Pilz PZE X4VP8 Data Sheet

Expander modules
Delayed
PZE X4VP8
Contact expander module for increa­sing the number of available contacts
PZE X4VP8

Unit features

` Positive-guided relay outputs:
– 4 safety contacts (N/O), delay-on
de-energisation
` LED indicator for:
– Switch status channel 1/2
` Plug-in connection terminals (either
cage clamp terminal or screw termi­nal)
` See order reference for unit types

Unit description

The unit meets the requirements of EN 60204-1 and IEC 60204-1. The con­tact expander module is used to increase the number of contacts available on a base unit. Base units are all safety relays with feedback loop. The category that can be achieved in accordance with EN 954-1 depends on the category of the base unit. The contact expander module may not ex­ceed this. The delay-on de-energisation safety contacts may only be used up to cate­gory 3.

Safety features

The unit meets the following safety re­quirements:
` The contact expander module ex-
pands an existing circuit. As the output relays are monitored via the base unit's feedback loop, the safe­ty functions on the existing circuit are transferred to the contact ex­pander module.
` The safety function remains effecti-
ve in the case of a component failu­re.
` Earth fault in the feedback loop:
Detected, depending on the base unit that is used.
` Earth fault in the input circuit:
The output relays de-energise and the safety contacts open.

Block diagram

A1 A2 17 27 37
Y1
=
Input
=
Power
K1
K2
Y2
18 28 38
47
48
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-294-01/05
Expander modules
Delayed
PZE X4VP8

Function description ` Single-channel operation: one in-

put circuit affects both output re­lays

Timing diagram

POWER
Input
Output safe
Feedback
t1 t1t2 t2
Key
` Power: Supply voltage ` Input: Input circuits A1
` Output safe: Safety contacts 17-18,
27-28, 37-38, 47-48
` Feedback: Feedback loop Y1-Y2
` t1: Switch-on delay
: Delay-on de-energisation
` t
2

Wiring

Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 17-18, 27-28, 37-38, 47-48
are delay-on de-energisation safety contacts.
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
R
= max. overall cable resi-
lmax
stance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-294-01/05Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
Expander modules
Delayed
PZE X4VP8

Preparing for operation

` Supply voltage

Supply voltage AC DC
24 V DC
0 V

` Input circuit

Input circuit Single-channel Dual-channel Base unit:
24 V DC
PNOZ X safety relay Driven via safety contacts
Base unit: PNOZelog safety relay Driven via semiconductor outputs (24 VDC)
0 V
O1
A1 A2
A1
PZE
A20 V
PZE
L-

` Feedback loop

Feedback loop Automatic reset Monitored reset Y1, Y2 and Input are inputs on the
base unit; they evaluate the feedback loop
Y1
Y2
Y1
Y2
PZE
Input
Y1
Y2
A1 A2
PZE
24 V DC
PZE
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de