Pilz S3UM Data Sheet

Electronic monitoring relays
Three-phase voltage monitoring
S3UM
The S3UM voltage monitoring relay is used to monitor overvoltage and und­ervoltage as well as the phase se­quence in 3-phase supplies.
Approvals
S3UM
Unit features
` Monitors supplies with and without
neutral conductors
` Trip device for undervoltage and
overvoltage
` Evaluates phase sequence ` Detects asymmetry ` Detects phase failure ` Reaction time can be set to up to
10 s
` Operates to normally energised or
normally de-energised mode
Description
The voltage monitoring relay is en­closed in an S-95, slimline housing. Various versions are available for AC and DC operation. Features
` Relay outputs: 1 auxiliary contact
(C/O)
` 2 measuring circuits ` Adjustable under voltage value
from 75 % - 100 % of nominal sup­ply voltage or from 40 %-100 % (unit type)
` Overvoltage value can be set from
100 % to 120 % of the rated mains voltage
` Fault status can be latching or non-
latching
` LED as supply voltage indicator ` LED for all faults: phase sequence
error, under/overvoltage
` Phase failure is detected even when
there is voltage feedback from con­nected loads
` Range switching 10 % for L1-L3 ` Separate supply voltage A1-A2
Approvals for versions up to 240 V AC
Internal wiring diagram
MR: Manual reset, AR: Automatic reset
U
U
B
B
A1 A2 L1 L2 L3 N
A1 A2 L1 L2 L3 N
~
~
G1
G1
=
=
Power
Power
U
U
M
M
Umformung
Umformung Transformer
Transformer Conversion
Conversion Transformación
Transformación Transformazione
Transformazione Omzetting
Omzetting
U
U
1-3
1-3
Erkennung
Erkennung Detection
Detection Détection
Détection Detección
Detección Riconoscimento
Riconoscimento Detectie
Detectie
U
U
min/Umax
min/Umax
Y3 Y2
Y3 Y2
Umschaltung
Umschaltung Switching
Switching Commutation
Commutation Commutación
Commutación Commutazione
Commutazione Omschakeling
Omschakeling
UB 10 %
UB 10 %
100-120 % U
100-120 % U
Skala/Scale/Echelle/
Skala/Scale/Echelle/ Escala/Scala/Schaal
Escala/Scala/Schaal
40/75-100 % U
40/75-100 % U
B
B
B
B
Reset
Reset
Y1 12 14
Y1 12 14
Ruhe-/Arbeitsstrom
Ruhe-/Arbeitsstrom Normally energised/de-energised
Normally energised/de-energised Mode retombée/excitation
Mode retombée/excitation Corriente de trabajo/reposo
Corriente de trabajo/reposo Corrente di riposo/di lavoro
Corrente di riposo/di lavoro Rust-/Arbeidsstroom
Rust-/Arbeidsstroom
K1
K1
MR/AR
MR/AR
t
t
R
R
Fault
Fault
11
11
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-030-2006-08
Electronic monitoring relays
Three-phase voltage monitoring
S3UM
Timing diagram
nicht speichernd
nicht speichernd non-latching
non-latching
sans mémorisation
sans mémorisation no acumuladora
no acumuladora
senza memorizzazione
senza memorizzazione
automatische reset
automatische reset
Ruhestromprinzip
Arbeitsstromprinzip
Arbeitsstromprinzip Normally
Normally de-energised mode
de-energised mode
Mode excitation
Mode excitation Principio de corriente de
Principio de corriente de trabajo
trabajo
Principio della
Principio della corrente di lavoro
corrente di lavoro
Arbeidsstroomprincipe
Arbeidsstroomprincipe
U
U
max
max
U
U
N
N
U
U
min
min
Ruhestromprinzip Normally energised
Normally energised mode
mode Mode retombée
Mode retombée Principio de cor-
Principio de cor­riente de reposo
riente de reposo Principio della
Principio della corrente di riposo
corrente di riposo Ruststroomprincipe
Ruststroomprincipe
speichernd
speichernd latching
latching
mémorisation
mémorisation acumuladora
acumuladora
con memorizzazione
con memorizzazione
handmatige reset
handmatige reset
Ruhestromprinzip
Ruhestromprinzip Normally energised mode
Normally energised mode
Mode retombée
Mode retombée Principio de corriente de reposo
Principio de corriente de reposo
Principio della corrente di riposo
Principio della corrente di riposo
Ruststroomprincipe
Ruststroomprincipe
Y1/Y2
Y1/Y2
Y1
Y1
Y2
Y2
11
11
11
11
11
11
11
11
Fault
Fault
Key
` U ` U
Overvoltage response value
max
Undervoltage response value
min
` UN Rated mains voltage
Reaction time
` t
R
` Y1/Y2 linked: Automatic reset
12
12
12
12
14
14
14
14
tR
tR
tRtR tR tR
tRtR tR tR