Powerware 9305 HS Series User And Installation Manual

Page 1
User’s and Installation Manual 20 - 80 kVA parallel UPS systems
Page 2
Page 3
User’s and Installation Manual 20 - 80 kVA Parallel Systems
1018390 Revision C
Table of content:
1. Safety Instructions .................................................................................................................... 5
2. Introduction .............................................................................................................................. 7
2.1 Overview ............................................................................................................................... 7
2.2. Easy power protection .......................................................................................................... 7
3. System Description ................................................................................................................... 8
3.1 Overview ............................................................................................................................... 8
3.2 Theory of operation .............................................................................................................. 9
3.3 Sizing ................................................................................................................................... 10
3.4 Accessories........................................................................................................................... 10
4. Instructions and preventive maintenance .................................................................................. 11
4.1 General ................................................................................................................................ 11
4.2 Unpacking and incoming inspection .................................................................................... 11
4.3 Storage ................................................................................................................................. 12
4.4 Handling and lifting ............................................................................................................. 12
4.5 Moving ................................................................................................................................. 12
4.6. Initial start-up and upgrades ................................................................................................ 12
4.7 Maintenance......................................................................................................................... 13
5. Mechanical installation ............................................................................................................. 14
5.1 Overview .............................................................................................................................. 14
5.2 Placing UPS modules............................................................................................................ 15
5.3 Placing battery cabinets ....................................................................................................... 17
6. Electrical installation ............................................................................................................... 18
6.1 Overview .............................................................................................................................. 18
6.2 Location of terminals ........................................................................................................... 18
6.3 Input and output power cables ............................................................................................. 19
6.4 Parallel operation ................................................................................................................ 20
6.5 Battery cables ....................................................................................................................... 20
6.6 SPM tie cabinet options ........................................................................................................ 23
6.7 Input filter option ................................................................................................................ 33
6.8 Installation check list ........................................................................................................... 34
7. Communication interfaces ........................................................................................................ 34
7.1 Overview .............................................................................................................................. 34
7.2 Software ............................................................................................................................... 35
7.3 RS-232 serial communication .............................................................................................. 35
7.4 Potential free relay outputs .................................................................................................. 36
7.5 Signal inputs......................................................................................................................... 37
8. Start-up and operation .............................................................................................................. 38
8.1 Overview .............................................................................................................................. 38
8.2 Start-up procedure ............................................................................................................... 38
8.3 Operating system bypass switch ........................................................................................... 39
8.4 Shut-down procedure ........................................................................................................... 40
8.5 Control panel operation ....................................................................................................... 41
8.6 Control panel displays ......................................................................................................... 42
9. Troubleshooting ....................................................................................................................... 45
9.1 Overview .............................................................................................................................. 45
9.2 Alarms and reasons .............................................................................................................. 45
10. Warranty ................................................................................................................................46
11. Technical specifications .......................................................................................................... 47
Page 4
Copyright 2003
The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to make design modifications is reserved.
Page 5
1. Safety Instructions
1.1 General
Warning!
The complete safety instructions (p/n: 1009917) must be followed when installing, operating and servicing the parallel UPS system. Study the complete safety instructions carefully.
Because of the high energy stored within the batteries, the UPS equipment must be handled with care. The UPS must always be kept in the position marked on the package and must not be dropped during storage or transportation. Moreover, do not place the parallel UPS system in an airtight room.
The instructions are important for electrical safety with all personnel involved in UPS handling. Any failure to recognise the electrical hazards could prove fatal or cause injury.
1.2 Installation and service
Switch off the supply to the distribution point to which the UPS unit is to be connected. Remove the fuses from the selected line for extra safety precaution. Make absolutely sure that there is no power connected to UPS modules.
Warning!
The parallel UPS system must be installed according to the instructions given on this manual. Qualified electricians should carry out all electrical installation and maintenance work on the parallel UPS system. Local safety legislation and regulations for electrical UPS installations must be followed.
Any installation work must be done with the power off, and power is not to be reconnected unless the installation work is complete. Ensure by measuring that the part of the cabinet you are working on is not live.
Warning!
UPS modules are not provided with automatic power feedback relay. A readily accessible disconnect device must be installed in the fixed input wiring. Note that dangerous voltages remain in battery terminals when disconnect device is opened.
Ensure that the output of an UPS module is disconnected from the other parallel modules. Thus, open the output service switch before any installation work or maintenance in a parallel connected UPS module.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
5
Page 6
1.3 User operations
Warning!
Do not open the UPS cabinet! Some components inside the UPS cabinet carry high voltages. To touch them may prove fatal or cause injury. All operations inside the unit must be carried out only by service personnel from the manufacturer or from an agent authorised by the manufacturer.
Do not operate the equipment in the presence of flammable gases or fumes. Operation of the electrical equipment in such an environment constitutes a safety hazard.
The only user operations permitted are:
Starting up and shutting down the UPS unit (not the initial start up).
Using the maintenance bypass switch of the system bypass module
Operating the user interface.
Connecting data interface cables.
Monitoring the UPS modules with LanSafe III and PowerVision software.
User operations must be performed according to the instructions given on this manual. During any of these operations, the user must take greatest care and perform only the prescribed operations. Any deviation from the instructions could be dangerous to the operator.
6
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 7
2. Introduction
2.1 Overview
This manual gives you the necessary information about parallel UPS systems in redundancy or capacity configuration. The largest systems include maximum of four UPS modules in parallel configuration.
Instructions and procedures are covered in this manual: shipping; storing; handling; installation; user start-up and operation; troubleshooting; and preventive maintenance. The manual is intended for the chief operator/system supervisor, electrical consultants and installation electricians. It describes the specific functions and features of the parallel UPS system.
Figure 1. A parallel configuration constructed with four UPS modules.
Always remember that the parallel UPS system is connected to the AC mains power and contains internal high-current batteries for back up. Hence, prudence principle must be followed to prevent electrical hazards when operating the parallel UPS system.
2.2. Easy power protection
One can choose from a variety of power protection devices to shield critical data and equipment from power problems. However, by far the most sophisticated devices are Uninterruptible Power Systems (UPS).
An on-line, double conversion UPS is ideally suited for the most critical equipment. It provides clean AC power and protects the critical load against nine types of power problems:
1. Power outages
2. Power sags
3. Power surges
4. Undervoltages
5. Overvoltages
6. Switching transients
7. Line noise
8. Frequency variations
9. Harmonic distortion
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
7
Page 8
3. System Description
3.1 Overview
Parallel UPS configurations are recognised as either redundancy or capacity systems. The redundancy system is used to improve the system reliability with N+1 redundant UPS module. The capacity system for its part provides the maximum output power without focusing to the highest system reliability.
A parameter selection is used to switch between the redundancy and capacity modes. It is important to remember that the mode is affecting to the output power rating and overall system reliability.
UPS modules of the parallel system share equally the load with Hot Sync™ technology. The parallel outputs are combined in a System Parallel Module or cabinet. It is the system component containing the obligatory service switches. Customer’s low-voltage distribution panel can also be used instead of the System Parallel Module. In the redundancy system, service switches enable the maintenance or service on an UPS module. In the capacity system, one needs to have a common system bypass switch to do the maintenance or service without safety hazards.
Figure 2. Parallel configurations with UPS modules.
Field upgrading can be used to extend existing capacity/redundancy systems with UPS modules. The upgrading must be carried out by service personnel from the manufacturer or from an agent authorised by the manufacturer.
8
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 9
3.2 Theory of operation
A double conversion on-line UPS conditions the raw mains and supplies continuous, clean three-phase power to the critical systems. It keeps the battery constantly charged while feeding the critical load. The UPS will continue to supply clean power without any interruption at the output even at mains failure. It will shut down in order to prevent a total discharge of the battery if the power failure outlasts the backup time of battery bank. The UPS will start up again automatically, providing power to the critical load and charging the battery bank, when the mains voltage is restored.
Figure 3a. Block diagram of UPS module
A double conversion UPS provides the best protection for computer systems and other intelligent devices such as measurement instruments and industrial automation applications. UPS modules incorporate digital signal processing technology to monitor and control its own operation. They protect different types of sensitive electrical devices such as computers, workstations, banking systems, sales terminals, critical instrumentation, telecommunications systems, process control systems, hospital equipment, etc.
Figure 3b. Functional components of UPS module
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
9
Page 10
The mains is rectified and boosted to DC power in the rectifier part. The rectifier provides power to the battery charger and the inverter load. The battery charger keeps the battery in recharged condition with ABM™ technology. The DC Link connects the rectifier output with the inverter input. It is the means for transferring power between these system components.
The output of the inverter is constantly maintained in phase synchronism with the bypass supply voltage provided that it is within the voltage and frequency tolerances specified for the load transfer condition. The inverter is changing the output operation to internal set frequency if the bypass supply exceeds these tolerances.
In the event of a mains power interruption, the battery is supplying the inverter load. The rectifier starts again to supply the inverter load when the AC mains power returns. The battery charger is recharging the battery after the mains return, too.
The static switch is initiating uninterrupted transfer of the load to the bypass line when the inverter is overloaded or the inverter is not able to feed the load. The output is protected with a tripping circuit breaker to separate the faulty UPS module from the parallel load bus.
The parallel load sharing is implemented individually in UPS modules with Hot Sync™ technology. The critical load is supported even in the unlikely situation of the redundant bus communication failure.
3.3 Sizing
The output power rating of the parallel UPS configuration should be specified according to the total power demand of the protected load. Some margin should be allowed for potential expansion, and for possible inaccuracy in calculating or measuring the actual power requirement.
The battery should be sized according to the desired backup time. Note that the backup time is longer if the load is less than the nominal power rating of the parallel UPS system.
3.4 Accessories
The following external options are available:
System Parallel Module (SPM):
– SPM9305 cabinet : 2-4 x 80 kVA – SPM9305 cabinet : 2-4 x 20-60 kVA – SPM9305/9340 cabinet : 2 x 80-130 kVA – SPM9305 module : 2 x 40-60 kVA – SPM9305 module : 2 x 20-30 kVA
Battery cabinets:
– BAT D, BAT E, and BAT F
Input filter:
– THDi 10%
ViewUPS:
– Remote status/control panel
LanQuattro:
– 4 x RS-232 data manager
ConnectUPS:
– SNMP adapter
Others:
– Engineered solutions upon request
10
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 11
4. Instructions and preventive maintenance
4.1 General
Proper provision must be made for transportation and handling because of heavy weight and high energy stored within batteries. See technical specifications for dimensions and weights of the UPS modules.
4.2 Unpacking and incoming inspection
Unpack the equipment and remove the shipping and packing materials. The shipping and packing materials should be stored for further investigation if damage has occurred during the transportation.
The equipment must be inspected for shipping damage. A claim must be filed immediately if visible damages can be noticed. Proceed as follows to file the claim for a shipment damage:
Inform the carrier about the damage within 7 days of receipt of the equipment.
Check and verify that the shipment is complete against the packing list.
The installation may proceed if there are no damages or discrepancies. UPS system is also thoroughly inspected and tested at the factory.
Figure 4. Removing the UPS module from the shipping pallet.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
11
Page 12
4.3 Storage
UPS modules must be stored in the original packing and shipping pallet. They should be handled with care. Make sure that you do not stack the pallets when the equipment is placed to local warehouse for storage.
If the UPS is not immediately installed the following must be remembered:
Electrical equipment must always be protected from moisture and weather.
The recommended storage temperature is between +15°C and +25°C
UPS batteries should be charged regularly for at least 8 hours every 6 months to
maintain the battery condition.
4.4 Handling and lifting
UPS modules are shipped on specifically designed packing and pallets. It is easy to move and lift them with a forklift. Hence, equipment should be lifted in the original and packed condition.
Crane lifting can be used if a suitable lifting net is used. There exist no lifting eyeholes for crane lifting. Note that equipment must be kept in an upright position and must not be dropped.
4.5 Moving
UPS can be simply pushed into place after unpacking. They are equipped with castors for easy movement but be careful not to tilt it. Please verify that the surface material, on which the UPS modules are moved, is strong enough for the heavy weight.
4.6. Initial start-up and upgrades
The authorised field service person shall perform the following procedure and tests during the start- up the new parallel UPS system:
1. Visual inspection
Make a visual inspection of the equipment for signs of damage or foreign material.
Observe the type of ventilation system, the cleanliness of the room, the use of safety signs, and other environmental factors affecting the functionality or personnel safety.
2. Mechanical and electrical inspection
Check the power connections, control wiring terminations, and plugs for tightness or
proper seating. Verify that the alarms log is clear and in the ’green’ condition.
Check the parallel UPS system for possible ground leakage, proper input and bypass
voltages, and correct phase rotation. Check the proper battery float voltage.
3. Operating inspection
Energise the parallel UPS system and verify the proper DC and AC output voltages.
Check the final DC link voltage and output wave form of the inverter output.
4. Operational training
Before leaving the site, the field service engineer shall familiarise responsible personnel
with the operation of the UPS system. The UPS equipment shall be available for demonstration of the modes of operation.
Normally, the complete parallel UPS system is calibrated at the factory and no output calibration is needed in the field. However, UPS module upgrades to the existing parallel UPS system require always the service visit due to the field adjustment of calibration settings. Special calibration software and tools are required to make the parallel system function properly with the new, purchased UPS module.
12
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 13
4.7 Maintenance
Warning!
Maintenance work must be performed only by a service person with the service training completed.
One should sign a service and maintenance contract with an authorised local service centre. The maintenance work for parallel UPS system can be done with the system bypass switch.
The good condition of the batteries is crucial to correct operation of the parallel UPS system. Therefore, a battery discharge test is recommended once or twice per year in the preventive maintenance procedure.
The UPS units are provided with the automatic battery test ABM™, which continuously controls the condition of the battery bank. “Battery failure” alarm is activated when the capacity of the battery bank has decreased remarkable from the default value.
Scrapping
Before scrapping UPS or its battery cabinet, battery bank and the lithium battery on the logic board must be removed. Due to high energy and high voltage, removal of batteries is allowed only for authorised service personnel. Local requirements must be followed in battery recycling or discard.
WARNING!
HAZARDOUS MATERIALS. Batteries may contain HIGH VOLTAGES, and CAUSTIC, TOXIC and FLAMMABLE substances. Batteries can injure or kill people and damage equipment if used improperly. DO NOT DISCARD unwanted batteries or battery material in the public waste disposal system. Follow ALL applicable, local regulations for storage, handling and disposal of batteries and battery materials.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
13
Page 14
5. Mechanical installation
5.1 Overview
Environmental requirements and restrictions described in the technical specification shall be met to guarantee the proper function and safety of the equipment.
Figure 5. Dimensions of the parallel UPS system components.
14
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 15
The installation surface must be smooth and steady to carry the point and distributed loading of the whole parallel UPS system.
noitpircseD
seirettabo/wSPUAVk03-020121,3025
seirettab).scp23x2(htiwSPUAVk03-020049,55621
seirettab).scp84x2(htiwSPUAVk03-020942,70551
seirettabo/wSPUAVk06-040620,4536
seirettabo/wSPUAVk080823,4086
4-06-5039MPS0121,3025
4-08-5039MPS0821,4596
2-031-0439/5039MPS0821,4596
2-06-5039MPS057,0521
2-03-5039MPS057,0521
tenibacDTABlanretxE0551,80381
tenibacEDIWDTABlanretxE0855,80391
tenibacETABlanretxE518210991
tenibacFTABlanretxE09314,015071
Table 1. The floor loading of the parallel UPS system components.
thgieW
)gk(
2
mc/gk(
5.2 Placing UPS modules
gnidaoltnioP
2
)
m/gk(
gnidaoldetubirtsiD
)
Maintain 1000-mm clearance at front of the UPS modules for service, user operations, and fire escape safety. Make also sure that free space requirements around UPS modules are met for the cooling air.
Figure 6a. Ventilation and space requirements for 20 - 30 kVA UPS.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
15
Page 16
Figure 6b. Ventilation and space requirements for 40 - 80 kVA UPS.
Power cables shall be routed from the bottom or rear side of the UPS modules. The cables shall be protected with a casing tube. The size and location of the cable entries is shown in the drawing.
Figure 7. Cable entries of UPS modules.
16
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 17
5.3 Placing battery cabinets
The detailed installation instructions for the external battery cabinets are included in the shipment. External battery cabinets shall be installed next to the UPS modules and the location of the cable routing is under the external battery cabinets:
20-30, 80 kVA UPS modules shall have the external battery cabinets on the left side.
40-60 kVA UPS modules shall have the external battery cabinets on the left or right side.
External battery cabinets shall be connected together by using narrow metal plates provided with external battery cabinets. The external battery cabinet shall be connected together without the side plate(s). Hence, remove both side plates if you are connecting an external battery cabinet in the middle of line-up. Do not remove the side plates from the UPS modules.
Figure 8. An UPS module connected to external battery cabinets with narrow metal plates.
Leave a 10-mm free space between the UPS module and the external battery cabinet by using the narrow metal plates provided with external battery cabinets.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
17
Page 18
6. Electrical installation
6.1 Overview
Qualified personnel should do the electrical installation planning of the parallel UPS system in compliance with the warnings laid down in this manual. The inspection and initial start up of the UPS modules and external battery cabinets must be carried out by service engineer from the manufacturer or from an agent authorised by the manufacturer.
Warning!
The UPS system contains high voltage and current that can injure or kill personnel and damage equipment.
Input and output power cables must be selected according to local regulations and installation environment. The recommendations of this manual can be used as a guideline for the installation and selection of power cables.
6.2 Location of terminals
Input and output terminals are located behind the door. A cover plate and a narrow front panel are protecting some of the terminals.
Figure 9. Location of terminals in UPS modules.
Cable routing is through the cable entry at the bottom or back of the UPS cabinet. Take care to maintain a safety distance between control and power cables to avoid disturbances caused by high frequency currents.
18
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 19
6.3 Input and output power cables
Input terminals X1 and X2 have a five-wire connection (L1, L2, L3, N, and PE) for the rectifier and bypass line. The output terminal X3 is located directly in the circuit breaker. Cables with copper conductors should be used to fit the terminals.
Figure 10. Bottom cabinet layout of power terminals.
Slow fuses (gG type) should be used to protect the input cables in case of a short circuit. The fuses should be dimensioned according to local safety regulations, appropriate mains voltage and the rated current of the UPS module. An internal circuit breaker is used to protect the input bridge and power semiconductors.
gnitarSPUrofelbactupnI
esuftupnIelbactuptuO
ssapyb/reifitcer
AVk02²mm61A0561 mm
AVk03²mm61A0561 mm
AVk04²mm61A3661 mm
AVk05²mm52A0852 mm
AVk06²mm53A00153 mm
AVk08²mm05A52105 mm
2
2
2
2
2
2
Table 2. Recommended input/output cables and fuses of parallel UPS modules.
Note!
Input and output cables must be of equal length (and type) to quarantine a balanced load distribution in parallel UPS configuration. A great variance in input/output cable lengths (or types) will cause the UPS modules to drop the critical load due to imbalance currents.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
19
Page 20
6.4 Parallel operation
UPS modules have a cable connection between them to inform about the phase synchronism of the bypass voltages. It is needed in order to transfer the critical load back from the bypass line to inverters at the same time. The transfer from inverters to bypass functions without the data bus connection in case of overload situation.
A cable entry is located on rear panel beside the power cable entry. Route the cables behind the narrow front panel to the circuit board A5: X3/X4. The cable is leaving from the terminal X4 on the circuit board A5 and connected to the terminal X3 in the next UPS module. See the figure for correct wiring of the communication bus.
Figure 11. Ring topology of the cable connection between UPS modules.
The shield of the parallel information cable has to be grounded to the UPS ground from the one end of the cable only. Connect the cable shield to the grounding screw of the RFI board (20-30 kVA) or the PCB A12 assembly plate (40-80 kVA).
6.5 Battery cables
Located behind the door, the external battery connection (+, -, N and PE) is used with BAT D, BAT E and BAT F cabinets.
Each shipment of external battery cabinets includes 16 mm installation. The electrical installation of external cabinets should be done according to appropriate wiring diagrams.
External battery cabinets also have a temperature measurement sensor that is located under the roof. The temperature information must be linked together when installing several external cabinets. The control cable of temperature measurement sensor should be connected to the male terminal X6 in the UPS module
Battery configurations with 20-30 kVA UPS modules
An optional battery breaker F4 (p/n: 1014196) is needed with each 20-30 kVA UPS modules if external battery cabinets are used. The breaker includes a four-part X9 plug terminal that is connected to the X8 plug terminal of the UPS module. Be careful with the X8-X9 terminal because it’s connected to the internal battery bank and contains high DC voltage.
2
power cables for the electrical
Power cables should be connected directly to the terminals of battery breaker F4. See the battery wiring diagrams and chapter ‘Location of terminals’ for the correct power cable connections.
20
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 21
Figure 12. Wiring diagram of the external battery cabinets D and E.
Figure 13. Wiring diagram of the external battery cabinet F.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
21
Page 22
Battery configurations with 40-80 kVA UPS modules
Power cables should be connected to the battery terminals of the UPS modules. See the battery wiring diagrams and chapter ‘Location of terminals’ for the correct power cable connections.
Figure 14. Wiring diagram of the external battery cabinets D and E.
22
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 23
Figure 15. Wiring diagram of the external battery cabinets F.
6.6 SPM tie cabinet options
The system parallel module (SPM) has input connections up to four or two parallel UPS modules and make-before-brake type of system bypass switch. The UPS manufacturer provides five (5) different types of System Parallel Modules:
.orntraPepyTnoitpircseD
25891012-031-0439/5039MPS seludomAVk031-08SPUx2-1roftenibacMPSgnidnats-roolF
05891014-08-5039MPS seludomAVk08-06SPUx4-1roftenibacMPSgnidnats-roolF
87971014-06-5039MPS seludomAVk06-02SPUx4-1roftenibacMPSgnidnats-roolF
57451012-06-5039MPS seludomAVk06-04SPUx2-1roftenibacMPSdetnuom-llaW
49251012-03-5039MPS seludomAVk03-02SPUx2-1roftenibacMPSdetnuom-llaW
Table 3. System Parallel Modules (SPM)
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
23
Page 24
Figure 16. A parallel 4 x UPS configuration with the SPM tie cabinet
Local regulations and installation environment shall be considered when selecting power cables and fuses/breakers. The recommendations of this manual can be used as a guideline for the electrical wiring and installation.
Slow gG fuses or C-type breakers should be used for short-circuit protection of the power cables. The electrical installation shall be dimensioned according to local safety regulations, appropriate mains voltage and the rated current of the load.
Notice!
Pay attention to the correct phase order when connecting the UPS output and system bypass cables to the SPM tie cabinet. Phases L1, L2 and L3 must be in the same order when transferring the load to the system bypass. The correct phase rotation is not enough to prevent UPS hardware damages. Make also sure that the neutral cable is properly connected in all terminals.
SPM9305/9340-130-2, SPM9305-80-4 and SPM9305-60-4 tie cabinets
The SPM tie cabinet provides the UPS connection terminals for the shared load bus. It also enables the make-before-break transfer of the load to the system bypass. This can be used for service or test purposes.
The available SPM tie cabinets have the following maximum power ratings:
epyTgnitarSPUgnitarssapyBegatlovmetsyS
2-031-0439/5039MPSAVk031x.scp2-1AVk062zH06ro05,V032/004
4-08-5039MPSAVk08x.scp4-1AVk023zH06ro05,V032/004
4-06-5039MPSAVk06x.scp4-1AVk042zH06ro05,V032/004
X2 and X4 input terminals have a five-wire connection (L1, L2, L3, N, and PE). Power cables with copper conductors should be used to fit the terminals. The wiring shall be done according to the wiring diagram. The terminals and cable routing is shown it the figure below.
Auxiliary contact information of the system bypass switch enables a safe transfer of the load. Pay attention that the signal cable of the bypass switch aux. contact is wired correctly to the UPS modules: the polarity of the signal must be the same for all parallel connected UPS modules because the signal sensing is done against the ground.
Notice!
UPS modules should get a minimum of 10 ms leading closed-contact signal when the system bypass switch is turned from UPS to BYPASS position.
24
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 25
Figure 17. Cable routing of SPM9305/9340-130-2 and SPM9305-80-4 tie cabinets.
Figure 18. Cable routing of SPM9305-60-4 tie cabinets.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
25
Page 26
Figure 19. Wiring diagram with SPM9305/9340-130-2 tie cabinet.
26
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 27
Figure 20. Wiring diagram with SPM9305-60-4 and SPM9305-80-4 tie cabinets.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
27
Page 28
eludomSPU elbaCA elbaCC esuF1
AVk02²mm61²mm61A05
AVk03²mm6mm61A05
AVk04²mm6mm61A36
AVk05²mm5mm61A08
AVk06²mm5mm61A001
AVk08²mm0mm52A521
eludom5039MPS
AVk02²mm61²mm61A05
AVk03
AVk04²mm6mm61A36
AVk05²mm5mm61A08
AVk06²mm5mm61A001
AVk08²mm0mm52A521
AVk09²mm0mm53A061
AVk00mm59²mm05A002
AVk02mm59²mm05A002
AVk05mm021²mm07A052
AVk06mm051²mm59A052
AVk08mm581²mm59A513
AVk00mm581²mm59A513
AVk04204mmm051A004
AVk02mm051xmm051A005roA052x2
elbaCB lbaCeD esuF2
²mm61²mm61A05
Table 4. Recommended cables and fuses for the wiring diagrams.
SPM9305-60-2 and SPM9305-30-2 tie cabinets
The SPM tie cabinet provides the UPS connection terminals for the shared load bus. It also enables the make-before-break transfer of the load to the system bypass. This can be used for service or test purposes.
The available SPM tie cabinets have the following maximum power ratings:
epyTgnitarSPUgnitarssapyBegatlovmetsyS
2-06-5039MPSAVk06x.scp2-1AVk021zH06ro05,V032/004
2-03-5039MPSAVk03x.scp2-1AVk06zH06ro05,V032/004
X2 and X4 input terminals have a five-wire connection (L1, L2, L3, N, and PE). Power cables with copper conductors should be used to fit the terminals. The wiring shall be done according to the wiring diagram. The terminals and cable routing is shown it the figure below.
Auxiliary contact information of the system bypass switch enables a safe transfer of the load. Pay attention that the signal cable of the bypass switch aux. contact is wired correctly to the UPS modules: the polarity of the signal must be the same for all parallel connected UPS modules because the signal sensing is done against the ground.
Notice!
UPS modules should get a minimum of 10 ms leading closed-contact signal when the system bypass switch is turned from UPS to BYPASS position.
28
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 29
Figure 21 . Cable routing and mounting holes for SPM9305-60-2 and SPM9305-30-2 tie cabinets.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
29
Page 30
Figure 22. Location of SPM9305-60-2 and SPM9305-30-2 control switches.
30
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 31
Figure 23. Wiring diagram with SPM9305-30-2 tie cabinet.
rewoP1esuF2esuFB/AelbaCD/CelbaC
AVk02A05A3mm61²mm61
AVk03A05A001²mm61²mm53
Table 5. Recommended cables and fuses for the wiring diagram.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
31
Page 32
Figure 24. Wiring diagram with SPM9305-60-2 tie cabinet.
rewoP1esuF2esuF3esuFB/AelbaCCelbaCDelbaC
AVk04A36A001A521²mm61²mm05mm61
AVk05A08A001A002²mm52²mm07mm61
AVk06A001A001A002mm53
2
Table 6. Recommended cables and fuses for the wiring diagram.
2
2
2
mm59
2
mm61
32
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 33
Local tie panel solutions
The internal wiring diagrams of SPM9305 tie cabinets can be used as a reference when designing local tie panels.
Parallel UPS configurations require a tie panel at the system output. It must facilitate service switches for each UPS module output. The system bypass switch is optional but helps when doing the maintenance for the whole parallel UPS system.
It’s recommend to source cabinet, cables, busbars, terminals, fuses, switches and breaker components from the local market. If needed, standard SPM9340 components can be ordered as spare parts from the UPS manufacturer.
Notice!
The operational function of the S51 system bypass switch or equivalent breaker system must be following:
1. The system bypass switch S51 is turned from ”UPS” to ”UPS+BYPASS” position.
2. Auxiliary contacts provide 10 ms leading signal with a closed contact
3. One should check from the LCD panels that UPS modules are not unsyncronised and the signal wiring polarity is correct.
4. All parallel UPS modules receive the auxiliary contact signal simultaneously and firmware transfers the UPS modules to internal bypass.
5. Now, the S51 system bypass switch is in ”UPS+BYPASS” position. The UPS and BYPASS power lines are in parallel and supply the load. The parallel UPS modules still receive the auxiliary contact signal, thus, forcing the UPS modules to internal bypass lines.
6. Turn S51 bypass switch to ”BYPASS” position. As a result, the system bypass line is alone supplying the load.
7. Load switches S11/S21/S31/S41 can be opened to do the maintenance in the parallel UPS system.
6.7 Input filter option
The terminal X7 provides a temperature sensor connection for the 10% THDi input filter. This terminal is located beside the input/output power terminals.
For more information see the installation instructions manual for the input filter option.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
33
Page 34
6.8 Installation check list
1. Check that electrical connections to the installation site have been properly executed.
2. Check that input cables from a low-voltage switchgear are connected to the UPS modules and the system parallel panel. Make sure that the neutral of UPS input is properly connected.
A readily accessible disconnect device with a contact separation of at least 3 mm is mandatory in the fixed input wiring of UPS modules. Use fuses or miniature circuit breakers to protect cables from a short circuit.
3. Check that the output cables of UPS modules are connected to the system tie panel. Pay a special attention to the correct phase order because the system bypass and UPS modules must have the same order of L1, L2 and L3 phases.
4. Check that the contact information of the system bypass switch is properly connected to all UPS modules. Make sure the polarity of the information is correct. Cables are delivered with the UPS modules.
5. Check that the parallel information cable between UPS modules has been properly connected in a ring configuration. Cables are delivered with the UPS modules.
6. Since the UPS does not have automatic backfeed isolation a warning label must be added on all primary power isolators installed remote from the UPS area to warn electrical maintenance personnel that the circuit feeds a UPS. The warning label shall carry the following wording or equivalent: ”ISOLATE UNINTERRUPTIBLE POWER SYSTEM (UPS) BEFORE WORKING ON THIS CIRCUIT.”
The UPS system should be now connected to the mains and to the load but there is no power.
7. Communication interfaces
7.1 Overview
A single UPS module sends information about mains, load, and internal operation and status. The information can be used in a computer to ensure a total protection of the critical software and data. It is available in two RS232 serial communication ports, four potential free relay outputs and four signal inputs. These communication interfaces are located behind the door.
UPS modules are provided with a 230 VAC power supply (terminal X5) for use with internal modem or portable computer. This power supply is protected with an automatic 10 A fuse F3.
UPS modules are delivered with the relay adapter circuit board that converts the 16-pin relay interface X102 to a 15-pin male D-sub terminal. It is used together with options such as ‘Remote Status Panel’ and ‘Alarm Extension Unit’.
34
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 35
Figure 25. Location of terminals in 20/30 kVA (left) and 40/50/60 kVA (right) UPS modules. Cable holders should be used for routing to the terminals.
Note! All communication connections must not have a galvanic connection to any mains connected circuits. Reinforced insulation to the mains is required for equipment and cables connected to these connections.
7.2 Software
UPS modules are designed to comply with LanSafe III and PowerVision software. Optional software solution packages are delivered with communication devices for complete power management. The pin configuration of the serial port should be verified if an unknown software is connected to the UPS modules.
Software can control or monitor UPS modules individually, not as a parallel system. Check from the software documentation that the platform running on your computer is supported. Use no other than the communication cable provided with the package to connect the UPS modules to a computer.
Please contact your local dealer if you are interested in special operating systems, SNMP and more advanced power protection solution combinations.
7.3 RS-232 serial communication
The RS232 interface on terminal X100 uses a 9-pin female D-sub connector. It is used for connecting a computer to the UPS module. The data includes information about the utility, load and the status of the UPS module.
1niPataddevieceR 2niPataddettimsnarT 4niPdnuorglangiS 8niPdetalugernuV21+ 9niPdnuorgSPU
Table 7. RS-232 connection (X100) for the computer, 9-pin female D-sub.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
35
Page 36
The RS-232 interface on terminal X101 uses a 9-pin male D-sub connector. It is used for connecting a modem (or a computer) to the UPS module. The data includes information about the utility, load and the status of the UPS module.
1niPdetcetedreirracataD 2niPataddevieceR 3niPataddettimsnarT 4niPydaerlanimretataD 5niPdnuorglangiS 7niPdnesotydaeR
Table 8. RS-232 connection (X101) for the modem, 9-pin male D-sub.
7.4 Potential free relay outputs
UPS modules have four potential free relays on terminal X102 with a maximum rating of 1A / 30VAC or 0.2A / 60VDC. They have a complete galvanic isolation from the other UPS circuits according to IEC60950 and EN50091-1. It is recommended that the relay output signals run as twisted pairs.
The relay interface includes the Pin 16, which is the UPS module shutdown input. It is active only when the UPS is in battery operation. A high level signal for 5 seconds is needed to turn off the UPS until proper voltage returns.
detcennocsrebmunniP etatsmetsyS
eruliafeniL
dessapybSPU
yrettabwoL
roko/noSPU
mralASPU
3-2 3-1
6-4 6-5
9-8 9-7
21-01 21-11
koeniL
eruliafeniL
ylppusretrevnI
ylppusssapyB
lamronyrettaB
wolyrettaB
ko/noSPU
mralaSPU
Figure 26. Potential free relay output connection (X102) for UPS module information.
36
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 37
7.5 Signal inputs
The programmable auxiliary inputs are used to control the operation of UPS modules. A double shielded cable is the best alternative but single shielded twisted multipair cable is also usable. Remember that signals should not have a galvanic connection to any mains connected circuits.
Emergency Power Off (EPO)
The emergency shut down wiring is connected to the terminal X4 with maximum resistance of 10 ohm. It can also be used for a remote shut down in the event of a room overtemperature by thermal relay. EPO terminals must not be connected in series with the parallel system configuration. Internal EPO circuits require a galvanic isolation of the signals.
The terminal X4 is a ‘normally closed’ type of connection. Hence, the logic circuitry will immediately shut down the UPS module when the connection is open. The terminal X4 has to be shorted to keep the UPS module running. A manual start is needed to make the UPS module run again after the emergence power off mode.
Generator On
Auxiliary contact wires of a generator control device are connected to the terminal X219. It is used for inhibiting the transfer to static bypass line when the UPS module is supplied from an unstable AC source. The information has to be connected to all parallel UPS modules.
The terminal X219 is a ‘normally open’ type of connection. Hence the logic circuitry will prevent the transfer to unstable power source when the connection is closed. UPS modules are delivered the connection open on the terminal X219.
Remote Output On/Off
The remote output on/off wiring is connected to the terminal X220. It can be used to turn off the UPS module output from a distance.
The terminal X220 is a ‘normally open’ type of connection. Hence the logic circuitry will turn off the inverter when the connection is closed. In order to turn on the inverter the connection between these pins has to be open.
System Bypass Switch
The auxiliary contact wiring of the system bypass switch is connected to the terminal X221. The information has to be connected to all parallel UPS modules. Make sure that the polarity of the auxiliary contact wiring is the same for all UPS modules.
In parallel UPS systems this signal must be connected to the auxiliary contact information of the system bypass switch in the tie panel.
The terminal X221 is a ‘normally open’ type of connection. Hence the logic circuitry will transfer the UPS modules to internal bypass line when the connection is closed.
Environment Alarm
The building alarm wiring is connected to the terminal X222. For example, it can be used for overtemperature or smoke detector alarms.
The terminal X222 is a ‘normally open’ type of connection. Hence the logic circuitry will indicate to the user through the RS-232 when the connection is closed.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
37
Page 38
8. Start-up and operation
8.1 Overview
This chapter contains the necessary information on how to use the UPS system. The starting up and shutting down procedures described here are only used on a few occasions for example when preparing for a long term mains failure or changing the batteries. In normal operation the UPS system runs automatically.
Figure 27. Location of switches and breakers
Initial start up is always performed by a service engineer of the manufacturer or by a representative of an agent authorised by the manufacturer. Otherwise the safety of personnel during installation or use, or that the unit will function properly, can not be guaranteed.
During commissioning the manufacturer representative will train the users to operate the parallel UPS system.
8.2 Start-up procedure
Check that the parallel UPS system has been installed and control wiring is done correctly before starting up any UPS modules. Make sure that ground connections have been done in the tie panel for UPS module outputs.
Depending on the situation, the parallel UPS system will start with normal start-up procedure (mains power is available), or with cold start-up procedure (battery power is available). The UPS modules will start-up to the load bus with 10-60 seconds delay of synchronisation.
The parallel UPS system should started in the orderly (UPS1-2-3-4) manner:
1. Check that the UPS modules are in the start-up condition (open front door): – Main switch, main circuit breaker, and battery breakers are in the OFF position
38
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 39
2. Check that the optional system bypass switch is in the ‘BYPASS’ position, and the individual service switches are in the ON position. If the system configuration does not include the external system bypass switch, the critical load must be disconnected, (when cold battery start) or UPS modules must be started immediately after each one (during 30 seconds) to prevent overload situation at the system start-up.
3. Start UPS modules one by one:
- Check that the output breaker S2 has not been tripped by resetting it to the ON position.
- Turn on the main breaker F1 and battery circuit breaker F2 to the ‘ON’ position.
- Turn on the circuit breaker F4 (20/30 kVA UPS modules with ext. BAT cabinets) to the ‘ON’ position.
4. Start the UPS module by turning the main switch S1 to the ‘ON’ position.
5. Check that the UPS module has started:
- Green UPS ON led is lit if mains power is available (normal start)
- Yellow BATTERY led is lit if the battery power is available (cold-start).
6. Check that yellow BYPASS led (contact signal of the system bypass switch is ok) is lit in the front panel.
7. Repeated sections 3 through 6 until all UPS modules have started.
8. Check that service switches of the SPM9305 (or local tie panel) are in the ‘ON’ position.
9. Transfer the critical load to UPS modules by turning the system bypass switch to ‘UPS’ position.
8.3 Operating system bypass switch
The system bypass switch is used to bypass the parallel system during maintenance or servicing. Maintenance bypass switch is located on the front panel of the optional SPM9305 cabinet. Using the switch does not cause any break in the output voltage, if the input voltage and frequency are accepted and the system is synchronised to the input mains.
The parallel module includes a mechanical bypass switch S51 (Make-Before-Break type) and four maintenance switches S11, S21, S31, and S41 for disconnecting the outputs of UPS modules during maintenance or service.
The maintenance bypass switch has the following positions:
‘I’ or ‘UPS’ normal position, the load is supplied from the UPS modules.
‘I+II’ or ‘UPS + BYPASS’ position, the load is supplied from UPS modules (internal bypass
mode) and the system bypass in parallel.
‘II’ or ‘BYPASS’ position, the UPS modules are bypassed and the critical load is supplied
from the system bypass power line.
If the system bypass switch needs to be used it is recommended to check that the bypass input power is connected and present in the SPM9305 cabinet. The switch is used only on rare occasions and the procedure is following:
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
39
Page 40
1. Check that the unsynchronised alarm is not active in the UPS modules. (Press Menu button, choose UPS status display)
2. Turn the maintenance bypass switch to BYPASS position.
Warning!
The use of the maintenance bypass switch will cause a break in the output voltage if the input voltage or frequency is not correct and the UPS system is not synchronised to mains.
Following procedure does returning to normal online mode:
1. Make sure UPS modules have been started according to chapter ‘Start-up procedure’.
2. Check that UPS ON and BYPASS LED’s are lit in the front panel.
3. Make sure service switches S11…S41 in the SPM9305 are in ‘ON’ position
4. Turn the system bypass switch S51 to ‘UPS’ position.
Figure 28. System bypass switch of the optional SPM9305.
8.4 Shut-down procedure
The UPS system does not have to be shut down at the end of each day. The system is designed to cope with a continuous load from the day it is installed until a change is needed in the backup battery bank.
40
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 41
It is possible to shut down a single UPS module and still get maximum protection for the critical load. This operation requires that the parallel system to be in the N+1 redundancy mode. In capacity mode, the system bypass switch should be used to transfer the system to bypass power.
Use the following procedure when you want to do service for a redundant UPS module:
1. Check that the UPS module is in the operational condition (open front door): – Main switch, main circuit breaker, and battery breakers are in the ‘ON’ position – Output breaker in the ‘ON’ position and has not been tripped. – No critical alarms or “Loss of redundancy” message in the control panel display.
2. Check that the parallel UPS system is in the N+1 redundancy mode. (Press Menu button, choose UPS parameters display P31.)
The system bypass switch must be used first to transfer to ‘BYPASS’ if the system is in the N capacity mode. The critical load must be disconnected if system does not contain the system bypass switch.
3. Turn the main switch S1 to the ‘OFF’ position
4. Turn off the battery circuit breakers F2 and F4 (20/30 kVA UPS modules with ext. BAT cabinets).
5. Turn off the main circuit breaker F1 to the ‘OFF’ position.
6. Check that UPS ON or BATTERY LED’s are not lit. – It has now stopped the supply of output power and is disconnected from the batteries.
7. Disconnect the appropriate service switch (S1…S4) to ‘OFF’ position at the optional SPM9305 or local tie panel. This prevents high voltage to be present in the output terminals of the UPS module because of the parallel configuration.
Warning!
Be careful because there are still be high voltages and live parts inside of the UPS module.
8.5 Control panel operation
Operation of the panel are controlled with the push buttons under the LCD display. The screen informs the user about the UPS type, measurements, and status alarms. The control panel shows the status of UPS operation with four LED indicators. It also generates an audible alarm if the user should be alerted.
The ‘MENU’ button allows the user to move through the options in the parameter menu.
↑↑
Push buttons the push button
1018390 Revision C
↓↓
are used to moving in the submenus. Display functions are selected with
↑↑
↓↓
↵↵
↵.
↵↵
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
41
Page 42
This green LED is lit when there is voltage at the output terminals and when the UPS is in normal or static bypass mode.
This yellow LED is lit when the UPS is operating in battery mode. When this LED is blinking the battery voltage is low and only few minutes of backup time is left.
This yellow LED is lit when the UPS is on and is operatingn in bypass mode.
This red LED is lit when a situation in the UPS requires immediate action.
Figure 29. Control panel and LED status indications.
8.6 Control panel displays
Normal display
The Normal display shows the UPS type. The panel automatically returns to this display state from any other display state after a delay time of 1 to 2 minutes from last display state change.
Menu display
The following display choices can be selected in the Menu display by scrolling through menu
↑↑
with
and
↑↑
UPS Status
Meters
Battery Status
Alarm log
UPS parameters
UPS Identification
Reset Button
Display Data
The control panel will return to Normal display if ‘MENU’ button is pressed.
↓↓
buttons and pressing
↓↓
↵↵
button:
↵↵
42
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 43
Figure 30. Menu map
UPS Status display
UPS Status display will indicate the current operation mode of the UPS on the top row of the display. The display will automatically come to this display state if there is some abnormal operation in the unit. If there is active alarm in the unit it will be indicated on the bottom row. Pressing be scrolled through with the
The display generates an audible alarm when an active alarm appears. Pressing any button shall silence it.
Pressing Menu button will return the display to Menu display.
↓↓
button will transfer the display to Active Alarms display. Here all the active alarms can
↓↓
↓↓
button and return to UPS Status display can be made with
↓↓
↑↑
button.
↑↑
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
43
Page 44
Meters display
The Meters display will inform various measurements of the UPS. Different measurements
↓↓
can be selected with
Output voltage, shows AC voltage of each output phase
Output current, shows current of each output phase
Output power, shows power in kW of each output phase
Output frequency, unit is Hz
Bypass voltage, shows bypass line voltages of each phase
Input voltage, shows rectifier input line voltages of each phase
Battery voltage, shows DC voltage of both positive and negative battery string
Battery current, shows battery current of both positive and negative battery string
Internal temp, shows temperature inside the UPS, unit is °C.
Batt backup time, shows the battery backup time in minutes. If backup time is more
↑↑
and
buttons. Following measurement information is available:
↓↓
↑↑
than 90 minutes the display shows 9999.
Pressing Menu button will return the display to Menu display.
Battery Status display
The Battery Status display informs what is the mode of operation of the ABM (Advanced Battery Management).
Pressing Menu button will return the display to Menu display.
Alarm Log display
The Alarm Log display will indicate the 8 latest alarms of the UPS and also the time when each alarm has happened. The time showed (days hrs:min:sec) is the time between consecutive alarms. The alarms can be viewed by pressing the
↓↓
button. Pressing Menu
↓↓
button will return the display to Menu display.
UPS parameters display
The UPS Parameters display will inform the values of the operational parameters of the UPS. These parameters are to be changed only by service personnel of the manufacturer or by a representative of an agent authorised by the manufacturer. The parameter value changes are password protected.
↓↓
The values of different parameters can be viewed with
↑↑
and
buttons. The display will
↓↓
↑↑
indicate first the parameter number (Pxx) and after that the value of the parameter (Vyy).
Pressing Menu button will return the display to Menu display.
UPS Identification display
The display informs the UPS type, unit serial number and unit part number. These options
↓↓
can be scrolled with
and
↓↓
↓↓
buttons.
↓↓
Pressing Menu button will return the display to Menu display.
Reset button display
Selecting this function will reset alarms that are not auto resetting. It will also return the unit to normal mode if the unit has locked to bypass due to too many transfers to bypass assuming transfer back to normal operation is enabled. The reset button does not correct the condition that caused the alarm.
Pressing Menu button will return the display to Menu display.
44
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 45
Display Data display
The display shows information about the display software: revision, compilation date and check sum. To adjust the contrast or select a different language push
↓↓
three seconds. These options can be scrolled with
Pressing Menu button will return the display to Menu display.
and
↓↓
↓↓
buttons.
↓↓
↵↵
button down during
↵↵
9. Troubleshooting
9.1 Overview
The firmware contains intelligence to cope with any failure that could occur in the parallel UPS system. Note that the capacity mode provides more output power but is more vulnerable to system failures compared to the N+1 redundant mode.
9.2 Alarms and reasons
The normal procedure from the parallel UPS system is to go to the battery operation or bypass operation in case of power problems. The alarm messages are used together with the events logger as part of a diagnostic system for the UPS service specialist.
Battery power is used when the rectifier cannot feed the DC link well enough from the mains. Hence, the transfer to battery operation is made based on the DC link voltage. It is possible that a single UPS module of the system is in the battery operation while other modules still have mains power available. The back-up time is dependent on how much battery capacity is selected for the UPS modules.
Before calling for assistance you may take one or more of the following actions.
1. Check the local mains power supply. One or more fuses may be blown or someone could have switched off the supply by a mistake.
2. Check that the cooling air intake has not been blocked or the ventilation of the electrical room is not sufficient.
3. Check that output load capacity has not been exceeded. Someone might have placed too many loads on the UPS system output.
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
45
Page 46
yalpsiDmralA nosaeR noitcaSPU ?odottahW
YRETTABWOL
EGATLOV
TIMILWOLYRETTAB
SEIRETTAB
DETCENNOCSID
ERULIAFYRETTAB
YRETTAB
EGATLOVREVO
SSAPYB
ELBALIAVANU
TENIBAC
ERUTAREPMETREVO
YCNEGREME
FFOREWOP
FOSSOL
YCNADNUDER
DELBASSIDSPU
DAOLREVOhgihootsidaolehT. .ssapybotsrefsnartSPU
YCNADNUDER
DAOLREVO
SUBLELLARAP
ERULIAF
.timil
.timilwoleht
.yrettab
.hgihoot
.)edom
.yticapac
.elbaliavaton
sahegatlovyrettabehT
mralaehtwolebdeppord
wolebsiegatlovyrettabehT
sahegatlovyrettabehT
.timilwolehtwolebdeppord
ytluafdetcetedsahMBA
neebsahegatlovyrettabehT
ssapybehtfoenotsaeltA
.stimilehtfotuosisegatlov
.hgihootsitenibac
SPUehtedisnierutarepmeT
.evitcasi4XtupniOPE
stinuehtforebmunehT
.decuderneebsahgninnur
)edomycnadnuder(
gninnurstinuforebmunehT
yticapac(decuderneebsah
ehtgnideecxesidaoL
metsysI+Ntnadnuder
sistinuneewtebnoitacinummoC
.enoN
.enoN
.enoN
.enoN.daollatotehtkcehC
.enoN
.edomyrettabno
.detaitini
.delbasid
emitpukcabdecudersahSPU
siretrevniehtfotuptuO
.sdnoces06niffodenrut
dnanoitarepoyrettaB
.delbasideragnigrahc
sielcycgnigrahcMBA
.ffodenruterasregrahC
erassapybotsrefsnarT
llA.tinuehtfonwodtuhS
dna,ffodenruteraslortnoc
.deppirtsirekaerbtiucricyrettab
mralaehtkcehC
ehtsasraepassid
otstratsregrahcyrettab
.etarepo
ssapybtahtkcehC
.kosinoitarepo
lanretxetahtkcehC
erasrekaerbyrettab
.desolcrofllaC
.ecnatsissa
evahseirettaB
riehtdedeecxe
llaC.emitefillamron
.ecnatsissarof
yrettabehtkcehC
llaC.noitarugifnoc
.ecnatsissarof
sniamlacolehtkcehC
roenO.ylppusrewop
ebyamsesuferom
ydob-emosronwolb
evahtnediccaybdluoc
.ylppusehtffodehctiws
gniloocehtfikcehC
ruoynoekatniria
.dekcolbneebsahSPU
norepmujehtkcehC
ehtfo4Xlanimret
.eludomSPU
rofnosaerehtkcehC
SPUnafossoleht
rofllaC.eludom
ecnatsissa
rofnosaerehtkcehC
SPUnafossoleht
rofllaC.eludom
.ecnatsissa
ydobemosfikcehC
.hcumootdecalpsah
.ecnatsissarofllaC
lellarapehtkcehC
.elbacnoitacinummoc
Table 9. Typical alarms with their indications.
10. Warranty
The product is warranted against defects in material and workmanship for a period of 12 months from its original date of purchase.
46
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 47
11. Technical specifications
1. General
1.1 Rated power 20 kVA, 30 kVA, 40 kVA, 50 kVA, 60 kVA, 80 kVA; at p.f. 0,7, inductive or non linear load
1.2 Technology Double conversion online topology with automatic bypass switch and maintenance bypass switch.
Voltage and Frequency Independent operation: Class VFI-SS-111 by IEC 62040-3
2. Input
2.1 Rated voltage 220/380, 230/400, 240/415 Vac; three phase input (3xL+N+PE)
2.2 Voltage range 170/294-279/484 VAC without depleting battery 20-50 kVA and 80 kVA 180/312-279/484 VAC without depleting battery 60 kVA 196/336-279/484 VAC full charge capability
2.3 Rated frequency 50/60 Hz
2.4 Frequency range for rectifier 45 - 65 Hz
2.5 Nominal/max input current 20 kVA 3 x 21 A / 3 x 30 A 30 kVA 3 x 36 A / 3 x 45 A 40 kVA 3 x 47 A / 3 x 65 A 50 kVA 3 x 60 A / 3 x 80 A 60 kVA 3 x 70 A / 3 x 93 A 80 kVA 3 x 97 A / 3 x 125 A
2.6 Input power factor > 0.96 (Cosphi 1)
3. Output
3.1 Nominal voltage 220/380, 230/400, 240/415 VAC, selectable
3.2 Voltage regulation < ± 1% static < ± 1% with 100% unbalanced load < ± 5% dynamic at 100% load change Recovery time < 1 ms
3.3 Voltage distortion < 1 % THD linear load < 5 % THD non linear load
3.4 Frequency 50/60 Hz, selectable
3.5 Frequency regulation Synchronisation to line, ± 0.5, ± 1.0 or ± 2.0 Hz selectable. Free-running ± 0.05 Hz Slew rate 0.5, 2.5, 6 Hz/sec, selectable
3.6 Over load 101% to 110% for 10 minutes (online) 111 - 125% for 60 sec (online) 126 - 150% for 30 sec (online) 151 - 170% for 5 sec (online) 125% continuous (bypass) 1000% for one cycle (bypass)
3.7 Parallel load sharing ±5% of the rated load
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
47
Page 48
Single UPS modules
rewoptuptuO
detartuptuO
tnerruc
kaeptuptuO
)sm003(tnerruc
ycneiciffE
)70.f.p(
noitapissidrewoPW0041W0561W0012W0062W0013W0093
egatlov-CD
seirettablanretnI
thgieWgk)004(094gk094gk032gk062gk062gk082
htdiWmm025mm025mm025mm025mm025mm025
htpeDmm887mm887mm887mm887mm887mm887
thgieHmm0351mm0351mm0351mm0351mm0351mm0351
AVk02
Wk41
A92x3A34x3A85x3A27x3A78x3A611x3
A511x3A511x3A821x3A091x3A091x3A052x3
%39%39%39%39%39%39
882x2
V)291x2(
84x2xhA7
)hA7x23x2(
AVk03
Wk12
V882x2V882x2V882x2V882x2V882x2
4x2hA7x8----
AVk04
Wk82
AVk05
Wk53
AVk06
Wk24
AVk08
Wk65
The number indicated in parentheses are for units with battery banks of 32 pcs battery system.
Parallel Hot Sync™ systems
edomycnadnudeRgnitarrewoP
seludomSPUforN
SPU1+1AVk02AVk03AVk04AVk05AVk06AVk08
SPU1+2AVk04AVk06AVk08AVk001AVk021AVk061
SPU1+3AVk06AVk09AVk021AVk051AVk081AVk042
edomyticapaCgnitarrewoP
seludomSPUforN
SPUx2AVk04AVk06AVk08AVk001AVk021AVk061
SPUx3AVk06AVk09AVk021AVk051AVk081AVk042
SPUx4AVk08AVk021AVk061AVk002AVk042AVk023
AVk02
seludom
AVk02
seludom
AVk03
seludom
AVk03
seludom
AVk04
seludom
AVk04
seludom
AVk05
seludom
AVk05
seludom
AVk06
seludom
AVk06
seludom
4. Environmental
4.1 Ambient temperature 0° ... + 40°C operating +15°C ... +25°C recommended
-25°C ... +55°C storage (without battery)
4.2 Ventilation Fan cooling, temperature µP monitored
4.3 Altitude 1000 m operating w/o derating 15 000 m during transportation
4.4 Humidity 15 ... 90% RH, non-condensing
4.5 Audible noise < 55 dB(A) at 1 meter distance 20-30 kVA < 60 dB(A) at 1 meter distance 40-60 kVA < 65 dB(A) at 1 meter distance 80 kVA
4.6 Protection class IP 21 S
AVk08
seludom
AVk08
seludom
48
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 49
4.7 Cooling air requirements Q=300 x P/t, where: Q=air flow in m3/h, P=power losses in kW, t=temp. rise in celcius, which means that each kW of losses needs an airflow of 300 m3/hour trough a room to keep temp raise at 10 celcius max.
5. Standards
5.1 Safety IEC 60950, EN 50091-1-1 (1996)
5.2 Emissions EN 50091-2 (1995)
5.3 Immunity EN 50091-2 (1995)
6. DC circuit
6.1 Battery type Valve regulated Lead Acid; 48 pcs. 12 V blocks with 5 or 10 years design.
6.2 Battery charging Advanced Battery Management™ or traditional float charging
6.3 Nominal battery voltage 2x288 V (2x144 cells)
6.4 DC voltage range 252 - 329 V (1.75 VDC - 2.28 VDC)
6.5 Battery charging current max. 8 A (40-80 kVA) max. 6 A (20-30 kVA)
External battery cabinets with sealed lead-acid batteries.
DTABETABFTAB
egatlov-CDV882x2V882x2V882x2
seirettaBhA42x42x2hA83x42x2hA56x42x2
thgieWgk055gk518gk0931
htdiWmm283mm025mm4301
)mm(htpeDmm887mm887mm887
)mm(thgieHmm0351mm0351mm0351
Note! A Battery cabinet F consists of two cabinets, total width is 1034 mm.
4-06-5039MPS2-06-5039MPS4-08-5039MPS2-03-5039MPS2-031-0439/5039MPS
rewoptuptuO
thgieWgk012gk05gk032gk05gk032
htdiWmm025mm005mm025mm005mm025
htpeDmm887mm052mm887mm052mm887
thgieHmm0351mm007mm0351mm007mm0351
AVk042
Wk861
AVk021
Wk48
AVk023
Wk422
AVk06
Wk24
AVk062
Wk281
ycneiciffE%98%19%09%09%19%19
1018390 Revision C
)elpmaxe(metsysSPUlellaraP1+1
rewoptuptuO
tnerruckaeptuptuOA002x3A002x3A083x3A083x3A083x3A005x3
noitapissidrewoPW0051W0581W0082W0053W0573W0005
AVk02
Wk41
AVk03
Wk12
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
AVk04
Wk82
AVk05
Wk53
AVk06
Wk24
AVk08
Wk65
49
Page 50
Appendix A – Dimension drawings 20-30 kVA UPS
50
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Page 51
Appendix B – Dimension drawings 40 - 80 kVA UPS
1018390 Revision C
20 - 80 kVA parallel UPS systems
User’s and Installation Manual
51
Page 52
Appendix C – Dimension drawings SPM9305
Ref. SPM9305-80-4 / SPM9305-60-4 / SPM9305/9340-130-2
52
20 - 80 kVA parallel UPS system
User’s and Installation Manual
1018390
Revision C
Loading...