The contents of this manual are the copyright of the publisher
and may not be reproduced (even extracts)
unless permission granted.
Every care has been taken to ensure the accuracy of
the information contained in this manual, but no liability
can be accepted for any errors or omission. The right
to make design modifications is reserved.
CE marking ................................................................................................................................................ 4
User precautions ......................................................................................................................................... 4
SPM tie cabinet ......................................................................................................................................... 23
6.Software and connectivity ................................................................................................... 26
Communication cables ............................................................................................................................. 26
Connection to the standard RS-232 port (X53) ....................................................................................... 26
User Settings ............................................................................................................................................. 33
Configuring user settings ...................................................................................................................... 34
Changing language ............................................................................................................................... 34
Changing charging current ................................................................................................................... 34
Using relay outputs ............................................................................................................................... 34
Normal start-up ........................................................................................................................................ 35
Cooling fan ........................................................................................................................................... 37
LED Indicators ......................................................................................................................................... 37
AC input ................................................................................................................................................... 44
DC circuit ................................................................................................................................................ 44
AC output ................................................................................................................................................. 44
The UPS operates with mains, battery or bypass power. It contains components that carry high
currents and voltages. The properly installed enclosure is earthed and IP20 rated against
electrical shock and foreign objects. However, only qualified personal is allowed to install and
service the UPS.
Warning!
Operations inside the UPS must be performed by a service engineer from the
manufacturer or from an agent authorised by the manufacturer.
Do not ever service inside the UPS when mains power is applied or the UPS is in battery mode.
Use the optional mechanical bypass if installed to the system. Remember to open battery
breaker. Always ensure by measuring with a multi-meter that no dangerous voltages are
present.
Audience
The intended audiences of this manual are people who plan the installation, install,
commission, and use or service the UPS. The manual provides guidelines to check delivery,
installing and commissioning of the UPS.
The reader is expected to know the fundamentals of electricity, wiring, electrical components
and electrical schematic symbols. This manual is written for a global reader.
Note!
Read the manual before operating or working on the UPS.
CE marking
The product has the CE marking in compliance with the following European directives:
•LV Directive (Safety)72/23/CEE and 93/68/CEE
•EMC Directive89/336/EEC and 93/68/EEC
Declaration of conformity with UPS harmonised standards and directives EN 62040-1-1
(Safety) and EN 50091-2 (EMC) are available on the web site (http://www.powerware.com).
User precautions
The only user operations permitted are:
•Start up and shut down of the UPS, excluding the commissioning start-up.
•Use of the LCD control panel and Maintenance Bypass Switch (MBS)
•Use of optional connectivity modules and their software
The user must follow the precautions and only perform the described operations. Any deviations
from the instructions could be dangerous to the user or cause accidental load loss.
4
UPS 8 – 15 kVA, 230V 50/60 Hz output
User’s Guide
1022403
Revision B1
Warning!
The user is not permitted to open of any screws excluding connectivity plates and the
MBS locking plate. Failure to recognise the electrical hazards could prove fatal.
Environment
The UPS must be installed according to the recommendations in this manual. Under no
circumstances the UPS should be installed in an airtight room, in the presence of flammable
gases, or in an environment exceeding the specification.
Excessive amount of dust in the operating environment of UPS may cause damage or lead to
malfunction. The UPS should be always protected from the outside weather and sunshine. The
recommended operating temperature is from +15 to +25 Celsius degrees.
Inquiries
Address any inquiries about the UPS and battery cabinet to the local office or agent authorised
by the manufacturer. Please quote the type code and the serial number of the equipment.
1022403
Revision B1
UPS 8 – 15 kVA, 230V 50/60 Hz output
User’s Guide
5
2. Mechanical installation
The UPS and accessories are delivered on a specifically designed pallet that is easy to move with
a forklift or a pallet jack. Keep the UPS always in upright position and do not drop the
equipment. Do not either stack the pallets because of high-energy batteries involved and the
heavy weight
Delivery check
The UPS is delivered with the following items:
•Plastic bag containing:
Quick Installation Guide, paper format, multilingual (coming later)
User’s Guide, paper format, multilingual
User’s Guide, CD-ROM format, multilingual (coming later)
Residual voltage warning stickers
Software Suite, CD-ROM format, English language
RS-232 serial cable for the Software Suite
•Delivery documents
Unpacking and visual inspection
Check that there are no signs of shipping damages. The outside ’Tip&Tel’ indicator should be
intact if the equipment has been transported in the upright position.
Note!
A claim for shipping damage must be filed immediately and the carrier must be
informed within 7 days of receipt of the equipment. The packing materials should be
stored for further investigation.
Unpack the equipment by removing the packing and shipping materials. Make a visual
inspection and check that the inside ‘Drop&Tell’ indicator is intact. Make sure that the floor
surface is solid and suitable for the wheeling and heavy weight, twist the levelling feets of the
unit to up position and remove the equipment from the pallet.
Figure1. Instructions for removing the equipment from the pallet.
6
UPS 8 – 15 kVA, 230V 50/60 Hz output
User’s Guide
1022403
Revision B1
Check the information on the type designation label of the equipment to verify that the unit is
of the correct type. The type designation label includes ratings, a CE marking, a type code, a
part number and a serial number. The serial number is important when making inquiries. It
allows individual recognition of the equipment.
Figure 2. Type designation label.
1022403
Revision B1
UPS 8 – 15 kVA, 230V 50/60 Hz output
User’s Guide
7
3. Planning before installation
The equipment must be installed in upright position. The equipment requires space to front
and back to enable cooling airflow, service and maintenance. All cooling air enters at front and
exits at unit rear. The required min. clearance from unit rear to an obstruction is 150 mm.
Figure 3.Ventilation space around the equipment.
It is required to arrange ventilation of the UPS room. Sufficient amount of air cooling is needed
to keep the max. room temperature rise at desired level:
•Temperature rise of max. +5°C requires the airflow of 600 m
•Temperature rise of max. +10°C requires the airflow of 300 m
3
per 1 kW of losses.
3
per 1 kW of losses.
An ambient temperature of 15 to 25 Celsius degrees is recommended to achieve a long life of
the UPS and batteries. The cooling air entering the UPS must not exceed +40 °C. Avoid high
ambient temperature, moisture and humidity.
The floor material should be non-flammable and strong enough to support the heavy load. The
UPS has (4) leveling feet that should be used when finalising the installation. The diameter of a
single leveling foot is 1 inch (25.4 mm).
Table 4. The floor surface must tolerate these loading.
8
UPS 8 – 15 kVA, 230V 50/60 Hz output
User’s Guide
1022403
Revision B1
4. Cabinet installation
The required distance for UPS units next to each other is ten millimetres. The same applies to
the optional battery cabinets that should be installed next to the UPS cabinet.
Figure 5. UPS and external battery cabinets.
The UPS family has several alternative battery cabinets and configurations depending on the
selected back-up time and quality of batteries.
Mechanical bypass switch
The mechanical bypass switch (MBS) shall be mounted in back of the UPS battery
compartment. It can be ordered factory installed.
Figure 6. Instructions for locating the mechanical bypass switch.
Please fix the mechanical bypass switch (MBS) to the wall (din rail) or to the back of the UPS
as shown below.
1022403
Revision B1
UPS 8 – 15 kVA, 230V 50/60 Hz output
User’s Guide
9
Figure 7.The mechanical bypass switch (MBS) when installed in the backside.
Figure 8. 9155 MBS assembly
10
UPS 8 – 15 kVA, 230V 50/60 Hz output
User’s Guide
1022403
Revision B1
Transformer option
The galvanic isolation transformer can be ordered as factory installed. The transformer is an
integral part of the UPS unit. Alternatively, the isolation transformer can be purchased as a
separate item to upgrade your existing system.
Figure 9. Transformer option can be ordered factory installed (integral) or separately.
The overtemperature sensor cable is connected to the control input (X45 or X44) of the UPS,
see the next drawing. In the factory installed systems this cable is ready-made for use.
Figure 10. Wiring diagram of the UPS and the external transformer option.
1022403
Revision B1
UPS 8 – 15 kVA, 230V 50/60 Hz output
User’s Guide
11
External battery cabinet option
It’s recommended to install external battery cabinets next to the UPS unit. The external battery
can be placed on either side of the UPS unit. Check before the installation that the battery
voltage values in the type plate of the UPS and external battery cabinets are the same. The
cables are delivered with the external battery cabinet. See External Battery Cabinet (EBC)
installation procedure.
Warning!
The UPS contains high DC voltages. A qualified person must do the connections between
the UPS and the external battery cabinet(s). The battery cabinet is connected electrically
in parallel with the internal batteries of the UPS.
Figure11.UPS and external battery cabinets.
Battery racks
External battery racks shall be sized to take the voltage drop in the cable into account. To
obtain support and help contact the local office or agent authorised by the manufacturer.
12
UPS 8 – 15 kVA, 230V 50/60 Hz output
User’s Guide
1022403
Revision B1
5. Electrical installation
The customer has to supply the wiring to connect the UPS to the local power source. The
electrical installation procedure is described in the following text. The installation inspection
and initial start up of the UPS and extra battery cabinet shall be carried out by a qualified
engineer with UPS installation experience.
Warning!
Physical injury or death may follow, or damage may occur to the UPS, or the load
equipment if these instructions are ignored.
Figure 12. Location of the power terminals.
1022403
Revision B1
UPS 8 – 15 kVA, 230V 50/60 Hz output
13
User’s Guide
The UPS unit has the following power connections:
•Three-phase (L1, L2, L3) and protective earth (PE) connection for the rectifier input
or
Single-phase (L1), Neutral (N) isolated connection point (bypass N is used in the rectifier)
and protective earth (PE) connection for the rectifier input.
•Single-phase (L1), Neutral (N) and protective earth (PE) connection for the bypass input
•Single-phase (L1), Neutral (N) and protective earth (PE) connection for the load output
•Plus (+), minus (-) and protective earth (PE) connection for the external batteries
Note!
The rectifier requires a Neutral to operate. It’s connected internally from the bypass
terminal to the rectifier, see wiring diagram.
Figure 13. Power terminals found in UPS units.
Power cables and protective fuses
Always use copper cable types to fit terminals with approximately 1.5 Nm torque for different load
currents. The Cu cable sizing is based on multi-core cables laid in conduits/trunkings on the wall or
on the floor (installation procedure C), ambient temperature 25°C, PVC insulation, surface
temperature up to 70°C. Cables of several UPS can be installed in parallel to each other.
Standards SFS 6000-5-52 (2002) and IEC 60364-5-52 (2001-08) “Electrical installations of
buildings” are used as a sizing guide. For any other conditions, size the cables according to the
local safety regulations regarding installation environment, appropriate voltage and currents of
the UPS.
Fuses are sized according to local safety regulations, appropriate input voltage and the rated
current of the UPS. Therefore, protect the input and bypass cables with gG (gL) fuses or B-C-D
type of circuit breakers against overload and short-circuit.
14
UPS 8 – 15 kVA, 230V 50/60 Hz output
User’s Guide
1022403
Revision B1