Powerware 5119 User Manual

02/15/01
Powerware®5119
User’s Guide
1000-3000 VA
www.powerware.com
Requesting aDeclaration ofConformity
Powerware Corporation Koskelontie 13 FIN-02920 Espoo Finland Phone: +358-9-452661 Fax: +358-9-452-66395
EMC Statement
Some configurations are classified under EN50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these configurations, the following applies:
WARNING Thisisa Class A-UPS Product. In a domesticenvironment, this product may cause radio interference, in which
case, the user may be required to take additionalmeasures.
Powerware is a registered trademark and Advanced Battery Management(ABM) is a trademark of Powerware Corporation.
.
Copyright 1999 Powerware Corporation, Raleigh, NC. All rights reserved. Nopart of this document may be repr oduced
in any way without the express written approval of Powerware Corporation.
Class A Statement forFCC andICES
(2000 VA - 3000 VA)
For Users in the United StatesOnly
NOTE Thisequipment has been tested and foundtocomply with the limitsforaClassAdigital device pursuant toPart15
of FCC Rules. These limits are designed to providereasonable protection against harmfulinterference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energyand,ifnot installed and used in accordance with the instruction manual, may cause harmfulinterference to radio communications. Operationofthis equipment in a residential area is likely to causeharmful interference,inwhich case the user willberequired to correct the interference at his/her own expense.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to
operate theequipment.
For Users in Canada
This ClassAInterference CausingEquipment meets all requirements of the CanadianInterference Causing Equipment Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
Self-Certified ClassB Statementfor FCC and ICES
(1000 VA - 1500 VA)
For Users in the United StatesOnly
THIS DEVICE COMPLIES WITH PART15 OF THE FCC RULES. OPERA TIO NIS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
NOTE Thisequipment has been tested and foundtocomply with the limitsfor a ClassBdevicepursuant to Part 15of
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated ina residential environment. This equipment generates, uses, and can radiate radiofrequency energy and, if not installed and used in accordance with theinstructionmanual, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmfulinterference to radioortelevision reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correctthe interference by oneormore of the followingmeasures:
Special Symbols
The following are examplesof symbols used onthe UPS toalert you toimportantinformation:
CAUTION
RiskofElectricShock
DoNotOpenCover
CAUTION Toreduce the riskof electric shock,
Donotremove cover (orback)
Nouser-serviceablepartsinside
Refer servicing to the factory
RISKOFELECTRIC SHOCK - Indicates that a risk ofelectric shock ispresentand the
associated warning should be observed.
CAUTION: REFER TO OPERATOR’SMANUAL - Refer to your operator’s manual for
additional information,such as important operating andmaintenance instructions.
This symbol indicates that youshouldnot discard the UPS or the UPS batteries in the trash. TheUPS may contain sealed, lead-acid batteries. Batteries must be recycled.
TABLE OF CONTENTS
1 Powerware 5119 –One ofthe Best! 1..................................
2 Installation 3.....................................................
InspectingtheEquipment 3.......................................................
SafetyPrecautions 3............................................................
Installing the UPS 4.............................................................
UPSRearPanels 7..............................................................
3 Operation 11......................................................
Turning the UPS On 11............................................................
StartingtheUPSon Battery 11...................................................
Turning the UPS Off 11...........................................................
StandbyMode 11...............................................................
UPSFrontPanel 12..............................................................
ACInputLEDs 13.............................................................
BatteryChargeLEDs 13........................................................
Load Level LEDs 14...........................................................
InitiatingtheSelf-Test 14.........................................................
4 Configuration 15...................................................
WhyChangeFactoryDefaults? 15...................................................
NominalInputVoltage 15.......................................................
OtherSettings 15.............................................................
ConfigurationMode 15...........................................................
5 UPS Maintenance 19...............................................
UPSandBatteryCare 19..........................................................
StoringtheUPSand Batteries 19..................................................
Whento ReplaceBatteries 19......................................................
ReplacingBatteries 20...........................................................
HowtoReplaceExternalBatteries 21..............................................
HowtoReplaceInternalBatteries 22...............................................
Testing New Batteries 23.........................................................
Recycling the Used Battery 24......................................................
Powerware®5119 User’sGuide:www.powerware.com
i
Table of Contents
6 Additional UPSFeatures 25..........................................
Communication PortConfigurations 25................................................
Communication Indicator 25.....................................................
PinOut 26..................................................................
NetworkTransient Protector 27.....................................................
LoadSegments 27..............................................................
OptionModules 27..............................................................
7 Specifications 29..................................................
8 Troubleshooting 33.................................................
AudibleAlarms and UPS Conditions 33................................................
Silencing anAudible Alarm 33....................................................
ServiceandSupport 35...........................................................
ii
Powerware®5119 User’sGuide:www.powerware.com
CHAPTER 1
POWERWARE 5119 – ONE OF THE BEST!
The Powerware95119 uninterruptible power system(UPS) protects your sensitive electronic equipme nt frombasic powerproblems such as power failures, power sags,power surges, brownouts, and line noise.
Poweroutagescan occur when youleastexpect it andpower quality can be erratic. These powerproblemshavethe potential to corrupt criticaldata, destroyunsaved work sessions, anddamage hardware
causing hours oflost productivity and expensive repairs. Withthe Powerware 5119,you c an safely eliminate the effects of power
disturbances and guard theintegrity ofyourequipment. ThePowerware 5119’s flexibility to handle anarray of network devices makes it the perfect choice to protect your LANs,servers, andworkstations.
Figure1.Powerware 5119 andExternal Battery Cabinet
Becausean integral part ofpowerprotectionispower management software,the Powerware 5119 comes fully equipped with a communication port, serial cable, anda CDcontaining both LanSafe III for networked systems and FailSafe IIIfor standalonesystems.
Powerware®5119 User’sGuide:www.powerware.com
1
Powerware5119– One of the Best!
Providing outstanding performance and reliability, the Powerware 5119’s unique benefits include the following:
:
Advanced Battery Management (ABMZ) doubles battery service life, optimizesrecharge time, andprovides a warningup to 60days before the end of useful battery life.
:
Buck and Double Boost regulationensures consistent voltage to your load by correctingvoltage fluctuations without using battery power.
:
Hot-swappable batteries simplify maintenance by allowing you to replacebatteriessafelywithoutpowering downthe critical load.
:
Network TransientProtector guards your modem, faxmachine,and othernetworkcommunications equipment from surges.
:
Start-on-battery compatibilityallowsyouto power upthe UPS even if utilitypower is not available.
:
Optionalpower communication cards provide enhanced communication capabilities for increased power protection and longerbatterybackup times.
:
The Powerware 5119is back e d by worldwide agencyapprovals.
2
Powerware®5119 User’sGuide:www.powerware.com
CHAPTER 2
INSTALLATION
This section explains:
:
Equipment inspection
:
Safetyprecautions
:
UPS installation
:
UPSrear panels
Inspecting the Equipment
If any equipment has beendamaged during shipment,keep the shipping cartons andpackingmaterialsfor the carrier or placeof purchase andfile a claimfor shippingdamage. If youdiscoverdamage after acceptance, file a claimfor concealed damage.
To file aclaim for shipping damage orconcealeddamage: 1) File with the carrier within15 days ofreceiptof the equipment; 2) Senda copyof the damage claim within 15 days to your service representative.
Safety Precautions
Read thefollowing before youinstallthe UPS.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.Thismanual contains important instructionsthatyou shouldfollowduringinstallation and maintenance of the UPS and batteries. Please read allinstructionsbefore operatingtheequipmentandsavethismanual for future reference.
Powerware®5119 User’sGuide:www.powerware.com
3
Installation
Installing the UPS
The following steps explain how to install the UPS. Figu re 3 on page 6 shows a typical installation only. See “UPS Rear Panels” on page 7 for
the rear panel ofeach model.
WARNING
:
ThisUPScontainsits own energy source (batteries).Theoutputreceptaclesmay carrylivevoltage even when theUPSisnot connected to anACsupply.
:
Donot removeor unplug the input cord when the UPS is turned on. This removes the safetyground from the UPS and the equipment connected to the UPS.
:
To reduce therisk of fire orelectric shock,installthis UPS in a temperature and humiditycontrolled, indoor environment,freeof conductivecontaminants. Ambienttemperaturemustnotexceed40C(104F).Donotoperatenear water or excessive humidity (95% max).
:
The sumof earth leakage current from the load connected to the UPS must not exceed1.5mA.
CAUTION
Asmallamountofarcingmayoccur whenconnecting an external battery to the UPS. InsertthebatterycableintotheUPSbatteryconnectorquickly and firmly.
NOTE Donot makeunauthorizedchangestothe UPS;otherwise,damagemayoccur to your equipmentand voidyourwarranty.
1. If the UPS has an external battery, connect it to the UPS as shownin Figure 3 on page 6.
2. If youare installing power management software, connect your computer to the UPS communication port using the supplied communication cable.
Some power management software has a Load Segment feature that allows you to control UPS output receptacles. If youplan to use this feature, read the appropriate sections ofyourpower management software manual before you install the UPS.
4
Powerware®5119 User’sGuide:www.powerware.com
Installation
3. On 230V models, plug theUPS power cord into the input connectoronthe UPS rear panel.
Customer-supplied power cords must correctly rated forthe UPS (see “Specifications”on page 29).You can also usethe
power cord from the largest load if it iscorrectlyrated.
4. Plug the UPS power cord into a wall outlet or power source. The UPS conducts a self-test and enters Standby mode. If a red
Site Wiring Fault or Battery Service indicator stays on, see Table 11 on page 33.
Site Wiring Fault Indicator
Battery Service Indicator
Figure 2. Fault Indicators
NOTE Lowvoltagemodelsmaynotrecognize 50-Hz outlets. If the UPS does not
startwhenconnectedtoa 50-Hz outlet,unplugthe UPS.Pressandholdthe
button for 3 seconds to start the UPS on battery and reconfigure the nominal
On inputvoltagetoeither100Vor 110V (see ”ConfigurationMode”onpage15).Turn the
UPSoff.Waitfor30seconds.ThenplugtheUPSintotheoutlet.
5. Plugthe equipment to be protected into the UPSoutput receptacles.
DO NOT protect laserprinters withthe UPS because ofthe exceptionally high powerrequirementsof the heating elements.
6. Start the UPS by pressing the On The Power On indicator illuminates indicating that power is available from the rear receptacles.
The installation iscomplete.To learn how tooperate the UPS, see “Operation” onpage 11. Tochangethe factory-set defaults,
see “Configuration” on page 15.
NOTE The UPSchargesto90% in approximately4hours.However,itis recommendedthatthe UPSchargefor 24 hours after installationorlongstorage.
Powerware®5119 User’sGuide:www.powerware.com
button as shownin Figure 3.
5
Installation
2
Connect communication cable from computer to UPS (optional)
1
Connect battery to UPS (if applicable)
3&4
Battery
Cabinet
5
Connect equipment to UPS
UPS
6
Powerware®5119 User’sGuide:www.powerware.com
UPS RearPanels
Installation
This section shows the rear panels of all Powerware 5119 models.
Powerware®5119 User’sGuide:www.powerware.com
7
Installation
8
Powerware®5119 User’sGuide:www.powerware.com
Installation
Communication Port
Battery Connector
Load Segment 1
(Three IEC-320 Receptacles)
Load Segment 2
(Three IEC-320 Receptacles)
(Three IEC-320 Receptacles)
Figure 8. 2000-2400 VA,230VRearPanel
Communication Port
Battery Connector
Output Circuit Breakers
Load Segment 1
(Three IEC-320 Receptacles)
/ 2 $ '
Load Segment 3
10A, IEC-320 Input Connector
Input Circuit Breaker
Option Slot
Network T ransientProtector
16A, IEC-320 Input Connector
Input Circuit Breaker
Load Segment 2
(Three IEC-320 Receptacles)
Load Segment 3
(Three IEC-320 Receptacles)
Figure 9. 3000 VA,230VRearPanel
Powerware®5119 User’sGuide:www.powerware.com
Option Slot
Network T ransientProtector
9
Installation
10
Powerware®5119 User’sGuide:www.powerware.com
CHAPTER 3
OPERATION
Thissectiondescribes:
:
Turning the UPS on and off
:
Starting the UPSon battery
:
Standby mod e
:
The UPS front panel and LEDs
:
Initiatingthe self-test
Turning the UPS On
After the UPS isconnected to a powersource, it conducts a self-testand enters Standby mode. To turnon the UPS, press the On front panel(showninFigure 10). ThePowerOn indicator illuminates indicating that poweris available from the rear receptacles.
Starting the UPS onBattery
To turnon the UPS without usin gutility power, press and holdthe On buttonfor three seconds.Whenthe UPS starts on battery, it does not conduct a self-test toconservebattery power.
buttononthe
Turning the UPS Off
To turn off the UPS, press the Off
Powerware®5119 User’sGuide:www.powerware.com
11
Operation
UPS FrontPanel
The UPS front panel LEDs indicate how theUPSis operating and also alert you of potential powerproblems.Figure 10 shows the UPS front panel indicators and controls.
Battery Charge LEDs
AC Input LEDs
Site Wiring Fault Indicator
T e st/AlarmResetButton
Load Level LEDs
Communication Indicator
On Button Off Button
12
Powerware®5119 User’sGuide:www.powerware.com
Operation
AC InputLEDs
The AC Input LEDs show information about the utility power coming intotheUPS(seeFigure11).
Normal Utility Input (Buck and Single Boost) Double Boost is on
Figure 11. AC InputLEDs (Normal Mode)
The second LED indicates that the UPSis operatingnormally from utility power. The UPS is providing consistent voltage with the Buck and SingleBoost feature.
The third LED indicates that the UPS is using the Double Boost feature to automaticallycorrect voltage fluctuations.
If any ACInputLEDs are red, see page 34 formore information.
Battery ChargeLEDs
Powerware®5119 User’sGuide:www.powerware.com
13
Operation
Load Level LEDs
The front panel displays the total load current or watts plugged into the UPS (see Figure 13).
33-66% 5-33%66-100%
Figure 13. Load LevelLEDs (Normal Mode)
Each LED represents 1/3of a fullload rating.Whenthe UPS is approximately fullyloaded (66-100%), all three LEDs illuminate.If the load is 33-66% of UPS capacity, the third and fourth LED illuminate. The last LED illuminates ifthe load isbetween 5%and 33%.
If any Load LevelLEDsare red, see page35 for more information.
Initiating the Self-Test
Press and hold the button for three seconds to initiatethe self-test. During the test, individual LEDs illuminate as various parts of the UPS arechecked. If theUPS finds a problem, an LEDindicateswhere the problem is.For more information, see “Troubleshooting” on page 33.
NOTE AllthreeBatteryChargeLEDsshould be lit and theUPSmustnotbein Batterymodeto perform the self-test.
14
Powerware®5119 User’sGuide:www.powerware.com
CHAPTER 4
CONFIGURATION
This section explains:
:
Whyyou may want tochange factory defaults
:
How to r econfigure options
Why Change Factory Defaults?
Nominal Input Voltage
When the utility power consistently fluctuates, the UPS repeatedly corrects theinputvoltageby switchingto battery powerwhenthe nominal input range is:
:
Higher than +20%of 120V or 230V nominal
:
Lower than -30%of 120Vor 230Vnominal
:
Higher than +20%and lower than -30% of120V or230V nominal
You can configure the UPS to more closely match the nominal input voltage by selecting a different input voltage or extending the input voltage range. See Table 1 onpage 17 fora list of available options.
Other Settings
You can change theUPS default configurations for alarms andshutdown parameters, including: timingfor the low battery alarm,the timedelay for anunconditional shutdown, alarms for loss ofutility power orsite fault, and controlling loads that use less than5% of the current when the UPS ison battery. See Table 1 onpage 17 for alist of available options.
Configuration Mode
When theUPS is in Configuration mode, the LEDs represent the configuration options. The control buttons (On are used to modify theUPS c onfiguration. Figure 14 showsthe LEDs and Table 1 explains the corresponding options.
Powerware®5119 User’sGuide:www.powerware.com
button and button)
15
Configuration
CAUTION
DONOTpresstheOff button whiletheUPSisinConfigurationmode;pressing the Off
button removesallpowertoyourequipment.
1. Press and hold the On button and the button simultaneously for one beep. The UPS switches to Configuration mode.
2. Press the On
button to scroll through theoptions. Each time youpressthe button,the UPS beeps. TheLED for the selected option blinks (see Figure 14 and Table 1).
If you press the On
button and nothing happens, the UPS is stillinOperationmode. Repeat Step1 for onebeep ONLYto enter Configuration mode, and then performStep 2.
3. Press the
button ONCE to toggle theselected optionon or off.The Power On indicator corresponds with the current setting.
Repeat Steps 2and 3 foreach option.
4. Press the On
button and the buttonsimultaneously to returnto O peration mode at any time. Scrolling pastthe last LED also returns the UPS to Operation mode.
16
Power On Indicator
2
Press theOn button to scroll tothenextoption.
3
Press theTest/Alarm Reset button totoggleanoptiononoroff.
Figure 14. Using the Configuration Mode
LEDs
1
&
4
Press theOn andTest/Alarm Reset buttons simultaneously to toggle between Configuration and Operation mode.
Powerware®5119 User’sGuide:www.powerware.com
Table 1.Configuration Mode LEDs andOptions
LED Option PowerOn
Indicator
Explanation
Configuration
120/230V Nominal Input Voltage
110/220V Nominal Input Voltage
127/240V Nominal Input Voltage
120/230V Extended Voltage Mode
Site Wiring Fault Alarm
ON (default) Nominal input voltage onlow voltage models is 120V and on high voltage
models is 230V; all other nominal input voltages are disabled.
OFF* 120/230V is disabled; one of the other input voltage options is selected.
*This is the default formodels that are factory-configured for 100V or 208V (see the rating ontheUPS rear panel).
ON Selecting this option changes the nominal input voltage on low voltage models
to 110V and to 220V for high voltage models.
OFF (default) 110/220V is disabled; one oftheotherinputvoltageoptionsisselected.
ON Selecting this option changes the nominal input voltage on low voltage models
to 127V and to 240V for high voltage models.
OFF (default) 127/240V is disabled; one oftheotherinputvoltageoptionsisselected.
ON The UPS accepts an input voltage within -35% to +20% of 120V or 230V
nominal input voltage before switching to battery.
OFF (default) The UPS acceptsaninput voltagewithin-30% to +20% of 120V or 230V
nominal input voltage before switching to battery.
ON (default) Alarmsoundswhenthepolarityoftheoutletisreversedortheground
connection is missing; have a qualified electrician repair the outlet wiring.
OFF* Alarm DOES NOT sound when the polarity of the outlet is reversed or the ground
connection is missing. *Site Wiring Fault is not available for 100V or 208V models; OFF is the default.
Low Battery Alarm ON(default) Alarm sounds approximately 3 minutes before battery shutdown.
OFF Alarm sounds approximately 5 minutes before battery shutdown.
Powerware®5119 User’sGuide:www.powerware.com
17
Configuration
OptionLED
Indicator
Shutdown Delay ON (default) 5-second delay before unconditional shutdown after the UPS receivesasignal
OFF 180-second delay beforeunconditional shutdown after the UPS receives a signal
AC Input Failure ON (default) Alarm sounds when there is an AC input failure.
OFF Alarm DOES NOT sound when there is an AC input failure.
Sleep Mode ON (default) When the UPS isonbattery and the load is drawing less than 5% of the current,
OFF Select this option if you want a load less than5% ofthecurrenttobeprotected
100/208V Nominal Input Voltage
ON* Selecting this option changes the nominal input voltage on low voltage models
ExplanationPowerOn
from a computer via the communication port.
from a computer via the communication port. When this LED is not enabled, the user canalsocreateanewdelaytimebyreconfiguringthecommunication port. See“Communication Port Configurations” on page 25 for more information.
the UPS shuts down the load. This feature conserves battery power.
by batterypower .
to 100V and to 208V on high voltage models. *This is the default forfactory-configured100V or 208V models (see the rating
label on theUPS rear panel).
OFF (default) 100/208V is disabled; one oftheotherinputvoltageoptionsisselected.
100/208V Extended Voltage Mode
Reset Defaults ON (default) All factory-set defaults areactive.
ON Select this option to extend the input voltage within-25% to +25% of 100V or
208V nominal input voltage before switching to battery (available on units that were specifically ordered with this option).
OFF (default) The UPS acceptsaninput voltagewithin-20% to +20% of 100V or 208V
nominal input voltage before switching to battery.
OFF One or more factory-set defaults have been changed.
18
Powerware®5119 User’sGuide:www.powerware.com
CHAPTER 5
UPS MAINTENANCE
This section explains how to:
:
Care for the UPS and batteries
:
Replace the batteries
:
Test ne w batteries
:
Recycle used batteries
UPS and Battery Care
Forthe best preventive maintenance,keep the area around theUPS clean and dust-free.If the atmosphere is verydusty, cleanthe outside of the system with a vacuum cleaner.
Forfullbattery life, keep theUPSat anambienttemperature of 25°C (77°F).
Storing theUPS andBatteries
If you store the UPSfor a long period, recharge the battery every 12 months by plugging the UPS into a power outlet. The UPS charges to 90% in approximately4 hours. However, it is recommendedthat the UPS charge for 24 hours after long storage.
When to Replace Batteries
When the Battery Service indicator illuminates, the batteries may need replacing (see Figure 10on page 12).Conduct a self-test by pressing the
button. If the indicator stays on, contact your service representative
to order new batteries.
Powerware®5119 User’sGuide:www.powerware.com
19
UPS Maintenance
Replacing Batteries
The hot-swappablebattery featureallows you to replace theUPS batteries easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the battery: 1) Press the Off internal processor shuts down before you disconnect the battery.
Consider allwarnings, cautions,and notes before replacing batteries.
:
:
Pullthebatteryout onto a flat, stable surface.Thebatteryisunsupportedwhenyou pullitoutof the UPS.
button and then unplug the UPS; 2) Wait 60 seconds while the
WARNING
Batteriescanpresentariskofelectrical shockor burn from high short circuit current.Thefollowingprecautions should be observed: 1) Removewatches,rings, or other metal objects;2)Usetoolswith insulated handles;3)Donotlaytoolsor metalpartsontop of batteries.
ELECTRICENERGYHAZARD.Donotattempt to alter any battery wiringor connectors.Attempting to alter wiring can cause injury.
CAUTION
20
NOTE Whenthe UPS isonline,allthreeBatteryChargeLEDsshould be lit before
hot-swappingthebatteries.DONOT DISCONNECT the batteries whiletheUPSisin Batterymode.
Powerware®5119 User’sGuide:www.powerware.com
How toReplace ExternalBatteries
Use the following steps to replace external batteries:
1. Unplug thebattery cable from the UPSand remove the old battery. See “Recycling the Batteries” onpage 24for proper
disposal.
2. Plugthe ne w battery cabinet into the UPS asshown in Figure 15.
Battery CabinetUPS
Battery Connector
Plug thebatterycable into thebattery connector
UPS Maintenance
Figure 15. External Battery Connections (120VModelShown)
Powerware®5119 User’sGuide:www.powerware.com
21
UPS Maintenance
How toReplace InternalBatteries
Use the following steps to replace internal batteries:
1. Pullthefrontpanelforwardand snap into placeas shown.
22
Powerware®5119 User’sGuide:www.powerware.com
1000 VA Models
UPS Maintenance
4. Remove the old battery. See “Recycling the Batteries” on page 24 for proper disposal.
5. Connect the new batteries to the UPSas shown inFigure16 and reinstall.
RedCablefrom UPS
PositiveTerminal
BlackCable fromUPS
NegativeTerminal
RedConnector from UPS
BlackCable fromUPS
1500 VA Models
Negative Terminal (Black)
Figure 16. Internal Battery Connections
Testing New Batteries
Press and hold the button for three seconds to initiatea self-test. After the test isfinished,the red Battery Service indicator should turn off a nd the Battery Charge LEDs should show a charge. If the Battery Serviceindicator stayson,check the battery connections.See the troubleshooting guide on page 33 or callyour service representative if the problem persists.
Powerware®5119 User’sGuide:www.powerware.com
RedBattery Connector
23
UPS Maintenance
Recycling the Used Battery
Contactyourlocal recycling orhazardous wastecenter for information on proper disposal of the usedbattery.
:
Donot disposeofbatteryor batteriesina fire.Batteriesmayexplode.Proper disposalofbatteriesisrequired. Refer to your local codes for disposal requirements.
:
Donot open or mutilate the battery or batteries. Releasedelectrolyteisharmful to the skinand eyes.Itmaybetoxic.
Donot discardtheUPSorthe UPS batteriesinthe trash.Thisproductcontains sealed,lead-acid batteries and must be disposed of properly.Formoreinformation, contactyourlocalrecyclingor hazardous wastecenter.
WARNING
CAUTION
24
Powerware®5119 User’sGuide:www.powerware.com
CHAPTER 6
ADDITIONAL UPS FEATURES
Thissectiondescribes:
:
UPS communication capabilities
:
The Network Transient Protector
:
Load segments
:
Optionmodules
Communication Port Configurations
To establishcommunication between theUPS and a computer, connect your computer to the UPS communication port using the supplied communication cable.
To prevent damagetoyourequipment,connect only a factory-suppliedcableora cablebuilttofactoryspecifications(seeTable 2) to the communicationport.A standardserialcablemaydamageyourcomputer.
Whenthe communication cableis installed,power management software canexchangedata with theUPS.The softwarepolls the UPS for de ta iled informationon the status of thepower environment. If a power emergencyoccurs,thesoftware initiates thesavingof all data and an orderly shutdown of the equipment.
CAUTION
Communication Indicator
Whenthe UPS receives a command from the computer to establish communication, the Communicationindicator onthe UPS frontpanel illuminates (see Figu re 10 onpage 12). Whendata is transferring, the Communication indicatorflashes.
Powerware®5119 User’sGuide:www.powerware.com
25
Additional UPS Features
Pin Out
As shown in Table 2, Pins 1 and 2 operate intwo modes: BasicAlarms mode and Serial Datamode. Basic Alarms mode hasAC fail alarm and output shutdown. Serial Data mode is UPS Code II compliant.
The system always starts in Basic Alarmsmode.Whenserialdata is received at Pin 1, the function ofPin1 and Pin 2 changesto Serial Data mode.
If serial data hasnot been received before going to batterypower, serial communication is disabled until AC input power returns.
6789
12345
Figure 17. Communication Port
Table 2.CommunicationPort Configuration
Pin SignalType Function
1
2
3 Output: Open collector transistor ON, 50 mA, 40 Vdc rating AC Input failure 4 SignalCommon Signal Common 5 Output: Open collector transistor ON, 50 mA, 40 Vdc rating Impending low battery 6 Input: RS-232 RTS Plug-and-play software enable trigger (activates
7 Input: Relay contact or RS-232 level Remote Emergency Power-Off: UPS total output can
8 Output: 8 to 25 Vdc, 5W constant power (0.63A max. @ 8V) Auxiliary Control Power 9 Chassis Connection to chassis
26
Basic Alarms Mode-Input: RS-232 level high (+12V) pulse 4 to5seconds
Serial Data Mode - Input: RS-232 data RS-232 serial communication input. 1200 baud,
Basic Alarms Mode-Output: RS-232 level high (+12V) AC Input failure Serial Data Mode - Output: RS-232 data RS-232 serial communication output. 1200 baud,
Remote UPS off. In absence of AC power, output is turned offuntilnormal AC power returns
8 bits,Noparity, 1 stop bit, 1 start bit
8 bits,Noparity, 1 stop bit, 1 start bit
when pin changes from +12V to -12V)
be keptoffwith low signal or closing relay contact
Powerware®5119 User’sGuide:www.powerware.com
Network Transient Protector
The Network Transient Protector, shown in Figure18, is located onthe rearpanel and has jackslabeled IN andOUT. This feature accommodatesa single RJ -45 (10BaseT) network connector.
Low voltage models can alsoaccommodate an RJ-11 telephone connectorthatprovides protection for modems, faxmachines,or other telecommunicationsequipment.As with most modemequipment, itis not advisable to use thisjack in digital PBX (Private Branch Exchange) environments.
Connect the input connector of the equipment you are protecting to the jack labeled IN.Connect theoutputconnectorto the jacklabeled OUT.
Additional UPS Features
IN OUT
Load Segments
Option Modules
IN
OUT
NETWORKTRANSIENTPROTECTOR
Figure 18. Network TransientProtector
Load segmentsare sets ofreceptacles thatcan be turned onindividually using powermanagementsoftware. Forexample,during a power outage,youcan keep key pieces ofequipment running while you turn off other equipment.Thisfeatureallowsyou to save batterypower. See yourpower managementsoftwaremanualfor details.
Optionmoduleshelp your UPS communicate in a varietyof networking environments and are installed inthe UPS option slot. See the manual that accompanieseach module for more information, or contact your salesrepresentative.
Powerware®5119 User’sGuide:www.powerware.com
27
Additional UPS Features
28
Powerware®5119 User’sGuide:www.powerware.com
CHAPTER 7
SPECIFICATIONS
Thissectionprovides thefollowing specificationsfor the Powerware 5119 mode ls:
:
Electrical input andoutput
:
W eights and dimensions
:
Environmental and safety
:
Indicatorsand controls
:
Battery
Table 3.ModelList
120V Models 230V Models
UPS Models PW5119 1000
PW5119 1500 PW5119 2000 PW5119 2400 PW5119 3000
PW5119 1000i PW5119 1500i PW5119 2000i PW5119 2400i PW5119 3000i
Table 4.Electrical Input
120V Models 230V Models NominalVoltage 120V default; 100, 110, 120, 127V selectable 230V default; 208, 220, 230, 240V selectable VoltageRange -30% to +20% at full load for nominal voltage; -35% to+20% user-selectable, extended range NominalFrequency 60 Hz; 50/60 if 100V or 110V selected 50/60 Hz Noise Filtering MOVs and line filter for normal andcommon mode noise
Connections 1000-1500 VA: 6-ft.powercordwith5-15plug
2000 VA: 6-ft.powercordwith5-20plug
2400-3000 VA: 6-ft.powercordwith5-30plug
Powerware®5119 User’sGuide:www.powerware.com
1000-2400 VA: 10A,IEC-320 input connector
3000 VA: 16A,IEC-320 input connector
29
Specifications
Table 5.Electrical Output
120V Models 230V Models
PowerLevels (ratedat nominalinputs)
RegulationOnline -10% to +6% of nominal voltage (-15% to +10% using extended range) RegulationOn-Battery
(NominalVoltage±5%)
VoltageWaveform Sine wave; <3% distortion with linear load Overcurrent Protection Online: Branch-rated orresettablecircuit breaker;
OutputReceptacles 1000-1500 VA: Six5-15
PW5119 1000: 1000VA,670W
PW5119 1500: 1440VA,960W PW5119 2000: 1920VA,1400W PW5119 2400: 2400VA,1600W PW5119 3000: 2880VA,2250W
120V for 110, 120, 127V; 100V for 100V 230V for 220, 230, 240V; 208V for 208V
On-Battery: Active current limit and short circuit protection
2000 VA: Six5-15,Two 5-20
2400-3000 VA: Six5-15, One 5-30
PW5119 1000i: 1000VA,670W
PW5119 1500i: 1500VA,960W PW5119 2000i: 2000VA,1400W PW5119 2400i: 2300VA,1600W PW5119 3000i: 3000VA,2250W
1000-1500 VA: Six IEC-320
2000-3000 VA: NineIEC-320
Table 6.WeightsandDimensions
120V Models 230V Models
UPS Dimensions (WxHxD)
UPS Weights 1000 VA: 43lb(20kg)
7 x8.8x17.1inches
(17.8 x 22.3 x43.4cm)
1500 VA: 57lb(26kg) 2000 VA: 32lb(15kg) 2400 VA: 36lb(16kg) 3000 VA: 41lb(19kg)
BatteryDimensions (WxHxD)
Battery Weights PW5119 1048BP: 47lb(21kg) PW5119 1748BP: 70 lb (32 kg)
30
7 x8.8x17.1inches
(17.8 x 22.3 x43.4cm)
Powerware®5119 User’sGuide:www.powerware.com
Specifications
Table 7.Environmental and Safety
120V Models 230V Models
OperatingTemperature 0°C to 40°C (32°F to 104°F); UL tested25°C (77°F) StorageTemperature -20°C to 60°C ( -4°Fto140°F) Relative Humidity 5-95% noncondensing OperatingAltitude Up to 3,000 meters above sea level AudibleNoise Less than45dBA typical SurgeSuppression IEEE 587/ANSI C62.41 Category B SafetyConformance UL 1778; CAN/CSA C22.2, No. 107.1 UL 1778; CAN/CSA C22.2, No. 107.1;
EN 50091-1 and IEC 60950
Safety Markings UL,CSA UL,CSA,CE EMC FCC,VCCI EN 50091-2
Table 8.Indicators and Controls
SerialCommunication Intelligent serial communication to provide alarms with history, measured parameters, self-test,
and many other features; contact yourauthorizeddealerforUPS/computer communication software options
Interface Ergonomic Indicators: WiringFault,Battery Service, Communication, Operation, System Normal
Bar Graphs: InputLevel,Battery Charge Level, % Load
ContactClosures AC Input Failure, Low Battery
Table 9.Battery
120V Models 230V Models
Configuration 1000-1500 VA: internalbatteries
2000-3000 VA: externalPW51191048BP
Voltage 24 Vdc for internal; 48 Vdc for external Type Sealed, maintenance-free, valve-regulated, lead-acid Charging Advancedchargingforfasterrecovery;approximately4hoursto90%usablecapacityatnominal
line and nosupplementary power supply load
Monitoring Advanced monitoring for earlier failure detection and warning
Powerware®5119 User’sGuide:www.powerware.com
1000-1500 VA: internalbatteries 2000-3000 VA: externalPW51191748BP
31
Specifications
Table 10.Battery Run Times (in Minutes)
Load(VA) 1000 Model 1500 Model 2000 Model 2400 Model 3000 Model
300 49 79 92 162 162 500 21 38 55 97 97
700 14 17 34 62 62 1000 8 6 24 43 43 1500 8 13 23 23 2000 8 16 16 2400 13 13 3000 7
NOTE
Battery times are approximate and vary depending on theloadconfigurationandbatterycharge.
32
Powerware®5119 User’sGuide:www.powerware.com
CHAPTER 8
TROUBLESHOOTING
This section explains:
:
UPS alarms and conditions
:
How to silence an alarm
:
Service and support
Audible Alarms andU PS Conditions
The UPS has anaudiblealarm featureto alert you ofpotentialpower problems. Use Table 11 to determine and resolve the UPS alarms and conditions.
Silencing an Audible Alarm
To silence the alarm foran existing fault,pressthe button.If UPS statuschanges, thealarm beeps, overridingthe previousalarmsilencing.
Table 11.Troubleshooting Guide
AlarmorCondition Possible Cause Action
The Power On indicator is not on; theUPS will not
start.
The UPS switches frequently between battery and AC input.
Powerware®5119 User’sGuide:www.powerware.com
A circuit breaker or an input fuse ontherearpanelisopen.
The line cordisnotconnected. The wall outlet is dead. Have a qualified electrician test and repair theoutlet. The UPS may be unable to
recognize a100V, 50-Hz wall outlet.
A battery fuse or circuit breaker is open.
Input voltage in your areadiffers from the UPS nominal.
Push thecircuit breakerbuttonorreplacethefuse(see“UPS Rear Panels” on page 7).
Connect the line cord.
See “Specifications” on page 29 to verify that your UPS accepts 100V nominal input.
Unplug the UPS. Start the UPS on battery andreconfigurethe nominal input voltage for 100V (see ”Configuration Mode” on page 15). Turn off the UPS for 30 seconds. Plug the UPS into the outlet.
Contact your service representative.
Change the UPS input voltage to match your local voltage; see “Configuration Mode” on page 15.
33
Troubleshooting
ActionPossible CauseAlarmorCondition
The Low Battery Alarm does not giveenough warning.
AC input high
AC input low
Site Wiring Fault
Low Battery Charge
The batteries needchargingor service.
The Low Battery Alarm is not set appropriately.
The AC input voltage is too high. The UPS is running on battery power.
The line voltage istoolow.The UPS is running on battery power.
Ground wire connection does not exist in thewall outlet or the line andneutralwires are reversed inthewalloutlet.
The batteryisrunninglow. 3 to5minutes orlessofbatterypowerremains (depending on
Plug theUPS into a wall outlet for 24 hours to charge the battery.Afterchargingthebattery, press and hold the
button for 3seconds;thenchecktheBatteryService indicator. If theBattery Service indicator is stillon,see“UPS
Maintenance” on page 19toreplacethebattery. Change the alarm setting. See “Configuration Mode” on
page 15. Correct the input voltage, if possible. The UPS continues to
operate onbatteryuntilthebatteryiscompletelydischarged. If the condition persists, theinputvoltageinyourareamay
differ from the UPS nominal. Change the UPS input voltage to match your local voltage (see “Configuration Mode” on page 15).
Correct the input voltage, if possible. The UPS continues to operate onbatteryuntilthebatteryiscompletelydischarged.
If the condition persists, theinputvoltageinyourareamay differ from the UPS nominal. Change the UPS input voltage to match your local voltage (see “Configuration Mode” on page 15).
Have a qualifiedelectriciancorrectthe wiring. T odisable this alarm, see “Configuration Mode” on page 15.
load andbatterycharge). Prepare for ashutdown. Save your work and turn offyour
equipment.
34
Powerware®5119 User’sGuide:www.powerware.com
Troubleshooting
ActionPossible CauseAlarmorCondition
The batterymay befully
Battery Service
Battery Service Overload
discharged because ofalong storageperiodorfailing because ofage.
The batteryisnotconnected correctly.
The DC voltage is high; the alarm does not clear.
Power requirements exceed UPS capacity or the load is defective.
Service and Support
If you have anyquestions orproblems withthe UPS, call your
Distributor
and ask fora UPS technical representative.
In the United States In Canada All other countries
or the
Help Desk
1-800-365-4892 1-800-461-9166 1-919-870-3149
Plug theUPS into a wall outlet for 24 hours to charge the battery.Afterchargingthebattery, press and hold the
button for 3seconds;thenchecktheBatteryService indicator. If theBattery Service indicator is stillon,see“UPS
Maintenance” on page 19toreplacethebattery. Check connections or call your service representative.
Contact your service representative.
Remove some of the equipment from the UPS. Youmay need to obtainalargercapacityUPS.
Local
at one of the following telephone numbers
Pleasehave the followinginformation ready whenyoucall the Help Desk:
:
Model number
:
Serial number
:
Version number (ifavailable)
:
Date offailure or problem
:
Symptoms of failure or problem
:
Customer return address and contactinformation
Powerware®5119 User’sGuide:www.powerware.com
35
Troubleshooting
If r epair is required, you will be given a Returned Material Authorization (RMA) Number. This number must appear on the outside of the package and onthe Bill Of Lading (ifapplicable). Use the original packagingor requestpackagingfromthe Help Deskor distributor.Units damaged in shipment as a resultof improper packaging are not covered underwarranty. Areplacement orrepairunitwillbe shipped, freight prepaidfor all warrantied units.
NOTE Forcriticalapplications,immediate replacement may be available.Callthe
Help Desk
for the dealer or distributor nearestyou.
36
Powerware®5119 User’sGuide:www.powerware.com
Loading...