Pilz PZE 9P Data Sheet

Expander modules
Instantaneous
PZE 9P
Contact expander module for increa­sing the number of available contacts
PZE 9P
Unit features
` Positive-guided relay outputs:
– 8 safety contacts (N/O), instanta-
neous
– 1 auxiliary contact (N/C), instan-
taneous
` Safe separation of safety contacts
23-24 ... 83-84 from input circuits K1-U2, K2-U2, Y3-Y4, feedback loop Y1-Y2 and auxiliary contact 91-92.
` LED indicator for:
– Switch status channel 1/2 – Supply voltage
` Plug-in connection terminals (either
cage clamp terminal or screw termi­nal)
` See order reference for unit types
Unit description
The unit meets the requirements of EN 60204-1 and IEC 60204-1. The con­tact expander module is used to increase the number of contacts available on a base unit. Base units are all
` Safety relays with feedback loop
` Programmable safety systems with
feedback loop The category that can be achieved in accordance with EN 954-1 depends on the category of the base unit. The contact expander module may not ex­ceed this.
Safety features
The unit meets the following safety re­quirements:
` The contact expander module ex-
pands an existing circuit. As the
output relays are monitored via the
base unit's feedback loop, the safe-
ty functions on the existing circuit
are transferred to the contact ex-
pander module.
` The safety function remains effecti-
ve in the case of a component failu-
re.
` Earth fault in the feedback loop:
Detected, depending on the base
unit that is used.
` Earth fault in the input circuit:
The output relays de-energise and
the safety contacts open.
Block diagram
* Galvanic isolation in accordance with EN 60947-1, 6 kV (see unit features)
UB = 24 V AC/DC UB = 24 V AC/DC
A1 A2
~
=
Power
B1 B2 13 23 33
K1 U1 K2 U2 Y3 Y4
Y1
~
Input
=
Power
=
K1
K2
~
A1 A2
U
= 100 - 240 V AC/DC
B
Y2
14 24 34
43
53 63 73 83 91
44
54 64 74 84 92
*
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-170-11/04
Expander modules
Instantaneous
PZE 9P
Function description ` Single-channel operation: one in-
put circuit affects both output re­lays
` Dual-channel operation:
Timing diagram
POWER
Input
Output safe
Output aux.
Feedback
t1 t1t2 t2
Key
` Power: Supply voltage ` Input: Input circuits K1-U1, K2-U2,
Y3-Y4
` Output safe: Safety contacts 13-14,
23-24, 33-34, 43-44, 53-54, 63-64, 73-74, 83-84
` Output aux: Auxiliary contacts 91-
92
Wiring
– two redundant input circuits af-
fect one output relay
– Detection of shorts across con-
tacts is also possible
` Feedback: Feedback loop Y1-Y2
: Switch-on delay
` t
1
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34, 43-
44, 53-54, 63-64, 73-74, 83-84 are safety contacts, output 91-92 is an auxiliary contact (e.g. for display).
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
= max. overall cable resi-
R
lmax
stance (see technical details)
/ km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-170-11/04Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
Expander modules
Instantaneous
PZE 9P
Preparing for operation
` Supply voltage
Supply voltage AC/DC AC/DC
Order no.: 777148, 787148 U
= 100 - 240 V
B
A1
A2
L1/L+ N/L-
Order no. 777148, 787148 UB = 24 V
B1
L1/L+
B2 PE
Order no. 777140, 787140 UB = 24 V
` Input circuit
Input circuit Single-channel Dual-channel without detection of shorts across
contacts
K1 U1
K2 U2 Y3 Y4
PZE
with detection of shorts across con­tacts
B2
A2
A1
K1 U1
K2 U2 Y3 Y4
K1 U1
K2 U2 Y3 Y4
N/L-
L1/L+
N/L-
PZE
PZE
` Feedback loop
Y1 and Y2 are feedback loop inputs on the base unit
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Y1
Y2
Y1
Y2
PZE
NSG-D-2-170-11/04