Philips EG1-4 User Manual

Lighting Systems
EG1-4

Page 1 of 5

1
5

Feature Specifications Electrical

Connections: Wiring is via 18 gauge wire. All electrical connections for standard

Energos 1-Light T5 per 4' (121.92cm) (Nominal) Louver

2 3

Features

1. Housing: 18 gauge steel. 6" (15.24cm) cast aluminum end caps. No exposed
fasteners or hardware.
2. Lamping: 1 T5 fluorescent lamps per 4' (121.92cm) section. Lamps by Lightolier
as an option, see ordering information.
3. Reflector: Precision die-formed premium anti-iridescent, highly reflective alu
minum.
4. Louver: Parabolic louver, low-iridescent semi-specular anodized aluminum, 25
degree shielding lengthwise. Blades are spaced 2.3" (5.84cm) O.C with a radius that matches the housing. 1" (2.54cm) tall louver attaches to housing.
5. Optional Slotted Top Reflector: Precision die-formed anti-iridescent, highly
reflective aluminum.
All sfafic ballasfs have fhe following feafures:
• Elecfronic
• High Power Facfor
• Class A sound rafing
• Mefal can
Emergency Battery Pack: Emergency Battery packs are designed to operate
when normal building power is interrupted. The battery packs operate for a mini mum of 90 minutes without any power via a rechargeable battery source. The pack does not utilize the standard static ballast for any of its operation since the pack carries its own pseudo ballast. For this reason, Lightolier does not recommend remote mounting EM Packs because all of the socket wiring would need to carry throughout the power feed end set. The EM batteries, even in their largest, most expensive form, operate the fluorescent lamps at only half the lamp rated output. Emergency battery packs are available in the following outputs:
• 450 Lumens (Standard)
• 635 Lumens
• 1100 Lumens
• 1375 Lumens
Emergency battery packs can be used for emergency egress lighting since all listed packs operate for a minimum of 90 minutes, or can be used as momentary lighting for emergency circuit power transitions. Smaller packs are recommended for this purpose.
Dimming: T8 and T5H0 lamps are dimmed with two wire ballasts. T8 lamps can
be dimmed down to 5% and T5H0 lamps can be dimmed down to 1%. T5 lamps require 5-wire dimming ballasts and can be dimmed down to 1%. A 5-wire power feed will be required for T5 (non-HO) dimming.

Labels Included

UL, cUL,and IBEW

Mountings

Cable suspension is on 48" (121.92cm) and 96" (243.84cm) centers and consists of a 4 1/2" (11.43cm) diameter canopy finished white enamel. A 1/16" (0.16cm) diameter stainless steel aircraft cable accomplishes suspension and is adjustable from 12" (30.48cm) to 36" (91.44cm). Power feed is 18-gauge SJT white cord. For special circuiting consult factory.

Finish

Powder coated, baked enamel, white or aluminum, as specified. Custom colors available, consult factory.

Ordering Instructions

Individual Fixtures:
1. Order number of MODULES required.
2. Order one POWER FEED END SET per MODULE.
Continuous Rows:
1. Determine run length.
2. Order the appropriate number of MODULES for the complete run.
3. Order one POWER FEED END SET for each run.
4. Order one CABLE ASSEMBLY per MODULE minus one per run.
5. For runs that exceed conductor ampacity ratings order the appropriate number of SINGLE CABLE & CORD SETS.
Job Information
Job Name:
Cat. No.:
Lamp(s): Notes:
1 Type:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. www.lightolier.com © 2009 Philips Group • F1109
PHILIPS
LIGHTOLIIzir
Lighting Systems
EG1-4

Page 2 of 5

Module Ordering Information

Family

When ordering no lamps provided by Lightolier, use Lamp code "Z".

Series Lamping &
EG 1
Distribution

1 = 1 Lamp

4 = 1 Lamp,
Slotted Top Reflector
Ballast Lamp Shielding Length Voltage Finish
See Ballast Chart Below
P
See Lamp Chart Below
r P
P = Parabolic
Louver

Module Ordering Specifications Lamping and Distribution

1 = 1 Lamp 4 = 1 Lamp, Slotted Top Reflector
Ballast Specifications
Code Lamp Type Ballast Factor
F T5 1.00 Program <10
G T5H0 1.00 Program <10
I Dim T5 1.00/.01 Program <10
J Dim T5H0 1.00/.03 Program <10
Dimming: Advance Mark-10 standard (no additional wires required) for T8 and
T5H0 fixtures. 5-wire dimming required forT5 (non-HO) fixtures. Optional dimming systems: Lutron ECO-10 and Hi-Lume (by others) require 4-wire modules and end sets. Mark-7, ULT, DALI and Lightolier HDL require 5-wire power feed end sefs.
Energos can accepf ballasfs not to exceed 1.7" (4.32cm) wide by 1.2" (3.05cm)
high.
Start Type
THD %

Shielding

P = Parabolic Louver

Length Voltage Finish

4 = 4ft (48") (121.92cm) 1 = 120VAC A = Aluminum 8 = 8ft (96") (243.84cm) 2 = 277VAC W = White

Energos 1-Light T5 per 4' (121.92cm) (Nominal) Louver

Options

(Blank)
P
4 = 4'(121.92cm) 8 = 8' (243.84cm)
Code Lamp Type Wattage
M T5 28 2600* 830 N T5 28 2600* 835
0 T5 28 2600* 841
P T5 54 4450* 830 Q T5 54 4450* 835 R
25°c Rating
1 = 120V
2 = 277V
Lamping Specifications
T5 54 4450* 841
A = Aluminum W = White
Rated Output
(Lumens)
4= 4 through wires 5= 5 through wires 6= 6 through wires D= Dual Switch T= Tandem Switch E= Emergency Pack
Color (K)

Feature Options (continued)

E = Emergency Battery Pack (E): Baffery packs provide 90 minufes of opera-
fion. Available lamp oufpufs: 450 Lumens (sfandard). Opfional: 635,1100 and 1375 Lumens. Sfandard Emergency wiring is fo have Baffery Pack operafing a single
lamp. All EM fixfures are wired as "swifched" and include 4fh fhrough wire for fhe wall swifch (see diagrams). All fixfures and power feeds in fhaf run should be ordered fo include a dedicafed 4fh fhrough wire fo carry fhe hot power all the way through the run to the EM pack.

Wiring Options

Blank = Leave blank if ordering sfandard fixfure. 4 = 4 fhrough wires 5 = 5 fhrough wires 6 = 6 fhrough wires

Feature Options

D = Dual Switching (AKA A/B swifching)
]□[
2-Light Option 3-Light Option
T = Tandem Switching (also available in 1-lamp configuration)
A B
Both Dual Switch and Tandem Switch fixtures ship with a 4th wire. Be sure to order the appropriate quantity of wires in fhe power feed.
631 Airporf Road, Lall River, MA 02720 • (508) 679-8131 • Lax (508) 674-4710 We reserve the right to change details of design, materials and finish. www.lighfolier.com © 2009 Philips Group • L1109
Unswitched Switched
Job Information Type:
PHILIPS
LIGHTOLIIzir
Loading...