Powers ES200-400 User Manual

Page 1
The Series ES Hydroguard thermostatically blends hot and cold water to deliver tepid water to emergency fixtures, quickly compensating for temperature variations due to changes in inlet temperature or pressure. Powers’ exclusive Dual Internal By-Pass* ensures cold water flow in the event of a valve failure or loss of hot water.
* US Patent 6,575,377
DESCRIPTION
• Properly size each valve based on the individual application
• Properly design the recirculation system to minimize pressure and temperature variations
• Conduct an weekly maintenance program to insure proper operation of all critical components
FAILURE TO COMPLY WITH PROPER INSTALLATION INSTRUCTIONS COULD CONTRIBUTE TO VALVE FAILURE, RESULTING IN INJURY OR DEATH.
TECHNICAL INSTRUCTIONS
Hydroguard®ES Series Emergency Tempering Valves
with Dual Internal Cold Water By-Pass
ES200 and ES400
Form TI ES200/ES400 v2
Table 1, Capacity Tables, present the Hydroguard discharge capacity in gpm and Ipm for various pressure differentials (the difference between the lowest inlet pressure and the discharge pressure at the Hydroguard).
SIZING
Operating
Maximum Pressure. . . . . . . . . . . . . . . . . . . . . . 125 psig (861.25 kPa)
Maximum Hot Water Temperature . . . . . . . . . . . . . . . . . 180°F (82°C)
Approach Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15°F (8°C)
Temperature Adjustment Range . . . . . . . . 60°F (15°C) - 95°F (35°C)
Factory Set Temperature . . . . . . . . . . . . . . . . . . . . . . . . 85°F (29°C)
Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . ANSI Z358.1 1998
Note: Set point cannot be less than the cold water temperature. For best operation, hot and cold water should be at least 15
°F (9.4°C) from desired set
point.
SPECIFICATIONS
Table 1- Capacity Tables
Flow Capacity in US gpm at 50-50 Mixed Ratio
Model Min. Flow Pressure Drop Across Valves in psi
Rate 5 10 20 30 45 60 75 ES200 3.0 gpm 15 20 30 36 45 52 58 ES400 3.0 gpm 27 38 54 66 80 93 104
Flow Capacity in lpm at 50-50 Mixed Ratio
Model Min. Flow Pressure Drop Across Valves in kP
A
Rate 34 69 138 207 310 414 517 ES200 11.0 lpm 57 76 113 136 170 197 220 ES400 11.0 lpm 102 144 203 249 305 352 393
By-Pass flows will vary depending on supply conditions and application.
Model ES400
Typical Flow
Hot and cold water supplies enter Hydroguard at indicated ports, (see Figure 1) then flow past their respective balanced poppet plug and seats. Next, hot and cold water flow is directed to the mixing chamber where the thermostatic actuator is located. Temperature adjustment screw moves the actuator/poppets to determine the discharge temperature. With a rise in discharge temperature due to pressure or tempera­ture fluctuation on the inlet, the actuator expands, decreasing hot water and increasing cold water flow to maintain the valve set point. The reverse occurs with a drop in discharge temperature.
• Cold water supply failure – causes actuator to expand allowing the motor to seat hot water poppet.
• Hot water supply pressure failure – causes actuator to contract opening cold water bypass ports. Secondary bypass mecha­nism opens upon failure of actuator or hot water.
OPERATION
Mixing Chamber
Body
Balanced Hot Water Poppet
Hot Water
Primary By-Pass Spring
Secondary By-Pass
Temperature Adjustment Screw
Adjustment Locking Screw
Thermostatic
Actuator
Cold Water By-Pass Ports
Cold Water
Balanced Cold Water Poppet
Motor Return Spring
Figure 1
Page 2
TI ES200/ES400 v2 Page 2
TAG DESCRIPTION
1 Etched Bonnet 2 Adjustment Screw 3 Bonnet Screw 4 Set Screw 5 Bonnet Gasket 6 Motor Housing 7 Housing Bolt 8 Temp Limit Spacer 9 Spacer Set Screw 10 Overload Assy 11 Overload “O” Ring 12 Funnel 13 Thermal Actuator 14 Funnel “O” Ring
TAG DESCRIPTION
15 Motor Adapter 16 Motor Adapter “O” Ring 17 Hot Water Poppet 18 Pressure Relief Spring 19 Pressure Relief Poppet 20 CW Bypass Plug 21 Bypass Spring 22 Cold Water Poppet 23 Return Spring 24 Body “O” Ring 25 Body 26 Body Cap “O” Ring 27 Body Cap
ES200 KIT NUMBER ES400 KIT NUMBER DESCRIPTION CONTAINS ITEMS:
390-573 390-574 Actuator Replacement Kit 5,13,15,16,24 390-575 390-576 Poppet Replacement Kit 15-24,26 390-577 390-578 Gasket and “O” Ring Kit 5,11,14,16,24,26
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
2
1
6
3
4
8
7
5
PARTS LIST
REPAIR KITS
RECIRCULATION
The mixing valve should be mounted as close as possible to the fixture(s) that it serves.
If the valve is some distance from the hot water source, recir­culation may be required to keep the hot water supply within specified limits.
CAUTION: Use care in installing the cold water line such that it does not pass through areas with high ambient temperatures or become exposed to direct sunlight.
Powers ES Series Tempering Valve Hot Water Recirculation
Tempered Water to Fixtures
Cold Water
Hot Water Return
Hot Water
H
C
Page 3
TI ES200/ES400 v2 Page 3
CALIFORNIA PROPOSITION 65 WARNING
WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm.
(Installer: California law requires that this warning be given to the consumer.)
For more information: www.wattsind.com/prop65
What to look for if:
• The flow of water is less than desired.
a. Stop valves or supply to Hydroguard not fully open. b. Clogged checkstop strainer screens. c. Accumulation of lime deposits around valve seats. d. Low supply pressures or unusual supply temperatures.
• The flow of water is completely shut off.
a. Stop valves or supply valves are completely closed. b. Valves downstream from Hydroguard fully closed. c. Loss of cold water supply pressure.
MAINTENANCE AND TROUBLESHOOTING
5. Remove four (4) body screws and carefully remove lower body.
6. Slide out hot water poppet and bypass assembly.
7. Loosen plug on bottom of lower body. Remove plug, spring, and cold water poppet.
CAUTION: The plug is under spring pressure. Use care when removing.
8. Remove the “O” rings from the body.
• Inspection:
1. Inspect the body for any damage, deposits, or pitting -
clean or replace as necessary.
2. Check the poppets, springs, and bypass assembly for any
damage, deposits, or pitting. If any component appears
stuck, worn, or damaged, replace all the internal parts.
3. Check the actuator for proper operation. Measure and
note the entire length of the actuator at room temperature or mark the stem with a piece of tape. Place the actuator in hot water (105-115
°F) for one (1) minute. Measure the
length of the actuator. Actuator should be at least 1/8" longer than when at room temperature.
DISASSEMBLY AND REPAIR INSTRUCTIONS
INSTALLATION INSTRUCTIONS
1. IMPORTANT: Flush all piping thoroughly before installing.
2. Locate the Hydroguard as close as possible to the fixture being supplied.
Note: Remove body screws to turn outlet to any of four positions. The Hydroguard body can be rotated to any position due to the union inlets. Install thermometer in discharge using supplied fittings.
Make certain the body screws and unions are tightened securely to prevent leakage.
3. CAUTION: When the Hydroguard supplies tempered water to self-closing and/or solenoid valves, provide a shock absorber (Powers Part No. 460-353) on the discharge line. This protects the Hydroguard thermostatic motor from dam­age by water shock waves generated by the quick closing valves.
4. Consult proper medical/safety authorities for the opti-
mum temperature for your application. Before use, check for proper discharge temperature. Reset if necessary. Valve is preset for 85
°F (29.4°C).
ADJUSTMENT AND TESTING
1. Replace adjustment screw and set to proper temperature. Open all fixtures and verify all outlet temperature is adequate.*
2. Verify adequate flow rate from fixtures.
3. Close the cold water checkstop. Verify that flow shuts down immediately.
4. Open cold water checkstop, and close hot water checkstop. Verify adequate flow from fixture(s).
5. Open hot water checkstop, verify temperature returns to set temperature.
6. Record test data on maintenance tag which should be attached to the valve.
*Contact factory for high temperature readjustment
procedure.
Consult proper medical/safety authorities for optimum temperature for your application. Before use, check for proper discharge temperature. Reset if necessary.
Per ANSI Z358.1-1998, Emergency fixtures should be tested weekly. Any unit failing any of the above tests should be repaired or replaced immediately.
Due to the safety nature of this product, we recommend removal of the valve and a full inspection of all components whenever the valve is disassembled for any reason.
• Disassembly:
1. Close supply valves and/or checkstops. Take apart unions between the valve and the checkstops.
2. Remove valve from its outlet piping. Work should be performed on a clean table or workbench. Use caution
when disassembling the valve as there are several small springs and parts inside.
3. Remove bonnet screws with a 3/15" hex wrench.
4. Remove bonnet and actuator.
Page 4
TI ES200/ES400 v2 Page 4
Insert the cold water poppet, spring, and plug into the bottom of the lower housing.
Carefully insert the bypass assem­bly into the body.
Install the hot water poppet using care not to disturb the springs or bypass assembly.
REASSEMBLY
Lubricate the body “O” ring, and place in groove on body. Tighten housing bolts.
Place actuator into motor adaptor
Install bonnet onto valve with 4­3/16” screws.
Form TIES200/ES400 v2 0335 EDP # 6508880 Printed in USA
© 2003 Powers, a Watts Industries Co.
USA Phone: 1.800.669.5430 • Fax 1.877.459.3440
Canada Phone: 1.888.208.8927 • Fax 1.888.882.1979
www.powerscontrols.com
Loading...