Some configurations are classified under EN50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these
configurations, the following applies:
WARNING Thisisa Class A-UPS Product. In a domesticenvironment, this product may cause radio interference, in which
case, the user may be required to take additionalmeasures.
Powerware is a registered trademark and Advanced Battery Management(ABM) is a trademark of Powerware Corporation.
.
Copyright 1999 Powerware Corporation, Raleigh, NC. All rights reserved. Nopart of this document may be repr oduced
in any way without the express written approval of Powerware Corporation.
Page 3
Class A Statement forFCC andICES
(2000 VA - 3000 VA)
For Users in the United StatesOnly
NOTE Thisequipment has been tested and foundtocomply with the limitsforaClassAdigital device pursuant toPart15
of FCC Rules. These limits are designed to providereasonable protection against harmfulinterference when this
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energyand,ifnot installed and used in accordance with the instruction manual, may cause harmfulinterference to radio
communications. Operationofthis equipment in a residential area is likely to causeharmful interference,inwhich case the
user willberequired to correct the interference at his/her own expense.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to
operate theequipment.
For Users in Canada
This ClassAInterference CausingEquipment meets all requirements of the CanadianInterference Causing Equipment
Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
Self-Certified ClassB Statementfor FCC and ICES
(1000 VA - 1500 VA)
For Users in the United StatesOnly
THIS DEVICE COMPLIES WITH PART15 OF THE FCC RULES. OPERA TIO NIS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
NOTE Thisequipment has been tested and foundtocomply with the limitsfor a ClassBdevicepursuant to Part 15of
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is
operated ina residential environment. This equipment generates, uses, and can radiate radiofrequency energy and, if not
installed and used in accordance with theinstructionmanual, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmfulinterference to radioortelevision reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correctthe interference by oneormore of the followingmeasures:
:
Reorientor relocate the receiving antenna.
:
Increasethe separation between theequipment and the receiver.
:
Connectequipment into an outlet on a circuit different from that towhich the receiver is connected.
:
Consultthe dealer or an experienced radio/TVtechnician for help.
:
Ensure that mountingscrews, connector attachment screws, and all ground wires aresecured and tight.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to
operate theequipment.
For Users in Canada
This ClassB Interference CausingEquipment meets all requirements of the CanadianInterference Causing Equipment
Regulations ICES-003.
Cet appareil numérique de la classe B respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
Page 4
Special Symbols
The following are examplesof symbols used onthe UPS toalert you toimportantinformation:
CAUTION
RiskofElectricShock
DoNotOpenCover
CAUTION Toreduce the riskof electric shock,
Donotremove cover (orback)
Nouser-serviceablepartsinside
Refer servicing to the factory
RISKOFELECTRIC SHOCK - Indicates that a risk ofelectric shock ispresentand the
associated warning should be observed.
CAUTION: REFER TO OPERATOR’SMANUAL - Refer to your operator’s manual for
additional information,such as important operating andmaintenance
instructions.
This symbol indicates that youshouldnot discard the UPS or the UPS batteries
in the trash. TheUPS may contain sealed, lead-acid batteries. Batteries must be
recycled.
Page 5
TABLE OF CONTENTS
1 Powerware 5119Rack Mount –One ofthe Best!1.......................
The Powerware95119 Rack Mount uninterruptible powersystem (UPS)
protects your sensitive electronic equipmentfrom basic power problems
such as power failures, power sags,power surges, brownouts, and line
noise.
Poweroutagescan occur when youleastexpect it andpower quality
can be erratic. These powerproblemshavethe potential to corrupt
criticaldata, destroyunsaved work sessions, anddamage hardware—
causing hours oflost productivity and expensive repairs.
Withthe Powerware 5119 Rack Mount,you can safely eliminate the
effectsof power disturbances and guard the integrity of your
equipment. The Powerware 5119 Rack Mount’s flexibility tohandle an
arrayof network devices makesit the perfect choiceto protect your
LANs, servers, and workstations.
Becausean integral part ofpowerprotectionispower management
software,the Powerware 5119 Rack Mountcomes fully equipped with a
communication port, serial cable, anda CDcontaining both LanSafe III
for networked systems and FailSafe III for standalonesystems.
Providingoutstanding performance and reliability, the Powerware 5119
Rack Mount’s unique benefits include thefollowing:
:
Compact design conservesvaluable space for other rackequipment
such as hubs, routers, disk arrays, and servers.
:
Advanced Battery Management (ABMZ) doubles battery service life,
optimizesrecharge time, andprovides a warningup to 60days before
the end of useful battery life.
:
Buck and Double Boost regulationensures consistent voltage to your
load by correctingvoltage fluctuations without using battery power.
:
Hot-swappable batteries simplify maintenance by allowing you to
replacebatteriessafelywithoutpowering downthe critical load.
:
Start-on-battery compatibilityallowsyouto power upthe UPS even
if utilitypower is not available.
:
Optionalpower communication cards provide enhanced
communication capabilities for increased power protection and
longerbatterybackup times.
:
The Powerware 5119Rack Mount is backed by worldwide agency
approvals.
If any equipment has beendamaged during shipment,keep the
shipping cartons andpackingmaterialsfor the carrier or placeof
purchase andfile a claimfor shippingdamage. If youdiscoverdamage
after acceptance, file a claimfor concealed damage.
To file aclaim for shipping damage orconcealeddamage: 1) File with
the carrier within15 days ofreceiptof the equipment; 2) Senda copyof
the damage claim within 15 days to your service representative.
Safety Precautions
Read thefollowing before youinstallthe UPS.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.Thismanual contains important instructionsthatyou
shouldfollowduringinstallation and maintenance of the UPS and batteries. Please
read allinstructionsbefore operatingtheequipmentandsavethismanual for future
reference.
ThisUPScontainsits own energy source (batteries).Theoutputreceptaclesmay
carrylivevoltage even when theUPSisnot connected to anACsupply.
:
Donot removeor unplug the input cord when the UPS is turned on. This removes
the safetyground from the UPS and the equipment connected to the UPS.
:
To reduce therisk of fire orelectric shock,installthis UPS in a temperature and
humiditycontrolled, indoor environment,freeof conductivecontaminants.
Ambienttemperaturemustnotexceed40C(104F).Donotoperatenear water
or excessive humidity (95% max).
:
The sumof earth leakage current from the load connected to the UPS must not
exceed1.5mA.
Mounting the UPSin a Rack
The UPS fits in a 19-inch rack. Follow the stepsbelowto install the UPS
in the rack.
The UPSisheavy(132lb/60kg).A minimum of two people are required to lift the
UPSintothe rack.
WARNING
CAUTION
NOTE Disconnect all cablesfrom the UPS before continuing.Removeallself-
1. Place the UPS on a flat, stablesurface with the front of the UPS
facing toward you.
2. If the mounting brackets are notalreadyinstalled, position the
mounting bracket overthe mountingholesonone side ofthe
unitand securewith the provided screws (see Figure 2).
If the mounting handles are not already installed, position the
mounting handle over thebracket and secure with the
provided screws (see Figure 3).
3. Repeat Step 2 for the other sideof the UPS.
4. Using at least two people, lift the UPS and slide it into therack.
5. Secure the UPS by screwing the mounting angles to the rack
face (screws not provided).The UPS is nowsecuredin the rack.
The following steps explain how to install the UPS. Figu re 5 on page 7
shows a typical installation only. See “UPS Rear Panels” on page 8 for
the rear panel ofeach model.
NOTE Donot makeunauthorizedchangestothe UPS;otherwise,damagemayoccur
to your equipmentand voidyourwarranty.
1. If youare installing power management software, connect your
computer to the UPS communication port using the supplied
communication cable.
Some power management software has a Load Segment feature
that allows you to control UPS output receptacles. If youplan
to use this feature, read the appropriate sections ofyourpower
management software manual before you install the UPS.
2. For 230V models and 1000-1500 VA/120Vmodels, plug the
UPSpower cord into the input connector onthe UPS rear
panel.
Customer-supplied power cords must correctly rated forthe
UPS(see “Specifications” onpage 29). Youcan also use the
power cord from the largest load if it iscorrectlyrated.
3. Plug the UPS power cord into a wall outlet or power source.
The UPS conducts a self-test and enters Standby mode. If a red
Site Wiring Fault or Battery Service indicator stays on, see
Table 11 on page 33.
Site Wiring Fault Indicator
Battery Service Indicator
Figure 4. Fault Indicators
NOTE Lowvoltagemodelsmaynotrecognize 50-Hz outlets. If the UPS does not
After the UPS isconnected to a powersource, it conducts a self-testand
enters Standby mode. To turnon the UPS, press the On
front panel(showninFigure 14). ThePowerOn indicator illuminates
indicating that poweris available from the rear receptacles.
Starting the UPS onBattery
To turnon the UPS without usin gutility power, press and holdthe
On buttonfor three seconds.Whenthe UPS starts on battery, it does
not conduct a self-test toconservebattery power.
buttononthe
Turning the UPS Off
To turn off the UPS, press the Offbuttonon the front panel and then
unplug the UPS from the power source. If you do not unplug the UPS, it
remainsin Standby mode.
Standby Mode
When the UPS isturned off and plugged into a wall outlet or other
power source, theUPS is in Standby mode.The battery recharges when
necessaryandthe Power Onindicator isoff,indicating that poweris not
available from the rear receptacles.
The UPS front panel LEDs indicate how theUPSis operating and also
alert you of potential powerproblems.Figure 14 shows the UPS front
panel indicators and controls.
Battery Charge LEDs
AC Input LEDs
Site Wiring Fault Indicator
Battery Service Indicator
T e st/AlarmResetButton
The following sections describe the LED functions during normal
operation. Ifany LEDs are red, seeTable 11 on page 33 to identify and
correct the problem.
NOTE The front panel is rotated clockwise 90degreesonsomemodels.
The AC Input LEDs show information about the utility power coming
intotheUPS(seeFigure15).
Normal Utility Input (Buck and Single Boost)
Double Boost is on
Figure 15. AC InputLEDs (Normal Mode)
The second LED indicates that the UPSis operatingnormally from
utility power. The UPS is providing consistent voltage with the Buck
and SingleBoost feature.
The third LED indicates that the UPS is using the Double Boost feature
to automaticallycorrect voltage fluctuations.
If any ACInputLEDs are red, see page 34 formore information.
Battery ChargeLEDs
The Battery ChargeLEDsshow information about theUPS batteries(see
Figure 16).
66-90%33-66%>90%
Figure 16. Battery Charge LEDs (NormalMode)
Each LED represents theapproximate percentage ofbatterycharge.
Whenthe battery is fully charged (greaterthan90%),the top three
LEDs illuminate. If the battery capacity is between 66% and 90%, the
second and third LED illuminate. The third LED illuminates if the
battery c harge isbetween 33%and 66%.
If any Battery Charge LEDs are red, seepages 34 and35 for more
information.
The front panel displays the total load current or watts plugged into the
UPS (see Figure 17).
33-66%5-33%66-100%
Figure 17. Load LevelLEDs (Normal Mode)
Each LED represents 1/3of a fullload rating.Whenthe UPS is
approximately fullyloaded (66-100%), all three LEDs illuminate.If the
load is 33-66% of UPS capacity, the third and fourth LED illuminate.
The last LED illuminates ifthe load isbetween 5%and 33%.
If any Load LevelLEDsare red, see page35 for more information.
Initiating the Self-Test
Press and hold thebutton forthreeseconds toinitiate the self-test.
During the test, individual LEDs illuminate as various parts of the UPS
arechecked. If theUPS finds a problem, an LEDindicateswhere the
problem is.For more information, see “Troubleshooting” on page 33.
NOTE AllthreeBatteryChargeLEDsshould be lit and theUPSmustnotbein
Batterymodeto perform the self-test.
When the utility power consistently fluctuates, the UPS repeatedly
corrects theinputvoltageby switchingto battery powerwhenthe
nominal input range is:
:
Higher than +20%of 120V or 230V nominal
:
Lower than -30%of 120Vor 230Vnominal
:
Higher than +20%and lower than -30% of120V or230V nominal
You can configure the UPS to more closely match the nominal input
voltage by selecting a different input voltage or extending the input
voltage range. See Table 1 onpage 19 fora list of available options.
Other Settings
You can change theUPS default configurations for alarms andshutdown
parameters, including: timingfor the low battery alarm,the timedelay
for anunconditional shutdown, alarms for loss ofutility power orsite
fault, and controlling loads that use less than5% of the current when
the UPS ison battery. See Table 1 onpage 19 for alist of available
options.
Configuration Mode
When theUPS is in Configuration mode, the LEDs represent the
configuration options. The control buttons (On
are used to modify theUPS c onfiguration. Figure 18 showsthe LEDs
and Table 1 explains the corresponding options.
Shutdown DelayON (default)5-second delay beforeunconditional shutdown after theUPS receives a signal
OFF180-second delay beforeunconditional shutdown after the UPS receives a signal
AC Input FailureON (default)Alarm sounds when there is an AC input failure.
OFFAlarm DOES NOT sound when there is an AC input failure.
Sleep ModeON (default)When the UPS is on battery and the load isdrawing less than 5% of thecurrent,
OFFSelect this option if you want a load less than5% ofthecurrenttobeprotected
100/208V Nominal
Input Voltage
ON*Selecting this option changes the nominal input voltage on low voltage models
ExplanationPowerOn
from a computer via the communication port.
from a computer via the communication port. When this LED is not enabled, the
user canalsocreateanewdelaytimebyreconfiguringthecommunication port.
See“Communication Port Configurations” on page 25 for more information.
the UPS shuts down the load. This feature conserves battery power.
by batterypower .
to 100V and to 208V on high voltage models.
*This is the default forfactory-configured100V or 208V models (see the rating
label on theUPS rear panel).
OFF (default)100/208V is disabled; one oftheotherinputvoltageoptionsisselected.
100/208V Extended
Voltage Mode
Reset DefaultsON (default)All factory-set defaults are active.
ONSelect this option to extend the input voltage within-25% to +25% of 100V or
208V nominal input voltage before switching to battery (available on units that
were specifically ordered with this option).
OFF (default)The UPS acceptsaninput voltagewithin-20% to +20% of 100V or 208V
nominal input voltage before switching to battery.
OFFOne or more factory-set defaults have been changed.
Forthe best preventive maintenance,keep the area around theUPS
clean and dust-free.If the atmosphere is verydusty, cleanthe outside of
the system with a vacuum cleaner.
Forfullbattery life, keep theUPSat anambienttemperature of
25°C (77°F).
Storing theUPS andBatteries
If you store the UPSfor a long period, recharge the battery every
12 months by plugging the UPS into a power outlet. The UPS charges to
90% in approximately4 hours. However, it is recommendedthat the
UPS charge for 24 hours after long storage.
When to Replace Batteries
When the Battery Service indicator illuminates, the batteries may need
replacing (see Figure 14on page 14).Conduct a self-test by pressing the
button. If the indicator stays on, contact your service representative
The hot-swappablebattery featureallows you to replace theUPS
batteries easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the battery: 1) Press the
Off
internal processor shuts down before you disconnect the battery.
:
:
The UPSand batteriesare heavy.You must support the front of theunitwhile
replacingthebatteries.
button and then unplug the UPS; 2) Wait 60 seconds while the
WARNING
Batteriescanpresentariskofelectrical shockor burn from high short circuit
current.Thefollowingprecautions should be observed: 1) Removewatches,rings,
or other metal objects;2)Usetoolswith insulated handles;3)Donotlaytoolsor
metalpartsontop of batteries.
ELECTRICENERGYHAZARD.Donotattempt to alter any battery wiringor
connectors.Attempting to alter wiring can cause injury.
CAUTION
22
NOTE Whenthe UPS isonline,allthreeBatteryChargeLEDsshould be lit before
hot-swappingthebatteries.DONOT DISCONNECT the batteries whiletheUPSisin
Batterymode.
Figure 19 shows howto replace the UPS batteries.Considerall
warnings, cautions,and notes before replacing batteries.
Disconnectthe battery
cablesandremove the
batterytray.Installthenew
batterytray andconnect
the battery cables.
1000-1500 VA Models
2000-3000 VA Models
4
Replacethefaceplate.
Figure 19. Replacing Batteries
Testing New Batteries
Press and hold thebutton forthreeseconds toinitiate a self-test.
After the test isfinished,the red Battery Service indicator should turn
off a nd the Battery Charge LEDs should show a charge. If the Battery
Serviceindicator stayson,check the battery connections.See the
troubleshooting guide on page 33 or callyour service representative if
the problem persists.
Contactyourlocal recycling orhazardous wastecenter for information
on proper disposal of the usedbattery.
:
Donot disposeofbatteryor batteriesina fire.Batteriesmayexplode.Proper
disposalofbatteriesisrequired. Refer to your local codes for disposal
requirements.
:
Donot open or mutilate the battery or batteries. Releasedelectrolyteisharmful
to the skinand eyes.Itmaybetoxic.
Donot discardtheUPSorthe UPS batteriesinthe trash.Thisproductcontains
sealed,lead-acid batteries and must be disposed of properly.Formoreinformation,
contactyourlocalrecyclingor hazardous wastecenter.
How to install the RemoteEmergency Power-Off switch
:
Load segments
:
Optionmodules
Communication Port Configurations
To establishcommunication between theUPS and a computer, connect
your computer to the UPS communication port using the supplied
communication cable.
To prevent damagetoyourequipment,connect only a factory-suppliedcableora
cablebuilttofactoryspecifications(seeTable 2) to the communicationport.A
standardserialcablemaydamageyourcomputer.
Whenthe communication cableis installed,power management
software canexchangedata with theUPS.The softwarepolls the UPS
for de ta iled informationon the status of thepower environment. If a
power emergencyoccurs,thesoftware initiates thesavingof all data
and an orderly shutdown of the equipment.
CAUTION
Communication Indicator
Whenthe UPS receives a command from the computer to establish
communication, the Communicationindicator onthe UPS frontpanel
illuminates (see Figu re 14 onpage 14). Whendata is transferring, the
Communication indicatorflashes.
As shown in Table 2, Pins 1 and 2 operate intwo modes: BasicAlarms
mode and Serial Datamode. Basic Alarms mode hasAC fail alarm and
output shutdown. Serial Data mode is UPS Code II compliant.
The system always starts in Basic Alarmsmode.Whenserialdata is
received at Pin 1, the function ofPin1 and Pin 2 changesto Serial Data
mode.
If serial data hasnot been received before going to batterypower, serial
communication is disabled until AC input power returns.
6789
12345
Figure 20. Communication Port
Table 2.CommunicationPort Configuration
PinSignalTypeFunction
1
2
3Output: Open collector transistor ON, 50 mA, 40 Vdc ratingAC Input failure
4SignalCommonSignal Common
5Output: Open collector transistor ON, 50 mA, 40 Vdc ratingImpending low battery
6Input: RS-232 RTSPlug-and-play software enable trigger (activates
7Input: Relay contact or RS-232 levelRemote Emergency Power-Off: UPS total output can
8Output: 8 to 25 Vdc, 5W constant power (0.63A max. @ 8V)Auxiliary Control Power
9ChassisConnection to chassis
26
Basic Alarms Mode-Input: RS-232 level high (+12V) pulse
4 to5seconds
Serial Data Mode - Input: RS-232 dataRS-232 serial communication input. 1200 baud,
Basic Alarms Mode-Output: RS-232 level high (+12V)AC Input failure
Serial Data Mode - Output: RS-232 dataRS-232 serial communication output. 1200 baud,
Remote UPS off. In absence of AC power, output is
turned offuntilnormal AC power returns
8 bits,Noparity, 1 stop bit, 1 start bit
8 bits,Noparity, 1 stop bit, 1 start bit
when pin changes from +12V to -12V)
be keptoffwith low signal or closing relay contact
The UPS has a REPO connector that can be wired to a device for turning
the UPS off from a remote location. The following instructions explain
how to wire the REPO switch.
ConnecttheREPOport to dry isolatednormally-opencontacts rated at60Vdc
maximum,30 Vac RMS maximum, and 20 mA maximum.Failure to conform to these
guidelinesmaycreate dangerousconditions for the operator bydisabling the safety
insulationoftheequipment.
NOTE The REPOfunctionactivateswhenthedryisolated normally-open REPO
contactsclose.
1. Remove the REPO connector fromthe REPO port on the rear
panel of the UPS.
2. Connectdry isolated normally-open contacts across theREPO
device to pin1 and pin 2 (see Figure 21). Use stranded,
non-shieldedwiring,size #22through#18.
3. Reconnectthe REPO connector to the UPS.
Additional UPS Features
WARNING
Figure 21. REPO Connector
Load Segments
Load segmentsare sets ofreceptacles thatcan be turned onindividually
using powermanagementsoftware. Forexample,during a power
outage,youcan keep key pieces ofequipment running while you turn
off other equipment.Thisfeatureallowsyou to save batterypower. See
yourpower managementsoftwaremanualfor details.
Optionmoduleshelp your UPS communicate in a varietyof networking
environments and are installed inthe UPS option slot. See the manual
that accompanieseach module for more information, or contact your
salesrepresentative.
Thissectionprovides thefollowing specificationsfor the Powerware
5119 Ra c k Mountmodels:
:
Electrical input andoutput
:
W eights and dimensions
:
Environmental and safety
:
Indicatorsand controls
:
Battery
Table 3.ModelList
120V Models230V Models
UPS ModelsPW5119 1K RM
PW5119 1.5K RM
PW5119 2K RM
PW5119 2K RM20R
PW5119 3K RM
PW5119 3K RM20R
PW5119 1Ki RM
PW5119 1.5Ki RM
PW5119 2Ki RM
PW5119 2.4Ki RM
PW5119 3Ki RM
Table 4.Electrical Input
120V Models230V Models
NominalVoltage120V default; 100, 110, 120, 127V selectable230V default; 208, 220, 230, 240V selectable
VoltageRange-30% to +20% at full load for nominal voltage; -35% to +20% user-selectable, extendedrange
NominalFrequency60 Hz; 50/60if100V or 110V selected50/60 Hz
Noise FilteringMOVs and line filter for normal andcommon mode noise
A circuit breaker or an input
fuse ontherearpanelisopen.
The line cordisnotconnected.
The wall outlet is dead.Have a qualified electrician test and repair theoutlet.
The UPS may be unable to
recognize a100V, 50-Hz wall
outlet.
A battery fuse or circuit breaker
is open.
Input voltage in your areadiffers
from the UPS nominal.
Push thecircuit breakerbuttonorreplacethefuse(see“UPS
Rear Panels” on page 8).
Connect the line cord.
See “Specifications” on page 29 to verify that your UPS
accepts 100V nominal input.
Unplug the UPS. Start the UPS on battery andreconfigurethe
nominal input voltage for 100V (see ”Configuration Mode” on
page 17). Turn off the UPS for 30 seconds. Plug the UPS into
the outlet.
Contact your service representative.
Change the UPS input voltage to match your local voltage; see
“Configuration Mode” on page 17.
33
Page 40
Troubleshooting
ActionPossible CauseAlarmorCondition
The Low Battery Alarm
does not giveenough
warning.
AC input high
AC input low
Site Wiring Fault
Low Battery Charge
The batteries needchargingor
service.
The Low Battery Alarm is not
set appropriately.
The AC input voltage is too
high. The UPS is running on
battery power.
The line voltage istoolow.The
UPS is running on battery
power.
Ground wire connection does
not exist in thewall outlet or
the line andneutralwires are
reversed inthewalloutlet.
The batteryisrunninglow.3 to5minutes orlessofbatterypowerremains (depending on
Plug theUPS into a wall outlet for 24 hours to charge the
battery.Afterchargingthebattery, press and hold the
button for 3seconds;thenchecktheBatteryService
indicator.
If theBattery Service indicator is stillon,see“UPS
Maintenance” on page 21toreplacethebattery.
Change the alarm setting. See “Configuration Mode” on
page 17.
Correct the input voltage, if possible. The UPS continues to
operate onbatteryuntilthebatteryiscompletelydischarged.
If the condition persists, theinputvoltageinyourareamay
differ from the UPS nominal. Change the UPS input voltage to
match your local voltage (see “Configuration Mode” on
page 17).
Correct the input voltage, if possible. The UPS continues to
operate onbatteryuntilthebatteryiscompletelydischarged.
If the condition persists, theinputvoltageinyourareamay
differ from the UPS nominal. Change the UPS input voltage to
match your local voltage (see “Configuration Mode” on
page 17).
Have a qualifiedelectriciancorrectthe wiring.
T odisable this alarm, see “Configuration Mode” on page 17.
load andbatterycharge).
Prepare for ashutdown. Save your work and turn offyour
If r epair is required, you will be given a Returned Material
Authorization (RMA) Number. This number must appear on the outside
of the package and onthe Bill Of Lading (ifapplicable). Use the original
packagingor requestpackagingfromthe Help Deskor distributor.Units
damaged in shipment as a resultof improper packaging are not covered
underwarranty. Areplacement orrepairunitwillbe shipped, freight
prepaidfor all warrantied units.
NOTE Forcriticalapplications,immediate replacement may be available.Callthe