 6
The left column shows the number of UPS incidents for the current month and
since the start date shown at the top of the screen. The top right column shows
the time that the UPS was on bypass, battery, or generator , and the amount of time
the UPS logic has been functioning since the start date. The lower right column
shows the percent of availability of the UPS and the bypass source.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
59
Page 68
Select Mimic from the Graphics menu to display a real-time graphical representation
of the flow of current through the UPS.
Figure 30 shows the Mimic screen.
Uninterruptible Power System
UPS System Normal
Alarm: None
Notice: None
Battery
Percent
100%
Bypass
CB1K3
RectifierInverter
04 MAY 1998 14:25:55
Graphics
Mimic
Events Statistics Graphics SetupMeters
K2
Battery
Figure 30. Mimic Screen
The Mimic screen shows the internal components of the UPS cabinet. The flow of
current through the components is highlighted.
60
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 69
Select Time from the Setup menu to display the Time Setup screen. The Time
Setup screen allows you to set the internal timestamp of the UPS. The timestamp
is used for logging events in the Event History Log. Figure 31 shows the Time
Setup screen.
Uninterruptible Power System
UPS System Normal
Alarm: None
Notice: None
Battery
Percent
100%
Setup
Port 1
Port 2
Time
Set Time & Date
DAY DT
MON 07
MON
APRYR98
HR:MN
15:06
04 MAY 1998 14:25:55
SAVE
YES
EventsMeters
Statistics Graphics Setup
Figure 31. Time Setup Screen
The small return arrow ( ) appears in the upper right corner of the Time Setup
screen. This arrow is a reminder that you can press the
pushbutton on the
Monitor Panel to toggle the pushbuttons between the menu box and the
information area. When the scroll bar is in the information area, the return arrow is
in the menu box. When the scroll bar is in the menu box, the return arrow is in the
information area.
When the scroll bar appears in the information area, you can use the pushbuttons
to change the timestamp settings. To change a setting in the timestamp, press the
andpushbuttons to highlight the setting you want to change. To increase the
setting (make it a higher value), press the
(make it a lower value), press the
pushbutton. If you want to save the settings
pushbutton. To decrease the setting
upon exit from this screen, be sure the SAVE field is set to YES.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
61
Page 70
Select Port 1 or Port 2 from the Setup menu to display one of the Port Setup
screens. The Port Setup screens allow you to specify settings for the two serial
communication ports on the UPS. Figure 32 shows the Setup Serial Port 1 screen.
Uninterruptible Power System
UPS System Normal
Alarm: None
Notice: None
Battery
Percent
100%
Setup
Port 1
Port 2
Time
MODE
TERMINAL
Setup Serial Port 1
RATE
DATA/STOP
9600
81
04 MAY 1998 14:25:58
HANDSHAKING
XON / XOFF
SAVE
NO
EventsMeters
Statistics Graphics Setup
Figure 32. Port Setup Screen
The small return arrow ( ) appears in the upper right corner of the Port Setup
screen. This arrow is a reminder that you can press the
pushbutton on the
Monitor Panel to toggle the pushbuttons between the menu box and the
information area. When the scroll bar is in the information area, the return arrow is
in the menu box. When the scroll bar is in the menu box, the return arrow is in the
information area.
When the scroll bar appears in the information area, you can use the pushbuttons
to change the port configuration. To change a setting, press the
andpushbuttons
to move the highlight to the setting you want to change. To scroll through the
available options for that setting, press the
orpushbutton. To save the
settings upon exit from this screen, be sure the SAVE field is set to YES.
The setup screens for Port 1 and Port 2 are identical.
62
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 71
Operating the UPS
This chapter describes how to start and stop the UPS and how
to transfer the system to maintenance bypass. Figure 33 shows the
location of the operating controls.
CONTROL
PANEL
MONITOR
PANEL
NOTE:
Before starting the UPS, ensure all installation tasks are complete and a preliminary
startup has been performed by authorized service personnel. The preliminary
startup verifies all electrical interconnections to ensure the installation was
successful and the UPS system operates properly.
BYPASS INPUT
BREAKER (BIB)
MAINTENANCEMAINTENANCERECTIFIER
BYPASS
BREAKER (MBP)
ISOLATION
SWITCH (MIS)
INPUT BREAKER
(CB1)
BATTERY
BREAKER
(CB2)
POWER
SWITCH
S1
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
Figure 33. Location of the Operating Controls
COLD
START
SWITCH
S2
63
Page 72
Using the Operating Controls
Although the operating controls appear easy to use, you should read these
instructions and thoroughly understand how the controls work before attempting
to use them. Refer to oneline drawing 164201261---3 in Appendix A to clarify control
functions. Refer to Chapter 9 --- Using the Monitor Panel for instructions on using
the monitor panel.
CAUTION:
Incorrect use of the power controls can cause a loss of power to your
critical load.
The following paragraphs describe the switches on the Control Panel (see Figure 34).:
•The MODE switch is a two-position rotary switch that controls the manual
transfer of the UPS to and from Bypass mode. The MODE switch is used to:
--- Place the critical load in Bypass mode when the UPS is operating in Normal
mode and the bypass source is within acceptable limits. If the transfer does
not occur within 2 seconds, an alarm sounds.
--- Prevent transfer to Normal mode when the UPS is in Bypass mode.
--- S h u t d o w n t h e power processing unit (inverter and rectifier) of the UPS.
NORMAL
OFF
PUSH
TO RESET
BATTERY
NORMAL
BYPAS S
START
Figure 34. UPS Control Panel
MODE
•The BATTERY switch is a two-position rotary switch that allows you to manually
enable or disable the Battery Breaker CB2. The battery switch is also used to
reset the DC to DC converter if the converter shuts down during normal
operation.
•The PUSH TO RESET pushbutton is described in the “Resetting UPS System
after Emergency Power Off” section of this chapter.
64
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 73
•The START switch activates the power controls on the Control Panel. The
START switch is center-biased (the key will rest only in the upright position). Its
operation is similar to that of an automobile ignition switch. After setting the
operator controls, you turn the START switch to the right momentarily to
activate the controls. When you release it, it returns to the upright position.
The following paragraphs describe the controls and indicators found in the
Environmental cabinet (see Figure 33).
•The circuit breaker (CB1) switch supplies power to the rectifier and inverter. If
CB1 is on (closed), the rectifier turns on when the START switch is activated
and the proper voltage is at the input terminals.
•The circuit breaker (CB2) switch controls the application of battery power to the
UPS. If CB2 is closed, the rectifier charges the battery through the DC to DC
converter during normal operation. If utility power is lost, battery power is
supplied to the inverter through the DC to DC converter.
SMaintenance Bypass (MBP) Circuit Breaker --- T h i s b r e a k e r i s
normally open. When closed, it feeds utility power to the critical load
when the MIS breaker is opened.
SMaintenance Isolation (MIS) Circuit Breaker --- This circuit breaker
is normally closed, feeding UPS power to the critical load. This
breaker is opened to isolate the UPS after the MBP breaker is
closed.
SBypass Input (BIB) Circuit Breaker --- This circuit breaker is
normally closed feeding bypass power to the UPS internal bypass
circuit. This breaker is opened to isolate the UPS bypass after the
load is transferred to maintenance bypass.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
65
Page 74
Operation
The following sections describe how to operate the controls to start, stop, or
change the operating mode of the UPS.
To Place the UPS in Normal Mode:
1. Close BIB circuit breaker.
2. Close CB1 circuit breaker.
3. Turn th e BATTERY switch to NORMAL.
4. Turn th e MODE switch to NORMAL.
5. Ensure the Emergency Power Off PUSH TO RESET pushbutton is pressed in.
6. Turn th e START switch to the right momentarily.
After the rectifier reaches 540 VDC, the DC to DC converter begins to turn on.
After the converter reaches full voltage, the OK To Close CB2 notice is
displayed on the Monitor Panel LCD screen.
7. When the OK To Close CB2 notice is displayed on the Monitor Panel LCD
screen, close circuit breaker CB2.
The inverter begins to turn on. When the inverter reaches full voltage, it turns
on and supplies power to the critical load.
IfabypasssourceisavailablewhenyouturntheSTART switch on, the critical
load is immediately supplied by the bypass source in Bypass mode until the
inverter turns on and the UPS transfers to Normal mode. The status indicators
on the Monitor Panel indicate when the UPS is in Bypass mode and Normal
mode.
To Shut Down the UPS from Normal Mode:
1. Turn th e MODE switch to BYPASS.
The UPS switches to Bypass mode. If the bypass source is not available, the
power processor remains on and an alarm sounds.
CB2 breaker switch to OFF. Then move the CB1 breaker switch to OFF.
The bypass source supplies the critical load and the power processor
de-energizes. The Bypass mode indicator illuminates on the Monitor Panel.
66
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 75
To Start the UPS in Bypass Mode:
If the power processing unit (PPU) of the UPS is not available and you need to
energize your critical load right away, you can energize your critical load without
the benefit of backup. To turn the UPS on in Bypass mode:
1. Turn th e MODE switch to BYPASS. (The remaining switches can be in any
position.)
2. Ensure the Emergency Power Off PUSH TO RESET pushbutton is pressed in.
3. Turn th e START switch to the right momentarily.
Power to the critical load is supplied by the bypass source. No backup is
available.
To Transfer the Critical Load to Maintenance Bypass from UPS Bypass:
1. Confirm BIB circuit breaker is closed.
2. Turn MODE switch to BYPASS.
The UPS switches to Bypass mode. If the bypass source is not available, the
power processor remains on and an alarm sounds.
3. Close MBP circuit breaker.
Caution: Failure to close the MBP circuit breaker will result in loss of power to
the critical load.
4. Open MIS circuit breaker. The critical load is now on maintenance bypass.
5. Open the BIB circuit breaker to electrically isolate the UPS bypass.
6. When the transfer is complete, move the CB2 breaker switch to OFF.Then
move the CB1 breaker switch to OFF.
The maintenance bypass source supplies the critical load and the power
processor de-energizes.
To Transfer the Critical Load t o UPS Bypass from Maintenance Bypass:
1. Confirm BIB circuit breaker is closed.
2. Turn th e MODE switch to BYPASS.
The UPS switches to Bypass mode. If the bypass source is not available, the
power processor remains on and an alarm sounds.
3. Close MIS circuit breaker.
Caution: Failure to close the MIS circuit breaker will result in loss of power to
the critical load.
4. Open MBP circuit breaker. The critical load is now on UPS bypass.
5. To transfer the critical load to normal mode follow the procedure “To Place the
UPS in Normal Mode” at the beginning of this section.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
67
Page 76
To Cold Start the UPS from Battery (No AC Input Power):
To start the UPS system when commercial power is not available, perform the
following procedure:
1. Ensure the feeder breaker is open (no input or bypass power available).
2. Place the BATTERY switch in the NORMAL position.
3. Place the MODE switch in the NORMAL position.
4. Ensure the Emergency Power Off PUSH TO RESET pushbutton is pressed in.
5. Close input breaker CB1.
6. Place Power Switch S1 (located in the environmental cabinet) to the ON
position.
Logic power comes on for all PCBs and Horn sounds every 2 seconds.
7.
The following UPS messages are displayed on the Monitor Panel LCD screen:
Status:Load Off
Alarm:Converter Offline
Notice:Bypass AC Under Voltage
Output AC Under Voltage
Converter in Shutdown
8. Monitor the LCD meter screen for battery voltage.
9. Press and hold Cold Start switch S2.
The converter K1 contactor closes after 5 seconds.
LCD meter screen should indicate 120 to 130 VDC.
The following message appears on the screen:
Notice:OK to Close CB2
Converter In Startup
10. Close battery breaker CB2.
11. When the DC reaches 250 VDC, the converter starts.
The DC walks up to 540 VDC.
The inverter starts.
K3 closes.
All fans and blowers are functional.
68
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 77
12. System is now on line (Inverter input supported by battery) and will continue
until the battery is depleted or commercial input power returns.
Thefollowingmessagesappearonthescreen:
Status:System Normal, On Battery
Alarm:On Battery more than 30 Seconds
Notice:Bypass AC Under Voltage
Bypass is Not Available
Input AC Under Voltage
13. Place Power Switch S1 (located in the environmental cabinet) to the OFF
position.
14. To return the UPS to NORMAL MODE of operation when commercial power
returns, close the feeder breaker.
The UPS can be transferred to bypass and shut down normally.
To Shut Down the UPS from Cold Start:
1. Place Power Switch S1 (located in the environmental cabinet) to the ON
position.
2. Place the BATTERY switch in the OFF position.
3. Place the MODE switch in the BYPAS S position.
4. Place Power Switch S1 (located in the environmental cabinet) to the OFF
position.
5. Open battery breaker CB2.
6. Open input breaker CB1.
To Reset the DC to DC Converter:
1. Turn BATTERY switch to OFF.
2. Wait at least four seconds. Turn BATTERY switch to NORMAL. The converter
restarts.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
69
Page 78
Using the EMERGENCY POWER OFF Pushbutton
Emergency Power Off is initiated by the covered, red EMERGENCY POWER OFF
pushbutton on the Monitor Panel. This pushbutton is protected by a clear plastic
shield to prevent accidental activation. In an emergency, you can press this
pushbutton to instantaneously open the input breaker and interrupt UPS output.
The UPS is cut off from utility power, and your critical load is de-energized. All
power to the critical load is lost. The UPS (including Bypass) remains locked off
until you reset the EMERGENCY POWER OFF pushbutton.
WARNING:
All power to the critical load is lost when you press this pushbutton. You should
use this feature only in an emergency or when you want to de-energize the critical
load.
To restart the UPS after pressing the EMERGENCY POWER OFF pushbutton,
follow the procedure “Resetting UPS System after Emergency Power Off” of this
chapter before starting the UPS.
NOTE: The Remote EMERGENCY POWER OFF option functions the same way as
the EMERGENCY POWER OFF pushbutton on the Monitor Panel.
To Use the EMERGENCY POWER OFF Pushbutton
1. Raise the clear plastic shield covering the red EMERGENCY POWER OFF
pushbutton on the Monitor Panel.
2. Press the EMERGENCY POWER OFF pushbutton.
The breakers open (you can hear them opening). The breaker CB1 trips, and the
Emergency Power Off PUSH TO RESET pushbutton on the UPS Control Panel pops
out. The UPS system shuts down.
Resetting UPS System after Emergency Power Off
CAUTION:
Do not attempt to restart the system until the cause of the emergency has been
identified and cleared.
The Emergency Power Off PUSH TO RESET pushbutton is a small white button on
the UPS Control Panel. The PUSH TO RESET pushbutton pops out and the CB1
switch trips when the EMERGENCY POWER OFF pushbutton on the Monitor
Panel is activated.
To r es et t he U PS s ys te m:
1. Press the Emergency Power Off PUSH TO RESET pushbutton until it clicks in
and remains recessed.
2. Move the CB1 switch from the TRIPPED (center) position to OFF.Theswitch
should be difficult to move from the TRIPPED position.
3. The UPS system is now reset. To restart the UPS system, follow the procedure
at the beginning of this chapter.
70
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 79
Using Features and Options
The many standard features of your UPS provide consistent,
economical, and dependable power protection. In addition, you
can add available options and accessories to enhance the performance of your
UPS system. This chapter provides detailed descriptions of some of the features
and options introduced earlier in this manual.
Building Alarm Monitoring
This standard feature lets you connect the UPS to your building alarms, such as
smoke detectors or overtemperature alarms. The terminals for external
connections are located inside the UPS on the customer interface panel
(see Figure 35).
TB1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
BLDG ALARM 1
BLDG ALARM 1 RTN
BLDG ALARM 2
BLDG ALARM 2 RTN
BLDG ALARM 3
BLDG ALARM 3 RTN
BLDG ALARM 4
BLDG ALARM 4 RTN
BLDG ALARM 5
BLDG ALARM 5 RTN
BLDG ALARM 6
BLDG ALARM 6 RTN
TB2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
REMOTE EPO
REMOTE EPO RTN
ON INV
ON INV RTN
ON BYPASS
ON BYPASS RTN
BATTERY CONTACTOR CLOSED
BATTERY CONT RTN
RELAY 1 NO
RELAY 1 NC
ALARM RTN
RELAY 2 NO
RELAY 2 NC
NOTICE RTN
RS485
NOTE:
All building alarm inputs or remote
features require an isolated, normally
open contact or switch (rated at 24 Vdc
20 mA minimum) connected between
the alarm input terminal and common
terminal as shown. All control wiring,
relay, and switch contacts are customer
provided.
RS232
(Optional)
Figure 35. External Connections for Building Alarm Monitoring
Regardless of how you assign the building alarms, they display as Building Alarm 1,
Building Alarm 2, Building Alarm 3, etc., on the LCD screen of the Monitor Panel. You
should use twisted pair wires for each alarm input and common.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
71
Page 80
Summary Alarm Contacts
Two summary alarm contacts are provided as a standard feature on the UPS. The
alarm contacts (one notice and one alarm) are located inside the UPS o n the
customer interface panel (see Figure 36).
TB2
ALARM NO
ALARM NC
COMMON
NOTICE NO
NOTICE NC
COMMON
10
11
12
13
14
15
Figure 36. Summary Alarm Contacts
You can specify that each contact be either normally closed (NC) or normally open
(NO). If the state of the contact changes from the state you specify as normal, an alarm
is issued. You can connect these contacts to equipment at your facility (such as a light
or an alarm bell) to let you know when an alarm is active on the UPS. This feature is
useful if the UPS is located in a remote area where the UPS alarm horn may not be
heard immediately.
CAUTION:
Contacts should not be operated in excess of 30 VAC or 42.4V peak AC or DC
@1Amaximum.
72
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 81
Remote Monitor Panel
As an option, you can install Remote Monitor Panels (RMPs) to monitor the
operation of the UPS system from virtually any location within your facility, up to
500 feet from the UPS. Each RMP contains backlit status indicators and a local
horn. You can flush-mount or surface-mount an RMP on a desktop, wall, or
wherever you have a serial interface line. A maximum of two monitoring
accessories (RMPs, Relay Interface Modules (RIMs), or Supervisory Contact
Modules (SCMs)) can be installed. See Table 1 for the number of accessories
permitted. Figure 37 shows an RMP.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
Figure 37. Remote Monitor Panel
Number and Type of Accessories Permitted
73
Page 82
The RMP contains a local horn and the following backlit status indicators:
SYSTEM NORMAL
The UPS is energized (either with utility
power or battery backup) and is supplying
conditioned power to the critical load.
NO REDUNDANCY
This indicator applies only to parallel
systems when one cabinet is not
functioning. This feature is not available on
this system.
ON GENERATOR
This alarm means that the UPS input and
bypass are being supplied by the power
from the generator, instead of from the
utility power.
ON BYPASS
Thebypasssourceissupplyingthecritical
load. Usually this means that the UPS is
not energized. The load is not protected in
Bypass mode, and a horn sounds after 30
seconds.
UPS ALARM
The UPS system is issuing an alarm.
Conditions that affect the current UPS
mode are indicated by the alarm lamps and
horn on the UPS.
ON BATTERY
The UPS battery backup is supplying the
critical load. The utility power is either
interrupted or out of specification. The
SYSTEM NORMAL indicator is also lit.
BYPASS UNAVAILABLE
The UPS system is in Normal mode, but
a bypass source is not within specification.
A horn sounds after 30 seconds.
SHUTDOWN IMMINENT
The UPS is preparing to shut down because the UPS is in Battery mode and the DC
voltage is approaching its low limit.
This light is accompanied by an audible alarm horn.
74
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 83
Relay Interface Module
An optional Relay Interface Module (RIM) uses relay contact closures to indicate
the operating status and alarm condition of the UPS system. A maximum of two
monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 1 for
the number of accessories permitted. Figure 38 shows the RIM with its four 15-pin
connectors labeled J1 through J4.
Figure 38. Relay Interface Mod ule
TheRIMcanprovidethesesignals:
•UPS AVAILABLE(pins 1 and 12) Contacts are closed when the UPS is
offline.
•UPS OFF LINE(pins 3 and 13) Contacts are closed when the UPS is
operating in Normal mode.
•UTILITY FAILURE(pins 6 and 15) Contacts are closed when Utility Failure is
detected.
•BATTERY WEAK(pins 5 and 14) Contacts are closed when approximately
2 minutes of battery time is remaining, before the critical
load is lost.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
75
Page 84
Supervisory Contact Module
An optional Supervisory Contact Module (SCM) establishes an interface between
the UPS manufacturer’s equipment and the customer’s monitor. This interface
allows the customer to monitor operational status of the UPS equipment. A
maximum of two monitoring accessories (RMPs, R IMs, or SCMs) can be installed.
See Table 1 for the number of accessories permitted. Figure 39 shows the SCM,
input connections on TB1, and output connections on TB2.
TB2
Figure 39. Supervisory Contact Module
The SCM provides signals for the following indications:
•SYSTEM NORMALTB 2 --- 1 t h r o ug h T B2 --- 3
•NO REDUNDANCYTB 2 --- 4 t h ro u g h T B 2 --- 6
•ON GENERATORTB 2 --- 7 t h r o ug h T B2 --- 9
•BYPAS S NOT AVAILABLET B 2 --- 1 0 t h r o u g h T B 2 --- 1 2
•ON BATTERYT B2 --- 1 3 t h ro u g h T B 2 --- 1 5
•UPS ALARMT B2 --- 1 6 t h ro u g h T B 2 --- 1 8
•ON BYPASST B2 --- 1 9 t h ro u g h T B 2 --- 2 1
•SHUTDOWN IMMINENTT B 2 --- 2 2 t h r o ug h T B2 --- 2 4
See Chapter 6, “Installing a Supervisory Contact Module” for TB2 contact
configurations.
76
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 85
When the UPS system is running in Normal mode, it continually
monitors itself and the incoming utility power. In Battery or Bypass
modes, the UPS may issue alarms to let you know exactly what event caused the
change from Normal mode. System events can be indicated by horns, lights on
the UPS, or both.
Select Active from the Events menu on the LCD screen to look at the Active
System Events screen. This screen shows any currently active alarms, notices,
or commands.
System Event Horns
The system event horn beeps according to the type of event it is signifying:
•When the UPS detects an alarm that requires your attention, the horn beeps at
½-second intervals.
•When a notice occurs, the horn beeps at 2-second intervals.
•If the battery contactor is open and the Bypass mode is unavailable, the horn
beeps every 4 seconds.
Responding to System Events
System Event Lights
The status indicators on the UPS Monitor Panel work in conjunction with the event
horn to let you know when the UPS is operating in any mode other than Normal.
Only the Normal indicator is visible during normal UPS operation. The others light
to indicate alarms or events. When an alarm occurs, you should first check these
indicators to see what type of event has taken place. For descriptions of the status
indicators, see “Reading the Status Indicators” section of Chapter 9, “Using the
Monitor Panel”.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
77
Page 86
System Event Messages
When a system event occurs, a message is added to the Event History Log. A
message may also appear on the Monitor Panel of the UPS. The Event History Log
contains all system event messages, whether or not they were displayed on the
Monitor Panel.
INVERTER ALARMS
Inverter Failure
Inverter AC Over Voltage
Inverter AC Under Voltage
Inverter Over Frequency
Inverter Under Frequency
Inverter DC Over Voltage
Bypass Phase Rotation
Inverter Phase Rotation
Service Required
UPS Tripped
Shutdown Imminent
UPS Off
Battery Contactor (K2) Failed
Bypass Contactor (K4) Failed
Inverter Contactor (K3) Failed
Bypass Control Failed
Check Unit Setup
Bypass Contactor (K4) Fail
Battery Ground Fault
100% Overload Shutdown
125% Overload Shutdown
Over Temperature Shutdown
Network Sync Failure
Inverter Calibration Required
Inverter Setup Required
78
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 87
RECTIFIER ALARMS
Rectifier Failure
Rectifier DC Over Voltage
Rectifier DC Under Voltage
Input Phase Rotation
Over Temperature
Over Temperature Warning
Temperature Sensor Failure
Rectifier Calibration Required
Rectifier Setup Required
MONITOR ALARMS
Overload Warning
Load Over 100%
Load Over 125%
Battery Test Failed
Battery Test Failed
EEPROM Write Failed
Logic Power Supply Failure
Fan Failure
UPS Failure
Other UPS is On Bypass
Other UPS Status is Unknown
Emergency Bypass Failure
Redundant Module Failure
Check KW Sensing
Check Parallel Setup
Parallel System Overload
On Battery more than 30 Seconds
Check UPM Breaker (CBS) AUX
Check Bypass Breaker (CBP) AUX
Monitor Calibration Required
Monitor Setup Required
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
79
Page 88
ENVIRONMENTAL CABINET ALARMS
Converter Offline
Converter Failure
Converter Fan Failure
Converter Fuse Blown
Converter Overtemp
Converter Link OV
Converter Link UV
Converter Battery OV
Converter Battery UV
Converter Overcurrent
Converter Calibration Required
Converter Setup Required
Converter Board Failure
INVERTER NOTICES
Input Breaker (CB1) Open
Bypass Mode
Bypass AC Over Voltage
Bypass AC Under Voltage
Bypass Over Frequency
Bypass Under Frequency
Bypass is Not Available
Battery Discharged
Battery DC Under Voltage
Battery Disconnected
Battery Not Charged
Phase A Current Limit
Phase B Current Limit
Phase C Current Limit
Battery Voltage Low
Inv. Logic Power Failure
80
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 89
RECTIFIER NOTICES
Input AC Over Voltage
Input AC Under Voltage
Input Over Frequency
Input Under Frequency
PowerSupplyOverVoltage
Power Supply Under Voltage
Input Transient
DC Voltage Low
DC Voltage High
Equalizing Battery
Testing Battery
Battery Test Failed
Input/Battery Current Limit
Reduced Input Current Limit
Rct. Logic Power Failure
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
81
Page 90
MONITOR NOTICES
Output AC Over Voltage
Output AC Under Voltage
Output Over Frequency
Output Under Frequency
ThreeWireACOverVoltage
ThreeWireACUnderVoltage
ThreeWireUnderFreq.
PowerNode Network Down
Power Off Switch
Rectifier Network Down
Inverter Network Down
Monitor Network Down
Battery Time Low
Batt Test Requires Calibration
Battery Time Low
MonitorLogicPowerFailure
Building Alarm 1 Active
Building Alarm 2 Active
Building Alarm 3 Active
Building Alarm 4 Active
Building Alarm 5 Active
Building Alarm 6 Active
Testing Battery
Battery Test Aborted (load)
Battery Test Aborted (utility)
Battery Passed Test
##Printing Sampled Data
Other UPS Bypass Not Available
Loss of Redundancy
82
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 91
CONVERTER NOTICES
Converter Shutdown
Converter In Startup
OK To Close CB2
ConverterLogicPowerOK
CONVERTER STATUSES
Converter Normal
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
83
Page 92
This Page Intentionally Left Blank.
84
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 93
Serial Communications
This chapter describes the serial communications feature of
t he P o w er w a re B P I I I H E U P S . O n e R S --- 2 3 2/ R S --- 4 8 5 serialcommunication port a nd a n o p t i o n a l R S --- 2 3 2 serial communication port allow the
connection of equipment to view system event information.
The following sections describe the serial communications feature, and provide
information about connecting hardware, setting up the ports, changing settings,
and changing modes.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
85
Page 94
Locating the Communications Panel
The Communications Panel inside the UPS contains two serial communications
ports, one DB---9 and one optional DB---25. The ports provide a computer interface
to a R emote Monitor Panel (RMP), Relay Interface Module (RIM), or remote terminal
and/or printer. The Communications Panel also contains terminals (TB1 and TB2)
for connecting your equipment to the UPS. Figure 40 shows the location of these
items inside the UPS.
TB1 and TB2
COMMUNICATIONS
Figure 40. Location of Communications Ports on the Powerware BPIII HE UPS (shown
86
PANEL
P O R T 1 ( D B --- 9 F )
RS---232/485
Connection
TB2
TB1
P O R T 2 ( D B --- 2 5 F )
R S --- 2 3 2
Connection
(Optional)
without the Environmental Cabinet)
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 95
Connecting Equipment to a Serial Port
You can connect a wide variety of terminals, printers, and computers to each port,
and configure the UPS as the Data Communication Equipment (DCE). Set up the
remote equipment using the appropriate parameters for the mode you select. The
following section provides more information about configuration.
The cables you use for connection depend on the equipment you are connecting
to the UPS. Cables should be no longer than 16m (50 ft). The connectors for
Port 1 and Port 2 on the Communications Panel in the UPS are female, so the
cables should be male. Figure 41 shows the pin assignments for Port 1, and
Table 2 describes them. Figure 42 shows the pin assignments for Port 2, and
Table 3 describes them.
PORT 1 (DB--9)
+24V
RS232 TXD
RS232 RXD
NOT USED
RETURN
Figure 41. Port 1 Pin Assignments
1
6
2
7
3
8
4
9
5
NOT USED
485 +
485 --
RETURN
Table 2. Pin Assignments for Port 1 (DB --- 9)
Pin #SymbolDescriptionComments
1+24V+24voltsDC
2TXDTransmit DataInput to UPS
3
5
7485+RS485 + Data
8
9
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
RXDReceive DataOutput from UPS
RTNReturn
485---RS485 --- Data
RTNReturn
87
Page 96
PORT 2 (DB--25)Optional
GND
RS232 TXD
RS232 RXD
RS232 RTS
RS232 CTS
RS232 DSR
RTN
+12V
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
RS232 DTR
NOT USED
--12V
NOT USED
NOT USED
NOT USED
Figure 42. Port 2 Pin Assignments
Table 3. Pin Assignments for Port 2 (DB --- 25)
Pin #SymbolDescriptionComments
1GNDChassis Ground
2TXDTransmit DataInput to UPS
3
4RTSRequest to SendInput to UPS
5
6DSRData Set ReadyOutput from UPS
7
8
20DTRData Terminal ReadyInput t o UPS --- typically not used by UPS
22--- 1 2 V--- 1 2 v o l t sOutput from UPS --- always true
RXDReceive DataOutput from UPS
CTSClear to SendOutput from UPS
RTNReturn
+12V+12 voltsOutput from UPS --- always true
NOTE: Pins 5 and 6 are tied together internally.
88
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 97
Configuring the Serial Ports
You must configure the port for communications using the LCD screen and
pushbuttons on the UPS Monitor Panel.
Select Port 1 or Port 2 (optional) from the Setup menu to display one of the Setup
Port screens. The screens for Port 1 and Port 2 are identical, and allow you to
specify settings for the two serial communication ports. Figure 43 shows the Setup
Serial Port 1 screen.
Uninterruptible Power System
UPS System Normal
Alarm: None
Notice: None
Battery
Percent
100%
03 JAN 1994 14:23:45
Setup Serial Port 1
Setup
Port 1
Port 2
Time
Mode
TERMINAL
EventsMeters
Statistics Graphics Setup
Rate
9600
Data/Stop
81
Handshaking
XON / XOFF
Save
NO
Figure 43. Setup Serial Port 1 Screen
A small return arrow ( ) appears in the upper right corner of the Setup Port screen.
This arrow is a reminder that you can press the
pushbutton on the Monitor
Panel to toggle the pushbuttons between the menu box and the information area.
If the scroll bar is in the menu box, press the
information area. The first setting (Mode) is highlighted. Press the
pushbutton to toggle to the
or
pushbutton to move the highlight to the setting you want to change. To scroll
through the available options for that setting, press the
orpushbutton.
To save the settings upon exit from this screen, be sure the Save field is set to YES.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
89
Page 98
Mode
Table 4 shows which options are available for each port. The sections that follow
describe the configuration settings you can change.
Tab l e 4 . Options Available for Each Communication Port
Port 1Port 2Options
XXTer mi na l M od e
Calibration Mode
XXSystem Configuration
XComputer Mode
XRemote Monitor Mode
XXBaud rate of 300, 1200, 2400, 4800, 9600, or 19,200
XXData size/stop bits of 8/1 or 8/2
XData size/stop bits of 7/1 or 7/2
XXDisabled handshaking
XXXON/XOFF handshaking
Rate
The operational mode of the port. Each communications port operates in one of
the following modes:
Te r m i n a l m o d eSystem events are logged immediately as they occur.
CalibrationUsed only by service personnel.
System Config.Allows you to set building alarms, battery tests, etc.
(Check with your Sales or Service Representative for availability.)
ComputerProvides a proprietary Binary Computer Mode (BCM) Interface.
Remote Monitor Sends all system event information to an RMP, RIM, or
Supervisory Contact Module (SCM). Available for Port 1 only.
Port 1 and Port 2 cannot be in the same mode simultaneously; they must always be
operating in different modes. The modes are described later in this chapter.
The baud rate of the equipment connected to this port. The baud rate determines
the speed of data transferred between the UPS and the connected equipment. For
Remote Monitor mode, the baud rate must be set to 300. All other modes should
operate at the highest baud rate available with the connected equipment. 300
baud is not recommended for any mode except Remote Monitor.
You can select a baud rate of 300, 1200, 2400, 4800, 9600, or 19,200.
90
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Page 99
Data/Stop
The data size and stop bits of the equipment connected to this port. These
settings determine the number of bits transmitted per ASCII character. The data
size and stop bits you specify depend on the configuration of your equipment.
For Port 1, the data size must be set to 8, with 1 or 2 stop bits. Settings of 7 data
bits/1 stop bit and 7 data bits/2 stop bits are available for Port 2.
NOTE: When connecting a computer running a terminal emulation program, you
should set your equipment to NO PARITY.
Handshaking
This setting controls handshaking. You can select XON/XOFF or Disabled for this
setting.
Disabled (No Handshaking)
If handshaking is disabled, the UPS will transmit and receive data via the serial
port, ignoring all inputs from handshaking lines.
XON/XOFF
If handshaking is enabled, the UPS uses special characters (XON and XOFF) to
handshake with the host terminal. The XON character is defined to be ASCII value
11 hex, and the XOFF character is defined to be ASCII value 13 hex. Upon
reception of an XOFF command, the UPS halts transmission until an XON
command is received. In the same way, if the terminal receives an XOFF
command, the UPS expects the terminal to halt transmission until the UPS sends
an XON command.
Save
Set to YES to save any changes to configuration settings upon exit from the Setup
screen. Set to NO if you do not want to save any changes.
Default Settings
The following are the default configuration settings for the serial communications
ports:
Port 1Remote Monitor300 baud8/1 Handshaking Disabled
Port 2Terminal9600 baud 8/1 Handshaking Disabled
Each communications port on the UPS operates in one of five modes which you
select when configuring the port using the Setup Port screen.
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation
164201261 Rev. F 111503
91
Page 100
Term i nal Mo d e
In this mode, system events are continually logged through the serial port to the
device connected to the port. Port 2 operates by default in Terminal mode.
The printed log entries contain a time and date stamp and the alarm text message.
Terminal mode uses this format for printing alarm entries:
MMM DDHH:MM:SS.hh KYWD MESSAGE::::<CF> <LF>
SymbolDescription
MMMonth (3 letters)
DDDay (2 digits)
HHHour (2 digits)
MMMinute (2 digits)
SSSecond (2 digits)
hhHundredths of Second (2 digits)
KYWDKeyword (ALARM, NOTICE, COMMAND, or STATUS)
::::System Diagnostic Information
<CF>Carriage Return Character (ASCII 13)
<LF>Line Feed (ASCII 10)
An alarm message is prefixed by the word “CLEAR” whenever an alarm is entered into
the Event History Log with a cleared status.
Printing Selected Information
If a port is operating in Terminal mode and is connected to a computer, you can
use key combinations at any time to print only selected information:
Ctrl+PPrints the entire log with a header
Ctrl+MPrints the current system meters with a header
Ctrl+APrints all system information
Ctrl+BPrints Battery Test Log
To use a key combination, hold down the Control key and press the letter key.
92
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.