Pilz PZE 5V Data Sheet

Expander Modules
Delayed
PZE 5V
Expander module in accordance with VDE 0113-1, 11/98, EN 60204-1, 12/97, and IEC 204-1, 11/98 to increase the number of safety contacts available.
Features
Delay-on de-energisation can be set via the rotary switch
Delay-on de-energisation is effective after power failure
Approvals
PZE 5V
Technical Details PZE 5V
Electrical Data
Supply Voltage AC: 24, 42, 110, 120, 230, 240 V
DC: 24 V Tolerance 85 ... 110 % Power Consumption Approx. 3.5 W/5 VA Residual Ripple DC 20 % Total Current max. 40 A Switching Capabilty in accordance with EN 60947-4-1, 10/91 AC1: 240 V/8 A/2000 VA
400 V/5 A/2000 VA
DC1: 24 V/8 A/200 W EN 60947-5-1, 10/91 AC15: 230 V/5 A; DC13: 24 V/7A (DC13: 6 cycles/min.) Output Contacts 4 safety contacts (N/O),
1 auxiliary contact (N/C) Contact Fuse Protection (EN 60947-5-1, 10/91) 10 A quick or 6 A slow
Times
Delay-on Energisation Time range 0.5 ... 3 s AC: 0.2/0.4/0.8/1.2 s
DC: 0.08/0.15/0.3/0.45 s Time Range 2 ... 8 s AC: 1/2/3/4 s
DC: 0.33/0.66/1/1.3 s Delay-on De-energisation Time range 0.5 ... 3 s 0.5/1/2/3 s Time range 2 ... 8 s 2/4/6/8 s Recovery Time Delay-on de-energisation + delay-on
energisation
Mechanical Data
Torque Setting on Connection Terminals 1.2 Nm (screws) Maximum Cross Section of 2 x 2.5 mm External conductors Single-core or multi-core with
crimp connectors Dimensions (H x W x D) 87 x 135 x 110 mm Weight Range 0.5 ... 3 s AC: 670 g, DC: 570 g Range 2 ... 8 s AC: 720 g, DC: 620 g
2
Description
135 mm, P-75 housing, DIN-Rail mounting
Positive-guided relay outputs: – 4 safety contacts (N/O) – 1 auxiliary contact (N/C)
Connection for feedback control loop
Delay-on energisation and delay­on de-energisation can be programmed
Single or dual-channel operation
2 versions available with different
time ranges.
Function Description
PZE 5V is used to increase the number of safety contacts available and the timed delay switching of an E-STOP command for
E-STOP relays
Safety gate monitors
Two-hand relays
All base units must have a feedback control loop.
NSG-D-2-096-02/02
6
Expander Modules
Delayed
PZE 5V
Internal Wiring Diagram
U
B
A1
(L+)
F1
~
G1
A2
(L-)
+
Input circuit
U
K1
=
K2
U
Input circuit
External Wiring
Example 1 Single-channel operation
L1
PE
X1
X2
(Y1)
(Y2)
Y1
K1
C1 C2 C3 C4
C5 C6 C7 C8
K2
Y2
A1
X1
(+)
Time ranges
132
45
(-)
X2
K1
K2
6
1314232433
Feedback
control loop
X1 X2
43
Safety contacts
13 23 33 51
14
24 34 5244
1
Y1
43
2
Auxiliary contacts
3
6
Base unit
14
1323
24
N
Example 2 Dual-channel operation
L1
PE
X1
X2
(Y1)
(Y2)
Base unit
14
1323
24
PZE 5V
K1
U
A1
X1
X2
(+)
PZE 5V
K1 K2UU
445152
A2
Y2
56
Y1
Y2
4
12
5
3
64
(-)
51
A2
52
(-)
K2U
(-)
34
131423
2433344344
N
NSG-D-2-096-02/02
Loading...