Contact expansion module for increasing the number of available contacts
Approvals
PZE X4.1P with universal power supply
Unit features
` Positive-guided relay outputs:
– 4 safety contacts (N/O), instanta-
neous
` LED indicator for:
– Switch status channel 1/2
– Supply voltage
` Plug-in connection terminals (either
spring-loaded terminal or screw
terminal)
` Suitable to be driven via a semicon-
ductor output
` See order reference for unit types
Unit description
The unit meets the requirements of
EN 60947-5-1, EN 60204-1 and
VDE 0113-1. The contact expansion
module is used to increase the number
of instantaneous safety contacts available on a base unit. Base units are all
safety relays with feedback loop monitoring.
The category that can be achieved in
accordance with EN 954-1 and
EN ISO 13849-1 depends on the category of the base unit. The contact expansion module may not exceed this.
Safety features
The unit meets the following safety requirements:
` The contact expansion module ex-
pands an existing circuit. As the
output relays are monitored via the
base unit's feedback loop, the safety functions on the existing circuit
are transferred to the contact expansion module.
` The safety function remains effec-
tive in the case of a component failure.
` Earth fault in the feedback loop:
Detected, depending on the base
unit that is used.
` Earth fault in the input circuit:
The output relays de-energise and
the safety contacts open.
Block diagram
A1 A2
~
Power
=
K1UK2
Input
K1
K2
Y2
13 23 33Y1
14 24 34
43
44
NSG-D-2-352-2008-12
Expander modules
Instantaneous
PZE X4.1P with universal power supply
Function description
` Single-channel operation: one in-
put circuit affects both output relays
Timing diagram
Output safe
Key
` Power: Supply voltage
` Input: Input circuits K1-U-K2
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34, 43-44
are safety contacts.
` To prevent contact welding, a fuse
should be connected before the
output contacts (see technical details).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
R
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with
capacitive and inductive loads.
` Dual-channel operation:
– two redundant input circuits af-
fect one output relay
POWER
Input
Feedback
t1t1t2t2
` Output safe: Safety contacts 13-14,
23-24, 33-34, 43-44
` Feedback: Feedback loop Y1-Y2
– Detection of shorts across con-
tacts is also possible
: Switch-on delay
` t
1
` t2: Delay-on de-energisation
NSG-D-2-352-2008-12
-2
Expander modules
Instantaneous
PZE X4.1P with universal power supply
Preparing for operation
` Supply voltage
Supply voltageACDC
A1
A2
L1
N
PE
` Input circuit
Input circuitSingle-channelDual-channel
Base unit:
PNOZ X safety relay
Driven via safety contacts
K1
U
K2
PZE
` Feedback loop
Y1 and Y2 are inputs on the base unit; they
evaluate the feedback loop
Y1
Y2
Y1
Y2
PZE
A1
A2
L+
L-
PE
K1
U
K2
PZE
NSG-D-2-352-2008-12
Expander modules
Instantaneous
PZE X4.1P with universal power supply
Terminal configuration
43
2313
33
P1
A1 U K1 K2
P2
PNOZ X4.1P
POWER
CH.1
CH.2
43
3323
44
141334
24
P2
A2 Y1 Y2
P1
342414
44
Installation
` The safety relay should be installed
in a control cabinet with a protection type of at least IP54.
` Use the notch on the rear of the unit
to attach it to a DIN rail.
` Ensure the unit is mounted securely
on a vertical DIN rail (35 mm) by using a fixing element (e.g. retaining
bracket or an end angle).
Dimensions
*with spring-loaded terminals
94 (3.70")
* 101 (3.98")
121 (4.76")
22,5
(0.88")
NSG-D-2-352-2008-12
-4
Expander modules
Instantaneous
PZE X4.1P with universal power supply
Notice
Service life graph
This data sheet is only intended for use
during configuration. For installation
and operation, please refer to the op-
10
AC15: 230 V
erating instructions supplied with the
unit.
1
Courant coupé (A)
D Nennbetriebstrom (A)
GB Nominal operating current (A)
F
0.1
E Corriente nominal de servicio (A)
ICorrente di esercizio nominale (A)
NL Nominale bedrijfsstroom (A)
10100100010000
D Schaltspielzahl x 10
GB Cycles x 10
F Nombre de manuvres x 10
Technical details
Electrical data
Supply voltage
Supply voltage U
AC/DC24 - 240 V
B
Voltage tolerance-15 %/+10 %
Power consumption at U
Power consumption at U
AC4.0 VA
B
DC2.0 W
B
Frequency range AC50 - 60 Hz
Residual ripple DC20 %
Voltage and current at
Input circuit DC: 24.0 V30.0 mA
Number of output contacts
Safety contacts (S) instantaneous:4
Category of output contacts in accordance with EN 954-1,
EN ISO 13849-1
Safety contacts (S) instantaneous:4
Utilisation category in accordance with EN 60947-4-1
Safety contacts: AC1 at 240 VI
Safety contacts: DC1 at 24 VI
: 0.01 A , I
min
P
max
: 0.01 A , I
min
P
max
Utilisation category in accordance with EN 60947-5-1
Safety contacts: AC15 at 230 VI
Safety contacts: DC13 at 24 V (6 cycles/min)I
max
max
Contact materialAgCuNi + 0.2 µm Au
External contact fuse protection (I
= 1 kA) to EN 60947-5-1
K
Blow-out fuse, quick
Safety contacts:6 A
Blow-out fuse, slow
Safety contacts:4 A
Circuit breaker 24 VAC/DC, characteristic B/C
Safety contacts:4 A
Max. overall cable resistance R
single-channel at U
single-channel at U
DC70 Ohm
B
AC70 Ohm
B
dual-channel without detect. of shorts across contacts at U
dual-channel without detect. of shorts across contacts at U
per input circuit
lmax
DC140 Ohm
B
AC140 Ohm
B
DC13: 24 V
3
3
max
: 1500 VA
max
: 150 W
: 3.0 A
: 4.0 A
: 6.0 A
: 6.0 A
DC1: 24 V
AC1: 230 V
E Número de ciclos x 10
INumero dei cicli di commutazione x 10
3
NL Aantal schakelingen x 10
3
3
3
NSG-D-2-352-2008-12
Expander modules
Instantaneous
PZE X4.1P with universal power supply
Times
Switch-on delay
with automatic reset typ.13 ms
with automatic reset max.20 ms
with automatic reset after power on typ.230 ms
with automatic reset after power on max.360 ms
Delay-on de-energisation
with E-STOP typ.10 ms
with E-STOP max.20 ms
with power failure typ. U
with power failure max. U
with power failure typ. U
with power failure max. U
Supply interruption before de-energisation 20 ms
Supply interruption before de-energisation in the input circuit2.5 ms
Environmental data
EMCEN 60947-5-1, EN 61000-6-2, EN 61000-6-4
Vibration to EN 60068-2-6
Frequency10 - 55 Hz
Amplitude0.35 mm
Climatic suitabilityEN 60068-2-78
Airgap creepage in accordance with EN 60947-1
Pollution degree2
Rated insulation voltage250 V
Rated impulse withstand voltage6.0 kV
Ambient temperature-10 - 55 °C
Storage temperature-40 - 85 °C
Protection type
Mounting (e.g. cabinet)IP54
HousingIP40
TerminalsIP20
Mechanical data
Housing material
HousingPPO UL 94 V0
FrontABS UL 94 V0
Cross section of external conductors with screw terminals
1 core flexible0.25 - 2.50 mm² , 24 - 12 AWG
2 core, same cross section, flexible:
with crimp connectors, without insulating sleeve0.25 - 1.00 mm² , 24 - 16 AWG
without crimp connectors or with TWIN crimp connectors0.20 - 1.50 mm² , 24 - 16 AWG
Torque setting with screw terminals0.50 Nm
Cross section of external conductors with spring-loaded termi-
nals: Flexible with/without crimp connectors
Spring-loaded terminals: Terminal points per connection2
Stripping length8 mm
Dimensions
Height101.0 mm Order no.: 787588
Width22.5 mm
Depth121.0 mm
Weight215 g Order no.: 787588
AC/DC: 24 V270 ms
B
AC/DC: 24 V350 ms
B
AC : 240 V1,300 ms
B
AC : 240 V1900 ms
B
0.20 - 1.50 mm² , 24 - 16 AWG
94.0 mm Order no.: 777588
220 g Order no.: 777588
The standards current on 2008-12 apply.
NSG-D-2-352-2008-12
-6
Expander modules
Instantaneous
PZE X4.1P with universal power supply
Conventional thermal current
Number of contactsI
16.00 A6.00 A
26.00 A6.00 A
34.50 A4.50 A
43.50 A3.50 A