Powerware 5115 RM User Manual

Powerware®5115 RM
User’s Guide
500–1500 VA
www.powerware.com
US Patent 6,462,961
Class B EMC Statements
NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
:
Reorient or relocate the receiving antenna.
:
Increase the separation between the equipment and the receiver.
:
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
:
Consult the dealer or an experienced radio/TV technician for help.
ICES-003
This Class B Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES-003.
Cet appareil numérique de la classe B respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
:
Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 950 Second Edition, Amendments A1, A2, A3, and A4
:
EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Powerware Corporation Koskelontie 13 FIN-02920 Espoo Finland Phone: +358-9-452 661 Fax: +358-9-452 665 68
93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC
Powerware and ABM are registered trademarks and X-Slot and ConnectUPS are trademarks of Powerware Corporation.
.
Copyright 2002-2003 Powerware Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be
reproduced in any way without the express written approval of Powerware Corporation.
Special Symbols
The following are examples of symbols used on the UPS to alert you to important information:
CAUTION
Risk of Electric Shock
Do Not Open Cover
CAUTION To r educe the risk of electric shock,
Do not remove cover (or back)
No user-serviceable parts inside
Refer servicing to the factory
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present a nd the
associated warning should be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for
additional information, such as important operating a nd maintenance instructions.
SAFETY EARTHING TERMINAL - Indicates the primary safety ground.
LOAD ON/OFF - Press the button with this symbol to energize the output
receptacles (
indicator is off).
(
RJ-45 RECEPTACLE - For 230V models only: this receptacle provides network
interface connections. Do not plug telephone or telecommunications equipment into this receptacle.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. The UPS may contain sealed, lead-acid batteries. Batteries must be recycled.
indicator illuminates) or to de-energize the output receptacles
TABLE OF CONTENTS
1 Powerware 5115 RM – One of the Best! 1..............................
2 Safety Warnings 3.................................................
3 Installation 19.....................................................
Inspecting the Equipment 19........................................................
UPS Setup 19..................................................................
Mounting the UPS in a 19” Rack 20................................................
Mounting the UPS in a 23” Rack 23................................................
Zero-U Mounting 25...........................................................
Wall-Mount Setup 26..........................................................
Installing the UPS 27.............................................................
4 Operation 29......................................................
Turning the UPS On 29............................................................
Starting the UPS on Battery 29....................................................
Turning the UPS Off 29...........................................................
Standby Mode 30...............................................................
UPS Front Panel 30..............................................................
Initiating the Self-Test 30..........................................................
5 Additional UPS Features 31..........................................
Voltage Configuration 31..........................................................
Network T ransient Protector 32.....................................................
Load Segments 33...............................................................
6 Communication 35.................................................
USB Port 35...................................................................
Communication Port 36...........................................................
X-Slot Cards 37.................................................................
7 UPS Maintenance 39...............................................
UPS and Battery Care 39..........................................................
Storing the UPS and Batteries 39..................................................
Replacing Batteries 40............................................................
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
i
Table of Contents
Testing New Batteries 42..........................................................
Recycling the Used Battery 42......................................................
8 Specifications 43..................................................
9 Troubleshooting 47.................................................
Audible Alarms and UPS Conditions 47................................................
Silencing an Audible Alarm 48....................................................
Site Wiring Fault (120V Models Only) 48.............................................
Service and Support 51...........................................................
ii
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
CHAPTER 1
POWERWARE 5115 RM – ONE OF THE BEST!
The Powerware95115 Rack-Mount (RM) uninterruptible power system (UPS)isahigh-densitypowerprotection solution ideal for servers, storage systems, network equipment, and other critical devices.
The slim design and wide range of installation possibilities make the Powerware 5115 RM the most versatile UPS available. With only 1U (1.75) of rack-height, the UPS can be installed in rack-mount, wall-mount, side-mount (zero U), and bench-top applications.
Providing a true sine wave output, the UPS delivers smooth, continuous power during normal and battery operation. In addition, the UPS corrects incoming voltage fluctuations to further protect the connected equipment from power problems such as power sags and surges.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
1
Powerware 5115 RM – ONE OF THE BEST!
: Network Transient Protector guards your network communications
equipment from surges. Low voltage models can also protect modems, fax machines, or other telecommunications equipment.
: Optional X-SlotZ modules provide enhanced communication
capabilities for increased power protection and control.
: The Powerware 5115 RM is backed by worldwide agency approvals.
2
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
CHAPTER 2
SAFETY WARNINGS
Read the following precautions before you install the UPS.
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions that you should follow during installation and maintenance o f the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
: This UPS contains its own energy source (batteries). The output receptacles may
carry live voltage even when the UPS is not connected to an AC supply.
: For 200–240V models, the output receptacles may remain electrically live. If the
input power source in your application is wired line-to-neutral (as in most European applications), the voltage to the output receptacles is 0V. With line-to-line input wiring, the voltage to the output receptacles is 100–120V (measured from line-to-ground or line-to-neutral, depending on the UPS wiring).
: Do not remove or unplug the input cord when the UPS is turned on. This removes
the safety ground from the UPS and the equipment connected to the UPS.
: To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40 excessive humidity (95% max).
: To comply with international standards and wiring regulations, the total equipment
connected to the output of this UPS must not have an earth leakage current greater than 3.5 milliamperes.
SAVE THESE INSTRUCTIONS
DANGER
WARNING
C (104F). Do not operate near water or
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
3
Safety Warnings
: The wall outlet must be within 2 meters of the equipment and accessible to the
operator.
: Batteries can present a risk of electrical shock or burn from high short-circuit
current. The following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries; 4) Disconnect charging source prior to connecting or disconnecting battery terminals.
: Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
: Never dispose of batteries in a fire. Batteries may e xplode when exposed to flame. : Never open or mutilate batteries. Released electrolyte is harmful to the skin and
eyes, and may be extremely toxic.
: Replace batteries with the same number and type of batteries as originally
installed in the UPS.
Sikkerhedsanvisninger
CAUTION
VIGTIGE SIKKERHEDSANVISNINGER GEM DISSE ANVISNINGER DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE SIKKERHEDSANVISNINGER
FARE
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og vedligeholdelse bør kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af UPS’ens indvendige dele kan repareres af brugeren.
ADVARSEL!
: Denne UPS indeholder egen energiforsyning (batterier). Udgangsnetstikkene kan
lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde.
: Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er
tændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.
: Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit
for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stød. Rumtemperaturen må ikke overstige 40 vand eller høj fugtighed (maksimalt 95%).
4
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
C. UPS’en bør ikke betjenes nær
: I overensstemmelse med internationale normer og bestemmelser for el-installation
må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 3,5 milliampere.
: Stikkontakten skal være højest 2 meter fra udstyret og skal være tilgængeligt til
operatøren.
: Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj
kortslutningsspænding. De korrekte forholdsregler bør overholdes.
: Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for
bortskaffelsesprocedurer.
: Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere
ved åben ild.
: Batterierne bør aldrig åbnes eller skilles ad. Udløst elektrolyt er skadeligt for hud
og øjne og kan være yderst giftigt.
Belangrijke Veiligheidsinstructies
Safety Warnings
ADVARSEL
BELANGRIJKE VEILIGHEIDSINSTRUCTIES BEWAAR DEZE INSTRUCTIES DEZE HANDLEIDING BEVAT BELANGRIJKE VEILIGHEIDSINSTRUCTIES
GEVAAR
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd. Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden GEREPAREERD.
WAARSCHUWING
: Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingen
kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten.
: Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit
terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
5
Safety Warnings
: Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in
een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40
C niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge
vochtigheid (max. 95%).
: Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de
gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van meer dan 3,5 milliampère hebben.
OPGELET
: De hoofdvoedingcontactdoos moet zich op minder dan 2 meter vande apparatuur
bevinden en makkelijk bereikbaar zijn voor de gebruiker.
: Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als
gevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op.
: De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw
plaatselijke voorschriften.
: Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. : Nooit batterijen openen of verminken. Vrijkomend elektrolyt is schadelijk voor de
huid en ogen, en kan uiterst giftig zijn.
Tarkeita Turvaohjeita
TÄRKEITÄ TURVAOHJEITA - SUOMI SÄILYTÄ NÄMÄ OHJEET TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.
: Tämä UPS sisältää oman energialähteen (akuston). Ulostuloliittimissä voi olla
jännite, kun UPS ei ole liitettynä verkkojännitteeseen.
: Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaa
turvamaadoituksen UPS-laitteesta ja siihen liitetystä laitteistosta.
6
VAARA
VAROITUS
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Safety Warnings
: Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin,
joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia epäpuhtauksia. Ympäristön lämpötila ei saa ylittää 40 ja vältä kosteita tiloja (95 % maksimi).
C. Älä käytä lähellä vettä
: Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän
UPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 3,5 milliampeeria (mA).
VARO
: Päävirtapistokkeen täytyy olla 2 m:n säteellä laitteistosta ja käyttäjän saatavilla.
UPS-laitteen virtakytkin ei eristä sisäosia virran saannilta.
: Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään
oikosulkuun. Noudata asianmukaisia ohjeita.
: Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia
määräyksiä.
: Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. : Älä avaa tai riko akkua. Paljastunut elektrolyytti on vahingollinen iholle ja silmille
ja voi olla erittäin myrkyllistä.
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES
DANGER!
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ. AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.
AVERTISSEMENT!
: Cet onduleur renferme sa propre source d’énergie (batteries). Les prises de sortie
peuvent être sous tension même lorsque l’onduleur n’est pas branché sur le secteur.
: Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension sous
peine de supprimer la mise à la terre de l’onduleur et du matériel connecté.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
7
Safety Warnings
: Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur
uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la température et l’humidité ambiantes sont contrôlées. La température ambiante ne doit pas dépasser 40 excessivement humide (95 % maximum).
C. Ne pas utiliser à proximité d’eau ou dans une atmosphère
: Afin d’être conforme aux normes et règlements internationaux de câblage, le
courant de fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas dépasser 3,5 mA.
ATTENTION!
: La prise principale secteur doit se trouver à moins de 2 mètres du matériel et être
accessible à l’utilisateur.
: Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par
des courts-circuits de haute intensité. Prendre les précautions nécessaires.
: Une mise au rebut réglementaire des batteries est obligatoire. Consulter les
règlements en vigueur dans votre localité.
: Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire
exploser.
: Ne jamais ouvrir ou mutiler des batteries. L’électrolyte qui s’en échappe est
nuisible à la peau et aux yeux et peut s’avérer extrêmement toxique.
Sicherheitswarnungen
WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAHREN. DIESES HANDBUCH ENTHÄLT WICHTIGE SICHERHEITSANWEISUNGEN.
Die USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten sollten nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine vom Benutzer zu wartenden Komponente
: Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An den
Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USV nicht an einer Wechselspannungsquelle angeschlossen ist.
8
WARNUNG
ACHTUNG
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Safety Warnings
: Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet
ist, weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Geräten entfernt wird.
: Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden
mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40 nicht übersteigen. Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %) betreiben.
C
: Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an
den Ausgang dieser USV angeschlossenen Geräte zusammen einen Erdschlußstrom von insgesamt 3,5 Milliampere nicht überschreiten.
VORSICHT!
: Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oder
Verbrennungen verursachen. Folgende Vorkehrungen sollten getroffen werden, wenn Sie mit der Battery arbeiten: 1) Entfernen Sie Uhren, Ring und andere metallische Objekte; 2) Verwenden Sie Werkzeug mit isolierten Griffen.
: Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen
Bestimmungen zu beachten.
: Batterien niemals verbrennen, da sie explodieren können. : Öffnen oder beschädigen Sie nicht die Batterien, ausfließendes Elektrolyt ist
schädlich für Haut und Augen.
: Falls Sie die Batterien austauschen, verwenden Sie bitte ausschließlich die gleiche
Anzahl und die Batterietypen.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
9
Safety Warnings
РспейдпрпйЮуейт БуцЬлейбт
УЗМБНФЙКЕУ ПДЗГЙЕУ БУЦБЛЕЙБУ ЦХЛБОФЕ БХФЕУ ÔÉÓ ПДЗГЙЕУ ÔÏ РБСПН ЕГЧЕЙСЙДЙП РЕСЙЕЧЕЙ УЗМБНФЙКЕУ ПДЗГЙЕУ БУЦБЛЕЙБУ
Áõôü ôï UPS ресйЭчей ИБНБФЗЦПСБ ÔÁÓÇ. ¼ëåò ïé ерйукехЭт êáé ïé ухнфзсЮуейт рсЭрей íá ãЯнпнфбй ÌÏÍÏ ÁÐÏ ЕОПХУЙПДПФЗМЕНП ÃÉÁ ÔÇ УХНФЗСЗУЗ РСПУЩРЙКП. Ôï UPS ÄÅÍ РЕСЙЕЧЕЙ КБНЕНБ ЕОБСФЗМБ ÐÏÕ ÍÁ МРПСЕЙ ÍÁ ЕРЙУКЕХБУФЕЙ ÁÐÏ ÔÏ ЧСЗУФЗ.
РСПЕЙДПРПЙЗУЗК
:
Ôï óõãкексймЭнп UPS ресйЭчей ôç äéêÞ ôïõ ðçãÞ енЭсгåéáò (ухуущсехфЭт). Ïé сехмбфпдьфет еоьдпх мрпсеЯ íá Эчпхн енесгü ôÜóç бкьмз êáé üôáí ôï UPS äåí еЯнбй ухндедемЭнп óå ðçãÞ енбллбууьменпх сеэмбфпт (AC).
:
Ìçí âãЬжефе áðü ôçí рсЯжб ôï кблюдйп фспцпдпуЯбт üôáí ôï UPS еЯнбй бнпйчфь. Ì UPS êáé áðü ôïí еопрлйумь ðïõ еЯнбй óхндедемЭнпт ìå ôï UPS.
:
Ãéá íá мейюуефе ôïí кЯндхнп рхскбгéÜò Þ злекфспрлзоЯбт, åãкбфбуфЮуфе ôï óõãкексймЭнп UPS óå еущфесйкь ÷þñï ìå åëåãчьменз иесмпксбуЯб êáé õãсбуЯб, ï прпЯпт íá ìçí ресйЭчей áãþãéìá хлйкЬ. Ç иесмпксбуЯб ресйвЬллпнфпт äåí рсЭрей íá оереснЬей ôïõò 40 хресвплйкЮ õãсбуЯб (ìÝãéóôç ôéìÞ: 95%).
:
Ãéá íá ухмцщнеЯ ìå ôá дйеинЮ рсьфхрб êáé ôïõò кбнпнйумпэт кблщдЯщузт, ôï сеэмб дйбсспЮт ðñïò ôç ãç пльклзспх ôïõ еопрлйумпэ, ðïõ еЯнбй ухндедемЭнпт ìå ôçí Эопдп ôïõ óõãкексймЭнпх UPS, äåí рсЭрей íá еЯнбй ìåãблэфесп áðü 3,5 mA.
áõôü ôïí фсьрп бцбйсеЯфе ôç ãеЯщуз буцблеЯбт áðü ôï
КЙНДХНПУ
C. Ìç чсзуймпрпйеЯфе ôï UPS кпнфЬ óå íåñü Þ
10
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
:
:
:
Avvisi di sicurezza
IMPORTANTI ISTRUZIONI DI SICUREZZA CONSERVARE QUESTE ISTRUZIONI QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONI DI SICUREZZA
la TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo statico di continuità NON vi sono PARTI RIPARABILI DALL’UTENTE.
Safety Warnings
РСПУПЧЗ
Ïé ухуущсехфЭт мрпсеЯ íá рспкблЭупхн злекфспрлзоЯб Þ Ýãкбхмб áðü õøçëü сеэмб всбчхкхклюмбфпт. ЛбмвЬнефе ôéò кбфЬллзлет рспцхлЬоейт.
БрбйфеЯфбй ущуфЮ дйЬиеуз ôùí ухуущсехфюн. ДеЯфе ôïõò фпрйкпэт кбнпнйумпэт ðïõ бцпспэн ôéò брбйфЮуейт дйЬиеуЮт ôïõò.
ÐïôÝ ìçí рефЬфе ôïõò ухуущсехфЭт óôç öùôéÜ, ãéáôß мрпсеЯ íá ексбгïýí.
PERICOLO
AVVERTENZA
: Questo gruppo statico di continuità contiene una fonte di energia autonoma (le
batterie). Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di continuità non è collegato con una fonte di alimentazione a corrente alternata.
: Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di
continuità è acceso poichè in tal modo si disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuità e dell’apparecchiatura ad esso collegata.
: Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di
continuità in un ambiente interno a temperatura ed umidità controllata, privo di agenti contaminanti conduttivi. La temperatura ambiente non deve superare i
C. Non utilizzare l’unità in prossimità di acqua o in presenza di umidità
40 eccessiva (95% max).
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
11
Safety Warnings
: Per conformità con gli standard internazionali e con le norme in merito al
cablaggio, tutta l’apparecchiatura collegata con l’uscita del gruppo statico di continuità non deve avere una corrente di dispersione di terra superiore a 3,5 milliampere.
ATTENZIONE
: La presa di alimentazione principale non deve trovarsi a oltre 2 metri
dall’apparecchiatura e deve essere accessibile all’operatore.
: Le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da
alta corrente dovuta a corto circuito. Osservare le apposite istruzioni.
: Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento
fare riferimento alle disposizioni locali.
: Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle
fiamme.
: Mai aprire nè mutilare le batterie poichè l’elettrolita da esse rilasciato è nocivo
alla cute e agli occhi e può essere altamente tossico.
Viktig Sikkerhetsinformasion
Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kun utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE SERVICE PÅ NOEN AV DELENE i UPS’en.
: Denne UPS’en har en egen energikilde (batterier). Stikkontaktene kan være
strømførende selv om UPS’en ikke er tilsluttet en vekselstrømforsyning.
: Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS’en er på, slik at
ikke sikkerhetsjordingen fjernes fra UPS’en og det utstyret som er forbundet med den.
: For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et
innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende, forurensende stoffer. Romtemperaturen må ikke overskride 40 ikke brukes i nærheten av vann eller ved meget høy luftfuktighet (95% maks.).
12
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
FARLIG
FARLIG
C. Den må
: Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere
total lekkasjestrøm enn 3,5 milliampere for å være i overensstemmelse med internasjonale standarder og forkablingsbestemmelser.
: Stikkontakten må befinne seg innen 2 m fra utstyret og må være tilgjengelig for
operatøren.
: Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy
kortslutningsstrøm. Følg instruksene.
: Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om
fjerning av batterier.
: Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild. : Batterier må aldri åpnes eller ødelegges. Frigjorte elektrolytter er skadelige for hud
og øyne og kan være ekstremt giftige.
Regulamentos de Segurança
Safety Warnings
FORSIKTIG
INSTRUÇÕES DE SEGURANÇA IMPORTANTES GUARDE ESTAS INSTRUÇÕES ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA IMPORTANTES
CUIDADO
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não há nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.
ADVERTÊNCIA
: Esta UPS contém sua própria fonte de energia (baterias). Os receptáculos de saída
podem conter voltagem ativa quando a UPS não se encontra conectada a uma fonte de alimentação de corrente alternada.
: Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto
removerá o aterramento de segurança da UPS e do equipamento conectado.
: Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente
interno com temperatura e umidade controladas e livres de contaminadores condutíveis. A temperatura ambiente não deve exceder 40 água ou em umidade excessiva (máx: 95%).
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
C. Não opere próximo a
13
Safety Warnings
: Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o
equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 3,5 miliampères.
PERIGO
: O soquete de alimentação principal deve estar à no máximo dois metros do
equipamento e acessível ao operador.
: As baterias podem apresentar o risco de choque elétrico, ou queimaduras
provenientes de alta corrente de curto-circuito. Observe as instruções adequadas.
: Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do
local para maiores informações sobre os regulamentos de descarte de produtos.
: Nunca jogue as baterias no fogo, porque há risco de explosão. : Nunca abra ou danifique as baterias. O eletrólito liberado é prejudicial à pele e
aos olhos e pode ser extremamente tóxico.
Предупреждения по мерам безопасности
14
ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ СОХРАНИТЕ ЭТИ УКАЗАНИЯ ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ
ОПАСНО
В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ. Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ. Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.
ПРЕДУПРЕЖДЕНИЕ
: Данный ИБП содержит собственные источники энергии
(аккумуляторы). На выходных розетках может иметься напряжение, даже когда ИБП не подключен к сети переменного тока.
: Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки
при включенном ИБП. При этом защитное заземление отключается от ИБП и от оборудования, подключенного к ИПБ.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Safety Warnings
: Для снижения опасности пожара или поражения электрическим
током устанавливайте ИБП в закрытом помещении с контролируемыми температурой и влажностью, в котором отсутствуют проводящие загрязняющие вещества. Температура окружающего воздуха не должна превышать 40 эксплуатируйте устройство около воды или в местах с повышенной влажностью (макс. 95%).
С. Не
: Для обеспечения соблюдения требований международных
стандартов и требований к разводке электрических цепей, суммарная величина тока утечки на землю всего оборудования, подключенного к выходу ИБП, не должна превышать 3,5 миллиампера.
ОСТОРОЖНО
: Аккумуляторы могут вызвать опасность поражения электрическим
током или ожога от тока короткого замыкания. Соблюдайте соответствующие меры предосторожности.
: Необходимо соблюдать правила утилизации аккумуляторов.
Обратитесь к местным нормативным актам за информацией о требованиях к утилизации.
: Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут
взорваться под воздействием огня.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
15
Safety Warnings
Advertencias de Seguridad
INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IMPORTANTES
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.
: Este SIE contiene su propia fuente de energía (las baterías). Los receptáculos de
salida pueden transmitir corriente eléctrica aun cuando el SIE no esté conectado a un suministro de corriente alterna (c.a.).
: No retire o desenchufe el cable de entrada mientras el SIE se encuentre
encendido. Esto suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE.
: Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un
lugar cubierto, con temperatura y humedad controladas, libre de contaminantes conductores. La temperatura ambiente no debe exceder los 40 del agua o con humedad excesiva (95% máximo).
: Para cumplir con los estándares internacionales y las normas de instalación, la
totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 3,5 miliamperios.
PELIGRO
ADVERTENCIA
C. No trabaje cerca
16
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
: El tomacorriente de pared debe encontrarse dentro de los 2 metros de distancia
del equipo y ser accesible para el operador.
: Las baterías pueden presentar un riesgo de descargas eléctricas o de quemaduras
debido a la alta corriente de cortocircuito. Preste atención a las instrucciones correspondientes.
: Es necesario desechar las baterías de un modo adecuado. Consulte las normas
locales para conocer los requisitos pertinentes.
: Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las
expone a la llama.
: Nunca abra o mutile las baterías. El electrolito liberado es peligroso para la piel y
los ojos, y puede ser extremadamente tóxico.
Säkerhetsföreskrifter
VIKTIGA SÄKERHETSFÖRESKRIFTER SPARA DESSA FÖRESKRIFTER DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA SÄKERHETSFÖRESKRIFTER
Safety Warnings
PRECAUCIÓN
FARA
Denna UPS-enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD SERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar som ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten.
VARNING
: Denna UPS-enhet har en egen energikälla (batterier). De utgående kontakterna kan
vara strömförande när UPS-enheten inte är ansluten till en växelströmkälla.
: Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort
skyddsjordningen från både UPS-enheten och den anslutna utrustningen.
: Minska risken för brand eller elektriska stötar genom att installera denna
UPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40 Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
C.
17
Safety Warnings
: För att överensstämma med internationell standard och installationsföreskrifter får
inte den totala utrustning som anslutits till uttagen på denna UPS-enhet ha läcksström som överstiger 3,5 milliampere.
VIKTIGT
: Huvudkontakten måste vara högst 2 meter från utrustningen och inom räckhåll för
användaren.
: Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström.
Följ tillämpliga anvisningar.
: Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. : Använda batterier får aldrig brännas upp. De kan explodera. : Öppna aldrig batterierna eller ta isär dem. Utsläppt elektrolyt är skadlig för hud
och ögon och kan vara mycket giftig.
18
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
CHAPTER 3
INSTALLATION
This section explains:
: Equipment inspection : UPS setup and installation : UPS rear panels
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service representative.
NOTE Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative.
UPS Setup
The Powerware 5115 RM UPS is designed for flexible configurations and can be installed in a rack, on a wall, or as a standalone cabinet. Set up the UPS according to the type of installation:
: “Mounting the UPS in a 19Rack” on the following page. : “Mounting the UPS in a 23Rack” on page 23. : “Zero-U Mounting” on page 25. : “Wall-Mount Setup” on page 26.
If you are using the UPS as a standalone cabinet, skip to “Installing the UPS” on page 27.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
19
Installation
Mounting the UPS in a 19” Rack
Use the following procedure to install the UPS in 19rack configuration:
1. Place the UPS on a flat, stable surface with the front of the UPS facing toward you.
2. On each side of the UPS, attach the long end of a mounting bracket to the UPS using four of the supplied M3 (see Figure 2).
Mounting Bracket
l 6 screws
20
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Installation
M6 l 10 Rear Rail Screws
Clip Nuts
Figure 4. Securing the Rear Rail
7. Secure only the bottom hole of the rail to the front of the rack with one M6
l 10 screw and clip nut (see Figure 5).
8. Install a clip nut in the top hole of the rail.
9. Repeat Steps 6 through 8 for the other rail.
10. Tighten the assembly wing nuts on both rail assemblies.
Assembly Wing Nuts
Clip Nuts
M6 l 10
Front Rail Screw
Figure 5. Securing the Front Rail
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
21
Installation
11. After installing the UPS chassis, secure the front of the UPS to the rack using the supplied hardware (one M6
l 10 screw on
each side as shown in Figure 6).
22
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Mounting the UPS in a 23” Rack
Use the following procedure to install the UPS in a 23rack configuration:
1. Place the UPS on a flat, stable surface with the front of the UPS facing toward you.
2. On each side of the UPS, attach the short end of a mounting bracket to the UPS using two of the supplied M3 (see Figure 7).
l 6 screws
Installation
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
23
Installation
4. After installing the UPS chassis, secure the front of the UPS to the rack using the supplied hardware (two M6
l 10 screws and
two clip nuts on each side, as shown in Figure 8).
Figure 8. Securing the UPS in a 23” Rack
24
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Zero-U Mounting
Use the following procedure to install the UPS in a zero-U rack configuration:
1. Place the UPS on a flat, stable surface with the front of the UPS facing toward you.
2. Attach four mounting brackets to the UPS as shown Figure 9.
Secure the short end of the mounting bracket to the UPS using two of the supplied M3
3. Adjust the sides of the rack to fit the UPS and brackets (within
22.54–22.78or 56.35–56.95 cm).
4. Secure the UPS to the side of the r ack cabinet using one
l 10 screw and one clip nut in each mounting bracket.
M6
l 6 screws.
Installation
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
25
Installation
Wall-Mount Setup
Use the following procedure to mount the UPS to a wall:
1. Place the UPS on a flat, stable surface with the front of the UPS facing toward you.
2. Attach four mounting brackets to the UPS as shown Figure 10.
Secure the short end of the mounting bracket to the UPS using two of the supplied M3
l 6 screws.
WARNING
The UPS MUST be positioned with the front panel at the top to prevent a battery hazard.
3. Secure the UPS to the wall using one bolt in each mounting bracket as shown. Select the bolt according to the wall type.
26
Wall
Figure 10. Mounting the UPS to a Wall
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Installing the UPS
The following steps explain how to install the UPS. See Figure 11 and Figure 12 for the UPS rear panels.
NOTE If you need to change the factory-set defaults for the output voltage or input voltage range, see “Voltage Configuration” on page 31 before installing the UPS.
Installation
1. If you did not mount the UPS in a r ack or to a wall, you can use the UPS as a standalone unit by placing the UPS in a flat, horizontal position.
2. If you are installing power management software, connect your computer to the USB port or UPS communication port using the supplied cable (see page 35).
3. Plug the equipment to be protected into the UPS output receptacles.
DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements.
4. On 230V models, plug the detachable power cord into the input connector on the UPS rear panel.
Communication Bay
X-Slot
6-ft Power Cord with
5-15 Plug
Network Transient
USB Port
Site Wiring Fault
Indicator
Protector
DIP Switches
Communication Port
Four 5-15 Receptacles
Figure 11. 500–1500 VA, 120V Rear Panel
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
27
Installation
10A, IEC-320 Input Connector
Communication Port
28
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
CHAPTER 4
OPERATION
This section describes:
: Turning the UPS on and off : Starting the UPS on battery : Standby mode : The UPS front panel and indicators : Initiating the self-test
Turning the UPS On
After the UPS is connected to a power outlet, the UPS enters Standby mode. T o turn on the UPS, press and hold the the UPS beep (approximately two seconds). After the UPS is turned on, it conducts a self-test and enters Normal mode. The Load 2 indicators illuminate indicating that power is available from the UPS output receptacles.
Starting the UPS on Battery
NOTE The UPS does not auto-detect the input frequency when starting on battery; the
default is the last frequency used by the UPS.
button until you hear
,Load1,and
To turn on the UPS without using utility power, press and hold the
button for two seconds. The UPS supplies power to your equipment
and goes into Battery mode.
Turning the UPS Off
To turn off the UPS, press and hold the button for two seconds and then unplug the UPS from the power outlet. If you do not unplug the UPS, it remains in Standby mode.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
29
Operation
Standby Mode
UPS Front Panel
When the UPS is turned off and remains plugged into a power outlet, the UPS is in Standby mode. All indicators are off and power is not available to your equipment. The battery recharges when necessary.
NOTE For 200–240V models, the output receptacles may remain electrically live (up to 100–120V). Unplug the UPS to ensure power is not available to the output receptacles.
The UPS front panel indicates the UPS status and also identifies potential power problems. Figure 13 shows the UPS front panel indicators and controls.
Load Segment 2 Indicator (Green)
Load Segment 1 Indicator (Yellow)
If the alarm beeps or a UPS alarm indicator stays on, see Table 8 on page 48 to identify and correct the problem.
Initiating the Self-Test
NOTE The batteries must be fully charged and the UPS must not be in Battery mode
to perform the self-test.
Press and hold the button for three seconds to initiate the self-test. If the UPS finds a problem, an LED indicates where the problem is. For more information, see “Troubleshooting” on page 47.
Service Indicator (Red)
On Battery Indicator (Yellow) Overload Indicator (Red)
Figure 13. UPS Front Panel
Power On Indicator (Green)
On/Off Button
Test/Alarm Reset Button
30
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
CHAPTER 5
ADDITIONAL UPS FEATURES
This section describes:
: Changing the voltage configuration : The Network Tr ansient Protector : Load segments
Voltage Configuration
The DIP switches on the UPS rear panel (see Figure 14) are used to configure the output voltage and input voltage range.
1. The UPS must be completely shutdown.
To turn off the UPS, press and hold the seconds and then unplug the UPS from the power outlet.
2. Set the DIP switches according to the configurations in Table 1.
3. Plug the UPS into a power outlet.
4. Press and hold the
(approximately two seconds) to turn the UPS on.
button for two
button until you hear the UPS beep
UPS Rear Panel
Figure 14. DIP Switches
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
ON
OFF
21
31
Additional UPS Features
Table 1. DIP Switch Settings
Output Voltage Input Voltage Range DIPSwitch1 DIPSwitch2
110V 99V-116V ON OFF/ON 120V* 108V–127V* OFF OFF/ON
Output Voltage Input Voltage Range DIPSwitch1 DIPSwitch2
220V 198V–233V ON OFF 230V* 207V–243V* OFF OFF/ON 240V 216V–254V ON ON
*Default position
Network Transient Protector
The Network Transient P rotector, shown in Figure 15, is located on the rear panel and has jacks labeled IN and OUT. This feature accommodates a single RJ-45 (10BaseT) network connector.
Low voltage models can also accommodate an RJ-11 telephone connector that provides protection for modems, fax machines, or other telecommunications equipment. As with most modem equipment, it is not advisable to use this jack in digital PBX (Private Branch Exchange) environments.
120V Models
230V Models
32
NOTE DO NOT connect any telephone or fax/modem equipment to the 230V models;
only network protection is available for 230V models.
1. Connect the input connector of the equipment you are protecting to the jack labeled IN.
2. Connect the network or telephone cable (low voltage models only) to the jack labeled OUT.
OutIn
Figure 15. Network Transient Protector
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Load Segments
Additional UPS Features
Load segments are sets of receptacles that can be controlled by power management software, providing an orderly shutdown and startup of your equipment. For example, during a power outage, you can keep key pieces of equipment running while you turn off other equipment. This feature allows you to save battery power. See your power management software manual for details.
NOTE If the power management software is not used, the individual load segments cannot be controlled.
Each model has two load segments as shown in Figure 16 and Figure17.TheLoad1andLoad2indicatorsontheUPSfrontpanel illuminate when output power is available to the specific load segment.
Load Segment 1 Load Segment 2
Figure 16. UPS Load Segments for 120V Models
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
33
Additional UPS Features
34
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
CHAPTER 6
COMMUNICATION
The Powerware 5115 RM has flexible communication options for local, network, or remote monitoring and management. You can use the USB port or the DB-9 communication port to connect your computer to the UPS. The X-Slot communication bay is also available for additional connectivity options.
NOTE Select only one method for communication. If an X-Slot card is installed, the USB and DB-9 ports are disabled. If an X-Slot card is not installed, be sure that only one port (USB or DB-9) is connected to the computer.
USB Port
The UPS can communicate with a USB-compliant computer using LanSafe Power Management Software (v4.15 or higher).
To establish communication between the UPS and a computer:
1. Connect the USB cable to the USB port on the UPS rear panel.
Connect the other end of the USB cable to the USB port on your computer.
USB Port
Figure 18. The USB Port
2. Install the LanSafe software and USB drivers according to the instructions provided with the Powerware Software Suite CD.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
35
Communication
Communication Port
To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable.
When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.
The cable pins are identified in Figure 19 and the pin functions are described in Table 2.
Table 2. Communication Port Pin Assignment
Pin Number
3
245
1
9
87
6
Figure 19. Communication Port
Signal Name Function Direction
from the UPS
36
1 Low Batt Low Battery relay contact; 20 mA, 30 Vdc
contact rating 2 TxD Transmit to external device Out 3 RxD Receive from external device In 4 DTR PnP (Plug and Play) from external device (tied
to Pin 6) 5 GND Signal common (tied to chassis) — 6 DSR To external device (tied to Pin 4) Out 7 No Connection — 8 AC Fail AC Fail relay contact; 20 mA, 30 Vdc contact
rating 9 Power Source +V (8 to 24 volts DC power) Out
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Out
In
Out
X-Slot Cards
ConnectUPS-X Web/SNMP Card
Communication
X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Powerware 5115 RM is compatible with any X-Slot card, including:
: ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities
Z
as w ell as monitoring through a Web browser interface; connects to a twisted-pair Ethernet (10/100BaseT) network.
: Multi-Server Card - has six serial communication ports that can
communicate simultaneously with other computers using LanSafe Power Management Software (provided on the Powerware Software Suite CD).
X-Slot Communication Bay
Multi-Server Card
Figure 20. Optional X-Slot Cards
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
37
Communication
38
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
CHAPTER 7
UPS MAINTENANCE
This section explains how to:
: Care for the UPS and batteries : Replace the batteries : Test new batteries : Recycle used batteries
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of 25°C (77°F).
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the battery every 6 m onths by plugging the UPS into a power outlet. The batteries charge to 90% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 6 to 24 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date has expired and the batteries wer e never recharged, do not use the UPS. Contact your service representative.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
39
UPS Maintenance
Replacing Batteries
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
With the hot-swappable battery feature, UPS batteries can be replaced easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the battery, press and hold the
Consider all warnings, cautions, and notes before replacing batteries.
: Batteries can present a risk of electrical shock or burn from high short circuit
: ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or
: Replace batteries with the same number and type of batteries as originally
button for two seconds and then unplug the UPS.
WARNING
current. The following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries.
connectors. Attempting to alter wiring can cause injury.
installed in the UPS.
40
CAUTION
Pull the battery group out onto a flat, stable surface. The battery is unsupported when you pull it out of the UPS.
Use the following steps to replace the batteries:
1. Pull the left side of the front panel to release the snaps to the left and middle of the panel. Remove the front panel from the right side.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
UPS Maintenance
2. Disconnect the white battery connector.
3. Remove and set aside the battery cover.
4. Pull the battery group out onto a flat, stable surface. See
“Recycling the Used Battery” on page 42 for proper disposal.
5. Slide the new battery group into t he UPS.
6. Reinstall the battery cover removed in Step 3.
7. Reconnect the white battery connector .
8. Reinstall the front panel.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
41
UPS Maintenance
Testing New Batteries
NOTE It is recommended that the batteries charge for 6 to 24 hours before testing.
Press and hold the button for three seconds to initiate a self-test. The 15-second test automatically distributes the load to the batteries and tests the battery’s performance. While the test is in progress, the indicators cycle through and the alarm sounds. When complete, the UPS returns to Normal mode as indicated by the
If there is a problem with the battery, the alarm beeps, the illuminates and the and be sure the battery is fully charged. Call your service representative if the problem persists.
Recycling the Used Battery
Contact your local recycling or hazardous waste center for information on proper disposal of the used battery.
and Load indicators.

indicator
indicator flashes. Check the battery connections
42
WARNING
: Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper
disposal of batteries is required. Refer to your local codes for disposal requirements.
: Do not open or mutilate the battery or batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
CAUTION
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your local recycling or hazardous waste center.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
CHAPTER 8
SPECIFICATIONS
This section provides the following specifications for the Powerware 5115 RM models:
: Dimensions and weights : Electrical input and output : Environmental and safety
: Battery
Table 3. Model List and Mechanical
120V Models 230V Models
UPS Models PW5115 500 RM
PW5115 750 RM PW5115 1000 RM PW5115 1500 RM
UPS Dimensions (WxHxD) 44.0 x 4.45 x 57.8 cm (17.3x1.75x 22.75) UPS Weights 500 VA: 17.36 kg (38.2 lb)
750–1000 VA: 20.23 kg (44.5 lb)
1500 VA: 22.95 kg (50.5 lb)
Table 4. Electrical Input
120V Models 230V Models
Nominal Voltage 120V default; 110V, 120V selectable 230V default; 220V, 230V, 240V selectable Voltage Range ±20% for nominal voltage at full load Nominal Frequency 45–65 Hz, 50/60 Hz auto-sensing Efficiency (Normal mode) 95% Noise Filtering Full-time EMI/RFI filtering Overcurrent Protection AC source overcurrent protection device Resettable input circuit protector Connections 6-ft, 5-15P power cord 10A, IEC-320 input connector
PW5115 500iRM
PW5115 750iRM PW5115 1000iRM PW5115 1500iRM
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
43
Specifications
Table 5. Electrical Output
120V Models 230V Models
Power Levels (rated at nominal inputs)
Power Factor 500 VA, 0.64
Regulation (Normal mode) -10% to +6% of nominal voltage
Regulation (Battery mode), Nominal Voltage ±5%
Voltage Waveform Sine wave Overcurrent Protection Inverter saturation current limited Output Receptacles (4) 5-15 (4) 10A, IEC-320
Same as selected nominal input voltage
500 VA, 320W 750 VA, 520W
1000 VA, 670W
1440 VA, 1000W
110V, 120V
500 VA, 320W 750 VA, 520W
1000 VA, 670W
1500 VA, 1000W
750–1500 VA, 0.67–0.69
Same as selected nominal input voltage
220V, 230V, 240V
Table 6. Environmental and Safety
120V Models 230V Models
Operating Temperature Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
Above 1,500 meters: 0°C to 35°C (32°F to 95°F)
Transit/Storage Temperature
Relative Humidity 5–95% noncondensing Operating Altitude Up to 3,000 meters above sea level Audible Noise Less than 45 dBA typical Surge Suppression ANSI C62.41 Category A (formerly IEEE 587) Safety Conformance UL 1778; UL 497A;
CSA C22.2, No. 107.1
Safety Markings UL, cUL UL, cUL, CE, TÜV EMC (Class B) FCC Part 15, ICES-003 EN 50091-2, FCC Part 15, ICES-003
-15°C to 55°C (5°F to 131°F)
UL 1778, UL 497A (data line only);
CSA C22.2, No. 107.1;
EN 50091-1-1 and IEC 60950
44
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Specifications
Table 7. Battery
Configuration 500 VA: (2) 6V, 9 Ah internal battery
750 VA: (4) 6V, 7.2 Ah internal batteries 1000 VA: (4) 6V, 9 Ah internal batteries 1500 VA: (6) 6V, 9 Ah internal batteries
Voltage 500 VA: 12 Vdc
750–1000 VA: 24 Vdc 1500 VA: 36 Vdc
Type Sealed, maintenance-free, valve-regulated, lead-acid Charging Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at
nominal line and no supplementary power supply load
Monitoring Advanced monitoring for earlier failure detection and warning Battery Run Times 5 minutes, typical at full load
NOTE
Battery times are approximate and may vary depending on the load configuration and battery charge.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
45
Specifications
46
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
CHAPTER 9
TROUBLESHOOTING
This section explains:
: UPS alarms and conditions : How to silence an alarm : Site wiring fault on 120V models : Service and support
Audible Alarms and UPS Conditions
The UPS has an audible alarm feature to alert you of potential power problems. Use Table 8 to determine and resolve the UPS alarms and conditions.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
47
Troubleshooting
on;theUPSdoesnotstart
Silencing an Audible Alarm
Before silencing an alarm, check the alarm condition and perform the applicable action to resolve the condition (see Table 8). To silence the alarm for an existing fault, press the button. If UPS status changes, the alarm beeps, overriding the previous alarm silencing.
Site Wiring Fault (120V Models Only)
The Site Wiring Fault indicator on the UPS rear panel illuminates if the ground wire connection does not exist or the line and neutral wires are reversed in the line receptacle. This indicator stays on until the condition is resolved. Have a qualified electrician correct the wiring fault. The UPS operates when the indicator is illuminated, but does not provideratednoiseandsurgesuppression.
Table 8. Troubleshooting
Alarm or Condition Possible Cause Action
The indicator is not
on; the UPS does not start.
The UPS operates in Battery mode only, even though normal utility power is present.
The UPS does not provide the expected backup time.
LOAD 2 LOAD 1
.
The power cord is not connected correctly.
The UPS is in Standby mode.
The wall outlet is faulty. Have a qualified electrician test and repair the outlet.
The input circuit protector is open (230V models only).
The batteries need charging or service.
Normal operation. None. The UPS is operating in Normal mode and
Check the power cord connections.
Press and hold the button until you hear the UPS beep (approximately two seconds) to supply power to the connected equipment.
Save your work and turn off your equipment. Turn off the UPS. Reduce the load, then press the input circuit protector on the UPS rear panel.
Plug the UPS into a power outlet for 24 hours to charge the battery. Press the button; if the alarm beeps, see “Replacing Batteries” on page 40 to replace the battery.
During extended power outages, turn off the UPS after saving your work and shutting down your computer to conserve battery power.
automatically provides consistent voltage with the Buck and Boost feature. Power is available to the load segments as indicated by Load 1 (Yellow) and Load 2 (Green).
48
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Troubleshooting
ActionPossible CauseAlarm or Condition
1 beep every 4 seconds. The UPS is on battery due
1 beep every 2 seconds. The battery is running low.
1 beep every 2 seconds.
1 beep per second.
1 beep per second.
to a utility failure.
The UPS is running on battery power because the input voltage is too high (>149V for 120V models; >290V for 230V models) or too low (<30V).
Power requirements exceed UPS capacity (overload is greater than 110%) or the load is defective.
The UPS is on battery, and the power requirements exceed UPS capacity (overload is greater than 110%) or the load is defective.
The UPS is powering your equipment with battery power. Prepare your equipment for shutdown. If this is an extended power outage, save your work and turn off your equipment to conserve battery power.
Two minutes or less of battery power remains (depending on load configuration and battery charge).
Save your work and turn off your equipment. The alarm cannot be silenced.
Correct the input voltage, if possible. The UPS continues to operate on battery until the condition is corrected or the battery is completely discharged.
If the condition persists, the input voltage in your area may differ from the UPS nominal.
The UPS will automatically shut down in 3 minutes. Save your work immediately and turn off your equipment. Turn off the UPS. The alarm cannot be silenced.
Remove some of the equipment from the UPS. You may need to obtain a larger capacity UPS.
Shutdown is imminent (30 seconds). Save your work and turn off your equipment. Turn off and unplug the UPS. The alarm cannot be silenced.
Remove some of the equipment from the UPS. Wait at least 5 seconds until all LEDs are off and restart the UPS. You may need to obtain a larger capacity UPS.
Battery test failed. Check the battery connections and be sure the battery
is fully charged. If the indicator still flashes, see “UPS
Maintenance” on page 39 to replace the battery. Call
Continuous beep.
UPS internal temperature is too high.
your service representative if the problem persists.
Shutdown is imminent. Save your work and turn off your equipment. Turn off and unplug the UPS. The alarm cannot be silenced.
Clear vents and remove any heat sources. Ensure the
Continuous beep.
airflow around the UPS is not restricted. Wait at least 5 minutes and restart the UPS. If the condition persists, contact your service representative.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
49
Troubleshooting
Continuous beep.
ActionPossible CauseAlarm or Condition
UPS fan fault. Save your work and turn off your equipment. Turn off
and unplug the UPS. Contact your service representative. The alarm cannot be silenced.
3 beeps every 10 seconds.
Continuous beep.
Continuous beep.
Failed attempt to start the UPS on battery.
The output wave is abnormal while the UPS is on battery.
The output voltage is below or above the limit while the UPS is on battery.
Plug the UPS into a power outlet for 24 hours to charge the battery. After charging the battery, press and hold the button for 3 seconds; then check the indicator. The alarm cannot be silenced.
If the indicator still flashes, see “UPS Maintenance” on page 39 to replace the battery.
Shutdown is imminent. Save your work and turn off your equipment. Turn off and unplug the UPS. Contact your service representative. The alarm cannot be silenced.
Save your work and turn off your equipment. Turn off and unplug the UPS. Contact your service representative. The alarm cannot be silenced.
50
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
Service and Support
If you have any questions or problems with the UPS, call your Local
Distributor
and ask for a UPS technical representative.
Troubleshooting
or the Help Desk at one of the following telephone numbers
In the United States: Europe, Middle East, Africa: Asia: Australia:
1-800-356-5737or1-608-565-2100 +44-17 53 608 700 +852-2830-3030 +61-3-9706-5022
Please have the following information ready when you call the Help Desk:
: Model number
: Serial number : Version number (if available) : Date of failure or problem : Symptoms of failure or problem : Customer return address and contact information
If repair is required, you will be given a Returned Material Authorization (RMA) Number. This number must appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging or request packaging from the Help Desk or distributor. Units damaged in shipment as a result of improper packaging are not covered under warranty. A replacement or repair unit will be shipped, freight prepaid for all warrantied units.
NOTE For critical applications, immediate replacement may be available. Call the
Help Desk for the dealer or distributor nearest you.
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com
51
Troubleshooting
52
Powerware®5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com