Powerware 700 3000 VA User Manual

Page 1
Powerware® 9120
User's Guide
7003000 VA
www.powerware.com
Page 2
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Powerware Corporation Koskelontie 13 FIN-02920 Espoo Finland Phone: +358-9-452 661 Fax: +358-9-452 665 68
93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC
VCCI Notice for Class A and Class B
(120V and 208V Models)
Powerware is a registered trademark of Powerware Corporation.
Copyright 2001 Powerware Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Powerware Corporation.
Page 3
Class A EMC Statements
(20003000 VA Models)
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
EN50091-2
Some configurations are classified under EN500912 as ClassA UPS for Unrestricted Sales Distribution." For these configurations, the following applies:
WARNING This is a Class AUPS Product. In a domestic environment, this product may cause radio interference, in
which case, the user may be required to take additional measures.
Class B EMC Statements
(7001500 VA Models)
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
ICES-003
This Class B Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES003.
Cet appareil numérique de la classe B respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
Page 4
Special Symbols
The following are examples of symbols used on the UPS to alert you to important information:
CAUTION
Risk of Electric Shock
Do Not Open Cover
CAUTION To reduce the risk of electric shock,
Do not remove cover (or back)
No user-serviceable parts inside
Refer servicing to the factory
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the
associated warning should be observed.
CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for
additional information, such as important operating and maintenance instructions.
RJ-45 RECEPTACLE - For 208V and 230V models only: this receptacle provides
network interface connections. Do not plug telephone or telecommunications equipment into this receptacle.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. The UPS may contain sealed, leadacid batteries. Batteries must be recycled.
Page 5
TABLE OF CONTENTS
1 Powerware 9120  One of the Best! 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Installation 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspecting the Equipment 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the Plug/Receptacle UPS 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Rear Panels 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the Hardwired UPS 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Operation 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Front Panel 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Mode 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Turning the UPS On 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting the UPS on Battery 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Turning the UPS Off 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standby Mode 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic Tests 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Configuration 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration Mode 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Additional UPS Features 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Emergency Power-Off 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Network Transient Protector 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load Segments 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Port 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
USB Port 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Slot 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SNMP/Web Adapter 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay Card 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 UPS Maintenance 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS and Battery Care 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Storing the UPS and Batteries 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
i
Page 6
Table of Contents
Replacing Batteries 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Replace External Batteries 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Replace Internal Batteries 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recycling the Used Battery 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 Specifications 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Troubleshooting 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Audible Alarms and UPS Conditions 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Silencing an Audible Alarm 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service and Support 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 7
C H A P T E R 1
POWERWARE 9120 ONE OF THE BEST!
The Powerware 9120 uninterruptible power system (UPS) protects your sensitive electronic equipment from the most common power problems including power failures, power sags, power surges, brownouts, line noise, high voltage spikes, frequency variations, switching transients, and harmonic distortion.
Power outages can occur when you least expect it and power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware  causing hours of lost productivity and expensive repairs.
With the Powerware 9120, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Figure 1 shows the Powerware 9120 UPS with an optional Extended Battery Module (EBM).
Figure 1. The Powerware 9120 and Optional EBM
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
1
Page 8
Powerware 9120  One of the Best!
Providing outstanding performance and reliability, the Powerware 9120's unique benefits include the following:
The Powerware 9120 incorporates the latest in high-frequency,
double-conversion online topology, which provides uninterrupted, clean, sine-wave power.
An intuitive LCD screen provides real-time updates of UPS status,
power usage, remaining battery run time, and other critical UPS parameters.
Flexible communication options with USB, serial, and network
capabilities.
Advanced power management with the Software Suite CD for graceful
shutdowns and power monitoring.
Sequential shutdown and load management through separate
receptacle groups, called load segments.
Network Transient Protector guards your network communications
equipment from surges. Low voltage models can also guard modems, fax machines, or other telecommunications equipment.
Hotswappable batteries simplify maintenance by allowing you to
replace batteries safely without powering down the critical load.
Startonbattery capability allows you to power up the UPS even if
utility power is not available.
Emergency shutdown control through the Remote Emergency
Power-Off (REPO) port.
The Powerware 9120 is backed by worldwide agency approvals and a
limited two-year warranty.
2
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 9
C H A P T E R 2
INSTALLATION
This section explains:
Equipment inspectionSafety precautionsPlug/receptacle UPS installation and rear panelsHardwired UPS installation
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service representative (see page 40).
Safety Precautions
Read the following precautions before you install the UPS.
I M P O R T A N T S A F E T Y I N S T R U C T I O N S
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
3
Page 10
Installation
This UPS contains its own energy source (batteries). The output receptacles may
carry live voltage even when the UPS is not connected to an AC supply.
Do not remove or unplug the input cord when the UPS is turned on. This removes
the safety ground from the UPS and the equipment connected to the UPS.
To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% max).
To comply with international standards, the sum of earth leakage current from the
load connected to the UPS must not exceed 1 mA.
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment and void your warranty.
Installing the Plug/Receptacle UPS
The following steps explain how to install the UPS. See UPS Rear Panels" on page 6 for the rear panel of each model.
1. If you are installing power management software, connect your computer to the UPS communication port using the supplied communication cable.
2. If installing an optional Extended Battery Module, plug the EBM cable into the battery connector on the EBM rear panel.
3. Plug the other end of the EBM cable into the battery connector on the UPS rear panel.
4. If additional EBMs are to be installed, plug the EBM cable of the second cabinet into the battery connector on the first EBM. Repeat for each additional EBM.
5. On 208V or 230V models, plug the power cord into the input connector on the UPS rear panel.
6. Plug the UPS power cord into a power outlet. The fan turns on and the UPS enters Standby mode.
W A R N I N G
4
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 11
Installation
7. Plug the equipment to be protected into the UPS output receptacles.
DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements.
NOTE If you are using the Load Segment feature, see page 24 for more information on controlling and assigning the load segments.
8. To start the UPS, press and hold the button until you hear the UPS beep (approximately one second). The LCD briefly displays
On Delay and the
UPS conducts a selftest, briefly displaying
indicator illuminates. Then the
On BATTERY. If an
alarm condition occurs, see Table 10 on page 37.
When the self-test is complete, the LCD displays On Line indicating that power is available from the UPS output receptacles.
9. If you installed optional EBMs, configure the number of EBMs through the front panel so that the UPS can estimate the available battery run time (see Configuration Mode" on page 17).
NOTE The batteries charge to 90% capacity in approximately 4 hours. However, it is recommended that the batteries charge for 6 to 24 hours after installation or long-term storage.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
5
Page 12
Installation
UPS Rear Panels
This section shows the rear panels of the Powerware 9120 plug/receptacle models.
Communication
Port
Fan
REPO Port
700 VA, 120V
Communication Port
Network Transient
Communication SlotUSB Port
Protector
Network Transient Protector
Battery Connector
Circuit Breaker
Four 515 Receptacles
6-ft Power Cord with 515 Plug
Fan
Communication
Port
Fan
REPO Port
Four 515
Receptacles
Communication SlotUSB Port
Communication SlotUSB Port
Network Transient Protector
Battery Connector
Circuit Breaker
Two 5-20 Receptacles
6-ft Power Cord with 515 Plug
1000 VA, 120V
Battery Connector
Circuit Breaker
REPO Port
Two 5-20
Four 515 Receptacles
Receptacles
6-ft Power Cord with 515 Plug
1500 VA, 120V
6
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 13
Installation
Communication
Port
Fans
Circuit Breaker
6-ft Power
Cord with
520 Plug
2000 VA, 120V
Communication
Port
Fans
Communication SlotUSB Port
USB Port
Communication
Network Transient Protector
Battery Connector
REPO Port
Six 5-20 Receptacles
Circuit Breaker
Port
Fans
6-ft Power
Cord with
L530 Plug
Communication SlotUSB Port
Network Transient Protector
Two 5-20 Receptacles
REPO Port
One L530 Receptacle
Four 515 Receptacles
3000 VA, 120V
Communication Slot
Network Transient Protector
Battery Connector
REPO Port
Two L6-15R Receptacles
6-ft Power
Cord with
L620 Plug
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
3000 VA, 208V
One L6-20R Receptacle
One L6-30R Receptacle
7
Page 14
Installation
USB Port
Communication
Port
Fan
REPO Port
Communication
Port
Fans
7001000 VA, 230V
USB Port
Communication Slot
Communication Slot
Network Transient Protector
Battery Connector
Four IEC-C13 Receptacles
IEC-C14 Input Connector
Communication
Communication
Port
Network Transient Protector
Battery Connector
REPO Port
One IEC-C19 Receptacle
Fans
USB Port
Port
REPO Port
Fan
IEC-C14 Input
Connector
USB Port
Communication Slot
Battery Connector
Network Transient Protector
Four IEC-C13 Receptacles
1500 VA, 230V
Communication Slot
Network Transient Protector
Battery Connector
REPO Port
One IEC-C19 Receptacle
IEC-C14 Input
Connector
8
2000 VA, 230V
Four IEC-C13 Receptacles
IEC-C20 Input
Connector
3000 VA, 230V
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Four IEC-C13 Receptacles
Page 15
Installing the Hardwired UPS
Only qualified service personnel (such as a licensed electrician) should perform the electrical installation. Risk of electrical shock.
The Powerware 9120 requires a dedicated branch circuit that meets the following requirements:
40A circuit with short circuit and overcurrent protection100-127 VacSingle-phase50/60 HzFlexible metal conduit is recommended for ease of service and
maintenance
To hardwire the UPS:
1. If you are installing power management software, connect your computer to the UPS communication port using the supplied communication cable.
2. If installing an optional Extended Battery Module, plug the EBM cable into the battery connector on the EBM rear panel.
3. Plug the other end of the EBM cable into the battery connector on the UPS rear panel.
4. If additional EBMs are to be installed, plug the EBM cable of the second cabinet into the battery connector on the first EBM. Repeat for each additional EBM.
5. Switch off utility power at the distribution point where the UPS will be connected. Be absolutely sure there is no power.
Installation
W A R N I N G
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
9
Page 16
Installation
6. Remove the terminal block cover and the wiring knockouts (see Figure 2). Retain the terminal block cover.
USB Port
Communication Port
Fans
Output Wiring
Access Knockout
Input Wiring
Access Knockout
Communication Slot
Network Transient Protector
Battery Connector
REPO Port
Panel Cover Screws
Terminal Block Cover
Panel Cover Screws
Figure 2. 3000 VA, 120V Hardwired Rear Panel
7. Pull the input wires through the conduit, leaving approximately 2 ft (0.5m) of exposed wire. Attach a flexible metal fitting to the end of the conduit.
8. Insert the conduit through the input wiring access knockout and attach the conduit fitting to the panel. Strip 0.5 (1.5 cm) of insulation from the end of each incoming wire.
9. Connect the input and ground wires to the input terminal block (see Figure 3).
10. Pull the output wires through the conduit, leaving approximately 2 ft (0.5m) of exposed wire. Attach a flexible metal fitting to the end of the conduit.
11. Insert the conduit through the output wiring access knockout and attach the conduit fitting to the panel. Strip 0.5 (1.5 cm) of insulation from the end of each incoming wire.
10
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 17
Installation
12. Connect the output and ground wires to the output terminal block (see Figure 3).
Line
Ground
Neutral
Line
Ground
Neutral
L
OUTPUT
N
L
INPUT
N
Output Connections
Input Connections
Figure 3. Terminal Block
13. Replace the terminal block cover.
14. Switch the main utility breaker on.
15. To start the UPS, press and hold the
button until you hear the UPS beep (approximately one second). The LCD briefly displays
On Delay and the
UPS conducts a selftest, briefly displaying
indicator illuminates. Then the
On BATTERY. If an
alarm condition occurs, see Table 10 on page 37.
When the self-test is complete, the LCD displays On Line indicating that power is available from the UPS output receptacles.
16. If you installed optional EBMs, configure the number of EBMs through the front panel so that the UPS can estimate the available battery run time (see Configuration Mode" on page 17).
NOTE The batteries charge to 90% capacity in approximately 4 hours. However, it is recommended that the batteries charge for 6 to 24 hours after installation or long-term storage.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
11
Page 18
Installation
12
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 19
C H A P T E R 3
OPERATION
This section describes:
The UPS front panelTurning the UPS on and offStarting the UPS on batteryStandby modeDiagnostic tests
UPS Front Panel
The UPS front panel indicates the UPS status and also identifies potential power problems. Figure 4 shows the UPS front panel indicators and controls.
LCD Panel
Power On Indicator (Green)
On Battery Indicator (Yellow)
Bypass Indicator (Yellow)
Alarm Indicator (Red)
NOTE If the alarm beeps or if the indicator is on, see Table 10 on page 37 to identify and correct the problem. To configure parameters through the front panel, see Configuration Mode" on page 17.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Scroll Button Enter Button
Figure 4. UPS Front Panel
 
On/Off Button
13
Page 20
Operation
Display Mode
To view the UPS current settings, press the button for one second. Use
button to scroll through the list of settings:
the
LCD Message Description
I/P VOLT= xxx.xV Input voltage.
I/P FREQ= xx.xHZ Input frequency.
O/P VOLT= xxx.xV Output voltage.
O/P FREQ= xx.xHZ Output frequency.
O/P Load = x% Approximate percentage of UPS load capacity being used by the
protected equipment.
O/P Watt= xW Output watts.
O/P VA= xVA Output VA.
O/P Cur= x.xA Output current.
BAT VOLT= xx.xV Battery voltage.
BAT CHARGE= xxx% Approximate percentage of battery capacity remaining.
BackUp Time= xxxM Approximate battery time remaining in minutes. The display changes
to seconds after one minute (Backup Time= xxxS).
CPU Version x.xx Firmware revision level.
NOTE The UPS exits Display mode automatically after five seconds if the button is not pressed.
Turning the UPS On
After the UPS is connected to a power source, the fan turns on and the UPS enters Standby mode. To turn on the UPS, press and hold the The LCD briefly displays Then the UPS conducts a selftest, briefly displaying alarm condition occurs, see Table 10 on page 37.
When the self-test is complete, the LCD displays power is available from the UPS output receptacles.
14
button until you hear the UPS beep (approximately one second).
On Delay and the
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
indicator illuminates.
On BATTERY. If an
On Line indicating that
Page 21
Starting the UPS on Battery
NOTE Before using this feature, the UPS must have been powered by utility power at
least once and the batteries must be completely charged.
To turn on the UPS without using utility power, press and hold the The UPS supplies power to your equipment and goes into Battery mode. The LCD briefly displays indicators illuminate. When the UPS starts on battery, it does not conduct a selftest to conserve battery power.
Turning the UPS Off
To turn off the UPS, press and hold the button until the long beep ceases (approximately five seconds).
NOTE When you press and hold the button, the LCD displays Shutdown Pending.
The  indicator turns off and the LCD briefly displays UPS OFF before going blank. The fan continues to run and the UPS remains in Standby mode until you unplug or remove utility power from the UPS.
Operation
button until you hear the UPS beep (approximately one second).
+
On Delay, then On Battery and the
and
-
Standby Mode
When the UPS is turned off and connected to a power source, the UPS is in Standby mode. The fan continues to run and the battery recharges when necessary. The indicating that power is not available from the UPS.
Diagnostic Tests
The UPS automatically performs a self-test when powered on and when the UPS restarts after a power outage. The self-test monitors the UPS electronics and battery and indicates any problems on the front panel.
A battery test is automatically performed every 30 days (720 hours) of continuous Normal mode operation. The test lasts approximately 15 seconds and any failure is displayed on the front panel.
Both the UPS and battery tests can be performed manually (see Configuration Mode" on page 17 for more information).
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
indicator is off and the LCD panel is blank,
15
Page 22
Operation
16
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 23
C H A P T E R 4
CONFIGURATION
This section describes how to reconfigure options using the Configuration mode, including: input and output voltage and frequency, site wiring fault, and silencing the alarm.
NOTE The UPS has been factory-configured with default settings appropriate for most installations. User configuration is not normally required.
Configuration Mode
The control buttons (
and ) are used to modify the UPS
configuration. Figure 5 shows the front panel and Table 1 explains the corresponding options.
NOTE The UPS can be configured while in Battery mode. If the UPS switches to battery power while in Configuration mode, the UPS exits Configuration mode and indicates Battery mode on the front panel.
1. Press the
button for one second to enter Configuration mode.
The LCD displays the first configuration parameter (see Table 1).
2. Press the
button to scroll through the parameters.
NOTE The UPS exits Configuration mode automatically after five seconds if a selection has not been made.
3. Press the button to select the parameter.
4. Press the
parameter; press the
You may be prompted to save the selection; press the
button to scroll through the options for the selected
button to select the option.
button to save. Other options are saved automatically. See Table 1 for more detail.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
17
Page 24
Configuration
5. To exit Configuration mode at any time, do not press any buttons for five seconds. The UPS returns to Normal mode and displays
LCD Panel
On Line.
 
Press the Scroll button to enter Configuration mode. Also press to scroll to the next option.
Press the Enter button to select a parameter. Also press the Enter button to select an option and to save the setting.
Figure 5. Using the Configuration Mode
Table 1. Configuration Mode Parameters
Parameter LCD Message Description Default Settings
Output Voltage Setting
Input Voltage Tolerance
Input Voltage Frequency
O/P V Setting To change the output voltage:
Select 100, 110, 120, or 127V for 120V models.Select 200, 208, 220, 230, or 240V for 208V models.Select 208, 220, 230, or 240V for 230V models.
You are prompted to save this setting.
I/P Bypass Set Select the input voltage tolerance range before the
UPS goes to Battery mode: ±10%, +10%/-15%, or +15%/-20%.
You are prompted to save this setting.
I/P F Setting The factory-default is 50 or 60 Hz, ±5%. Select ±2%
for a narrower frequency range. Select ±7% for a wider frequency range.
You are prompted to save this setting.
For 120V models:
O/P V= 120V
For 208V models:
O/P V= 208V
For 230V models:
O/P V= 230V
I/P Tol=+10%/-15%
Freq Tol.=+/-15%
18
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 25
Default SettingsDescriptionLCD MessageParameter
Configuration
High-Efficiency Mode
HE Mode Setting Select whether High-Efficiency mode is On or Off. If
enabled, you must also select the input voltage range: ±10% or ±15%.
While operating in High-Efficiency mode, the UPS transfers to utility power when: 1) the input voltage is outside ±10% or ±15% from nominal; 2) the input frequency is greater than ±3%; or 3) the input line is not available.
You are prompted to save this setting.
Free Run Mode Free Run Mode Select whether Free Run mode is On or Off. If enabled,
you must also select Bypass Disable or Bypass Enable. This selection defines how your UPS runs when the
input frequency (from the utility) is outside the selected frequency tolerance (set via the I/P F Setting, above), but is inside the maximum frequency limits the UPS can accept before switching to Battery mode.
For example: If your 60 Hz UPS is set to the factory default window of ±5% before the UPS starts regulating the frequency:
The output frequency tracks the input frequency
exactly from 57 to 63 Hz.
If input frequency is between 45 and 57 Hz, or
between 63 and 65 Hz, the output frequency is regulated by the UPS to exactly 60 Hz (±0.5 Hz).
You are prompted to save this setting.
Alarm Silence Alarm Silence Select whether Silence is On or Off. If enabled, the
UPS silences the alarm for an existing fault. If the UPS status changes, the alarm beeps, overriding the previous alarm silencing. The alarm does not silence if there is a low battery condition.
Manual Battery Test
Manual Bat Test To initiate a manual battery test, press the button
twice. During the test, the LCD displays
On BATTERY.
The UPS resets the automatic timer after a manual battery test.
Manual UPS Test Manual UPS Test To initiate a manual UPS self-test, press the button
Site Wiring Fault Alarm
twice. During the test, the LCD displays
Site Fault Set Select Enable or Disable. When enabled, the alarm
sounds when the ground connection is missing or the
On BATTERY.
line and neutral wires are reversed in the wall outlet.
Modem Support Modem Support This parameter is reserved for future use, and should
not be modified by the user.
HE Mode Off
Free Run On (Bypass Disable)
Silence Off
Battery Test
UPS Test
Detect Enable
No Modem Support
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
19
Page 26
Configuration
Default SettingsDescriptionLCD MessageParameter
Number of Extended Battery Modules
Bat Pack Num Set Select the number of EBMs connected to the UPS:
For 7001500 VA models, select 0 through 2.For 20003000 VA models, select 0 through 5.
You are prompted to save this setting.
Communications Lock-out
COM Control Cmds For greater levels of security, users may choose to
have the UPS disregard shutdown commands that come from the power management software or other communication sources.
When disabled, the UPS does not accept a shut
down command via the communication port, USB port, or communication slot adapter.
When enabled, the UPS operates normally in
response to external commands.
You are prompted to save this setting.
Load Segment Control
Load Group Set Allows manual control of load segments (see Load
Segments" on page 24). By repeatedly pressing the scroll button, the individual
load segments can be turned on and off.
CAUTION To prevent the unintentional shutdown of
specific load segments, confirm your selection before pressing the button.
Manual Bypass Manual Bypass GO This parameter is used to manually place the UPS in
Bypass mode.
Configuration Mode Setting
Config Mode Set This parameter is reserved for future use, and should
not be modified by the user. The setting may be toggled between
ConfigMode. It should always be set to EscapeConfigMode.
EscapeConfigMode and Enter
Extern Pack: 0
Enable
Group 1On 2On
Bypass OFF
EscapeConfigMode
20
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 27
C H A P T E R 5
ADDITIONAL UPS FEATURES
This section describes:
Remote Emergency Power-OffNetwork Transient ProtectorLoad segmentsUsing the communication port or USB portOptional Powerware Corporation communication cards
Remote Emergency Power-Off
The Powerware 9120 includes a REPO port that allows power to be switched off at the UPS output connections from a customer-supplied switch in a remote location.
The REPO feature shuts down the protected equipment immediately, whether or not the UPS is in Normal or Battery mode, and does not follow the orderly shutdown procedure initiated by any power management software. The UPS switches to Standby mode.
When the external REPO switch is re-closed, the UPS must be manually restarted to provide power to the connected equipment.
If the in Standby mode when restarted until the
button is pressed after the REPO is activated, the UPS remains
button is pressed again.
The REPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be separated from any hazardous voltage circuits by reinforced insulation.
To ensure the UPS stops supplying power to the load during any mode of operation, the input power must be disconnected from the UPS when the emergency power-off function is activated.
NOTE The REPO function activates when the REPO contacts open.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
W A R N I N G
C A U T I O N
21
Page 28
Additional UPS Features
Use the following procedure to install the REPO switch:
1. Verify that the UPS is off and unplugged or removed from utility power.
2. Unscrew and remove the REPO connector from the mating plug on the UPS rear panel.
3. Remove the short wire from the REPO connector.
4. Connect isolated, normallyclosed, dry contacts (rated at
60 Vdc maximum, 30 Vac RMS maximum, and 20 mA maximum) across the REPO device to Pin 1 and Pin 2 (see Figure 6). Use stranded, nonshielded wiring, size 1822 AWG
2
(0.75 mm
0 mm2). See Figure 7.
Pin 1 Pin 2Pin 1 Pin 2
22
Figure 6. REPO Connector
REPO Connector
Powerware 9120 UPS
Normally Closed, Isolated Switch
Figure 7. REPO Wiring Diagram
5. Reconnect the REPO connector to the REPO port on the UPS rear panel.
6. Verify that the externally-connected REPO switch is closed to enable power to the UPS output connections.
7. Connect the UPS to a power source.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 29
8. To start the UPS, press and hold the button until you hear the UPS beep (approximately one second).
9. Open the external REPO switch to test the REPO function.
10. Close the external REPO switch and restart the UPS.
Network Transient Protector
The Network Transient Protector, shown in Figure 8 and Figure 9, is located on the rear panel and has jacks labeled IN and OUT. This feature accommodates a single RJ45 (10BaseT) network connector.
Low voltage models can also accommodate an RJ11 telephone connector that provides protection for modems, fax machines, or other telecommunications equipment. As with most modem equipment, it is not advisable to use this jack in digital PBX (Private Branch Exchange) environments.
Connect the input connector of the equipment you are protecting to the jack labeled IN. Connect the output connector to the jack labeled OUT.
Additional UPS Features
OUT
Figure 8. Network Transient Protector (120V and 208V Models)
IN
Figure 9. Network Transient Protector (230V Models)
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
OUT
NETWORK TRANSIENT PROTECTOR
IN
NETWORK TRANSIENT PROTECTOR
IN
OUT
IN
OUT
23
Page 30
Additional UPS Features
Load Segments
Load segments are sets of receptacles that can be controlled by power management software (such as Powerware's Software Suite CD), providing an orderly shutdown and startup of your equipment. For example, during a power outage, you can keep key pieces of equipment running while you turn off other equipment. This feature allows you to save battery power. See your power management software manual for details.
The individual load segments can also be turned on and off through the front panel (see Configuration Mode" on page 17).
Figure 10 and Figure 11 show the load segments for all plug/receptacle models.
Load
Segment 1
2000 VA, 120V
24
700 VA, 120V
Load Segment 2
Load Segment 1
Load Segment 2
Load
Segment 1
1000 VA, 120V
Segment 1
Load Segment 2
Load Segment 2
Load Segment 1
3000 VA, 120V
Figure 10. 120V and 208V Model Load Segments
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Load
3000 VA, 208V
Load Segment 2
1500 VA, 120V
Load Segment 1
Load Segment 2
Page 31
Load
Segment 1
7001000 VA, 230V
Load Segment 2
Additional UPS Features
Load Segment 1
Load Segment 2
1500 VA, 230V
2000 VA, 230V
Load Segment 1
Load Segment 2
Figure 11. 230V Model Load Segments
Load Segment 1
Load Segment 2
3000 VA, 230V
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
25
Page 32
Additional UPS Features
Communication Port
To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable.
When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.
The cable pins are identified in Figure 12 and the pin functions are described in Table 2.
Table 2. Communication Port Pin Assignment
Pin Number
3
245
1
9
87
6
Figure 12. Communication Port
Signal Name Function Direction from
the Multi-Port Module
26
1 Low Batt Low Battery relay contact Out
2 RxD Transmit to external device Out
3
4 No Connection
5 GND Signal Ground
6 No Connection
7 No Connection
8 AC Fail AC Fail relay contact Out
9 Power Source +V (8 to 24 volts DC power) Out
TxD Receive from external device In
RS-232 low level signal for >0.4 seconds
Conditional Power Off: In absence of AC power, output is turned off until normal AC power returns
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
In
Page 33
USB Port
The UPS is also equipped with a USB communication port. Either the DB-9 communication port or the USB port may be used to monitor the UPS; however, they cannot operate simultaneously. Refer to the power management software instructions for using the USB port.
Communication Slot
The Powerware 9120 UPS has a communication slot that allows quick installation of the optional SNMP/Web adapter or other similar communication interfaces. These interface adapters extend the capabilities of the Powerware 9120 system to provide compatibility with network and remote monitoring/management systems.
SNMP/Web Adapter
This adapter provides the Powerware 9120 system with its own ethernet network connection, allowing it to be remotely monitored and controlled via industry-standard internet browsers. The HTML interface enables UPS monitoring and management from anywhere on the internet or within your intranet. In addition, third-party Simple Network Management Protocol (SNMP) software packages may also be used to communicate remotely with the Powerware 9120 system.
Additional UPS Features
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
27
Page 34
Additional UPS Features
Relay Card
This interface provides true relay contact output to peripheral devices. Outputs are user-selectable as normally open or normally closed.
Table 3. Relay Card (AS/400) Pin Assignment
Pin Number Signal Name Definition Direction
1 UPS Fail Relay contact; normally open, closes
when UPS fails.
2 Summary Alarm Relay contact; normally open, closes
when UPS fails, bypass is activated, utility power failure, or low battery status.
3 Remote Shutdown (-) Ground
4 Remote Shutdown (+) Activated by +5 to +12V for one second In
5 Common Relay common connection for pins 1, 2,
6, 7, 8, and 9.
6 Bypass Relay contact; normally open, closes
when the UPS is in Bypass mode.
7 Low Batt Low Battery relay contact; normally
open, closes when the battery is almost discharged.
8 Battery Mode
Remote Shutdown
9 AC Fail AC Fail relay contact; normally open,
Activated by +5 to +12V for one second. In
closes when utility power fails.
Out
Out
Out
Out
Out
28
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 35
C H A P T E R 6
UPS MAINTENANCE
This section explains how to:
Care for the UPS and batteriesReplace the batteriesRecycle used batteries
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS clean and dustfree. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of 25°C (77°F).
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the battery every 10 months by connecting the UPS to a power source. The batteries charge to 90% capacity in approximately 4 hours. However, it is recommended that the batteries charge for 6 to 24 hours after long-term storage.
Replacing Batteries
With the hotswappable battery feature, UPS batteries can be replaced easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the battery, press and hold the seconds). Then unplug or remove utility power from the UPS.
Consider all warnings, cautions, and notes before replacing batteries.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
button until the long beep ceases (approximately five
29
Page 36
UPS Maintenance
W A R N I N G
Batteries can present a risk of electrical shock or burn from high short circuit
current. The following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries.
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or
connectors. Attempting to alter wiring can cause injury.
Replace batteries with the same number and type of batteries as originally
installed in the UPS.
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
How to Replace External Batteries
Use the following steps to replace external batteries:
1. Unplug the EBM cable from the UPS and the old battery.
2. Remove the old battery. See Recycling the Used Battery" on
page 32 for proper disposal.
3. Plug the EBM cable into the battery connector on the new battery.
4. Plug the other end of the EBM cable into the UPS as shown in Figure 13.
30
EBM Battery Connectors
UPS Battery
Connector
Figure 13. External Battery Connections (120V Model Shown)
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
EBM Cable
Page 37
UPS Maintenance
How to Replace Internal Batteries
Use the following steps to replace the internal batteries:
1. Using caution not to put stress on the LCD display cable, pull the top of the front panel forward. Release the spring latches at the bottom of the front panel and remove it, placing it to the side of the UPS.
2. Unscrew the metal battery cover (1000 VA model shown).
3. Pull the battery out onto a flat, stable surface (1000 VA model
shown).
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
31
Page 38
UPS Maintenance
4. Remove the old battery. See Recycling the Used Battery" for proper disposal.
5. Install the new battery.
6. Reinstall the metal battery cover and front panel.
Recycling the Used Battery
Contact your local recycling or hazardous waste center for information on proper disposal of the used battery.
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper
disposal of batteries is required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, leadacid batteries and must be disposed of properly. For more information, contact your local recycling or hazardous waste center.
W A R N I N G
C A U T I O N
32
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 39
C H A P T E R 7
SPECIFICATIONS
This section provides the following specifications for the Powerware 9120 models:
Electrical input and outputEnvironmental and safetyWeights and dimensionsBattery
Table 4. Electrical Input
120V Models 208V Models 230V Models
Nominal Voltage
Voltage Range 80144V for
Nominal Frequency
Noise Filtering MOVs and line filter for normal and common mode noise
Connections PW9120 700: 6-ft, 5-15P
120V default;
100, 110, 120, 127V selectable
100, 110, 120, 127V nominal
power cord
PW9120 1000: 6-ft, 5-15P
power cord
PW9120 1500: 6-ft, 5-15P
power cord
PW9120 2000: 6-ft, 5-20P
power cord
PW9120 3000: 6-ft, L5-30P
power cord
PW9120 3000H: Hardwired
200, 208, 220, 230 240V selectable
208V default;
160276V for
200, 208, 220, 230, 240V nominal
50/60 Hz, ±5% user-selectable
PW9120 3000B: 6-ft, L6-20P
power cord
208, 220, 230 240V selectable
208, 220, 230, 240V nominal
PW9120 700i: 10A, IEC-C14
PW9120 1000i: 10A, IEC-C14
PW9120 1500i: 10A, IEC-C14
PW9120 2000i: 10A, IEC-C14
PW9120 3000i: 16A, IEC-C20
230V default;
160276V for
input connector
input connector
input connector
input connector
input connector
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
33
Page 40
Specifications
Table 5. Electrical Output
120V Models 208V Models 230V Models
Power Levels (rated at nominal inputs)
Regulation (Normal mode)
Regulation (Battery mode)
Voltage Waveform
Output Connections
PW9120 700: 700 VA, 490W PW9120 1000: 1000 VA, 700W PW9120 1500: 1500 VA, 1050W PW9120 2000: 2000 VA, 1400W PW9120 3000: 3000 VA, 2100W
PW9120 3000H: 3000 VA, 2100W
Normal mode: Sine wave; <5% THD with full PFC and nonlinear load
PW9120 700: (4) 5-15R
PW9120 1000: (4) 5-15R,
(2) 5-20R
PW9120 1500: (4) 5-15R,
(2) 5-20R PW9120 2000: (6) 5-20R PW9120 3000: (4) 5-15R,
(2) 5-20R,
(1) L5-30R
PW9120 3000H: Hardwired
PW9120 3000B: 3000 VA, 2100W PW9120 700i: 700 VA, 490W
PW9120 1000i: 1000 VA, 700W PW9120 1500i: 1500 VA, 1050W PW9120 2000i: 2000 VA, 1400W PW9120 3000i: 3000 VA, 2100W
Nominal output voltage ±2%
Nominal output voltage ±3%
PW9120 3000B: (2) L6-15R,
(1) L6-20R, (1) L6-30R
PW9120 700i: (4) IEC-C13 PW9120 1000i: (4) IEC-C13 PW9120 1500i: (4) IEC-C13 PW9120 2000i: (4) IEC-C13,
(1) IEC-C19
PW9120 3000i: (4) IEC-C13,
(1) IEC-C19
34
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 41
Specifications
y
Table 6. Environmental and Safety
120V Models 208V Models 230V Models
Operating Temperature
Storage Temperature
Relative Humidity 095% noncondensing
Operating Altitude
Audible Noise 7001500 VA: Less than 48 dBA Normal mode, typical load
Surge Suppression
Safety Conformance
Agency Markings UL, cUL UL, cUL, CE, C-Tick
EMC FCC Part 15, ICES-003, VCCI EN 50091-2, FCC Part 15, ICES-003
0°C to 40°C (32°F to 104°F) 01500 meters above sea level
0°C to 35°C (32°F to 95°F) 15003000 meters above sea level
Optimal battery performance: 25°C (77°F)
-15°C to 50°C (-5°F to 131°F)
Up to 3,000 meters (10,000 ft) above sea level
20003000 VA: Less than 54 dBA Normal mode, typical load
ANSI C62.41 Category B (formerly IEEE 587)
UL 1778, UL 497A;
CAN/CSA C22.2, No. 107.1
UL 1778 (7002000 Models),
UL 497A (data line only);
CAN/CSA C22.2, No. 107.1
EN 50091-1-1 and IEC 60950;
Table 7. Weights and Dimensions
UPS Models
120/208V Models 230V Models
Dimensions (WxDxH)
Weight PW9120 700: 29 lb (13.2 kg)
PW9120 1000: 35.5 lb (16.1 kg) PW9120 1500: 46.5 lb (21.1 kg) PW9120 2000: 82 lb (37.2 kg)
PW9120 3000: 89 lb (40.5 kg) PW9120 3000H: 89 lb (40.5 kg) PW9120 3000B: 85 lb (38.5 kg)
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
7001000 VA: 6.2 x 16.2 x 9.6
(15.8 x 41.2 x 24.3 cm)
1500 VA: 6.7 x 17.5 x 10.8
(17.0 x 44.4 x 27.5 cm)
20003000 VA: 8.6 x 18.6 x 14.2
(21.7 x 47.2 x 36.1 cm)
PW9120 700i: 28 lb (12.6 kg) PW9120 1000i: 34 lb (15.3 kg) PW9120 1500i: 44 lb (19.8 kg) PW9120 2000i: 81.6 lb (37 kg) PW9120 3000i: 85 lb (38.5 kg)
Extended Battery Module Models
7001000 VA: 6.2 x 16.2 x 9.6
(15.8 x 41.2 x 24.3 cm)
1500 VA: 6.7 x 17.5 x 10.8
(17.0 x 44.4 x 27.5 cm)
20003000 VA: 8.6 x 18.6 x 14.2
(21.7 x 47.2 x 36.1 cm)
PW9120 BAT-700: 31 lb (14 kg) PW9120 BAT-1000: 44 lb (20 kg) PW9120 BAT-1500: 57 lb (26 kg) PW9120 BAT-3000: 110 lb (50 kg)
35
Page 42
Specifications
Table 8. Battery
Configuration 700 VA: (2) 12V, 7 Ah internal batteries; 24 Vdc
1000 VA: (3) 12V, 7 Ah internal batteries; 36 Vdc 1500 VA: (4) 12V, 7 Ah internal batteries; 48 Vdc 20003000 VA: (8) 12V, 7 Ah internal batteries; 96 Vdc
EBM Configuration
Type Sealed, maintenancefree, valveregulated, leadacid
Charging Approximately 4 hours to 90% usable capacity at nominal line voltage after full load discharge
PW9120 BAT-700: (4) 12V, 27 Ah; 24 Vdc PW9120 BAT-1000: (6) 12V, 27 Ah; 36 Vdc PW9120 BAT-1500: (8) 12V, 27 Ah; 48 Vdc PW9120 BAT-3000: (16) 12V, 27 Ah; 96 Vdc
Table 9. Battery Run Times (in Minutes)
Number of Batteries
700 VA 1000 VA 1500 VA 2000 VA 3000 VA
UPS Internal Batteries 7/18 7/18 7/18 12/34 6/15
1 EBM 34/70 36/80 29/67 49/107 30/70
2 EBMs 64/140 66/155 56/130 93/195 58/128
3 EBMs 141/310 87/191
4 EBMs 192/403 120/264
5 EBMs 240/504 148/325
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Run Times at Full/Half Load by UPS VA Ratings
36
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 43
C H A P T E R 8
TROUBLESHOOTING
This section explains:
UPS alarms and conditionsHow to silence an alarmService and support
Audible Alarms and UPS Conditions
The UPS has an audible alarm feature to alert you of potential power problems. When the alarm is activated, the UPS beeps in different intervals according to a particular condition. Use Table 10 to determine and resolve the UPS alarms and conditions.
Silencing an Audible Alarm
There are two ways to silence the alarm for an existing fault:
Press one of the front panel control buttons (Turn the Alarm Silence option on through the front panel (see
Configuration Mode" on page 17).
If UPS status changes, the alarm beeps, overriding the previous alarm silencing. The alarm does not silence if there is a low battery condition.
, , or ).
Table 10. Troubleshooting
LCD Message or Condition
UPS does not turn on.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Possible Cause Action
The UPS is not correctly connected to the power source.
The wall outlet is faulty. Have a qualified electrician test and repair the outlet.
The REPO connector is missing or open.
A circuit breaker or an input fuse on the rear panel is open.
Check connections to the power source.
Reconnect or close the REPO switch (see page 22). Restart the UPS.
Push the circuit breaker button or replace the fuse. Restart the UPS.
37
Page 44
Troubleshooting
Condition
ActionPossible CauseLCD Message or
LCD panel is blank.
UPS does not provide the expected backup time.
The UPS operates normally, but some or all of the protected equipment is not on.
On-Battery 1 beep every 5 seconds.
Low Battery 2 beeps every 5 seconds.
The UPS is in Standby mode. Press and hold the button until your hear the UPS beep
(approximately one second).
The LCD has failed. Contact your service representative.
The battery may be fully discharged because of:
long-term storagefrequent power outagesend of battery life
The equipment is not connected to the UPS.
The output circuit breaker (if applicable) is open.
One of the load segments has been turned off.
Utility power failure. The UPS is powering your equipment with its internal
The battery is running low. 2 minutes or less of battery power remains (depending on
Connect the UPS to a power source for 24 hours to charge the battery. Perform a battery test (see Configuration Mode" one page 17). If the battery test fails, see Replacing Batteries" on page 29 to replace the battery. During extended power outages, save your work and turn off your equipment to conserve battery power.
Verify that the equipment is properly connected to the UPS.
Reset the circuit breaker (push the circuit breaker button or reset the switch).
Reactivate the segment with the power management software or through the front panel (see Configuration Mode" one page 17).
battery. If this is an extended power outage, save your work and turn off your equipment to conserve battery power.
load and battery charge). Prepare for a shutdown. Save your work and turn off your
equipment. The alarm cannot be silenced.
Replace Battery 3 beeps every 5 seconds.
Low Charge 3 beeps every 5 minutes.
Output Overload 2 beeps per second.
38
The battery needs replacing. See Replacing Batteries" on page 29 to replace the battery.
The battery voltage is low. The UPS is charging the batteries and may not deliver full
run time. The alarm continues until at least two minutes of run time is available.
Power requirements exceed UPS capacity (110125% for 1 minute or 126150% for 10 seconds) or the load is defective. The UPS switches to Bypass mode.
Remove some of the equipment from the UPS. The UPS automatically switches back to Normal mode when the capacity returns to an acceptable level. You may need to obtain a larger capacity UPS.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 45
Condition
Troubleshooting
ActionPossible CauseLCD Message or
Battery Overload 2 beeps per second.
Site Fault 1 beep per second.
Battery Test The UPS is performing a battery
Over-Temperature Constant beep.
Over-Charge Constant beep.
Charger Failure Charger has failed. Save your work and turn off your equipment. Turn off the
The UPS is on battery, and the power requirements exceed UPS capacity (130% for 10 seconds or >130% for
1.5 seconds) or the load is defective.
Ground wire connection does not exist or the line and neutral wires are reversed in the wall outlet.
test.
UPS internal temperature is too high.
Batteries are over-charged. Save your work and turn off your equipment. Turn off the
Shutdown is imminent (30 seconds). Save your work and turn off your equipment. Turn off and unplug or remove utility power from the UPS. Remove some of the equipment from the UPS. Restart the UPS. You may need to obtain a larger capacity UPS.
Have a qualified electrician correct the wiring. To disable this alarm, see Configuration Mode" on page 17.
None. The UPS returns to Normal mode when it completes a successful battery test.
Shutdown is imminent. Save your work and turn off your equipment. Turn off the UPS. Clear vents and remove any heat sources. Ensure the airflow around the UPS is not restricted. Wait at least 5 minutes and restart the UPS. If the condition persists, contact your service representative.
UPS. Contact your service representative.
UPS. Contact your service representative.
Output Short Constant beep.
High Output Voltage Constant beep.
Low Output Voltage Constant beep.
High DC Bus 2 beeps per second.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Output short circuit. Save your work and turn off your equipment. Turn off the
High output voltage. Save your work and turn off your equipment. Turn off the
Low output voltage. Save your work and turn off your equipment. Turn off the
High internal DC bus voltage. Save your work and turn off your equipment. Turn off the
UPS. Contact your service representative.
UPS. Contact your service representative.
UPS. Contact your service representative.
UPS. Contact your service representative.
39
Page 46
Troubleshooting
Service and Support
If you have any questions or problems with the UPS, call your Local
Distributor
and ask for a UPS technical representative.
In the United States 1-800-365-4892 In Canada 1-800-461-9166 All other countries 1-919-870-3149
Please have the following information ready when you call the Help Desk:
Model numberSerial numberVersion number (if available)Date of failure or problemSymptoms of failure or problemCustomer return address and contact information
If repair is required, you will be given a Returned Material Authorization (RMA) Number. This number must appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging or request packaging from the Help Desk or distributor. Units damaged in shipment as a result of improper packaging are not covered under warranty. A replacement or repair unit will be shipped, freight prepaid for all warrantied units.
or the Help Desk at one of the following telephone numbers
40
NOTE For critical applications, immediate replacement may be available. Call the
Help Desk for the dealer or distributor nearest you.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Page 47
Page 48
42
*05147426A*
05147426 A
42
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy
Loading...