Technical Details PSWZ-F
Electrical Data
Supply Voltage 24 V DC Tolerance 85 ... 110 % Residual Ripple DC 20 % Power Consumption Approx. 4.5 W Switching Capability in accordance with EN 60947-4-1, 02/01 AC1: 240 V/6 A/1500 VA
EN 60947-5-1, 11/97 AC15: 230 V/4 A; DC13: 24 V/3A (DC13: 6 cycles/min.) Output Contacts 2 safety contacts (N/O),
Hysteresis per channel Response value Uon: 20 ... 500 mV
Standstill monitor in accordance with VDE 0113-1, 11/98, EN 60204-1, 12/97, EN 1088, 12/95 and IEC 204-1, 11/98.
Features
Safe standstill monitoring
Single or dual-channel operation
No external components
necessary
Simultaneity monitoring
Semiconductor output for fault
signalling
Input for reset
Cable break detection
Limited use for variable-
frequency inverter operation
Automatic self-test
Approvals
PSWZ-F
Release value U Measuring Circuit Input voltage 110 ... 500 VAC overload up to 690 VAC Frequency range 0 ... 1,5 kHz Input impedance Approx. 660 k Contact Fuse Protection 6 A quick or 4 A slow (EN 60947-5-1, 08/00) Semiconductor outputs 24 V DC/50 mA, short-circuit proof External supply voltage 24 C DC ± 20 % Semiconductor input 24 V DC/30 mA
Times
Delay-on Energisation Approx. 1 s Delay-on De-energisation Approx. 170 ms Delay-on Energisation after failure and Approx. 1.5 s return of the operating voltage Simultaneity channel 1/2 Approx. 6 s Recovery Time Approx. 1.5 s Max. Supply Interruption before Approx. 35 ms De-energisation
Mechanical Data
Maximum Cross Section of 2 x 2.5 mm External Conductors Single-core or multi-core with
Torque Setting on Connection Terminals 1.2 Nm (screws) Dimensions (H x W x D) 87 x 90 x 115 mm Weight 440 g
DC1: 24 V/6 A/150 W
1 auxiliary contact (N/C)
: 2 x U
off
on
W
2
crimp connectors
5
Descritpion
90 mm, P-75 housing, DIN-Rail
mounting
Positive-guided relay outputs: – 2 safety contacts (N/O)
– 1 auxiliary contact (N/C)
Measuring inputs for single and three-phase motors
Measuring voltages for channels can be set separately
Increase in the number of safety contacts available by connecting expander modules.
2 semiconductor outputs for status, fault signalling
Operating Modes
1 semiconductor input for reset
LEDs for power, channel 1, channel 2 and relay status
Single-channel operation
Dual-channel operation
NSG-D-2-314-01/02
5-1
Safe Monitoring Relays
Standstill
PSWZ-F
Function Diagram
U
B
Y1-Y2
13-14
23-24
Y35
RESET
UL1/UL2
U
an
U
ab
t<t
g
tg = Simultaneity monitoring
Connection Example
t
>t
g
ca.50 ms
1,5 s
5
L1 L2 L3
F1
A1 13 14
23 24 A2
S1 K2
S0
S4
S23
S2
S13
S24
S14
PST1
S3
S5
A1 13 23 L1 L3
14 24
K1
RESET
41 L2
Y31 Y32
42
Y30
0 V 24 V
SPS
Y35
PSWZ-S
Y2
A2Y1
H
F2
K2
K3
M
K4
K1 K2 K3 K4
S0: Off-switch S1: On-switch S2/S4: E-STOP or safety gate switch
S3: Release
Switch operated
Gate open
Gate closed
NSG-D-2-314-01/02
Safe Monitoring Relays
Standstill
PSWZ-F
General Technical Data
Unless stated otherwise in the technical details for the specific unit
Electrical Data
Frequency Range AC 50 ... 60 Hz Residual Ripple DC 160 % Contact Material AgSnO Continuous Duty 100 %
Environmental Data
EMC EN 50081-1, 01/92, EN 61000-6-2, 03/00 Vibration in accordance with Frequency: 10 ... 55 Hz, EN 60068-2-6, 01/00 Amplitude: 0.35 mm Climatic Suitability DIN IEC 60068-2-3, 12/86 Airgap Creepage DIN VDE 0110 part 1, 04/97 Ambient Temperature -10 ... +55 °C Storage Temperature -40 ... +85 °C
Mechanical Data
Torque Setting on Connection Terminals 0.6 Nm (screws) Mounting Position Any Housing Material Thermoplast Noryl SE 100 Protection Mounting: IP 54
2
Housing: IP 40 Terminal Range: IP 20
The units were tested in accordance with the relevant standards current at the time of development.
Order References
Type U
PSWZ-F 24 V DC 475 945
B
Order No.
5
NSG-D-2-314-01/02