Powerware is a registered trademark of Powerware Corporation.
Copyright 2001 Powerware Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be
reproduced in any way without the express written approval of Powerware Corporation.
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
i
Table of Contents
ii
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
C H A P T E R 1
INSTALLATION
This section explains:
Equipment inspection
Safety precautions
UPS installation
UPS top and side panels
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping
cartons and packing materials for the carrier or place of purchase and
file a claim for shipping damage. If you discover damage after
acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with
the carrier within 15 days of receipt of the equipment; 2) Send a copy of
the damage claim within 15 days to your service representative.
Safety Precautions
Read the following precautions before you install the UPS.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you
should follow during installation and maintenance of the UPS and batteries. Please
read all instructions before operating the equipment and save this manual for future
reference.
WARNING
This UPS contains its own energy source (batteries). The output receptacles may
carry live voltage even when the UPS is not connected to an AC supply.
Do not remove or unplug the input cord when the UPS is turned on. This removes
the safety ground from the UPS and the equipment connected to the UPS.
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
1
Installation
To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient
temperature must not exceed 40°C (104°F). Do not operate near water or
excessive humidity (95% max).
With the exception of the user-replaceable battery, all servicing of this equipment
must be performed by qualified service personnel.
Before maintenance or repair, all connections must be removed. Before
maintenance, repair, or shipment, the unit must be completely switched off and
unplugged or disconnected.
CAUTION
Important NoticeThe UPS ground (earth) conductor carries leakage current from
the loads in addition to any leakage current generated by the UPS. This UPS
generates no more than 0.5 mA of current (120V Model), or 1 mA of current
(230V Model).
To limit the total leakage current to 3.5 mA, the load leakage must be limited to
3 mA on the 120V Model and 2.5 mA on the 230V Model.
If you do not know the load leakage current, replace the UPS power cord
(230V Model only) with a power cord that uses a locking plug with a minimum
rating of 10A (such as IEC 309).
If you do not have a matching receptacle, consult an electrician to install the
proper receptacle.
The three-wire receptacle that you plug the UPS into must have a good
(low-impedance) ground (protective earth) connection to provide a safe path for
leakage current.
Quick Startup
2
The Powerware 3110 provides protection against many power problems,
including power outages. It also provides spike suppression and line
noise filtering to protect your equipment.
1. On 230V Models, plug the UPS power cord into the input
connector on the UPS side panel.
2. Plug the equipment to be protected into the UPS output
receptacles.
DO NOT protect laser printers with the UPS because of the
exceptionally high power requirements of the heating elements.
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
3. Start the UPS by pressing the switch as shown in Figure 3
or Figure 4 on page 4. The Power indicator illuminates
indicating that power is available from the UPS output
receptacles.
The units beeps and the front panel LEDs illuminate several
times. The green indicator remains on, indicating normal
operation.
If the unit continues to beep, or if the green indicator is off
even though input power is available from the wall outlet, see
Troubleshooting" on page 13.
NOTE Let the unit charge the battery for at least 3 hours. You may use the unit while
the battery charges, but the battery backup runtime will be reduced until the battery is
fully charged. This will take up to 8 hours after a full discharge while the UPS is fully
loaded.
UPS Top and Side Panels
Figure 1 and Figure 3 identify features of the 120V Model (USA) units,
with attached input line cord. Figure 2 and Figure 4 identify features of
the 230V Model (European) units, which have a connector for the input
line cord as well as different output receptacles.
Installation
Fault Indicator
Output Receptacles
(Battery and Surge Protection)
Figure 1. 120V Model Top Panel
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
Power Indicator
Output Receptacles
(Surge Protection Only)
3
Installation
Fault Indicator
Output Receptacles
(Battery and Surge Protection)
Figure 2. 230V Model Top Panel
Network Transient Protector
Circuit BreakerPower Cord
Figure 3. 120V Model Side Panel (600 VA Shown)
Power Indicator
Output Receptacles
(Surge Protection Only)
Communication Port
On/Standby Switch
Network Transient Protector
Circuit BreakerInput Connector
Communication Port
On/Standby Switch
Figure 4. 230V Model Side Panel (600 VA Shown)
4
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
C H A P T E R 2
FEATURES
This section covers:
Using the communication port
Starting the UPS on battery
Communication Port
Powerware Corporation offers an accessory interface kit that allows you
to connect many types of computer systems to the UPS communication
port. For specific information on Powerware Corporation interface kits,
call your service representative.
Pinouts
Contacts consist of open collector circuits capable of switching up to
+30 Vdc, 6 mA resistive load.
Table 1. Communication Port Pin Assignment
PinSignal TypeFunction
1RS-232 Level Shutdown+12 Vdc signal held for 5 seconds on this pin shuts the UPS down
120 seconds later. The UPS restarts after 15 seconds when utility
power returns.
2Not UsedNot Used
3Normally Open On-Battery ContactA normally open contact that closes 15 seconds (pulls to
Common) after the UPS switches to battery power.
4CommonThe signal ground for all signal pins.
5Normally Open Low-Battery-Alarm ContactA normally open contact that closes (pulls to Common) during a
Low Battery Alarm.
6Normally Closed Low-Battery-Alarm ContactA normally closed contact that opens (releases from Common)
during a Low Battery Alarm. This tells some shutdown software
when to start a computer shutdown.
7Not UsedNot Used
8Normally Closed On-Battery ContactA normally closed contact that opens 15 seconds (releases from
Common) after the UPS switches to battery power.
9Not UsedNot Used
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
5
Features
Battery Start Feature
The Battery Start feature allows you to turn on the UPS when utility
power is not available. The battery-start range is up to about 40% of
nominal input; otherwise, the UPS displays an input voltage fault and
the alarm beeps.
Network Transient Protector
The Network Transient Protector is located on the side panel and has
jacks labeled IN and OUT. This feature accommodates a RJ11
telephone connector that provides protection for modems, fax machines,
or other telecommunications equipment. As with most modem
equipment, it is not advisable to use this jack in digital PBX (Private
Branch Exchange) environments.
Low voltage models can also accommodate a single RJ45 (10BaseT)
network connector.
Connect the input connector of the equipment you are protecting to the
jack labeled IN. Connect the output connector to the jack labeled OUT.
6
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
C H A P T E R 3
UPS MAINTENANCE
This section explains how to:
Care for the UPS and batteries
Replace the batteries
Recycle used batteries
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS
clean and dustfree. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of
25°C (77°F).
Storing the UPS
If you store the UPS for a long period, recharge the battery every
6 months by plugging the UPS into a power outlet.
Replacing Batteries
The Powerware 3110's battery is user-replaceable. Before replacing the
battery, make sure that you read the safety information below.
WARNING
Batteries can present a risk of electrical shock or burn from high short circuit
current. The following precautions should be observed: 1) Remove watches, rings,
or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or
metal parts on top of batteries.
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or
connectors. Attempting to alter wiring can cause injury.
Replace batteries with the same number and type of batteries as originally
installed in the UPS.
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
7
UPS Maintenance
CAUTION
The 230V Models require replacement by qualified service personnel.
1. Contact your service representative to order a replacement
battery. It must be the same type and rating as the original
battery (see Table 3 on page 12).
2. Switch off and unplug the protected equipment from the UPS.
3. Turn off the UPS and disconnect the power cord.
4. Turn the UPS upside down.
Battery
Battery Cover
Figure 5. Removing the Battery Cover and Battery
5. Remove the battery cover:
Models 425 and 600 Use a screwdriver to remove the four screws
securing the battery cover and lift the battery cover off.
Model 250 Press down on the battery cover tabs and slide the
battery cover off of the end of the case.
6. Lift the battery up and out of the case.
7. Disconnect the red and black cables from the used battery.
8. Replace the battery. See Recycling the Used Battery" for proper
disposal.
9. Reconnect the cables to the new battery; red to positive (
black to negative (
8
), and slide the battery back into the case.
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
+),
10. Replace the battery cover by pushing the cover until it snaps
into place securely. Replace any battery cover screws that were
removed to access the battery.
11. Turn the UPS right side up. Reconnect the UPS power cord and
turn the unit on.
12. Reconnect the equipment. Switch on the protected equipment
one piece at a time.
Recycling the Used Battery
Contact your local recycling or hazardous waste center for information
on proper disposal of the used battery.
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper
disposal of batteries is required. Refer to your local codes for disposal
requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
UPS Maintenance
WARNING
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed,
leadacid batteries and must be disposed of properly. For more information, contact
your local recycling or hazardous waste center.
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
CAUTION
9
UPS Maintenance
10
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
C H A P T E R 4
SPECIFICATIONS
Powerware Corporation reserves the right to change specifications
without prior notice.
Table 2. Electrical
120V Model230V Model
Nominal Voltage120V230V
Power Factor0.67
Voltage RangeOnline: 90152V
On Battery: 0100V and 152160V
Nominal Frequency50/60 Hz auto-sensing
5763 Hz (60 Hz)
4753 Hz (50 Hz)
Efficiency
(Normal mode)
Noise FilteringFull-time EMI/RFI filtering
Overcurrent ProtectionResettable circuit breaker
ConnectionsAttached 5-15P power cordIEC 320-C14 input connector
Power Levels
(rated at nominal
inputs)
Total Output Current10A maximum
Load CompatibilitySwitch-mode power supply or resistive load
Output Frequency
(Battery mode)
Connections(4) 5-15 receptacles with UPS
PW3110 250: 250 VA, 168W
PW3110 425: 425 VA, 285W
PW3110 600: 600 VA, 400W
50/60 Hz ±1 Hz of nominal frequency
and surge protection
(2) 5-15 receptacles with surge
protection only
> 95%
(4) IEC 320-C13 receptacles with UPS
(2) IEC 320-C13 receptacles with surge
Online: 176272V
On Battery: 0192V and 278290V
Input fault current: 15A maximum
PW3110 250i: 250 VA, 168W
PW3110 425i: 425 VA, 285W
PW3110 600i: 600 VA, 400W
and surge protection
protection only
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
C H A P T E R 5
TROUBLESHOOTING
The front panel LEDs and an audible beep indicate the UPS status (see
Table 6). The UPS beeps whenever the unit is on battery power or an
alarm is present.
Table 6. Troubleshooting
Alarm or ConditionPossible CauseWhat to Do
Normal operation.None. The UPS is operating in Normal mode.
Line loss due to:
1 beep every 5 seconds.
Utility power outage.
Loose plug connection. Check the power cord connections.
Tripped circuit breaker. Reset the circuit breaker.
Power cord failure.
Low battery alarm; shutdown is
imminent.
Wait for utility power to return.
Contact your service representative for a new power
cord.
Prepare for a UPS shutdown. Save your work and turn
off your equipment.
The unit automatically restarts when acceptable power
returns.
2 beeps every 5 seconds.
The battery needs charging or
service.
3 beeps every 5 seconds.
The battery is discharged and
battery power is not available.
3 beeps every 5 minutes.
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
Turn the UPS off and plug the UPS into a power outlet
for 24 hours to charge the battery. Turn the UPS on to
test the battery. If the alarm still beeps, see Replacing
Batteries" on page 7 to replace the battery.
The UPS automatically recharges the battery. The alarm
clears when the battery is recharged.
NOTE If the UPS has not recharged the battery after
24 hours, the alarm changes to 3 beeps every 5 seconds
and the battery must be replaced. See Replacing
Batteries" on page 7 to replace the battery.
13
Troubleshooting
What to DoPossible CauseAlarm or Condition
Power requirements exceed the
UPS capacity.
1 beep every half second.
Output short circuit.Turn off or unplug the equipment connected to the UPS.
Input voltage is out of range
when the UPS is turned on.
Continuous beep.
UPS fault.Contact your service representative.
Service and Support
If you have any questions or problems with the UPS, call your Local
Distributor
and ask for a UPS technical representative.
In the United States1-800-365-4892
In Canada1-800-461-9166
All other countries1-919-870-3149
Please have the following information ready when you call the Help
Desk:
Model number
Serial number
Version number (if available)
Date of failure or problem
Symptoms of failure or problem
Customer return address and contact information
If repair is required, you will be given a Returned Material Authorization
(RMA) Number. This number must appear on the outside of the
package and on the Bill Of Lading (if applicable). Use the original
packaging or request packaging from the Help Desk or distributor. Units
damaged in shipment as a result of improper packaging are not covered
under warranty. A replacement or repair unit will be shipped, freight
prepaid for all warrantied units.
Remove some of the equipment from the UPS. You may
need to obtain a larger capacity UPS.
Turn off the UPS until acceptable input voltage
restored.
or the Help Desk at one of the following telephone numbers
14
NOTE For critical applications, immediate replacement may be available. Call the
Help Desk for the dealer or distributor nearest you.
Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.