Expander modules
Instantaneous
PZE X4.1P with universal power supply
ohne Abbildung
Contact expansion module for increasing the number of available contacts
Approvals
PZE X4.1P with universal power supply
Unit features
` Positive-guided relay outputs:
– 4 safety contacts (N/O), instanta-
neous
` LED indicator for:
– Switch status channel 1/2
– Supply voltage
` Plug-in connection terminals (either
spring-loaded terminal or screw
terminal)
` Suitable to be driven via a semicon-
ductor output
` See order reference for unit types
Unit description
The unit meets the requirements of
EN 60947-5-1, EN 60204-1 and
VDE 0113-1. The contact expansion
module is used to increase the number
of instantaneous safety contacts available on a base unit. Base units are all
safety relays with feedback loop monitoring.
The category that can be achieved in
accordance with EN 954-1 and
EN ISO 13849-1 depends on the category of the base unit. The contact expansion module may not exceed this.
Safety features
The unit meets the following safety requirements:
` The contact expansion module ex-
pands an existing circuit. As the
output relays are monitored via the
base unit's feedback loop, the safety functions on the existing circuit
are transferred to the contact expansion module.
` The safety function remains effec-
tive in the case of a component failure.
` Earth fault in the feedback loop:
Detected, depending on the base
unit that is used.
` Earth fault in the input circuit:
The output relays de-energise and
the safety contacts open.
Block diagram
A1 A2
~
Power
=
K1 U K2
Input
K1
K2
Y2
13 23 33Y1
14 24 34
43
44
NSG-D-2-352-2008-12
Expander modules
Instantaneous
PZE X4.1P with universal power supply
Function description
` Single-channel operation: one in-
put circuit affects both output relays
Timing diagram
Output safe
Key
` Power: Supply voltage
` Input: Input circuits K1-U-K2
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34, 43-44
are safety contacts.
` To prevent contact welding, a fuse
should be connected before the
output contacts (see technical details).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
R
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with
capacitive and inductive loads.
` Dual-channel operation:
– two redundant input circuits af-
fect one output relay
POWER
Input
Feedback
t1 t1t2 t2
` Output safe: Safety contacts 13-14,
23-24, 33-34, 43-44
` Feedback: Feedback loop Y1-Y2
– Detection of shorts across con-
tacts is also possible
: Switch-on delay
` t
1
` t2: Delay-on de-energisation
NSG-D-2-352-2008-12
-2
Expander modules
Instantaneous
PZE X4.1P with universal power supply
Preparing for operation
` Supply voltage
Supply voltage AC DC
A1
A2
L1
N
PE
` Input circuit
Input circuit Single-channel Dual-channel
Base unit:
PNOZ X safety relay
Driven via safety contacts
K1
U
K2
PZE
` Feedback loop
Y1 and Y2 are inputs on the base unit; they
evaluate the feedback loop
Y1
Y2
Y1
Y2
PZE
A1
A2
L+
L-
PE
K1
U
K2
PZE